TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
|
|
|
- Philomena Powers
- 10 years ago
- Views:
Transcription
1 TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/ Derry Court York, PA phone: fax:
2 TEST REPORT July 26, 2013 TABLE OF CONTENTS 1.0 General Information Reference Standards Assembly Fastener Testing Guardrail End-Use Adjustments Structural Performance Testing of Assembled Railing Systems Closing Statement Revision Log Appendix A - Drawings Appendix B - Photographs
3 1.0 General Information 1.1 Product TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC 20 Bogden Boulevard Millville, New Jersey Rigid Cellular PVC Guardrail System - Hampton RS Project Description Report No: Test Date: 06/11/13 Through: 06/28/13 Report Date: 07/26/13 Architectural Testing was contracted by INTEX Millwork Solutions, LLC to perform structural testing on their Hampton RS40 rigid cellular PVC guardrail (railing) system. This report is in conjunction with Architectural Testing Report No.'s and , which include material test results which were used to determine the end-use adjustment factors applied to structural performance tests reported herein. The purpose of the testing is code compliance evaluation in accordance with the following criteria; however, INTEX Millwork Solutions, LLC does not plan on submitting the test results for evaluation: ICC-ES AC174 (approved January, 2012), Acceptance Criteria for Deck Board Span Ratings and Guardrail Systems (Guards and Handrails). ICC-ES AC was developed by the ICC Evaluation Service, Inc. (ICC-ES ) as acceptance criteria to evaluate compliance with the following building codes: 2012 International Building Code, International Code Council 2012 International Residential Code, International Code Council 1.3 Limitations Architectural Testing All tests performed were to evaluate structural performance of the railing assembly to carry and transfer imposed loads to the supports (posts). The test specimen evaluated included the balusters, rails, rail brackets and attachment to the supporting structure. The support posts were conventional construction and not within the scope of the evaluation. Posts were therefore not a tested component and were included in the test specimen only to facilitate anchorage of the rail brackets. Anchorage of support posts to the supporting structure is not included in the scope of this testing and would need to be evaluated separately. 130 Derry Court York, PA phone: fax:
4 Page 2 of Qualifications Architectural Testing in York, Pennsylvania has demonstrated compliance with ANS/ISO/IEC Standard and is consequently accredited as a Testing Laboratory (TL-144) by International Accreditation Service, Inc. Architectural Testing is accredited to perform all testing reported herein. 1.5 Product Description Hampton RS40 railing systems are comprised of rigid cellular PVC rails, balusters, and post sleeves produced by an extrusion process. Extruded products are mono-extruded. Test specimens consisted of one colored product identified by the manufacturer as follows: White. Drawings are included in Appendix A to verify the overall dimensions and other pertinent information of the tested product, its components, and any constructed assemblies. 1.6 Product Sampling INTEX Millwork Solutions, LLC supplied the assembled rail systems tested and reported herein. 1.7 Witnessing Joseph Umosella of INTEX Millwork Solutions, LLC was present on 06/13/13 to witness the following tests and/or test setups: Structural performance testing of assembled railing systems 1.8 Conditions of Testing Unless otherwise indicated, all testing reported herein was conducted in a laboratory set to maintain temperature in the range of 68 ± 4ºF and humidity in the range of 50 ± 5% RH. Test specimen materials were not stored in the laboratory environment for 40 hours prior to testing. 2.0 Reference Standards ASTM D , Standard Test Methods for Mechanical Fasteners in Wood ASTM D , Standard Specification for Establishing Performance Ratings for Wood-Plastic Composite Deck Boards and Guardrail Systems (Guards or Handrails) 3.0 Assembly Fastener Testing Re: ICC-ES AC174 - Section General The purpose of this testing was to simulate a 90 bracket loading condition for the in-line application, which addresses a situation when the guardrail system is to be installed with the top rails in a corner condition.
5 Page 3 of Test Specimens Short sections of the top rail were attached at each end to short sections of posts. Specimens were supplied to Architectural Testing Inc. by INTEX Millworks Solutions, LLC in a preassembled condition. The rail brackets were attached to treated 4x4 wood posts (Southern Pine) via stainless steel brackets with 3-1/2 in wide by 6 in high by 3/4 in thick sections of cellular PVC post sleeve material used as spacers between the bracket and wood post. Brackets were secured to the post and to the rail as described in Section 5.4 Fastening Schedule. 3.3 Test Setup The testing machine was fitted with the post sections at the top and bottom to accommodate anchorage of the rail and brackets. The top post section was attached to the test machine s crosshead with a swivel mechanism, and the bottom post section was attached rigidly to the base of the test machine. Reference photographs in Appendix B for test setups. 3.4 Test Procedure Testing was performed in accordance with ASTM D 1761 and by using a computer-monitored and -controlled INSTRON Testing Machine. Tests were run at a crosshead speed of 0.05 in/min, and each specimen was tested in tension to its ultimate load capacity. 3.5 Test Results Specimen No. Ultimate Load (lb) Deviation From Average % Mode of Failure % Fastener Withdrawal % Average 2470 Allowable Capacity lb OK 2 1 Average ultimate load divided by a factor of safety of three (3.0) 2 Acceptance criteria determined from the uniform load test: 50 plf x 96 in 12 in 2 brackets = 200 lb 3.6 Summary and Conclusions The maximum design load rating required for guardrail systems for use in IRC One- and Two-Family Dwellings and for rail lengths up to and including 8 ft for use in IBC All Use Groups is 200 lb. Therefore, fasteners / connectors reported herein meet the performance requirements of ICC-ES AC174 for use in corner conditions.
