HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
|
|
|
- Kimberly Johnson
- 10 years ago
- Views:
Transcription
1 HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable CDW Chillers Piping Configurations Chiller Tower Optimization Pumping Optimization 2 1
2 LOW FLOW LOW TEMPERATURE HIGH EFFICIENCY SYSTEMS 3 Low Flow, Low Temperature High Efficiency 1.Slow the Flow 2.Drive the Chiller Harder 3.Chillers more efficient than ancillaries ~/ $ piping +/-$ air handlers +/-$ +/-$ chillers ~/ $ ductwork controls +/-$ FIRST COST & OPERATING COST COMFORT, ACOUSTICS & EFFICIENCY 4 2
3 Low Flow Low Temperature Low flow CHW and/or CDW improves system efficiency at part load Pumping power reduction more than offset slight increase in chiller power Low flow also decreases infrastructure costs Piping, valves Insulation Pumps Towers CT sizing can reduce with warm (design) condenser water and lower flows Re-invest some of the capital back into higher efficiency chillers, towers, coils and controls 5 Chiller Efficiency (Code vs Best in Class) Higher efficiencies today allow for better chiller utilization COP kw MEPS AU s 1980s 1990s 2000s 2010s 6 Note: Efficiencies at full load at AHRI (Standard MEPS) conditions water-cooled chillers 3
4 CHW Design Parameters Parameter Past/Conventional EarthWise Leaving CHW, [ o C] 6 ~ 7 4 ~ 6 CHW δt, [K] 5 ~ 7 9 ~ 12 CHW Flow, [L/s/MW] 34 ~ ~ 26 Leaving CDW, [ o C] ~ 38 CDW δt, [K] ~ 10 CDW Flow, [L/s/MW] ~ 35 Cooltools TM Chilled Water Plant Design Guide (Dec 2009) recommends 6.7 to 11.1K δt on chilled water and 6.7 to 10K δt on condenser δt Steven Taylor (ASHRAE Dec 2011), Clearly life-cycle costs will be lower, the higher the (chilled water) δt... within the range of their analysis (up to 13.9K δt) 7 CHW Plant Efficiency Chiller efficiency improvements Minimum code requirements: MEPS compliant AHRI or Eurovent certified; assurance of performance CHW Plant Ancillaries do Count! CHW pumps CDW pumps Cooling Tower fans CHW Plant System Efficiency [COP] defined by COOLING CAPACITY [kw] TOTAL POWER INPUT [kw] 8 Total Power Input includes power input of chillers and ancillaries 4
5 CHW Plant Efficiency Scale 9 Source: Thomas Hartman, 2001 CHW Plant Efficiency Conventional CHW plants spend significant portion of operational hours at part load Ancillaries power input are significant at part load % Total kw input % 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 25% 50% 70% 100% Note: Based on two screw chillers in parallel, AHRI conditions and sequenced. Pump heads at 400/250 kpa, cross-flow towers Tower Fans CDS Pumps EVP Pumps Chillers Plant Capacity 5
6 VARIABLE FLOW CHILLED WATER SYSTEMS 11 Primary only CV Design 1 2 (each) 3 Primary CV pumps 300 L/s Bypass 300 L/s 12 6
7 Primary only CV Part Load 11.7 C 11.7 C 1 2 (each) 11.7 C C Primary CV pumps 50 L/s 250 L/s Bypass 250 L/s 13 Primary secondary Design (each) Primary CV pumps 300 L/s bypass (decoupler) secondary VV pumps 300 L/s 14 7
8 Primary secondary Part load 11.7 C 11.7 C 1 2 (each) 11.7 C C Primary CV pumps 50 L/s 250 L/s bypass (decoupler) Secondary VV pumps 250 L/s 15 Variable primary Design 150 L/s (each) P Primary VV (or flow meter) pumps 0 L/s 300 L/s 300 L/s 16 8
9 Variable primary Part load 125 L/s (each) L/s L/s L/s P Primary VV (or flow meter) pumps 0 L/s 250 L/s 250 L/s 17 Variable primary System Flow < Chiller Min Flow 9.0 C 1 pump 40 L/s 9.0 C 40 L/s OFF OFF P Primary VV (or flow meter) pumps L/s 20 L/s 20 L/s 18 9
10 VPF - Advantages Less capital...more space Energy efficient Pumping savings during most operating conditions, down to minimum flow Pumping kw {Flow} 2.0 to 2.8 Improves reliability of system with manifold arrangement Separates pumping duty from cooling duty Not operating pumps to start chillers Chillers can fully realize its maximum capacity Over-pumping during part load to fully load chillers before bringing on the next chiller 19 VPF Chiller Lab Test 50% Flow in 30 sec Capacity Control with Water Flow Compensation 1, , L/s 1, Water Temp [degf] Evaporator W ater Flow Water Flow [gpm] 38 L/s 60 Evap Entering W ater Temp C C 40 Evap Leaving W ater Temp :00:00 0:10:00 0:20:00 0:30:00 0:40:00 0:50:00 Time (hour:min:sec) 20 10
