Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures

Size: px
Start display at page:

Download "Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures"

Transcription

1 Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures R. A. Van Straaten 1, G. A. Kopp 2, J. F. Straube 3 1 Research Lab for Better Homes, University of Western Ontario, London, Canada. rvanstra@uwo.ca 2 Boundary Layer Wind Tunnel Lab, University of Western Ontario, London, Canada. gak@blwtl.ca 3 Building Engineering Group, University of Waterloo, Waterloo, Canada jfstraube@uwaterloo.ca ABSTRACT A method for testing a series of windows exposed to simulated real dynamic wind loads is proposed. Three vinyl framed residential windows installed in a full scale wood framed house were tested with the method. The windows were exposed to realistic fluctuating wind pressures on the surface of a building, obtained from wind tunnel experiments, and were replicated in full-scale using novel pressure loading actuators. In the series of tests reported herein, the incidence of water penetration was compared between static and dynamic pressure tests. It was found that the peak pressures at which the window s gasket systems could tolerate water exposure were much higher for realistic wind pressures than for those in the static pressure tests. The test methodology has the potential of providing greater insights of the performance of such systems exposed to actual severe wind storm conditions. 1. INTRODUCTION Water leakage, and particularly water leakage associated with window systems, has been identified as a significant contributor to moisture problems in buildings [1]. The recent North American Fenestration Standard/Specification for Windows, Doors, and skylights AAMA / WDMA / CSA 101 / I.S.2 / A [2] includes testing requirement for a window product s water infiltration performance under constant (i.e., static) pressure be reported as per test methodology ASTM E [3]. A methodology for water penetration testing under cyclical applications of air pressures is provided in ASTM E [4]. These cyclic pressures include application of a constant pressure for 5 minutes, reduced to no pressure for 1 minute, and repeated for at least 15 minutes. ASTM E [5] includes water penetration testing with rapid pulsed air pressure differences. These tests involve cycling pressure between 50% and 150% of a median air pressure. The frequency of the cycles is 0.5 Hz. The standard includes the detail The median test pressure used in this test method is defined as the specified test pressure supplied by the user and related to the maximum positive building design pressure. This detail will be discussed later in this paper. The standard also includes the commentary The pulsed pressure of this test method may act to pump water past dry seals and breather systems of units incorporating these features, thereby making the test method more severe than a static pressure

2 test method. On the other hand, the low pressure portions of the pressure cycles of this test method may allow weep systems and drainage dams to dissipate water from units incorporating these features, thereby making the test method less severe than a static pressure test method. From these comments it would seem sensible to apply realistic fluctuating pressures to such tests to address these concerns. Testing full scale building and building components under realistic wind pressures and driving rain conditions is undergoing or in development at several research institutions. Girma et al. [6] are using the International Hurricane Research Center s Wall of Wind, a wall consisting of large powerful fans, and water spray rack to expose building components to driving rain conditions. The advantage of introducing the water spray into a stream of air flowing past the specimen is that it allows the water droplets to follow more realistic paths. In ASTM testing the spray racks send a stream of water with impinging velocity and distribution irrespective of actual driving rain behaviour. Salzano et al. [7] have recently published testing on water penetration resistance of residential window installations using the University of Florida Hurricane Simulator. The system consists of water spray racks and eight large vaneaxial fans that produce stagnation pressures up to 1.67 kpa. The setup applies driving rain similarly to the Wall of Wind but they include rapidly varying cyclical pressures as high at 0.33 Hz. The Institute for Home and Business Safety [8] is developing a very large wind tunnel with capacity to test full scale houses. This facility will be able to replicate realistic fluctuating wind pressures (as opposed to sinusoidal pressures) and will also introduce wind driven rain into experiments. The Insurance Research Lab for Better Homes (IRLBH) at the University of Western Ontario has developed technology capable of imposing realistic static pressures following pressure traces derived from wind tunnel or field data. To date, use of this equipment in published research studies has been conducted the Cyclone Testing Station in Townsville Australia [9] to investigate structural performance of building components. IRLBH s equipment consist of relatively small pressure load actuators whose characteristic are described in greater detail by Kopp et. al. [10]. The equipment could be used for testing under realistic air pressure in small window test laboratories without the need for the electrical power and financial capital to construct large fan arrays. this paper reports on the most recent progress on the development of testing methodologies that utilize dynamic wind loads to investigate water penetration through window systems. 2. OBJECTIVE The objective of the work reported in this paper is to develop testing methodologies to investigate windows water penetration resistance performance under realistic fluctuating air pressures resulting from high wind conditions. 3. SCOPE The test method was applied to 89 cm x 153 cm windows installed in a house built to the Ontario Building Code in our laboratory. The house was used in a previous study which included application of high wind loads to the roof which may have affected the entire structure of the house. All windows were square and opened freely and did not appear to have significantly shifted or been effected structurally at the time of the testing. Some initial caulking failures on the exterior of the windows were evident prior to testing. Due to this consideration, the use of the results in this paper is limited to developing testing methodologies and not to make conclusion regarding window performance.