6 Page 4 of Guardrail End-Use Adjustments Re: ICC-ES AC174 Sections General Data from UV and freeze-thaw resistance testing reported in Architectural Testing Report No as well as temperature and moisture effect testing reported in Architectural Testing Report No was used for determination of applicable adjustment factors. 4.2 End-Use Adjustment Factors End-Use Factors Comparison (% Change) with Standard (Control) Conditions Rigid Cellular PVC Material Adjustment Factors ASTM D 7032 Criteria (as referenced by AC174) Strength 1 Stiffness 2 Strength Stiffness UV +11.1% +3.8% Loss within 10% Freeze-Thaw +3.5% +5.0% Loss within 10% Greatest of: +125ºF -35.9% -27.8% -20ºF +40.9% +17.4% Loss within 25% Moisture % +1.3% Overall End-Use Adjustment Factor: Moment or MOR (Modulus of Rupture) 2 EI (the product of MOE and the Moment of Inertia) or MOE (Modulus of Elasticity) 3 Product does not absorb moisture. Pursuant to compliance with ICC-ES AC174, the test loads were increased by the amount in excess of 10% for UV exposure and freeze-thaw cycling, as well as 25% for temperature and moisture effect. This sets the overall end-use adjustment factor at Therefore, tests are performed to a maximum test load equal to 2.81 times design load ( = 2.81). In addition, the deflection observed at design load is adjusted for the cumulative effect on stiffness properties in excess of the same tolerances specified for strength (0.97).
7 Page 5 of Stiffness Analysis For rails reinforced with aluminum, adjustment factors were further evaluated for their effect on the combined rigid cellular PVC/aluminum component by applying the strength or stiffness loss only to the percentage carried by the rigid cellular PVC, which was determined by relative stiffness analysis. Relative Stiffness Analysis - Horizontal Loading Hampton RS40 Rail and Aluminum Insert Member E (ksi) I y (in 4 ) EI y % Carried Top Rail Cap % Top Rail Base % Aluminum % EI= 2145 Greatest property loss for strength or stiffness is -36%. Applying this to the rigid cellular PVC component only, the overall effect is: 0.17 (1-0.36) = This represents a 6% loss for the combined rigid cellular PVC/aluminum component. ASTM D 7032 allows 25%; therefore, no adjustment factor was required for test loads applied to aluminum-reinforced rails. The full adjustment factor was applied to loading on rigid cellular PVC balusters, which were not reinforced with aluminum. Relative Stiffness Analysis - Vertical Loading Hampton RS40 Rail and Aluminum Insert Member E (ksi) I x (in 4 ) EI x % Carried Top Rail Cap % Top Rail Base % Aluminum % EI= 734 Greatest property loss for strength or stiffness is -36%. Applying this to the rigid cellular PVC component only, the overall effect is: 0.07 (1-0.36) = This represents a 3% loss for the combined rigid cellular PVC/aluminum component. ASTM D 7032 allows 25%; therefore, no adjustment factor was required for test loads applied to aluminum-reinforced rails.
8 Page 6 of Structural Performance Testing of Assembled Railing Systems Re: ICC-ES AC174 - Section General Railing assemblies were tested in a self-contained structural frame designed to accommodate anchorage of a rail assembly and application of the required test loads. The specimen was loaded using an electric winch mounted to a rigid steel test frame. High strength steel cables, nylon straps, and load distribution beams were used to impose test loads on the specimen. Applied load was measured using an electronic load cell located in-line with the loading system. Deflections were measured to the nearest 0.01 in using electronic linear displacement transducers. 5.2 Railing Assembly Description The Hampton RS40 guardrail systems consisted of extruded rigid cellular PVC rails with spaced balusters between the rail members. The level railing systems had an overall top rail length (inside of post to inside of post) of 96 in and 120 in with an overall rail height (top of top rail to bottom of bottom rail) of 39 in. The stair railing systems had an overall top rail length (inside of post to inside of post) of 72 in and 96 in with an overall rail height (top of top rail to bttom of bottom rail) of 40-1/2 in. Top and bottom rails attached to treated 4x4 wood posts (Southern Pine) via stainless steel brackets with 3-1/2 in wide by 6 in high by 3/4 in thick sections of cellular PVC post sleeve material used as spacers between the bracket and wood post. See Section 5.4 Fastening Schedule for connection details. One support block was used along the underside of the 72 in stair railing system, two support blocks were used along the underside of the 96 in stair and level railing systems and three support blocks were used along the underside of the 120 in level railing system. Support blocks were equally spaced along the length of the bottom rail. See drawings in Appendix A and photographs in Appendix B for additional details.