11 VPF Chiller Selections Flow range-ability Ratio of minimum to design flow rates Aim for 1:2 ratio as a minimum Better ratios with larger centrifugal chillers than smaller screw type due to HX combinations available Higher velocities (high number of passes) will have higher design δp but also better range High design δp does not mean high energy consumption as chiller plant runs at part load most of the time Low flow designs may have poorer range-ability unless piped in series Consult manufacturers with experience 21 VPF System Considerations 22 System level Controls, not stand alone loops Basic operation Enable plant Control pumps Start lead chiller Start and stop lag chillers Vary flow to demand with dynamic reset Manage chiller and bypass operation at low flow Managing lead-lag Transient flows Sequence of Operation System integrator with experience 11
12 SYSTEM LEVEL CONTROLS Variable primary Controls 1 40 L/s 2 OFF 3 OFF Primary VV pumps P (or flow meter) P 23 System Options and Analysis No one ideal flow or temperature for all jobs There is a trend of lower operating costs with lower flows up to a certain point Need comprehensive analysis, not spreadsheet 24 12
13 Full Load System Input kw System kw Tower Fans CDS Pumps EVP Pumps Chillers Parallel AHRI Parallel AHRI, VPF Low Flow CHW Low Flow CHW & CDW 25 Note: Based on two screw chillers in parallel, sequenced. AHRI conditions compared to Low Flow CHW 5.5/15.5C; Low Flow CDS 28/36C. Pump heads at 400/250 kpa, cross-flow towers 75% Load System Input kw System kw Tower Fans CDS Pumps EVP Pumps Chillers 50 0 Parallel AHRI Parallel AHRI, VPF Low Flow CHW Low Flow CHW & CDW 26 Note: Based on two screw chillers in parallel, sequenced. AHRI conditions compared to Low Flow CHW 5.5/15.5C; Low Flow CDS 28/36C. Pump heads at 400/250 kpa, cross-flow towers 13
14 50% Load System Input kw System kw Tower Fans CDS Pumps EVP Pumps Chillers Parallel AHRI Parallel AHRI, VPF Low Flow CHW Low Flow CHW & CDW 27 Note: Based on two screw chillers in parallel, sequenced. AHRI conditions compared to Low Flow CHW 5.5/15.5C; Low Flow CDS 28/36C. Pump heads at 400/250 kpa, cross-flow towers 25% Load System Input kw System kw Tower Fans CDS Pumps EVP Pumps Chillers 20 0 Parallel AHRI Parallel AHRI, VPF Low Flow CHW Low Flow CHW & CDW 28 Note: Based on two screw chillers in parallel, sequenced. AHRI conditions compared to Low Flow CHW 5.5/15.5C; Low Flow CDS 28/36C. Pump heads at 400/250 kpa, cross-flow towers 14
15 Variable Condenser Flow (VCF) 29 System efficiency of VCF improvements are less compared to VPF on CHW Tower static head remains constant Chiller power increases due to higher lift at low flow Less or not effective on lift sensitive chillers (VSD) Possible Improvement on system efficiency especially at low loads < 50% - requires system level optimization controls Care with centrifugal chillers with surge limit and loss of VSD benefit More sensitive with single stage centrifugals Check unloading at various condenser flows and temperatures CHILLER PIPING & CONFIGURATIONS 30 15
16 Parallel - Parallel COP Chillers 6.1 System o C 29.4 o C, 59 L/s 34.6 o C 20 kw 29.4 o C, 59 L/s 20 kw 12.2 o C 25 kw 1100 kw COP o C, 47 L/s 12.2 o C 25 kw 34.6 o C 1100 kw 6.7 o C, 47 L/s COP K Waterside Lift o C Note: Based on two screw chillers in parallel, sequenced at AHRI conditions. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans Series - Parallel COP Chillers 6.3 System o C 29.4 o C, 62 L/s 34.7 o C 21 kw 29.4 o C, 57 L/s 19 kw 15.5 o C 28 kw 1080 kw 10.1 o C 1020 kw COP 6.8 COP o C 5.5 o C, 52.4 L/s 24.6 K 29.2 K Waterside Lift 10.1 o C 5.5 o C 32 Note: Based on two screw chillers in series evap low flow, parallel cond. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans 16
