MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida

Size: px
Start display at page:

Download "MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida"

Transcription

1 Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL: 2500 HVHZ Flush glaze This report contains in its entirety: Cover Page: 1 page Report Body: 28 pages Sketches: 3 pages Drawings: 14 pages Test Dates: 06/12/12 Through: 06/21/12 Miami-Dade County Notification No.: ATI FL 12007

2 Page 1 of Report Issued To: American Products, Inc Lynmar Blvd. Tampa, Florida Test Laboratory: Architectural Testing, Inc Massaro Blvd. Tampa, Florida (813) Project Summary: 3.1 Product Type: Aluminum Storefront with Double Doors 3.2 Series/Model: 2500 HVHZ Flush glaze 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test methods. The samples were tested per Florida Building Code, Test Protocols for High Velocity Hurricane Zone, Protocols TAS , TAS , and TAS The three samples tested with Sentry Glass interlayer met the performance requirements set forth in the protocols for a ±60.00 psf Design Pressure rating. 3.4 Miami-Dade County Notification No.: ATI FL Test Dates: 06/12/ /21/ Test Location: Architectural Testing, Inc test facility in Tampa, Florida. 3.7 Test Sample Source: The test specimens were provided by the client. Representative samples of the test specimens will be retained by Architectural Testing for a minimum of ten years from the test completion date. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimens reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix C. Any deviations are documented herein or on the drawings. 3.9 List of Official Observers: Name Company Client Name John C McClane Shawn G Collins, P.E. Scott Parker Company Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc.

3 Page 2 of Test Specifications: TAS , Impact Test Procedures. TAS , Criteria for Testing Impact and Non Impact Resistant Building Envelope Components Using Uniform Static Air Pressure Loading. TAS , Criteria for Testing Products Subject to Cyclic Wind Pressure Loading. 5.0 Test Specimen Description: 5.1 Product Sizes: Test Unit #1 Overall Area: ft 2 Width (inches) Height (inches) Overall size Active door 47-1/2 95-1/2 Inactive door 47-1/2 95-1/2 Test Unit #2 (Double Doors) Overall Area: 69.1 ft 2 Width (inches) Height (inches) Overall size /2 Active door 47-1/2 95-1/2 Inactive door 47-1/2 95-1/2 Test Unit #3 (Double Doors with Transom) Overall Area: 80.6 ft 2 Width (inches) Height (inches) Overall size Active door 47-1/2" 95-1/2" Inactive door 47-1/2" 95-1/2"

4 Page 3 of Test Specimen Description: (Continued) 5.2 Frame Construction: Test unit #1 Frame Member Material Description Sub sill Sill Head Jambs Vertical mullion (Deep pocket) Vertical mullion (Shallow pocket) Horizontal mullions Extruded aluminum Extruded aluminum Extruded aluminum Extruded aluminum Extruded aluminum Extruded aluminum Extruded aluminum Part #API-2550; 5-1/4 wide by 2-1/2 high back leg, secured to a concrete slab utilizing Dow 795 and 5/16 x 2-3/4" tapcons. End dams were located at each end measuring 5-1/4" wide by 2-1/2" high and secured with silicone. Part #API-2520; square cut, butted, sealed with Dow 795 silicone. The sill was secured to the sub sill utilizing 5/16" x 1-1/2" self drilling tek screws and through the jambs and vertical mullions into the screw bosses. Part #API-2510; square cut, butted and sealed with Dow 795 silicone. The head was secured with three #12 x 1 pan head screws through the jambs and vertical mullions into the screw bosses. Part #API-2512; square cut, secured to the head and sill screw bosses with four #12 x 1 pan head screws and the horizontal mullion was secured with three #12 x 1 pan head screws. Part #API-2564 and API-2511; square cut, secured to the head and sill screw bosses with four #12 x 1 pan head screws and the horizontal mullion was secured with three #12 x 1 pan head screws. Part #API-2564 and API-2511; square cut, secured to the head and sill screw bosses with four #12 x 1 pan head screws and the horizontal mullion was secured with three #12 x 1 pan head screws. Part #API-2564; The horizontal mullions were square cut and secured with three #12 x 1 pan head screws through the jambs and vertical mullions into the screw bosses.