9 Page 7 of Component Descriptions The scope of testing performed and reported herein was intended to evaluate the Hampton RS40 series railing system consisting of the following components (see Appendix A for drawings): Top Rail: Flat Top Rail Cap 7/8 in high by 3-1/2 in wide extruded rigid cellular PVC flat profile Top Rail Base 1-1/2 in high by 2-15/16 in wide extruded rigid cellular PVC contoured rail profile Note: The Flat top rail cap (I x = in 4 ; I y = in 4 ) was deemed worst case from a stiffness analysis versus the Contoured top rail cap (I x = in 4 ; I y = in 4 ) and was therefore used for all performance tests reported herein. Bottom Rail: 1-1/2 in high by 2-15/16 in wide extruded rigid cellular PVC contoured rail profile Note: The Bottom Rail section is same section as top rail base rotated 180. Aluminum Reinforcing Insert: 1 in high by 1-3/4 in wide 6063-T5 extruded aluminum C section (0.12 in thick web; 0.06 in thick flanges) with four raceway channels running the entire length. Used in top and bottom rail of all systems. Balusters: 1-1/4 in square extruded rigid cellular PVC pickets Support Block: 1-1/4 in square extruded rigid cellular PVC picket cut to length and secured to the underside of the bottom rail as described in Section 5.4 Fastening Schedule. Rail to Post Connection: Level / Stair (High End) 1-1/8" high by 1-3/4 in wide (0.114 in thick) stainless steel plate with connection details as found in Section 5.4 Fastening Schedule. Stair (Low End) 1-3/4 in long with 1 in legs (0.114 in thick) stainless steel connection angle with connection details as found in Section 5.4 Fastening Schedule. Post Sleeves: 6 in high by 3-1/2 in wide by 3/4 in thick section of extruded rigid cellular PVC sleeve material used as spacers between the bracket and support post Support Post: Preservative-treated wood (Southern Pine) 4x4
10 Page 8 of Fastening Schedule Connection Top / Bottom Rail Bracket to Post Top / Bottom Rail Bracket to Rail - Level Top / Bottom Rail Bracket to Rail - Stair (High End) Top / Bottom Rail Bracket to Rail - Stair (Low End) Baluster to Top Rail Base and Aluminum Insert - Level and Stair Baluster to Bottom Rail Top Rail Base to Top Rail Cap Bottom Rail to Foot Block Fastener (2) #10-12 x 3" (0.131 in minor diameter) hex washer head, slotted drive, stainless steel screws (4) #8-15 x 1-1/4" (0.120 in minor diameter) trim head, square drive, stainless steel screws (4) #8-15 x 1-1/4" (0.120 in minor diameter) trim head, square drive, stainless steel screws (2) #8-15 x 1-1/4" (0.120 in minor diameter) trim head, square drive, stainless steel screws (1) #10-8 x 2-1/2" (0.112 in minor diameter, in shank diameter) trim head, square drive, type 17 point, stainless steel screw (1) #10-8 x 2-1/2" (0.112 in minor diameter, in shank diameter) trim head, square drive, type 17 point, stainless steel screw; (1) #10-8 x 1-1/2 (0.112 in minor diameter, in shank diameter) trim head, square drive, type 17 point, stainless steel screw (1) #8-12 x 1-3/4" (0.110 in minor diameter, in shank diameter), twist shank, trim head, star drive, type 17 point, stainless steel screw at both ends and third points (1) #10-8 x 2-1/2" (0.112 in minor diameter, in shank diameter) trim head, square drive, type 17 point, stainless steel screw
11 Page 9 of Test Setup The railing assembly was installed and tested as a single railing section by directly securing the 4x4 treated wood posts (Southern Pine) to a rigid test frame. The 4x4 treated wood posts were included only to facilitate anchorage of the test specimen and were not tested components. Transducers mounted to an independent reference frame were located to record movement of reference points on the railing system components (ends and mid-point) to determine net component deflections. See photographs in Appendix B for test setups. 5.6 Test Procedure Testing and evaluation was performed in accordance with Section 5.1 of ICC-ES AC174. The test specimen was inspected prior to testing to verify size and general condition of the materials, assembly, and installation. No potentially compromising defects were observed. One specimen was used for all load tests which were performed in the order reported. Each design load test was performed using the following procedure: 1. Zeroed transducers and load cell at zero load; and 2. Increased load to specified test load in no less than ten seconds. 5.7 Test Results Unless otherwise noted, all loads and displacement measurements were normal to the rail (horizontal). The test results apply only to the railing assembly between supports and anchorage to the support. The test load adjustment factor was increased from 2.5 x design load to 2.81 x design load for the infill load tests only. This increase in required maximum test loads was determined from test results as summarized in Section 4.0 Guardrail End-Use Adjustments. Key to Test Results Tables: Load Level: Target test load Test Load: Actual applied load at the designated load level (target). Elapsed Time (E.T.): The amount of time into the test with zero established at the beginning of the loading procedure.
