ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
|
|
|
- Mildred Poole
- 10 years ago
- Views:
Transcription
1 Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its entirety: Cover Page: 1 page Report Body: 16 pages Test Equipment: 1 page Sketches: 5 pages Photograph: 1 page Drawings: 7 pages Report No.: Revision 1: 09/21/09 Test Dates: 08/17/09 Through: 08/23/09 Report Date: 09/11/09 Expiration Date: 08/23/ :01:43-04'00' 130 Derry Court York, PA phone: fax:
2 ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. 100 South Road Torrington, Connecticut Report No.: Test Dates: 08/17/09 Through: 08/23/09 Report Date: 09/11/09 Expiration Date: 08/23/13 Project Summary: Architectural Testing, Inc. was contracted by Norse, Inc. to perform testing on three Series/Model Flush Mount and Series/Model Surface Mount, hurricane shutter fastening system. The samples tested met the performance requirements set forth in the referenced test procedures for a ±2155 Pa (±45.0 psf) Design Pressure with missile impacts corresponding to Missile Level D and Wind Zone 4. Test specimen description and results are reported herein. The samples were provided by the client. Test Procedures: The test specimens were evaluated in accordance with the following: ASTM E , Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. ASTM E , Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials. ASTM E , Standard Specification for Performance of Exterior Windows, Glazed Curtain Walls, Doors and Storm Shutters Impacted by Wind Borne Debris in Hurricanes. 130 Derry Court York, PA phone: fax:
3 Page 2 of 16 Test Specimen Description: Test Specimen #1 through #3: Series/Model: Flush Mount Fastening System Product Type: Hurricane Shutter Overall Size: 1829 mm (72") wide by 2032 mm (80") high Rough Opening Size: 1829 mm (72") wide by 2032 mm (80") high Test Specimen #4: Series/Model: Surface Mount Product Type: Hurricane Shutter Fastening System Overall Size: 1902 mm (74-7/8") wide by 2073 mm (81-5/8") high Rough Opening Size: 1829 mm (72") wide by 2032 mm (80") high The following descriptions apply to all specimens. Finish: All hardware had a mill finish. All plywood was natural. Panel Construction: The shutter panels were constructed of two sheets of nominal 5/8" thick plywood sheathing. The two panels utilized a 6" wide by 3/4" thick piece of plywood at the center vertical joint. The 6" wide piece of plywood was secured to the exterior left plywood panel with #10 x 1-5/8" long pan head screws located at each end, and spaced 4-1/2" on center with a staggered spacing. Test Buck Construction: The test bucks were constructed of C12 x 20.7 steel C-Channel wrap. The wrap utilized fully welded corners. The test buck utilized a solid poured concrete (3000 psi) sill, measuring 14" wide by 7-1/2" tall. Hollow 8" by 8" by 8" long grout-filled CMU half-block was laid up each jamb with nominal 1/4" mortar joints. A solid 8" by 8" continuous lintel was utilized at the top of the test wall. The grout-filled CMU block and the lintel was secured to the steel wrap with 1/4" x 1-1/2" long Tapcon anchors spaced 16" on center. The test bucks utilized 1" by 1" by 0.062" thick aluminum tubing inside the rough opening. The aluminum tubing was utilized to simulate an aluminum window/patio door frame. The tubing was secured to the test buck with 1/4" x 1-1/2" long Tapcon anchors spaced 12" on center. The surface mount utilized the tubing at the exterior edge of the opening and the flush mount utilized the tubing set back 5/8" from the exterior edge of the test buck.