3 4. METHODOLOGY The facility utilized Pressure Load Actuators (PLAs) to provide the desired pressures. The units consist of a regenerative blower with high and low pressure side connected to a special valve. The valve position is changed by a high speed servo motor. The system is capable of following pressure traces with a frequency up of 7 Hz and pressures in a 1.2 m x 1.2 m enclosure air box up to 10 kpa when well air sealed. For this study a simple mobile air box was installed on the inside of the test house windows (Figure 1). Water was introduced with a spray rack system as prescribed in ASTM E and shown in Figure 2. Figure 2. Water Spray Rack. Figure 1.Air Box installed on inside of house. For this study, wind loads (air pressure traces) were drawn from positions on the building with high and moderate exposure and from a variety of wind velocities. The base wind pressures were derived from testing at the Boundary Layer Wind Tunnel Laboratory [11] and for higher wind velocities using previously developed techniques [12]. The pressures are spatially uniform, which is realistic for small windows away from corners. The windows were tested at constant pressures of 150 Pa, 360 Pa, 540 Pa, and 720 Pa with water exposure for 15 minutes as per ASTM E331. The windows were allowed to dry for at least 24 hrs between tests. These same windows were then tested when exposed to realistic air pressures traces derived from wind tunnel measurements of wall pressures at two points on a building at wind velocities of 20, 25 and 20 m/s. These traces had mean (peak) pressures of 113 (690) Pa, 169 (814) Pa, 180 (1078) Pa, 270 (1273) Pa, 261 (1552) Pa, and 394 (1832) Pa. Two of these traces are plotted in Figure 3. All pressure traces and exposures lasted for 15 minutes.

4 Pressure (kpa) m/s trace 20 m/s trace Time (s) Figure 3. Wind Pressure Trace with 20 m/s (690) Pa and 30 m/s (1552) Pa Mean (Peak) Pressure. In the test performed water leaked through the window gaskets well below rated performance of the window (B7 or 720 Pa static pressure as per CSA A440). We did not disassemble the window to investigate water leakage within the wall assembly between tests due to concerns about changing the nature of the window system between tests. Hence, water leakage may or may not have been occurring at the window to wall interface at the pressure reported in this paper or lower. A picture of a small water leak and a large water leak are shown in Figures 5 and 6. Water penetration on the indoor face of the specimen was recorded to identify failure. 5. RESULTS Measured pressure is plotted relative to the corresponding target pressure trace at peak pressure in Figure 4. Close agreement between targeted and achieved pressures are achieved in the test demonstrating the equipment s capabilities. Figure 5. Small (<5 g) Water Leak Air Pressure (kpa) m/s Trace Achieved 25 m/s Trace Achieved Figure 6. Large (>100 g) Water Leak Time (s) Figure 4. Trace (Targeted) and Achieved Air Pressure at 20 m/s (690) Pa and 25 m/s (1270) Pa Mean (Peak) Pressure Traces at Peak Pressure We did not attempt to measure the amount of water which leaked through the windows during the constant air pressure tests. However, it was generally a large amount which ran over the indoor window