17 Series Counter-flow COP Chillers 6.4 System o C 31.7 o C 28.0 o C, 75.5 L/s 25 kw 15.5 o C 28 kw 1200 kw 10.1 o C 1000 kw COP 6.4 COP o C 31.7 o C 5.5 o C, 52.4 L/s 26.0 K 26.2 K Waterside Lift 10.1 o C 5.5 o C 33 Note: Based on two screw chillers in series evap low flow, counter-flow cond. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans Parallel Configuration Large Capacity Plants COP Chillers 6.6 System o C 28.0 o C, 349 L/s 116 kw p 30.5 K 36.0 o C 5.5 o C Waterside Lift 16.5 o C 4 off 2.5MW, COP o C, 217 L/s 113 kw p 34 Note: Based on two duplex centrifugal chillers in series evap low flow, counter-flow cond. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans 17
18 Parallel Configuration Large Capacity Plants COP Chillers 6.9 System o C 28.0 o C, 344 L/s 115 kw p 16.5 o C 26.0 K 36.0 o C 2 off 5.0 MW, COP K 31.5 o C 5.5 o C, 217 L/s 115 kw p 10.0 o C 5.5 o C Waterside Lift 35 Note: Based on two duplex centrifugal chillers in parallel evap low flow, counter-flow cond. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans Series Series (counter-flow) Large Capacity Plants COP Chillers 7.4 System o C 31.6 o C 28.0 o C, 340 L/s 113 kwp 15.5 o C 127 kw 5.5MW, p COP o C 23.2 K 23.8 K 10 o C 33.8 o C 31.6 o C 4.5MW, COP K 29.8 o C 5.5 o C, 238 L/s 12.7 o C Waterside Lift 10 o C 7.7 o C 5.5 o C 36 Note: Based on two duplex centrifugal chillers in series evap low flow, counter-flow cond. Pump heads at 400/250 kpa, cross-flow towers. System COP includes chillers, pumps & tower fans 18
19 Summary of EarthWise Chiller Plant Configurations Low flow CHW and CDW improves system COP Series connection improves performance at full and part load Use variable flow to improve pumping efficiency VPF with Series chillers maximizes pump savings Potential savings with variable condenser water flow at low loads Couple with overall chiller, pump and tower sequencing strategy Include optimal tower water control 37 CHILLER, TOWER AND PUMPING OPTIMIZATION 38 19
20 Chiller Tower Optimization Wet-bulb Condenser water temperature Heat Rejection Load Tower Design Cooling Load Condenser water temperature Chiller design 39 Condenser water control At Part Load Hot? 29ºC minimizes tower fan power, increases chiller power Cold? 15ºC minimizes chiller power, increases tower fan power Wet-bulb + 3K approach? Assumption that Load WB... Not always true! Approach is not fixed Optimized? Dynamic reset based on load & ambient to minimize system energy 40 20
21 Chiller Tower Optimization energy consumption, kw total chiller tower optimal control point condenser water temperature, C Note: Chiller at 50% Load, ambient 10ºC WB CTO comparisons 1,200,000 CHW Plant Annual Energy Cons [kwh] 1,000, , , , ,000-15C 18C 20C 22C 25C CTO ~ 6% Towers Pumps Chillers 2 3 yr payback 40% ROI CT Minimum Temp Set Point [ºC] 42 Sydney Commercial Office Application; BCA Class 5 schedules 2,200 kw cooling, water-cooled screw chillers, VAV, Econ cycle, 21
22 Chiller Tower Optimization RH T T TRACER SYSTEM LEVEL CONTROLS F F 43 Pumping Optimization Variable Flow CHW systems System Level critical valve reset Keeps critical valve near fully open Dynamic reset of δp set point Minimizes pumping power Better coil and temperature control Air Handling Units Better acoustics TRACER SYSTEM LEVEL CONTROLS VFD VV CHWP Control Valves Pressure Differential Controller or Transmitter 44 22
23 Questions or Comments Simon Ho e: 45 23
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
Optimizing Design & Control Of Chilled Water Plants Part 5: Optimized Control Sequences
This article was published in ASHRAE Journal, June 212. Copyright 212 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates
Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.
providing insights for today s hvac system designer Engineers Newsletter volume 43 2 Chilled-Water Systems Design Issues Learning from past mistakes As with anything in life, you can learn HVAC design
ULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-
How To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
What are the Carrier ChillerVu Energy Dashboards?