4 Page 3 of 16 Test Specimen Description: (Continued) Installation Details: Flush Mount Installation: The shutter system was installed into a concrete-masonryunit (CMU) grout filled wall. Steel hooks, measuring 1-3/8" wide by 1" tall by 0.07" thick were secured to the lintel with two #10 x 2" long Tapcon concrete anchors, (Reference Norse drawing). The hooks were located on the lintel, 4" from each CMU jambs and spaced approximately 9" on center (eight total clips, four per panel). Receiving clips for the hooks were located on the plywood panel at each hook location. The receiving clips were secured with two #10 x 1" long machine bolts with nuts and washers. Surface Mount Installation: The shutter system was installed onto the exterior surface of a concrete-masonry-unit (CMU) grout filled wall. Steel hooks, measuring 1-3/8" wide by 1" tall by 0.07" thick were secured to the lintel with two #10 x 2" long Tapcon concrete anchors, (Reference Norse drawing). The hooks were located on the lintel, 4" from each CMU jambs and spaced approximately 7" on center (ten total clips, five per panel). Receiving clips for the hooks were located on the plywood panel at each hook location. The receiving clips were secured with two #10 x 1" long machine bolts with nuts and washers. The following installation details apply to both Flush Mount and Surface Mount test specimens. The left and right sides of the plywood were secured with a "keyed-hooking" system, (Reference Norse drawing). Four clips were utilized on each side, located 8" from the head and sill and spaced approximately 21-1/2" on center. The "keyed-hooks" were secured to the plywood sheathing with four #10 x 5/8" long pan head screws. The receiving clip for the "keyed-hooks" was secured to the CMU jambs with two #10 x 2" long Tapcon concrete anchors. The vertical joint four of the "keyed-hooks", located 8" from the head and sill and spaced approximately 21-1/2" on center. The "keyed-hooks" were secured to the plywood sheathing with four #10 x 5/8" long pan head screws. The receiving clip for the "keyed-hooks" was secured to the plywood sheathing with two #10 x 1" long machine bolts with nuts and washers. The bottom of the plywood was secured with 0.12" thick steel L-shaped clips measuring 1-1/2" wide by 1" wide and tall. The clips were located 4" from each end and spaced approximately 13-1/2" on center. The clips were secured to the plywood with two #10 x 5/8" long pan head screws through the clips and into the plywood. The clip was also secured to the poured concrete sill with one #1/4 x 1-1/2" long hex head lag bolt with concrete anchor, (Reference Norse Drawing).
5 Page 4 of 16 Test Results: The following results have been recorded: Protocol ASTM E330-02, Static Air Pressure Tests Test Unit #1 (Flush Mount) Design Pressure: ±45.0 psf Title of Test Results Indicator Readings (inch) Structural Loads #1 #2 #3 #4 #5 #6 #7 #8 #9 50% of Test Pressure ( psf) Maximum Deflection Permanent Set <0.01 <0.01 Design Pressure ( psf) Maximum Deflection Permanent Set < % of Test Pressure ( psf) Maximum Deflection Permanent Set Design Pressure ( psf) Maximum Deflection Permanent Set Test Pressure ( psf) Maximum Deflection Permanent Set Test Pressure ( psf) Maximum Deflection Permanent Set Note: See Architectural Testing Sketch #1 for indicator locations.
6 Page 5 of 16 Test Results: (Continued) Protocol ASTM E330-02, Static Air Pressure Tests Test Unit #4 (Surface Mount) Design Pressure: ±45.0 psf Title of Test Results Indicator Readings (inch) Structural Loads #1 #2 #3 #4 #5 #6 #7 #8 #9 50% of Test Pressure ( psf) Maximum Deflection Permanent Set Design Pressure ( psf) Maximum Deflection Permanent Set % of Test Pressure ( psf) Maximum Deflection Permanent Set Design Pressure ( psf) Maximum Deflection Permanent Set Test Pressure ( psf) Maximum Deflection Permanent Set Test Pressure ( psf) Maximum Deflection Permanent Set Note: See Architectural Testing Sketch #1 for indicator locations.
7 Page 6 of 16 Test Results: (Continued) ASTM E 1886, Large Missile Impact Conditioning Temperature: 22 C (72 F) Missile Weight: 4196 g (9.25 lbs) Missile Length: 2.3 m (7' 8-1/2") Muzzle Distance from Test Specimen: 5.2 m (17 ft.) Test Unit #1 (Flush Mount) Impact #1: Missile Velocity: 15.4 m/s (50.6 fps); orientation within ±5 of vertical Impact Area: Center of right panel Observations: Missile hit target area, no penetration. Deflection: 5.6 mm (0.22") Results: Pass Impact #2: Missile Velocity: 15.2 m/s (50.0 fps); orientation within ±5 of vertical Impact Area: Upper right corner of right panel Observations: Missile hit target area, resulting in minor splitting of the plywood, no penetration. Deflection: 3.3 mm (0.13") Results: Pass Impact #3: Missile Velocity: 15.4 m/s (50.6 fps); orientation within ±5 of vertical Impact Area: Midspan of vertical joint. Observations: Missile hit target area, no penetration. Deflection: 5.1 mm (0.20") Results: Pass Note: See Architectural Testing Sketch #2 for impact locations.