5 sills, down the drywall, and onto the floor. These leaks are all indicated in Figure 7 as 100 g of water leakage even through they we not actually measured. Water Leakage (g) Window 1 Window 2 Window Static Pressure Test (Pa) Realistic Wind Test (Pa mean) Figure 7. Water Penetration Resistance Testing Results for Constant and Realistic Air Pressures. The results of the realistic pressure tests are also shown in Figure 7. Window 3 was the worst performer in both test methodologies. Windows 1 and 2 performed similarly. The windows failed at lower mean pressure conditions during the realistic fluctuating pressure testing than during the static pressure tests. Generally the water leakage in these tests appeared to be set off at peak gusts during the exposure period. During these tests we chose to measure the actual water leakage because in some cases only a small amount of water leaked through the gasket during a very brief and severe pressure fluctuation. The leakage was measured by weighing paper towels before and after being used to absorb as much of the leaked water as possible. 6. CONCLUSIONS The testing reported in this paper demonstrates the capability of pressure load actuator equipment to generate dynamic air pressures following real fluctuating wind data or wind tunnel data for water penetration resistance performance testing of building envelop components. Since only three samples were tested it is not possible to make broad conclusions relating the windows performance under static and dynamic pressure traces. However, the results suggest that testing windows at static pressures derived from mean wind induced surface pressures may optimistically predict performance during actual exposure. Providing a test methodology that more closely reflects real air pressure conditions could allow manufacturers to design to window to withstand more realistic wind conditions during exposure to exterior water. A review of wind conditions during rain events would assist selection of appropriate conditions for such tests under various climate conditions. A larger scale study of water penetration performance of windows utilizing realistic fluctuating wind traces would provide greater insights into to actual performance should be considered now that such capabilities are readily available. In future tests we would consider installing moisture detection systems within the assembly to investigate water penetration at the wall to window interface. Since reinstallation of the windows could affect performance, we are greatly interested in the potential for moisture detection devices to allow repeated testing on single installations with minimal time delay between tests. 7. ACKNOWLEDGEMENTS We would like to thank Juan Botero and Greg Hebb for there input and assistance in the lab. We would also like to thank Chris Schumacher at Building Science Corporation for his insights and lending equipment for this study.

6 8. REFERENCES [1] RDH Building Engineering Limited (2002) Water Penetration Resistance of Windows Study of Manufacturing, Building Design, Installation and Maintenance Factors, Report for CMHC, Canada. [2] AAMA/WDMA/CSA 101/I.S.2/A (2008) NAFS North American Fenestration Standard/Specification for windows, doors, and skylights. [3] ASTM E (2000) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference. [4] ASTM E (2000) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference. [5] ASTM E (2004) Standard Test Method for Water Penetration of Exterior Windows, Skylights, and Doors by Rapid Pulsed Air Pressure Difference. [6] Girma B., Chowdhury A., and Sambare D. (2009) Application of a full-scale testing facility for assessing wind-driven-rain intrusion, Building and Environment, 44 pp [7] Salzano C., Masters F., and Katsaros J., (2010) Water penetration resistance of residential window installation options for hurricaneprone areas, submitted to Building and Environment. [8] Reinhold T. (2005) Testimony to the Subcommittee on Disaster Prevention and Prediction of the Committee on ommerce, Science, and Transportation of the United States Senate, June 29, [9] Henderson D., Ginger J., Morrison M., and Kopp G. (2009) Simulated tropical cyclonic winds for low cycle fatigue loading of steel roofing, Wind and Structures, 12(4) pp [10] Kopp G., Morrison M., Iizumi E., Henderson D., and Hong H. (2008) The Three Little Pigs Project: Hurricane Risk Mitigation by Integrated Wind Tunnel and Full-Scale Laboratory Tests, submitted to ASCE Natural Hazards Review. [11] Oh T., Surry D., Morrish D., and Kopp G. (2005) The UWO contribution to the NIST aerodynamic database for wind loads on low buildings: Part 1. Archiving format and basic aerodynamic data, Journal of Wind Engineering and Industrial Aerodynamics, 93 pp [12] St. Pierre L., Kopp G., Surry D., and Ho T. (2005) The UWO contribution to the NIST aerodynamic database for wind loads on low buildings: Part 2 Comparison of data with wind load provisions Journal of Wind Engineering and Industrial Aerodynamics, 93 pp