Energy Dashboard CARRIER CORPORATION 2015 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-564-01 12/9/2015 Verify that you have the most current version of this
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
Secondary Loop Chilled Water In Super High-Rise
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
Typical Cooling Load Profile
Ice Storage Systems and Impact on Electric Demand Georges Hoeterickx Specialists in Heat Transfer Products and Services 1 2 Cooling Load Typical Cooling Load Profile 0 2 4 6 8 10 12 14 16 18 20 22 Time
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian
Denver International Airport Total Facility Optimization Josh Foerschler Aurom Mahobian AGENDA DIA Intro BMcD-DIA History Optimization Projects Results Conclusion Denver International Airport Opened February
Building Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
TES for Medical Center
First Place: Industrial Facilities or Processes, New This article was published in ASHRAE Journal, November 2012. Copyright 2012 ASHRAE. Reprinted here by permission from ASHRAE at www.tecothermalenergy.com.
*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.
providing insights for today s hvac system designer Engineers Newsletter volume 41 3 Condenser Water System Savings Optimizing flow rates and control Optimized flow rates in the condenser water system
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Water cooled chiller plant (cp/vs)
Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the
ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS
ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS By: T. S. Wan Date: April 19, 1994 (1st draft 3/7/86) Copyright 1994 by T. S. Wan (All rights reserved) ABSTRACT: The technology of energy
BEC 2012 Vs BEC 2015 - Summary of Major Amendments
- Summary of Major Amendments Note: 1. The following summary table includes the major amendments, with requirements tightened in general for enhanced energy efficiency. Please refer to BEC 2015 for the
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Model-Based Approach for Optimizing a Data Center Centralized Cooling System
Model-Based Approach for Optimizing a Data Center Centralized Cooling System Monem H. Beitelmal, Chandrakant D. Patel Enterprise Software and Systems Laboratory HP Laboratories Palo Alto HPL-6-67 April
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
Enclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP [email protected] CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
Tim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
Large Energy Savings Per Installation VFDs for Large Chillers
This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.tiaxllc.com.
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
NetApp Data Center Design
NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions Data Center Design Evolution Capacity Build Cost
CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa
CHILLED WATER PLANT PUMPING SCHEMES James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa ABSTRACT From the advent of central chilled water plants, the system for delivering chilled water to
ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS
ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS Van D. Baxter, Oak Ridge National Laboratory, Oak Ridge, TN 37831-6070 ABSTRACT Present supermarket refrigeration systems require very large refrigerant charges
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Datacenter Efficiency Program
Datacenter Efficiency Program Yuming Qiu, CLEAResult Anna Stieve, CLEAResult Michael Stachowiak, CLEAResult Abstract Worldwide, datacenter energy consumption is skyrocketing and datacenter energy efficiency
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
PAYGO for Data Center -- Modular Infrastructure
PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
CODE ON PERIODIC ENERGY AUDIT OF BUILDING COOLING SYSTEM. 1 st Edition. 1 P a g e
CODE ON PERIODIC ENERGY AUDIT OF BUILDING COOLING SYSTEM 1 st Edition 1 P a g e Contents INTRODUCTION... 4 1. SCOPE... 5 2. DEFINITIONS... 5 3. STATUTORY REQUIREMENTS... 7 3.1 Act and Regulations... 7
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium
HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING Cleide Aparecida Silva 1, [email protected] Stéphane Bertagnolio 1, [email protected]
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
HVAC System Selection Criteria. RTSPco Technical department M.dadkhah
HVAC System Selection Criteria RTSPco Technical department M.dadkhah An HVAC system maintains desired environmental conditions in a space. In almost every application, many options are available to the
Data Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.
Tips and Tricks for Estimating Energy Savings Celeste Cizik, P.E. Project Manager E M C Engineers, Inc. AIA Quality Assurance Learning Objectives 1. Understand the pros and cons of various energy calculation
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program
High Altitude HVAC. Silvertip Integrated Engineering Consultants [email protected] www.silvertipconsultants.com
Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering
Section 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2
HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS
HEATING AND COOLING GENERATION AND DISTRIBUTION SYSTEMS Central Vs Decentralized Systems Stephan Richter, Ph.D GEF Inginieur, Germany Scot Duncan Retrofit Originality Incorporated, USA Heating and cooling
SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING
SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING Prof. Gershon Grossman Faculty of Mechanical Engineering Technion, Israel Institute of Technology Haifa 32000, ISRAEL November 2010 Solar Cooling,
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
Advanced Heat Reclaim Systems. Harrison Horning, PE, CEM Delhaize America - Hannaford
Advanced Heat Reclaim Systems Harrison Horning, PE, CEM Delhaize America - Hannaford Outline Basic refrigeration cycle Conventional series heat reclaim Full-condensing parallel heat reclaim Direct Hydronic
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