8 Page 7 of 16 Test Results: (Continued) ASTM E 1886, Large Missile Impact Conditioning Temperature: 22 C (72 F) Missile Weight: 4196 g (9.25 lbs) Missile Length: 2.3 m (7' 8-1/2") Muzzle Distance from Test Specimen: 5.2 m (17 ft.) Test Unit #2 (Flush Mount) Impact #1: Missile Velocity: 15.2 m/s (49.9 fps); orientation within ±5 of vertical Impact Area: Center of right panel Observations: Missile hit target area, no penetration. Deflection: 31.8 mm (1.25 ") Results: Pass Impact #2: Missile Velocity: 15.3 m/s (50.3 fps); orientation within ±5 of vertical Impact Area: Lower left corner of right panel Observations: Missile hit target area, no penetration. Deflection: 10.7 mm (0.42") Results: Pass Impact #3: Missile Velocity: 15.4 m/s (50.4 fps); orientation within ±5 of vertical Impact Area: Midspan of vertical joint. Observations: Missile hit target area, cracked the plywood strip, joining the panels, no penetration. Deflection: 10.2 mm (0.40") Results: Pass Note: See Architectural Testing Sketch #3 for impact locations.
9 Page 8 of 16 Test Results: (Continued) ASTM E 1886, Large Missile Impact Conditioning Temperature: 22 C (72 F) Missile Weight: 4196 g (9.25 lbs) Missile Length: 2.3 m (7' 8-1/2") Muzzle Distance from Test Specimen: 5.2 m (17 ft.) Test Unit #3 (Flush Mount) Impact #1: Missile Velocity: 15.2 m/s (49.9 fps); orientation within ±5 of vertical Impact Area: Center of right panel Observations: Missile hit target area, resulting in full penetration of missile, 3" sphere cannot freely pass through penetration. Deflection: N/A (transducer released upon impact) Results: Pass Impact #2: Missile Velocity: 15.2 m/s (49.9 fps); orientation within ±5 of vertical Impact Area: Upper right corner of right panel Observations: Missile hit target area, resulting in full penetration of missile. 3" sphere cannot freely pass through penetration. Deflection: N/A (transducer released upon impact) Results: Pass Impact #3: Missile Velocity: 15.4 m/s (50.4 fps); orientation within ±5 of vertical Impact Area: Midspan of vertical joint. Observations: Missile hit target area, cracked the plywood strip, joining the panels, no penetration. Deflection: 10.2 mm (0.40") Results: Pass Note: See Architectural Testing Sketch #4 for impact locations.
10 Page 9 of 16 Test Results: (Continued) ASTM E 1886, Large Missile Impact Conditioning Temperature: 22 C (72 F) Missile Weight: 4196 g (9.25 lbs) Missile Length: 2.3 m (7' 8-1/2") Muzzle Distance from Test Specimen: 5.2 m (17 ft.) Test Unit #4 (Surface Mount) Impact #1: Missile Velocity: 15.3 m/s (50.1 fps); orientation within ±5 of vertical Impact Area: Center of right panel Observations: Missile hit target area, no penetration. Deflection: 4.1 mm (0.16") Results: Pass Impact #2: Missile Velocity: 15.3 m/s (50.1 fps); orientation within ±5 of vertical Impact Area: Lower left corner of right panel Observations: Missile hit target area, resulting in a full penetration of the missile, 3" sphere cannot freely pass through the penetration. Deflection: N/A Results: Pass Impact #3: Missile Velocity: 15.3 m/s (50.3 fps); orientation within ±5 of vertical Impact Area: Midspan of vertical joint. Observations: Missile hit target area, no penetration. Deflection: 12.2 mm (0.48") Results: Pass Note: See Architectural Testing Sketch #5 for impact locations.