12 Page 10 of Test Results (Continued) Test Series No in by 42 in Hampton RS40 Level Guardrail System IBC All Use Groups / ICC-ES AC174 Specimen No. 1 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :16 greater than 141 lb without Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :14 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Horizontal Uniform Load on Top Rail lb (2.5 x D.L.) :50 greater than 1000 lb without 1 Uniform load was simulated with quarter point loading. Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :45 greater than 1000 lb without 1 Uniform load was simulated with four equally distributed point loads.
13 Page 11 of Test Results (Continued) Test Series No. 1 (Continued) Specimen No. 1 of 3 (Continued) Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) 1 Load Level Test Load (lb) E.T. (min:sec) End 2 Mid End 2 Net 200 lb (D.L.) : lb (2.5 x D.L.) :34 Deflection Evaluation: Limits per AC : h + l = + = 2.5" Result: greater than 500 lb without 1 Transducer at center of top rail disconnected during loading; therefore, a deflection reading at 200 lb was not recorded and net deflection could not be calculated. 2 Each end displacement was measured at the center of the support. 3 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :29 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Specimen No. 2 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :12 greater than 141 lb without
14 Page 12 of Test Results (Continued) Test Series No. 1 (Continued) Specimen No. 2 of 3 (Continued) Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :13 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Horizontal Uniform Load on Top Rail lb (2.5 x D.L.) :50 greater than 1000 lb without 1 Uniform load was simulated with quarter point loading. Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :44 greater than 1000 lb without 1 Uniform load was simulated with four equally distributed point loads.
15 Page 13 of Test Results (Continued) Test Series No. 1 (Continued) Specimen No. 2 of 3 (Continued) Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :38 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 200 lb = 1.37 in on a 96 in rail Adjusted deflection for end use factors = 1.37 in 0.97 = 1.41 in Limits per AC174 2 h l : + = + = 2.5" > 1.41" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :33 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Specimen No. 3 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :19 greater than 141 lb without
16 Page 14 of Test Results (Continued) Test Series No. 1 (Continued) Specimen No. 3 of 3 (Continued) Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :11 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Horizontal Uniform Load on Top Rail lb (2.5 x D.L.) :53 greater than 1000 lb without 1 Uniform load was simulated with quarter point loading. Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (96 in 12 in/ft) = 400 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :32 greater than 1000 lb without 1 Uniform load was simulated with four equally distributed point loads. Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :33 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 200 lb = 1.31 in on a 96 in rail Adjusted deflection for end use factors = 1.31 in 0.97 = 1.35 in Limits per AC174 2 h l : + = + = 2.5" > 1.35" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements.
17 Page 15 of Test Results (Continued) Test Series No. 1 (Continued) Specimen No. 3 of 3 (Continued) Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :36 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Test Series No in by 42 in Hampton RS40 Level Guardrail System IRC One- and Two-Family Dwellings / ICC-ES AC174 Specimen No. 1 of 3 Test No. 1 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :17 greater than 141 lb without Test No. 2 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :15 greater than 141 lb without
18 Page 16 of Test Results (Continued) Test Series No. 12 (Continued) Specimen No. 1 of 3 (Continued) Test No. 3 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :34 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 207 lb = 2.12 in on a 120 in rail Adjusted deflection for end use factors = 2.12 in 0.97 = 2.19 in Limits per AC174 2 h l : + = + = 2.75" > 2.19" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 4 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :26 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Specimen No. 2 of 3 Test No. 1 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :16 greater than 141 lb without
19 Page 17 of Test Results (Continued) Test Series No. 2 (Continued) Specimen No. 2 of 3 (Continued) Test No. 2 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :10 greater than 141 lb without Test No. 3 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :36 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 200 lb = 2.10 in on a 120 in rail Adjusted deflection for end use factors = 2.10 in 0.97 = 2.16 in Limits per AC174 2 h l : + = + = 2.75" > 2.16" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 4 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :27 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled.
20 Page 18 of Test Results (Continued) Test Series No. 2 (Continued) Specimen No. 3 of 3 Test No. 1 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :17 Test No. 2 Test Date: 06/27/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets greater than 141 lb without 141 lb (2.81 x D.L.) :11 greater than 141 lb without Test No. 3 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :33 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 207 lb = 2.15 in on a 120 in rail Adjusted deflection for end use factors = 2.15 in 0.97 = 2.22 in Limits per AC174 2 h l : + = + = 2.75" > 2.22" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements.