5 Page 4 of Test Specimen Description: (Continued) 5.2 Frame Construction: (Continued) Test unit #1 (Continued) Joinery Type Mechanically All corners fastened Detail Square cut, butted, sealed with Dow Corning 795 silicone and secured into screw boss. Test unit #2 Frame Member Material Description Head Jambs Horizontal Mullions Extruded aluminum Extruded aluminum Extruded aluminum Part #API-2563; square cut, butted and sealed with Dow 795 silicone. The head was secured with three #12 x 1 pan head screws through the jambs into the screw bosses. Part #API-2563; square cut, secured to the head screw bosses with four #12 x 1 pan head screws and the horizontal mullion was secured with three #12 x 1 pan head screws. Part #API-2564; The horizontal mullion was square cut and secured with three #12 x 1 pan head screws through the jambs into the screw bosses. All corners Joinery Type Mechanically fastened Detail Square cut, butted, sealed with Dow Corning 795 silicone and secured into screw boss. Test unit #3 Frame Member Material Description Head Jambs Extruded aluminum Extruded aluminum Part #API-2563; square cut, butted and sealed with Dow 795 silicone. The head was secured with three #12 x 1 pan head screws through the jambs into the screw bosses. Part #API-2563; square cut, secured to the head screw bosses with four #12 x 1 pan head screws and the horizontal mullion was secured with three #12 x 1 pan head screws. All corners Joinery Type Mechanically fastened Detail Square cut, butted, sealed with Dow Corning 795 silicone and secured into screw boss.

6 Page 5 of Test Specimen Description: (Continued) 5.3 Door panel Construction: The following descriptions apply to all specimens. Panel Member Material Description Door stiles Extruded aluminum Part #API , 1217and API Door rails Extruded aluminum Part #API and 1213 All corners Joinery Type Mechanically fastened Detail The top and bottom door rails were square cut, and butted. The rails utilized shear blocks at each end and were secured to the rails with four #10 x 1/2" Philips head machine screws. The bottom rail was secured to the doors locking and hinge stiles utilizing two Hex head self-tapping 1" screws through the shear blocks. The top rail utilized one Hex head self-tapping 1" screws through the shear blocks. The top and bottom rails also utilized an aluminum tack weld at the top and bottom corners of each rail. 5.4 Weatherstripping Test unit #1 and #2 Description Quantity Location 0.320" high by 0.430" backed polypile 1 Row Active door locking stile Interior glazing gasket 1 Row All four sides of the glazing pocket Exterior glazing gasket 1 Row All four sides of the glazing pocket Door sweep 1 Row The bottom of each door 3/8" hollow bulb gasket 1 Row Jambs and head 1/4" hollow bulb gasket 1 Row Threshold

7 Page 6 of Test Specimen Description: (Continued) 5.4 Weatherstripping Test unit #3 Description Quantity Location 0.320" high by 0.430" backed polypile 1 Row Active door locking stile Door sweep 1 Row The bottom of each door 3/8" hollow bulb gasket 1 Row Jambs and head 1/4" hollow bulb gasket 1 Row Threshold 5.5 Glazing: Test Unit #1 Glass Spacer Type Type 1-1/4" IG Aluminum reinforced butyl Interior Lite Two sheets of 1/4" heat strengthened glass separated by 0.090" Sentry Glass interlayer by DuPont Exterior Lite 1/4" tempered glass Glazing Method Exterior glazed onto interior glazing gasket and secured with snap-in glazing bead and exterior glazing gasket. Two 4" wide by 5/8" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the sill. Three 9-1/2" long by 7/8" wide by 1/8" thick side blocks were utilized in each of the deep pockets of the jambs and vertical mullions. Double Doors Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" Sentry Glass interlayer by DuPont Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf.

8 Page 7 of Test Specimen Description: (Continued) 5.5 Glazing: (Continued) Test Unit #1 Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" PVB interlayer Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf. Location Quantity Daylight Opening Glass Bite Lower left and right lite 2 60" x 92-7/8" 3/4" Upper left and right lite 2 60" x 19" 3/4" Center upper lite 1 96" x 19" 3/4" Lower left inactive door /8" x 82-3/4" 3/4" Lower right active door /8" x 82-3/4" 3/4" Test unit #2 Double Doors with Transom Glass Spacer Interior Lite Type Type 1-1/4" IG Aluminum reinforced butyl Two sheets of 1/4" heat strengthened glass separated by 0.090" SentryGlass interlayer by DuPont Exterior Lite 1/4" tempered glass Glazing Method Exterior glazed onto interior glazing gasket and secured with snap-in glazing bead and exterior glazing gasket. Two 4" wide by 5/8" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the sill. Three 9-1/2" long by 7/8" wide by 1/8" thick side blocks were utilized in each of the deep pockets of the vertical mullions.

