PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
|
|
|
- Helen Allen
- 10 years ago
- Views:
Transcription
1 PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: Test Date: 05/17/10 Report Date: 09/21/ th Ave S Kent, WA phone: fax:
2 PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. P.O. Box 396 Enumclaw, WA Report No: Test Date: 05/17/10 Report Date: 09/21/10 Project Summary: Architectural Testing, Inc. was contracted by Architectural Metal Solutions, Inc. to perform testing on their AMS Armor-Lock Standing Seam Metal Roof Panel System. The test specimen was tested for air, water, and structural performance in accordance with the referenced test standards. This report includes comprehensive written and photographic documentation of testing performed. Test Buck Description: The test buck was constructed of 2 x 8 fir, and 24 gauge 2" galvanized steel channel was fastened to the interior of the test buck at the head and sill with #8 x 1" Tek screws 16" on center. A 24 gauge 2" galvanized steel angle was fastened to the interior of the test buck at the jambs with #8 x 1" Tek screws 16" on center. One 2 x 6 fir purlin was utilized, spaced at 2'-6". Test Specimen Description: Series/Model: AMS Armor-Lock Product Type: Standing Seam Metal Roof Panel System Overall Size: 65" wide by 60" high Test Specimen Construction: AMS Armor-Lock 24 gauge panels are produced with hot-melt rubber based sealant in the side laps. Additionally, the panel ends and sides are set on the galvanized framing members in butyl sealant. Panel vertical ribs have sealant applied at each end. Panel clips are one piece 22 gauge galvanized steel and attach to the top of the concealed vertical leg of the panel. Clips are secured to the 2 x 6 fir purlin at 2'-6" on center with one #10 x 1" pancake head Tek screw. Each panel is secured to the test buck with #10 x 1-1/2" screws at all four corners of each panel. This construction was used for the ASTM E 1592, ASTM E 1646, and ASTM E 1680 tests th Ave S Kent, WA phone: fax:
3 Page 2 of 4 Test Methods: ASTM E , Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference ASTM E (Re-approved 2003), Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference ASTM E (Re-approved 2003), Standard Test Method for Rate of Air Leakage Through Exterior Metal Roof Panel Systems Test Results: Test Method Title of Test Results ASTM E psf Air 1.57 psf >0.01 cfm/ft 2 Air psf >0.01 cfm/ft 2 Air 4.0 psf >0.01 cfm/ft 2 Air -4.0 psf >0.01 cfm/ft 2 ASTM E 1646 Water Penetration 6.24 psf No leakage ASTM E 1592 Structural Performance Max. +90 psf Max. -90 psf No damage (See tables below) Notes: 1. Reference Appendix A Photograph Number 3 for transducer (deflection) locations. 2. Reference Appendix B for Deflection and Permanent Set tables.
4 Page 3 of 4 The data sheets, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice; and the service life of this report by Architectural Testing, Inc. will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Paul S. Brunner Technician Jeffrey L. Dideon Director - Regional Operations Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Photographs (2) Appendix-B: Tables (1)
5 Page 4 of 4 Revision Log Rev. # Date Page(s) Revision(s) 0 09/21/10 N/A Original report issue. 1 11/19/10 Page 1 Client's address was changed. This report produced from controlled document template ATI 00300, issued 11/07/07.
6 APPENDIX A Photographs
7 Photograph Number 1 Test Specimen - Exterior Photograph Number 2 Test Specimen - Interior
8 Photograph Number 3 (Deflection gauge locations identified)
9 APPENDIX B Tables Deflection Measurements (inches) Pressure (psf) #1 #2 #3 #4 #5 #6 #7 #8 # Permanent Set Measurements (inches) Pressure (psf) #1 #2 #3 #4 #5 #6 #7 #8 # Deflection Measurements (inches) Pressure (psf) #1 #2 #3 #4 #5 #6 #7 #8 # Permanent Set Measurements (inches) Pressure (psf) #1 #2 #3 #4 #5 #6 #7 #8 #
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window
BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window
Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight
FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims
PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130
PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM
PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700
TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
Nucor VR16 II TM Vertical Rib Standing Seam Roof System
Nucor VR16 II TM Vertical Rib Standing Seam Ro System www.nucorbuildingsystems.com Nucor VR16 II Vertical Rib Standing Seam Ro Perfect for the Marketplace The Nucor Building Systems VR16 II Ro Panel is
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing
TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.
PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report
Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023
Specifications Preformed Metal Wall and Roof Panels Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Section 07410 Preformed Metal Wall and Roof Panels Structural
Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
WINDOW PANNING AND TRIMS
OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.
DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Standing Seam Roof Systems
Standing Seam Roof Systems REAL PEOPLE. REAL PRODUCTS. REAL SOLUTIONS. www.a-s.com Building Benefits You Can Expect From A&S Materials Standing Seam roof panels weigh a relatively modest 11/2 pounds per
TEST REPORT. Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California
Architectural Testing TEST REPORT Report No.: A8865.01-301-41 Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California TYPE: Dome Assembly Only SERIES/MODEL: Nano Insulgel - ALT-CM-2-CPM/16 mm CNANO Thermally
238T Standing Seam Metal Roof System (SSMRS)
238T Standing Seam Metal Roof System (SSMRS) Text in red are instructions to the specifier and should be deleted. Text in blue are choices that need to be made, with those not selected, deleted. McElroy
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Slim Seam Architectural Design Manual
Slim Seam Architectural Design Manual Headquarters: 3449 Hempland Road Lancaster, PA 17601 Phone: 800-477-2741 Fax: 800-283-4289 Architectural Products Division: 308 Alabama Blvd. Jackson, GA 30233 Phone:
Versa-Span STRUCTURAL STANDING SEAM
Versa-Span STRUCTURAL STANDING SEAM Features and Benifits 18" Standard Panel Width 1 3/4" Snap Lock Seam Custom Lengths 2' 0" to 300' 0" Concealed Clip System-No Seaming Required Minimum Slope 2 : 12 UL
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"
TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405
VERTICAL LOCK Table of Contents
Table of Contents TABLE OF CONTENTS Vertical Lock Product Data Sheet... 2 Vertical Lock Engineering Data... 3 General Information... 6 Material Testing... 7 Panel Overview... 8 Handling Material & Storage
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
PERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
AAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
Metal Roof Systems in High-Wind Regions
Metal Roof Systems in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for designing and installing metal roof systems that will enhance wind resistance
CB-100 CB-150 CS-100 SL-100 SL-150 SLZ-1000
CB-100 CB-150 CS-100 SL-100 SL-150 SLZ-1000 Details and Installation Guide October 2013 All information, descriptions and dimensions in this manual are current at the time of printing. As always, Custom-Bilt
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Metal Roofing Practical Design
Metal Roofing Practical Design Metal Roofing Practical Design Learning Outcomes Minimum Requirements Design Resources Low Slope Metal Roofing Design Details Continuously Insulated (Ci) Systems Minimum
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
PRODUCT SPECIFICATIONS
LokSeam LokSeam 12" One of the most versatile architectural metal panels available today, LokSeam by ABC, is a snap-together, concealed fastener, standing seam roof system with a 13/4" tall vertical rib,
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
continuing professional education. As such, it construed to be an approval or endorsement by
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any
The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems
The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions
Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions All questions and concerns please call 904-696-9700 Discount Direct Metal Roofing Plus Rib metal roofing panels are a strong,
Specifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
PANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com
SERIES 900 CASEMENT WINDOW Page 1 of 6 RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com SPECIFICATION GUIDE SERIES 900 CASEMENT WINDOW RAM Industries
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
AIA PRESENTATION. Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour
AIA PRESENTATION Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour Best Practice MBCI is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned
INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels
INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels Grand Rib-3 / Multi-Purpose / Classic Rib Grand Rib-3 / Multi-Purpose / & Classic Rib Grand Rib 3 panels are a strong,
STANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation
Product Catalog. Extreme Roofing, Inc. 2680 Rt. 982 Mammoth, PA 724.838.7695 www.extremeroofinginc.com
2012 Product Catalog Extreme Roofing, Inc. 2680 Rt. 982 Mammoth, PA 724.838.7695 www.extremeroofinginc.com 2 PH. 724.838.7695 Email. [email protected] Website. www.extremeroofinginc.com Fax.
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT
BRIDGE & SUPPLY COMPANY. Installation Guide. Ultra 2000. Includes:
BRIDGE & SUPPLY COMPANY Installation Guide Ultra 2000 Includes: Ultra 2000 Installation Guide Stock Trim Profiles Ultra 2000 Trim Installation Guide Page 2 Table of Contents Ultra 2000 Profile, Colors
Screw Penetration Testing with the ProSTUD
Screw Penetration Testing with the ProSTUD 24 June 2010 Structural Testing and Research Inc. 498 Eagle St. N., Unit 6 Cambridge, ON, Canada, N3H 1C2 Tel: (519) 653-5255 www.starlabs.ca STaR Technical Report
SECTION 07410 METAL ROOF & WALL PANELS
This document specifies Metal Roofing Systems prefinished factory formed metal roofing marketed as MRS System 2500 steel and aluminum roofing systems and includes MRS flashing and Trim. MRS finish is a
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
PRO-PANEL II. Panel Information. Detail Conditions. Flashing Profiles. Notes. Accessory Profiles. Testing Information
Table of ontents Product Page No. Product Page No. Panel Information Profile... PPP-2 Panel Overview... PPP-2 Flashing Profiles Eave (Direct Fasten)... PPP-3 leat... PPP-3 Box Gutter... PPP-3 Box Gutter
TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.
Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with
SECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
Brick Veneer Construction
Brick Veneer Construction Check list of suggested tools & support items Claw hammer Tape measure 3/4" [19 or 20] Wood chisel Wood or plastic shims Pry bar Utility knife Caulking and caulking gun Power
For the purposes of this Part, the following words shall have the following meanings:
LOUISIANA REVISED STATUTES TITLE 51. TRADE AND COMMERCE CHAPTER 2. PARTICULAR GOODS PART XIV-B. MINIMUM STANDARDS FOR INSTALLATION OF MANUFACTURED HOMES Current through all 2010 Regular Session Acts 912.21.