21 Page 19 of Test Results (Continued) Test Series No. 2 (Continued) Specimen No. 3 of 3 (Continued) Test No. 4 Test Date: 06/27/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :28 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Test Series No in by 42 in by 32 Hampton RS40 Stair Guardrail System IBC All Use Groups / ICC-ES AC174 Specimen No. 1 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :12 greater than 141 lb without Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :18 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Horizontal Uniform Load on Top Rail 1 Load Level Test Load (lb) E.T. (min:sec) Result 750 lb (2.5 x D.L.) :36 greater than 750 lb without 1 Uniform load was simulated with quarter point loading.
22 Page 20 of Test Results (Continued) Test Series No. 3 (Continued) Specimen No. 1 of 3 (Continued) Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :00 greater than 750 lb without 1 Uniform load was simulated with four equally distributed point loads. Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :30 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 200 lb = 0.74 in on a 72 in rail Adjusted deflection for end use factors = 0.74 in 0.97 = 0.76 in Limits per AC174 2 h l : + = + = 2.25" > 0.76" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :31 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled.
23 Page 21 of Test Results (Continued) Test Series No. 3 (Continued) Specimen No. 2 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :17 greater than 141 lb without Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :10 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Horizontal Uniform Load on Top Rail lb (2.5 x D.L.) :32 greater than 750 lb without 1 Uniform load was simulated with quarter point loading. Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :24 greater than 750 lb without 1 Uniform load was simulated with four equally distributed point loads.
24 Page 22 of Test Results (Continued) Test Series No. 3 (Continued) Specimen No. 2 of 3 (Continued) Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :32 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 200 lb = 0.62 in on a 72 in rail Adjusted deflection for end use factors = 0.62 in 0.97 = 0.64 in Limits per AC174 2 h l : + = + = 2.25" > 0.64" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :34 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Specimen No. 3 of 3 Test No. 1 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :14 greater than 141 lb without
25 Page 23 of Test Results (Continued) Test Series No. 3 (Continued) Specimen No. 3 of 3 (Continued) Test No. 2 Test Date: 06/13/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :11 greater than 141 lb without Test No. 3 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Horizontal Uniform Load on Top Rail lb (2.5 x D.L.) :30 greater than 750 lb without 1 Uniform load was simulated with quarter point loading. Test No. 4 Test Date: 06/13/13 Design Load: 50 plf x (72 in 12 in/ft) = 300 lb Vertical Uniform Load on Top Rail lb (2.5 x D.L.) :27 greater than 750 lb without 1 Uniform load was simulated with four equally distributed point loads. Test No. 5 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :28 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 210 lb = 0.60 in on a 72 in rail Adjusted deflection for end use factors = 0.60 in 0.97 = 0.62 in Limits per AC174 2 h l : + = + = 2.25" > 0.62" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements.
26 Page 24 of Test Results (Continued) Test Series No. 3 (Continued) Specimen No. 3 of 3 (Continued) Test No. 6 Test Date: 06/13/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :29 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Test Series No in by 42 in by 32 Hampton RS40 Stair Guardrail System IRC One- and Two-Family Dwellings / ICC-ES AC174 Specimen No. 1 of 3 Test No. 1 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :14 greater than 141 lb without Test No. 2 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :15 greater than 141 lb without
27 Page 25 of Test Results (Continued) Test Series No. 4 (Continued) Specimen No. 1 of 3 (Continued) Test No. 3 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :31 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 209 lb = 1.43 in on a 96 in rail Adjusted deflection for end use factors = 1.43 in 0.97 = 1.47 in Limits per AC174 2 h l : + = + = 2.5" > 1.47" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 4 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :30 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. Specimen No. 2 of 3 Test No. 1 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :11 greater than 141 lb without
28 Page 26 of Test Results (Continued) Test Series No. 4 (Continued) Specimen No. 2 of 3 (Continued) Test No. 2 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :10 greater than 141 lb without Test No. 3 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :24 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 204 lb = 1.34 in on a 96 in rail Adjusted deflection for end use factors = 1.34 in 0.97 = 1.38 in Limits per AC174 2 h l : + = + = 2.5" > 1.38" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements. Test No. 4 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :26 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled.
29 Page 27 of Test Results (Continued) Test Series No. 4 (Continued) Specimen No. 3 of 3 Test No. 1 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Center of Two Pickets 141 lb (2.81 x D.L.) :13 greater than 141 lb without Test No. 2 Test Date: 06/28/13 Design Load: 50 lb / 1 Square ft of Infill at Bottom of Two Pickets 141 lb (2.81 x D.L.) :11 greater than 141 lb without Test No. 3 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Midspan of Top Rail Displacement (inches) Load Level Test Load (lb) E.T. (min:sec) End Mid End Net lb (D.L.) : lb (2.5 x D.L.) :24 Result: greater than 500 lb without Deflection Evaluation: Maximum rail deflection at 203 lb = 1.31 in on a 96 in rail Adjusted deflection for end use factors = 1.31 in 0.97 = 1.35 in Limits per AC174 2 h l : + = + = 2.5" > 1.35" ok Each end displacement was measured at the center of the support. Net displacement was the rail displacement relative to the supports. 2 Deflection limit calculation based on worse case 36" railing height to satisfy One- and Two-Family Dwelling requirements.