11 Page 10 of 16 Pressure Range Pa (psf) 430 to 1077 (9.0 to 22.5) 0 to 1293 (0 to 27.0) 1077 to 1724 (22.5 to 36.0) 646 to 2155 (13.5 to 45.0) Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #1 (Flush Mount) Design Pressure: ±2155 Pa (±45.0 psf) Number of Cycles Average Cycle Time (seconds) POSITIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 5.3 (0.21) 5.3 (0.21) 5.3 (0.21) 5.3 (0.21) 0.3 (0.01) 46.5 (1.83) 51.0 (2.01) 63.2 (2.49) 71.1 (2.80) 7.1 (0.28) 5.6 (0.22) 5.6 (0.22) 5.6 (0.25) 7.4 (0.29) 2.0 (0.08) 5.3 (0.21) 4.3 (0.17) 4.3 (0.17) (0.21) (0.17) (0.19) (0.25) (0.17) (0.27) (0.27) (0.17) (0.27) Permanent Set (0.01) (0.01) (0.05) 10.9 (0.43) 11.4 (0.45) 13.2 (0.52) 14.0 (0.55) 2.5 (0.10) 14.0 (0.55) 14.7 (0.58) 17.0 (0.67) 18.3 (0.72) 2.3 (0.09) 11.2 (0.44) 11.4 (0.45) 13.5 (0.53) 14.2 (0.56) 4.6 (0.18) Pressure Range Pa (psf) 646 to 2155 (13.5 to 45.0) 1077 to 1724 (22.5 to 36.0) 0 to 1293 (0 to 27.0) 430 to 1077 (9.0 to 22.5) Number of Cycles Average Cycle Time (seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 # (0.54) 10.9 (0.43) 10.7 (0.42) 10.2 (0.40) 0.5 (0.02) 73.2 (2.88) 63.8 (2.51) 52.8 (2.08) 48.5 (1.91) 5.3 (0.21) 18.3 (0.72) 17.5 (0.69) 12.4 (0.49) 13.2 (0.52) 4.8 (0.19) 10.4 (0.41) 23.6 (0.93) 9.9 (0.39) (0.39) (0.90) (0.37) (0.28) (0.23) (0.21) (0.35) (0.19) (0.22) Permanent Set (0.14) (0.18) (0.07) 17.3 (0.68) 15.5 (0.61) 10.9 (0.43) 10.7 (0.42) 1.5 (0.06) 18.0 (0.71) 17.0 (0.70) 11.7 (0.46) 10.9 (0.43) 1.0 (0.04) 13.7 (0.54) 13.0 (0.51) 5.8 (0.23) 5.1 (0.20) 0.3 (0.01) Observations: No additional damage was observed. Result: Pass Note: See Architectural Testing Sketch #1 for indicator locations.
12 Page 11 of 16 Pressure Range Pa (psf) 430 to 1077 (9.0 to 22.5) 0 to 1293 (0 to 27.0) 1077 to 1724 (22.5 to 36.0) 646 to 2155 (13.5 to 45.0) Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #2 (Flush Mount) Design Pressure: ±2155 Pa (±45.0 psf) Number of Cycles Average Cycle Time (seconds) POSITIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 7.4 (0.29) 7.6 (0.30) 9.9 (0.39) 9.9 (0.39) 2.5 (0.10) 47.8 (1.88) 53.1 (2.09) 67.1 (2.64) 73.4 (2.89) 10.9 (0.43) 10.9 (0.43) 11.4 (0.45) 13.0 (0.51) 13.7 (0.54) 6.6 (0.26) 3.6 (0.14) 6.6 (0.26) 6.9 (0.27) (0.14) (0.26) (0.28) (0.18) (0.32) (0.34) (0.18) (0.33) (0.34) Permanent Set (0.07) (0.15) (0.16) 13.7 (0.54) 14.0 (0.55) 16.3 (0.64) 16.8 (0.66) 8.9 (0.35) 17.0 (0.67) 17.8 (0.70) 20.6 (0.81) 21.3 (0.84) 11.2 (0.44) 16.3 (0.64) 17.0 (0.67) 19.3 (0.76) 20.1 (0.79) 10.2 (0.40) Pressure Range Pa (psf) 646 to 2155 (13.5 to 45.0) 1077 to 1724 (22.5 to 36.0) 0 to 1293 (0 to 27.0) 430 to 1077 (9.0 to 22.5) Number of Cycles Average Cycle Time (seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 # (1.55) 39.4 (1.55) 35.8 (1.41) 34.3 (1.35) 25.4 (1.00) 96.3 (3.79) 90.2 (3.55) 75.9 (2.99) 71.4 (2.81) 28.4 (1.12) 31.2 (1.23) 30.7 (1.21) 27.7 (1.09) 26.7 (1.05) 15.2 (0.60) 15.2 (0.60) 17.8 (0.70) 17.3 (0.68) (0.60) (0.69) (0.68) (0.58) (0.67) (0.73) (0.58) (0.67) (0.68) Permanent Set (0.51) (0.58) (0.60) 21.8 (0.86) 21.8 (0.86) 18.5 (0.73) 17.8 (0.70) 12.4 (0.49) 26.7 (1.05) 26.4 (1.04) 22.1 (0.87) 21.1 (0.83) 14.7 (0.58) 24.9 (0.98) 24.4 (0.96) 20.8 (0.82) 19.8 (0.78) 14.8 (0.56) Observations: No additional damage was observed. Result: Pass Note: See Architectural Testing Sketch #1 for indicator locations.
13 Page 12 of 16 Pressure Range Pa (psf) 430 to 1077 (9.0 to 22.5) 0 to 1293 (0 to 27.0) 1077 to 1724 (22.5 to 36.0) 646 to 2155 (13.5 to 45.0) Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #3 (Flush Mount) Design Pressure: ±2155 Pa (±45.0 psf) Number of Cycles Average Cycle Time (seconds) POSITIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 # (0.42) (1.75) (0.21) (0.32) (0.36) (0.36) (0.47) (0.51) (0.46) (0.44) (1.81) (0.23) (0.33) (0.37) (0.37) (0.48) (0.52) (0.48) (0.52) (2.42) (0.31) (0.42) (0.45) (0.45) (0.58) (0.63) (0.56) (0.54) (2.63) (0.34) (0.44) (0.48) (0.47) (0.62) (0.67) (0.59) Permanent Set (0.27) (0.42) (0.14) (0.21) (0.23) (0.19) (0.25) (0.29) (0.23) Pressure Range Pa (psf) 646 to 2155 (13.5 to 45.0) 1077 to 1724 (22.5 to 36.0) 0 to 1293 (0 to 27.0) 430 to 1077 (9.0 to 22.5) Number of Cycles Average Cycle Time (seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 # (0.90) (2.81) (0.65) (0.60) (0.52) (0.43) (0.70) (0.82) (0.72) (0.87) (2.58) (0.60) (0.57) (0.49) (0.40) (0.64) (0.76) (0.65) (0.84) (2.33) (0.54) (0.57) (0.49) (0.39) (0.59) (0.69) (0.59) (0.79) (2.14) (0.51) (0.56) (0.47) (0.39) (0.57) (0.67) (0.57) Permanent Set (0.26) (0.70) (0.17) (0.39) (0.38) (0.18) (0.33) (0.31) (0.34) Observations: No additional damage was observed. Result: Pass Note: See Architectural Testing Sketch #1 for indicator locations.