FIELD TESTING SERVICES

FIELD TESTING SERVICES FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue

More information

continuing professional education. As such, it construed to be an approval or endorsement by

continuing professional education. As such, it construed to be an approval or endorsement by This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any

More information

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction

More information

research highlight Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification

research highlight Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification research highlight November 2003 Technical Series 03-125 Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification introduction Over the past decade, there has been

More information

PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE

PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE Report to: Ceramitex Inc. 520 Clarke Rd. London, Ontario

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This

More information

Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems

Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water

More information

WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:

WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,

More information

Table of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide

Table of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide VOLUME 1 - WINDOWS AND DOORS Window and Door Selection Guide PART 1 WINDOW SELECTION GUIDE WSG-11 PART 2 - PERFORMANCE SPECIFICATIONS Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows

More information

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

RenaissanceRe Wall of Wind Research -- Moving Innovations from Theory to Applications

RenaissanceRe Wall of Wind Research -- Moving Innovations from Theory to Applications RenaissanceRe Wall of Wind Research -- Moving Innovations from Theory to Applications by Arindam Gan Chowdhury, PhD Director, Laboratory for Wind Engineering Research, International Hurricane Research

More information

Architectural Testing

Architectural Testing FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard

More information

How To Control Water Penetration In A Window

How To Control Water Penetration In A Window WATER PENETRATION CONTROL FOR WINDOWS A SERVICE LIFE APPROACH David R. Ricketts, P.Eng. 1 and Silvio Plescia, P.Eng. 2 INTRODUCTION Building envelope performance problems and their close link to poor window

More information

RDH Building Sciences Inc.

RDH Building Sciences Inc. MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM

More information

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles. Prepared for: Ben Hales

Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15 x 9 Format Roof Tiles. Prepared for: Ben Hales Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles Prepared for: Ben Hales Manthorpe Building Products Ltd. 24 th June 2014 Report number 295-318 1 Rain Penetration

More information

Window Sill Details for Effective Drainage of Water

Window Sill Details for Effective Drainage of Water Construction Technology Update No. 76 Window Sill Details for Effective Drainage of Water By M.A. Lacasse and M.M. Armstrong Satisfactory window performance demands a good product and proper installation.

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

Assessing Curtain Walls

Assessing Curtain Walls Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building

More information

Water Entry through Roof Sheathing Joints and Attic Vents: A Preliminary Study Sealed Roof Deck Tests

Water Entry through Roof Sheathing Joints and Attic Vents: A Preliminary Study Sealed Roof Deck Tests Water Entry through Roof Sheathing Joints and Attic Vents: A Preliminary Study Sealed Roof Deck Tests Demonstrating the value of sealing the roof deck and providing information on the relative importance

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration

More information

Specifying Windows. Performance Standards

Specifying Windows. Performance Standards 1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed

More information

A Case for Standardized Dynamic Wind Uplift Pressure Test for Wood Roof Structural Systems

A Case for Standardized Dynamic Wind Uplift Pressure Test for Wood Roof Structural Systems A Case for Standardized Dynamic Wind Uplift Pressure Test for Wood Roof Structural Systems Kenneth Hill 1, Peter Datin 1, David O. Prevatt, Ph.D., PE 2, Kurtis Gurley,Ph.D. 3, Gregory A. Kopp, Ph.D. 4

More information

Approval Standard for Class 1 Exterior Wall Systems

Approval Standard for Class 1 Exterior Wall Systems Approval Standard for Class 1 Exterior Wall Systems Class Number 4881 November 2007 2007 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that the

More information

resist water infiltration and avoid water damage to buildings.

resist water infiltration and avoid water damage to buildings. INTRODUCTION Uncontrolled water penetration through the building façade, exterior walls, and especially fenestrations (windows) results in billions of dollars of damage in the con struction industry every

More information

How To Test For An Architectural Test

How To Test For An Architectural Test Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System

More information

Non Invasive Roof Leak Detection Using Infrared Thermography

Non Invasive Roof Leak Detection Using Infrared Thermography Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing

More information

The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage

The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand Sam@HammerandHand.com Florian Speier, Zola Windows Florian@ZolaWindows.com Paul Grahovac,