30 Page 28 of Test Results (Continued) Test Series No. 4 (Continued) Specimen No. 3 of 3 (Continued) Test No. 4 Test Date: 06/28/13 Design Load: 200 lb Concentrated Load at Both Ends of Top Rail (Brackets) Load Level 1 Test Load (lb) E.T. (min:sec) Result 1000 lb (2.5 x D.L.) x :27 Each end withstood load equal to or greater than 500 lb without 1 Load was imposed on both ends of rail using a spreader beam; therefore, loads were doubled. 5.8 Summary and Conclusions The railing assemblies reported herein meet the structural performance requirements of Section 5.1 of ICC-ES AC174 as installed between adequate supports with guardrail details and Occupancy Classification as shown in the following table: Hampton RS40 Guardrail System Guardrail Type Baluster Top Rail Cap Code Occupancy Classification 96 in by 42 in 120 in by 42 in 72 in by 42 in 96 in by 42 in Level Stair 1-1/4 in Square Cellular PVC Picket Flat and Contoured IBC All Use Groups IRC One- and Two- Family Dwellings IBC All Use Groups IRC One- and Two- Family Dwellings The railing supports were not included within the scope of this testing, and these conclusions would apply only for a railing that is provided with adequate supports that provide equal or better substrate material (Southern Pine wood) for the fasteners used to anchor the rail brackets. Anchorage of support posts to the supporting structure is not included in the scope of this testing and would need to be evaluated separately.
31 Architectural Testing Page 29 of Closing Statement Architectural Testing will service this report for the entire test record retention period. The report retention will be four years from the report date. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. Results obtained are tested values and were secured using the designated test methods. This report neither constitutes certification of this product nor expresses an opinion or endorsement by this laboratory; it is the exclusive property of the client so named herein and relates only to the tested specimens. This report may not be reproduced, except in full, without the written approval of Architectural Testing. For ARCHITECTURAL TESTING: Kyle J. Evans Technician II Structural Systems Testing V. Thomas Mickley, Jr., P.E. Senior Project Engineer Structural Systems Testing KJE:vtm/drm Attachments (pages): This report is complete only when all attachments listed are included. Appendix A - Drawings (13) Appendix B - Photographs (7)
32 Page 30 of 30 Revision Log Rev. # Date Page(s) Revision(s) 0 07/26/13 N/A Original report issue This report produced from controlled document template ATI 00412, Revised 04/27/12.
33 APPENDIX A Drawings
34
35
36
37
38
39
40
41
42
43
44
45
46
47 APPENDIX B Photographs
48 Photo No. 1 Assembly Fastener Test Setup
49 Photo No. 2 Infill Loading at Center of Two Balusters Photo No. 3 Infill Loading at Bottom of Two Balusters
50 Photo No. 4 Horizontal Uniform Load on Top Rail Photo No. 5 Vertical Uniform Load on Top Rail
51 Photo No. 6 Concentrated Load at Midspan of Top Rail Photo No. 7 Concentrated Load at Both Ends of Top Rail (Brackets)
52 Photo No. 8 Bracket to Post Attachment Photo No. 9 Bracket to Rail Reinforcing Attachment - Level and Stair (High End)
53 Photo No. 10 Bracket - Stair (Low End) Photo No. 11 Top Rail Base to Top Rail Cap Attachment
54 Photo No. 12 Top Rail Base to Baluster Attachment Photo No. 13 Bottom Rail to Baluster Attachment
TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"
TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing
TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry
TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized
ATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 09/01/2016 Issued: 09/04/2015 Visit www.ati-es.com for current status Page 1 of 17 UFP Ventures II,
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims
PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight
FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM
PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700
Wisconsin Building Products Evaluation
Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
RadianceRail Installation Guide
RadianceRail Installation Guide Installing RadianceRail with CableRail by Feeney... 2 Installing CableRail by Feeney for RadianceRail... 7 Installing RadianceRail Stairs with CableRail by Feeney... 10
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
AZEK Rail Install Guide
TRIM MOULDING DECK PORCH RAIL PAVERS AZEK Rail Install Guide Installing AZEK Rail with CableRail by Feeney... 1 Installing CableRail by Feeney for AZEK Rail... 7 Installing AZEK Rail Stairs with CableRail
PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.
PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report
ESR-1190 Reissued December 1, 2009 This report is subject to re-examination in two years.