14 Page 13 of 16 Pressure Range Pa (psf) 430 to 1077 (9.0 to 22.5) 0 to 1293 (0 to 27.0) 1077 to 1724 (22.5 to 36.0) 646 to 2155 (13.5 to 45.0) Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #3 (Flush Mount) Design Pressure: ±2155 Pa (±45.0 psf) Number of Cycles Average Cycle Time (seconds) POSITIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 #9 7.6 (0.30) 7.9 (0.31) 8.4 (0.33) 8.9 (0.35) 1.0 (0.04) 58.7 (2.31) 66.0 (2.60) 72.6 (2.86) 87.1 (3.43) 3.8 (0.15) 4.6 (0.18) 4.6 (0.18) 5.1 (0.20) 6.4 (0.25) 1.5 (0.06) 3.8 (0.15) 4.3 (0.17) 3.8 (0.15) (0.15) (0.17) (0.16) (0.16) (0.20) (0.18) (0.18) (0.21) (0.18) Permanent Set (0.13) (0.07) (0.12) 2.5 (0.10) 2.8 (0.11) 3.0 (0.12) 3.6 (0.14) 1.5 (0.06) 1.3 (0.05) 1.3 (0.05) 1.5 (0.06) 1.8 (0.07) 1.3 (0.05) 1.5 (0.06) 2.0 (0.08) 2.3 (0.09) 2.3 (0.09) 1.0 (0.04) Pressure Range Pa (psf) 646 to 2155 (13.5 to 45.0) 1077 to 1724 (22.5 to 36.0) 0 to 1293 (0 to 27.0) 430 to 1077 (9.0 to 22.5) Number of Cycles Average Cycle Time (seconds) NEGATIVE PRESSURE Maximum Deflection at Indicator mm (inch) #1 #2 #3 #4 #5 #6 #7 #8 # (0.60) 19.6 (0.77) 22.3 (0.88) 22.3 (0.88) 21.3 (0.84) 79.0 (3.11) 76.7 (3.02) 70.4 (2.77) 65.8 (2.59) 4.8 (0.19) 16.0 (0.63) 16.8 (0.66) 15.7 (0.62) 16.5 (0.65) 2.5 (0.10) 11.7 (0.44) 12.2 (0.48) 5.8 (0.23) (0.73) (0.69) (0.70) (0.78) (0.70) (0.69) (1.42) (0.68) (0.65) Permanent Set (0.94) (0.24) (0.21) 18.0 (0.71) 18.0 (0.71) 16.3 (0.64) 15.7 (0.62) 3.0 (0.12) 19.8 (0.78) 19.8 (0.78) 17.8 (0.70) 17.3 (0.68) 2.8 (0.11) 19.1 (0.75) 19.1 (0.75) 16.8 (0.66) 16.0 (0.63) 2.8 (0.11) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #1 for indicator locations.
15 Page 14 of 16 General Note: Upon completion of testing, the specimens met the requirements of Section 7 of ASTM E Test Equipment: (See Appendix A) Cannon: Constructed from steel piping utilizing compressed air to propel the missile Missile: 2x4 Southern Pine Timing Device: Electronic Beam Type Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein. List of Official Observers: Name Chris Langer Alfred C. Langer Aaron M. Shultz Tim J. McGill Michael D. Stremmel, P.E. Eric M. Brennan Company Norse, Inc. Norse, Inc. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc.
16 Page 15 of 16 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Eric M. Brennan Technician Michael D. Stremmel, P.E. Senior Project Engineer EMB:dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Test Equipment (1) Appendix-B: Sketches (5) Appendix-C: Photograph (1) Appendix-D: Drawings (7)
17 Page 16 of 16 Revision Log Rev. # Date Page(s) Revision(s) 0 09/11/09 N/A Original report issue 1 09/21/09 Cover Page, Page 15, and Appendix D Revised drawing packet to include missed drawings. This report produced from controlled document template ATI 00165, revised 03/05/09.
18 Appendix A Test Equipment Instrument Manufacturer Asset # 20" Linear Transducer Celesco Y " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco Y " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco Control Panel (Blower) Architectural Testing, Inc Control Panel (Blower) Architectural Testing, Inc Cannon Architectural Testing, Inc
19 Appendix B Sketches
20
21
22
23
24
25 Appendix C Photograph Product Overview
26 Appendix D Drawings
27
28
29
30
31
32
33
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight
FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims
PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM
PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window
BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window
Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing
TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry
TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized
TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
2.9 WINDOW & DOOR BUCKS
2.9 WINDOW & DOOR BUCKS Bucks provide attachment surfaces for windows and doors while holding back concrete from these openings during concrete placement. Mark the center and edges of openings as you place
TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"
TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405
PERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.
PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions
Y Parts Included: Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Tools Required: Power Driver Drill Bit (Determined by fastener) Driver Bit (Determined by fastener)
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
TEST REPORT. Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California
Architectural Testing TEST REPORT Report No.: A8865.01-301-41 Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California TYPE: Dome Assembly Only SERIES/MODEL: Nano Insulgel - ALT-CM-2-CPM/16 mm CNANO Thermally
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
ICC-ES Evaluation Report
ICC-ES Evaluation Report ESR-2369 Reissued May 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
Protecting Your Home From Hurricane Wind Damage
T H E W I N D Protecting Your Home From Hurricane Wind Damage During a hurricane, homes may be damaged or destroyed by high winds and high waves. Debris can break windows and doors, allowing high winds
DE Frame with C Series Sidelight
TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
Architectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
SECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
Protecting Your Home from Wind Damage
Protecting Your Home from Wind Damage During severe thunderstorms or hurricanes, homes may be damaged or destroyed by high winds. Debris flying through the air can break windows and doors, allowing high
WHI 90-Minute Rated Veneered Door Frame Installation Instructions
No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,
SERIES 238 WINDOWS. NOTE: Read instructions completely before attempting any installation.
1 Installation Instructions SERIES 238 WINDOWS Page 2: Page 3-4: Page 5: Page 6: Page 7: Opening Preparation and Wood Buck Installation Installation Instructions for Series 238 WINDOWS Figure 1: Buck preparation
WINDOW PANNING AND TRIMS
OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
SECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
STANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Superform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
Wind Mitigation Inspection
[email protected] Tampa Bay Area: SW & Central Florida: (813) 368-6407 (239) 896-3986 Wind Mitigation Inspection VonHaase, Dale 4585 Bowen Bayou Road Sanibel, FL 33957 5/6/2013 Note to Policyholder:
Important Information for Installer & Homeowner
Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
STANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
Specifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015
0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:
F-Series Camera Mounting Accessories
F-Series Camera Mounting Accessories Document Number: 427-0462-00-12 Version: 100 Issue Date: September 2010 2010. All rights reserved worldwide. FLIR Commercial Systems, Inc. 70 Castilian Drive Goleta,
Impact-Resistant Windows and Sliding Glass Doors
Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they
Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors
Installation Manual Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors SW602206 Rev B Table of Contents Chapter 1: Safety Warning... 3 Chapter 2: Kit Contents... 4 Included in Kit...
How to secure your property after a disaster
How to secure your property after a disaster The Red Guide to Recovery HOuse secured properly Board-Up of Windows, Doors and Roof Hole. Lot secured with Perimeter Fencing. Fires, floods, tornadoes, hurricanes,
General Approach. Structure Components. Is all lumber the same? Lumber Grades. Rafters Girders / Beams Columns. Sketch general structural layout
General Approach Sketch general structural layout Determine roof loading Determine required lumber dimensions Transfer load down the structure Structure Components Plants Structure Components Top Side
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
ATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 09/01/2016 Issued: 09/04/2015 Visit www.ati-es.com for current status Page 1 of 17 UFP Ventures II,
Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows
Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Series 2050 Garden Window The Series 2050 standard garden window has an outstanding reputation for its distinctive design and excellent
PERIMETER FLASHING. Table of Contents
FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...
www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014
ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION
SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
RPS - [email protected] - 858 755 4505-12478 San Bruno Cove, San Diego, CA 92130
RPS - [email protected] - 858 755 4505-2478 San Bruno Cove, San Diego, CA 9230 SWH Solar Mount Rail R-MR-SW-SR-0.5, R-MR-SW-SR-2, R-MR-SW-SR-4, R-MR-SW-SR-4B, R-MR-SW-SR-7 Part No. MR-SW-SR-0.5, MR-SW-SR-2,
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures R. A. Van Straaten 1, G. A. Kopp 2, J. F. Straube 3 1 Research Lab for Better Homes, University of Western
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
INSTALLATION INSTRUCTIONS for Vinyl Windows without Nailing Fin (JII011) ImPOrTANT INFOrmATION & GlOssAry. rough OPeNINGs
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for vinyl windows without a nailing fin (including finless, flush fin and flange). Read these instructions
Discipline: Structural Issued 04-26-06
California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This
Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
Custom 30 x 20-8 Garage Plan Plan #g233 By SDS-CAD Specialized Design Systems
P O Box 34 Mendon, Utah Custom 30 x 20-8 Garage Plan Plan #g233 By Page 1 Title Page Page 2 Main Floor Plan Page 3 Foundation Plan Page 4 Elevation Views Page 5 Framing and Details Page 6 Typical Section