More information

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,

More information

WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION

WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION for Florida Concrete & Products Association and NCMA Education and Research Foundation Conducted by: Masonry Information Technologists

More information

CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings

CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings RICHARD S. DUNCAN, Ph.D., P.E. JINHUANG WU, Ph.D. NOTICE: All statements, information and data given herein are believed to be accurate

More information

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357

More information

BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS. Wagdy Anis, FAIA, LEED ap*

BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS. Wagdy Anis, FAIA, LEED ap* BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS Wagdy Anis, FAIA, LEED ap* Abstract: Six of the ways condensation can occur on cold surfaces in buildings are discussed here. They are: 1. Air Leakage,

More information

T H E A A M A C E R T I F I C A T I O N P R O G R A M

T H E A A M A C E R T I F I C A T I O N P R O G R A M T H E A A M A C E R T I F I C A T I O N P R O G R A M AAMA STANDS FOR QUALITY Since 1962, AAMA Certification, the original third-party window performance program, has provided manufacturers with the means

More information

National Building Code of Canada 2010

National Building Code of Canada 2010 National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building

More information

NAFS and The 2012 Building Code

NAFS and The 2012 Building Code NAFS and The 2012 Building Code Presented to BCBEC on 2013-04-18 Al Jaugelis B.Sc. Arch. ajaugelis@rdhbe.com NAFS changes everything... No more ABC s New concepts New terminology New rating system New

More information

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed

More information

Informational Bulletin

Informational Bulletin Informational Bulletin March 2007 Bulletin #31 *Replaces Informational Bulletin #8 Updated Impact Requirements for Building Components This Bulletin presents a general overview of the current impact requirements

More information

Figure 1A. Typical brick veneer installation over wood frame construction.

Figure 1A. Typical brick veneer installation over wood frame construction. Figure 1A. Typical brick veneer installation over wood frame construction. BACKGROUND In general, the description of any building, whether a high-rise or a warehouse, can be simplified into two basic components:

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07

More information

Developing, Validating and Demonstrating Ways to Reduce Property Damage from Natural Hazards

Developing, Validating and Demonstrating Ways to Reduce Property Damage from Natural Hazards Developing, Validating and Demonstrating Ways to Reduce Property Damage from Natural Hazards Tim Reinhold, Ph.D., P.E., Sr. VP for Research PAMIC Claims Summit Gettysburg, Pennsylvania, April 7, 2015 What

More information

Windows, skylights, vents, and glazed portions of doors are critical components of a building s

Windows, skylights, vents, and glazed portions of doors are critical components of a building s WINDOWS, DOORS, AND OPENING PROTECTION 10 Windows, Doors, and Opening Protection 10.1 Introduction Windows, skylights, vents, and glazed portions of doors are critical components of a building s envelope.

More information

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe

More information

BECx& Building Airtightness. Presented by: Eric Amhaus Principal

BECx& Building Airtightness. Presented by: Eric Amhaus Principal BECx& Building Airtightness Presented by: Eric Amhaus Principal The Building Enclosure 2007 study: out of 17,000 construction defect claims, 69% result of moisture related defects in building enclosure

More information

Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA

Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

Center for Energy Education Laboratory

Center for Energy Education Laboratory Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and

More information

The Florida Building Code

The Florida Building Code The Florida Building Code Florida s Response to Hurricane Risk Rick Dixon Florida Building Commission Florida Building Commission Architect Structural Engineer Mechanical Engineer Fire Protection Engineer

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,

More information

PERFORMANCE OF STANDING SEAM METAL ROOFS UNDER REALISTIC WIND LOADING

PERFORMANCE OF STANDING SEAM METAL ROOFS UNDER REALISTIC WIND LOADING PERFORMANCE OF STANDING SEAM METAL ROOFS UNDER REALISTIC WIND LOADING Filmon Habte, Maryam Asghari Mooneghi, Peter Irwin, Arindam Gan Chowdhury ABSTRACT: A full-scale experimental investigation was conducted

More information

The Florida Building Code

The Florida Building Code Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building