ICC-ES Evaluation Report ESR-90 Reissued December, 2009 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
WHAT S DIFFERENT. about TimberTech CableRail? Covered under warranty by ONE trusted manufacturer. Saves TIME and EFFORT
WHAT S DIFFERENT about TimberTech CableRail? Covered under warranty by ONE trusted manufacturer Consumers want project simplicity. Offer them the added luxury by building high-end custom cable railing
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
CONTENTS 1. INTRODUCTION...1 2. METHODOLOGY...2 3. RESULTS & FINDINGS...9 APPENDIX
Load Testing of Balustrade Systems Test Report No. S365 CONTENTS 1. INTRODUCTION...1 2. METHODOLOGY...2 2.1 BALUSTRADE LOAD ASSESSMENTS... 2 2.2 TEST SYSTEMS... 3 2.3 TEST PROCEDURE... 8 3. RESULTS & FINDINGS...9
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
WHAT S DIFFERENT ABOUT OUR CABLERAIL?
WHAT S DIFFERENT ABOUT OUR CABLERAIL? Manufactured for use with: Covered under warranty by ONE trusted manufacturer Consumers want project simplicity. Offer them the added luxury by building high-end custom
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
AZEK Rail Install Guide
TRIM MOULDING DECK PORCH RAIL PAVERS AZEK Rail Install Guide Installing AZEK Rail with Glass Infill... 2 Installing AZEk Rail Stairs with Glass Infill... 9 Notes...14 Please read all instructions completely
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
CLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
CLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
CLEAR-DIVISIONS VARIOFOLD
CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the
C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S
C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S January 2009 Issue 6 Valu Guide Brackets The Ultimate in Adjustability and Cost Savings Valu Guide brackets are part of a family
TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window
BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report
TSL Professional Services
Report For: Laboratory #: 402876-05 5375 Edgeway Drive, ALLENDALE, MI, USA Report Date: December 21, 2005 49401 Received Date: November 3, 2005 Phone: 616 875 7725 Fax: 616 875 6009 Customer P.O. #: COD
SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS
Page 1 of 5 SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS Guarda Security Window Screens in this specification are appropriate for use in windows, storefronts, curtain walls, vents, and any other applications
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
Casement/Awning Window Parts Reference Catalog
Casement/Awning Window Parts Reference Catalog (Includes Miscellaneous Parts for Eyebrow Casement and Garden Bay Windows) #1028654 (Revised 03/02) Weather Shield Mfg., Inc. Medford, WI 54451 715/748-2100
3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form
3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form THIS FULLY COMPLETED DOCUMENT MUST BE INCLUDED WITH EACH RETURN SHIPMENT IN ORDER FOR CREDIT TO BE ISSUED. ALL CREDITS WILL BE ISSUED TO
ICC-ES Evaluation Report
ICC-ES Evaluation Report ESR-2369 Reissued May 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
RPS - [email protected] - 858 755 4505-12478 San Bruno Cove, San Diego, CA 92130
RPS - [email protected] - 858 755 4505-2478 San Bruno Cove, San Diego, CA 9230 SWH Solar Mount Rail R-MR-SW-SR-0.5, R-MR-SW-SR-2, R-MR-SW-SR-4, R-MR-SW-SR-4B, R-MR-SW-SR-7 Part No. MR-SW-SR-0.5, MR-SW-SR-2,
Perforated Shearwall Design Method 1
Perforated Shearwall Design Method 1 Philip Line, P.E., Bradford K. Douglas, P.E., American Forest & Paper Association, USA Abstract Wood frame shearwalls are traditionally designed using full-height shearwall
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
Introduction to Beam. Area Moments of Inertia, Deflection, and Volumes of Beams
Introduction to Beam Theory Area Moments of Inertia, Deflection, and Volumes of Beams Horizontal structural member used to support horizontal loads such as floors, roofs, and decks. Types of beam loads
Stainless Steel Cable Assemblies to Enhance Any Railing and Any View!
2014 Feeney (9/14) King Architectural Metals Stainless Steel Cable Assemblies to Enhance Any Railing and Any View! Standard Cable Assemblies Easy-to-install, prefabricated cable assemblies are an attractive,
Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. www.r-control.com CONTROL, NOT COMPROMISE.
R-CONTROL s STRUCTURAL INSULATED PANELS Note: Information deemed reliable at time of printing. Please visit www.r-control.com for latest information. June 2012 CONTROL, NOT COMPROMISE. www.r-control.com
Cable railing. Standard Cable Assemblies. Visit us online at www.geobezdan.com. Email your questions to [email protected].
Cable railing Standard Cable Assemblies Visit us online at www.geobezdan.com. Email your questions to [email protected]. Figure 1 Figure 2 Figure 3 Figure 4 special end fittings are easy to install and
F-Series Camera Mounting Accessories
F-Series Camera Mounting Accessories Document Number: 427-0462-00-12 Version: 100 Issue Date: September 2010 2010. All rights reserved worldwide. FLIR Commercial Systems, Inc. 70 Castilian Drive Goleta,
TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.
Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with
Design of Commercial/Industrial Guardrail Systems for Fall Protection
Design of Commercial/Industrial Guardrail Systems for Fall Protection Course No: S02-016 Credit: 2 PDH Brian McCaffrey, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point,
TREX SELECT RAILING. Installation Instructions 1 800 BUY TREX PARTS G * I ** H *
TREX SELECT RAILING NOTE: All Trex Select Railing lengths are manufactured at ON CENTER dimensions (spanning from center of each post): 67-5/8" (76.8 cm) for 6' (.83 m) on center, and 9-5/8" (35.3 cm)
LOAD TESTING OF ACRO BUILDING SYSTEMS 12075 RAKE-EDGE GUARDRAIL SYSTEM
1049 Triad Court, Marietta, Georgia 30062 (770) 423-1400 Fax (770) 424-6415 LOAD TESTING OF ACRO BUILDING SYSTEMS 12075 RAKE-EDGE GUARDRAIL SYSTEM ATS JOB # D167754-1 PURCHASE ORDER # 22383 Prepared for
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window
Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:
10 ModLite Minimal (Option 4) Trade Show Display Booth
This Display provides a modern, slick, and stylish appearance. The extrusion based exhibit features a NEW velcro-applied fabric graphic. Headers and wings are available in UV printed graphics or frosted
SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS
1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...
Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information
SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex
(Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying cold-formed metal deck framing products and execution. The specifier needs to edit the guide
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014
ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
Creep Behavior of Structural Insulated Panels (SIPs)
Creep Behavior of Structural Insulated Panels (SIPs) Results from a Pilot Study Dwight McDonald Marshall Begel C. Adam Senalik Robert J. Ross Thomas D. Skaggs Borjen Yeh Thomas Williamson United States
MAT 75 STRUCTURAL SUPPORT SYSTEM
MAT 75 STRUCTURAL SUPPORT SYSTEM A GROUP COMPANY Structural Support Applications About the Mat 75 System For decades, Mabey Bridge & Shore has served the international construction community by providing
Dock Hardware & Accessory Products Catalog
Dock Hardware & Accessory Products Catalog Product Page # Product Page # Angle Brackets/Clips 8 Back Up Plate 5 Backing Plate/Hurricane Stop 10 Carriage Bolt Sets 4 Chain Retainer 10 Connector Pin Set
Uncovered Decks & Porches
Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
STANDARDS FOR TESTING AND RATING SCAFFOLD ASSEMBLIES AND COMPONENTS
American National Standard STANDARDS FOR TESTING AND RATING SCAFFOLD ASSEMBLIES AND COMPONENTS Scaffolding, Shoring & Forming Institute, Inc. Sponsor: Scaffolding, Shoring & Forming Institute, Inc. 1300
Typical Deck Details
Fairfax County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential, single-level decks only. Construction cannot deviate
Summary of ET Plus Guardrail End Treatment Inspections
Summary of ET Plus Guardrail End Treatment Inspections 12/16/2015 Maine Department of Transportation Prepared by Brian Burne, Atlee Mousseau, Clark Sulloway, Doug Gayne, Ulrich Amoussou Guenou & Dale Peabody
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED
SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams
Installation Instructions
Installation Instructions Issued: March 10, 2004 GeoDeck Deck and Railing System (ICC-ES Legacy Report No. 21 71, former BOCA Report No. 21 71) Design and Installation Manual Congratulations! You have
METHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
Uniform Construction Code (UCC) Manufactured Homes. Modular Homes. Building Permit Application Package
Uniform Construction Code (UCC) Manufactured Homes (Single-Wide, Double-Wide) Modular Homes Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per
glass & Glazing Products
glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system
How to Design Helical Piles per the 2009 International Building Code
ABSTRACT How to Design Helical Piles per the 2009 International Building Code by Darin Willis, P.E. 1 Helical piles and anchors have been used in construction applications for more than 150 years. The
Overhang Bracket Loading. Deck Issues: Design Perspective
Deck Issues: Design Perspective Overhang Bracket Loading Deck overhangs and screed rails are generally supported on cantilever brackets during the deck pour These brackets produce an overturning couple
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
Cable Installation Accessories. Cable Hoisting and Attachment. Snap-In Hangers. SnapStak Hangers
SnapStak Hangers New design increases stack height SnapStak hangers have become the industry standard for maximizing space utilization on crowded towers and now that utility is further expanded with the
Stair Railing. Installation Guide
Stair Railing Installation Guide THE BEST CHOICE FOR STRONG & DURABLE RAILING SYSTEMS Our exclusive manufacturing process ensures our vinyl railing will provide superior strength plus it is virtually maintenance
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