More information

WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION AND FORENSIC INVESTIGATION OF BUILDING LEAKAGE

WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION AND FORENSIC INVESTIGATION OF BUILDING LEAKAGE WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION FORENSIC INVESTIGATION OF BUILDING LEAKAGE F RANCESCO J. SPAGNA, PE; SIMPSON GUMPERTZ BRON S. BUCHBERG, PE HEGER, INC. 41 Seyon Street,

More information

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE June 24, 2011 North Carolina Has a New Energy Conservation Code! By R. Christopher Mathis Executive Summary On Friday, June 24, 2011, Governor Beverly Perdue signed SB 708 into law and, with it, approved

More information

Impact-Resistant Windows and Sliding Glass Doors

Impact-Resistant Windows and Sliding Glass Doors Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they

More information

Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise

Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise Building Design for Advanced Technology Instruments Sensitive to Acoustic Noise Michael Gendreau Colin Gordon & Associates Presentation Outline! High technology research and manufacturing instruments respond

More information

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration

More information

can be seen in the contrast between solid masonry-wall construction

can be seen in the contrast between solid masonry-wall construction Introduction tal moisture, higher applied loads, larger pace with increased construction activity. Over the past several decades, there has deflections, and reduced water storage In the end, it seems our

More information

Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor

Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor ROXUL Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor January 2014 Prepared by: Building Science Consulting Inc. 167 Lexington Court, Unit 5 Waterloo, Ontario Canada N2J 4R9 www.buildingscienceconsultinginc.com

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005

10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005 10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with

More information

IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2014-023-S2 AWNING WITH FIXED WINDOW PROTOTYPE TEST to AS2047-1999. for. Finesse Window Systems Australia

IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2014-023-S2 AWNING WITH FIXED WINDOW PROTOTYPE TEST to AS2047-1999. for. Finesse Window Systems Australia IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2014-023-S2 AWNING WITH FIXED WINDOW PROTOTYPE TEST to AS2047-1999 for Finesse Window Systems Australia November 2014 Accreditation No. 2371 Accredited for compliance

More information

Water Management & Damage Prevention:

Water Management & Damage Prevention: Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and

More information

PERFORMANCE TEST REPORT

PERFORMANCE TEST REPORT PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789

More information

Lightweight Partition Design for Residential and Commercial Buildings

Lightweight Partition Design for Residential and Commercial Buildings Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation

More information

What you need to know about concrete block basement construction.

What you need to know about concrete block basement construction. Designing and planning your new residence is a vitally important process, which will have a great influence on the future enjoyment of your home. A successful process will ensure all areas of the home

More information

Commercial Residential Model Reviews

Commercial Residential Model Reviews Commercial Residential Model Reviews Prepared by the Professional Team for The Florida Commission on Hurricane Loss Projection Methodology May 2002 I. Background and Items for Consideration In May, 2000,

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

AIR-INS inc. 1320, MONTÉE STE-JULIE, VARENNES (Québec) J3X 1P8 TEL: (514) 652-0838 - FAX: (514) 652-7588

AIR-INS inc. 1320, MONTÉE STE-JULIE, VARENNES (Québec) J3X 1P8 TEL: (514) 652-0838 - FAX: (514) 652-7588 1320, MONTÉE STE-JULIE, VARENNES (Québec) J3X 1P8 TEL: (514) 652-0838 - FAX: (514) 652-7588 RESISTANCE TO WATER PENETRATION TESTING "NOVABRIK" BRICK CLADDING Prepared for: Mr. Michel Bouchard, Eng. Les

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Water Damage & Repair

Water Damage & Repair Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below

More information

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration

More information

Comment Form on Proposed Gut Rehabilitation Alternatives

Comment Form on Proposed Gut Rehabilitation Alternatives Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line

More information

Dynamic Wind Testing of Commercial Roofing Systems

Dynamic Wind Testing of Commercial Roofing Systems Construction Technology Update No. 55 Dynamic Wind Testing of Commercial Roofing Systems by A. Baskaran Single-ply roofs (SPRs) behave differently than built-up roofs and a simple test method is needed

More information

Field Water Testing - Lessons Learned

Field Water Testing - Lessons Learned Quicklinks Lots of Questions - How About Answers Let's Start with the Specifications Test Methods VS. Performance Standard Using the Correct Test Method Conclusion About the Author Compilation of Test

More information

2009 IECC Update. Scope. Content. International Energy Conservation Code

2009 IECC Update. Scope. Content. International Energy Conservation Code 2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are

More information

JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs

JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition

More information

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

Why is my air conditioner dripping on my customers?

Why is my air conditioner dripping on my customers? De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These

More information

Homeowner s Guide Foundation Water PenetrationTips TIPS TO IDENTIFY WATER PENETRATION PROBLEMS / CRACKING BASEMENTS

Homeowner s Guide Foundation Water PenetrationTips TIPS TO IDENTIFY WATER PENETRATION PROBLEMS / CRACKING BASEMENTS Homeowner s Guide Foundation Water PenetrationTips TIPS TO IDENTIFY WATER PENETRATION PROBLEMS / CRACKING BASEMENTS MAINTAINING YOUR HOME BASEMENT FOUNDATION BY HOMEOWNER PREVENTATIVE MAINTENANCE LUX WATERPROOF

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

Moisture Control. System Solutions to Prevent Mold

Moisture Control. System Solutions to Prevent Mold System Solutions to Prevent Mold How a systems approach to managing moisture is the most effective strategy for minimizing the growth of mold. Moisture Control Architects, designers, contractors and maintenance

More information

State of Connecticut Department of Public Health RADON PROGRAM

State of Connecticut Department of Public Health RADON PROGRAM State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon

More information

Design Requirements for Eyewash and Safety Shower Units APPLICATION: Detailed Installation, Operation and Design. Eyewash Stations.

Design Requirements for Eyewash and Safety Shower Units APPLICATION: Detailed Installation, Operation and Design. Eyewash Stations. APPLICATION: Eyewash Stations must be provided in the following areas. Laboratories Plumbed emergency eyewash equipment shall be installed in every lab or room, where an MSDS for the materials used specifies

More information

Avoiding Air Barrier Pitfalls

Avoiding Air Barrier Pitfalls Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great

More information

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards

More information

December 24, 2008. twalker@sedaconstruction.com. SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216

December 24, 2008. twalker@sedaconstruction.com. SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216 December 24, 2008 twalker@sedaconstruction.com SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216 RE: Georgetown Community 2C - Revised Assessment Date: October

More information

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Energy Code Compliance With SIPs Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Outline Overview of 2009 and 2012 energy codes Code compliance with SIPs Reducing air infiltration with SIP

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE

More information

MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS

MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS MOISTURE MANAGEMENT DURING THE CONSTRUCTION PROCESS Ed Light 1,*, James Bailey 1, and Roger Gay 1 1 Building Dynamics, LLC, Ashton, MD (USA) *Corresponding email: ELight@building-dynamics.com Published

More information

AIR LEAKAGE: DIFFICULTIES IN MEASUREMENT, QUANTIFICATION AND ENERGY SIMULATION

AIR LEAKAGE: DIFFICULTIES IN MEASUREMENT, QUANTIFICATION AND ENERGY SIMULATION AIR LEAKAGE: DIFFICULTIES IN MEASUREMENT, QUANTIFICATION AND ENERGY SIMULATION Michael B. Waite 1 and Sean M. O Brien 2 ABSTRACT Air leakage through the building enclosure can have a significant impact

More information

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses

More information

Standard Operating Procedures for Flood Preparation and Response

Standard Operating Procedures for Flood Preparation and Response Standard Operating Procedures for Flood Preparation and Response General Discussion Hurricanes, tropical storms and intense thunderstorms support a conclusion that more severe flooding conditions than

More information

Flood-Damage Resistive Residential Envelope Systems. Ed Laatsch,, FEMA Robert Wendt, ORNL

Flood-Damage Resistive Residential Envelope Systems. Ed Laatsch,, FEMA Robert Wendt, ORNL Flood-Damage Resistive Residential Envelope Systems Ed Laatsch,, FEMA Robert Wendt, ORNL Floods have been a way of life in the U.S. (FEMA News Photo) They strike throughout the country - CA to FL, ND to

More information

Points of Construction

Points of Construction Points of Construction BCB Homes builds the best homes in America. Period. The physics of building in the South Florida hot, humid climate are hard enough on their own, but BCB executes the details better

More information