9 Page 8 of Test Specimen Description: (Continued) 5.5 Glazing: (Continued) Test unit #2 (Continued) Double Doors with Transom Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" Sentry Glass interlayer by DuPont Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf. Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" PVB interlayer Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf. Test unit #2 Location Quantity Daylight Opening Glass Bite Center upper lite 1 96" x 19" 3/4" Lower left inactive door /8" x 82-3/4" 3/4" Lower right active door /8" x 82-3/4" 3/4" Test unit #3 Double Doors Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" Sentry Glass interlayer by DuPont Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf.

10 Page 9 of Test Specimen Description: (Continued) 5.5 Glazing: (Continued) Test unit #3 (Continued) Double Doors Glass Type Glazing Glazing Method Monolithic Two sheets of 1/4" heat strengthened glass separated by 0.090" PVB interlayer by Oldcastle Interior glazed onto exterior glazing gasket and secured with snap-in glazing bead and interior glazing utilized a wet glaze with DOW 995. Two 2" wide by 1/4" high by 1-1/4" deep setting blocks located at quarter points from the edge of the glass were utilized at the bottom rail of the door leaf. Location Quantity Daylight Opening Glass Bite Lower left inactive door /8" x 82-3/4" 3/4" Lower right active door /8" x 82-3/4" 3/4" 5.5 Drainage: Test unit #1 Drainage Method Size Quantity Location Weep hole 5/16" 4 Water diverter 1-1/4" wide by 1-1/2" long 7/8" wide by 2" deep Sub-sill 7" from each end and 9" each side of vertical mullions, through the first two vertical walls. 6 Each end of horizontal mullions. Open glazing Each end of sill and horizontal 10 pocket ends mullions members. Threshold 96" x 5" 1 The bottom of the double doors Test unit #2 and #3 Drainage Method Size Quantity Location Threshold 96" x 5" 1 The bottom of the double doors

11 Page 10 of Test Specimen Description: (Continued) 5.6 Hardware: The following descriptions apply to all specimens. Description Quantity Location Part #MS1851SW Located 40" from the bottom of the active 1 Deadbolt lock door leaf Part # IB Threshold Located at the bottom of the active door leaf 1 bolt locking stile Part # point Located at the top of the active door leaf 1 lock (header Bolt) stile Part #FB-2210A-18 2 Located at the top and bottom of the inactive door leaf stile Part # thumb turn 1 Located 40" up from the bottom of the active door leaf locking stile Part # standard Located 40" up from the bottom of the active 1 cylinder door leaf locking stile Located 9-1/2", 35-3/8", 61-1/4" and 87" Part # /2" x 4" 4 from the bottom of the active door leaf hinge hinge stile Part # continuous hinge Pat #BF Reinforcement: No reinforcement was utilized. 5.8 Screen Construction: No screen was utilized. 6.0 Installation: 1 Full length of the inactive door leaf hinge stile Two 10" exterior pull handles located 34" and 44-1/4" from the bottom of both active and inactive door leaf at the locking stiles. Two 45" push bars on the interior side of both door leaves 44-1/4" up from the bottom of each door. Test unit #1 The specimen was installed into a C8 steel C-channel and plywood chamber with an interior perimeter of a nominal double 2 x 8 southern yellow pine lumber wrap. The rough opening allowed for a 3/8" shim space at the top and jambs. The exterior and interior perimeter of the storefront wall was sealed with Dow 795.

12 Page 11 of Installation: (Continued) Test unit #1 (Continued) Location Anchor Description Anchor Location Head Sub sill Sill Threshold 5/16" x 3-3/4" Tapcons 5/16" x 2-3/4" Tapcons 5/16" x 1-1/2" selfdrilling pan head screw 5/16" x 2-3/4" Tapcons Four anchors 1-1/2" in from each jamb and each side of the vertical mullions 3" on center into the wood header. The center transom head utilized an additional two anchors 32" in from each vertical mullion. Four anchors 1-1/2" in from each jamb and each side of the vertical mullions 3" on center into the concrete slab. Four anchors 1-1/2" in from each jamb and each side of the vertical mullions 1-1/2" on center into the sub sill. Eight anchors 6" in from each vertical mullion 12" on center into the concrete slab. Test unit #2 and #3 The specimen was installed into a C8 steel C-channel. The rough opening allowed for a 3/8" shim space at the top and jambs. The exterior and interior perimeter of the double doors and were sealed with Dow 795. Test unit#2 Location Anchor Description Anchor Location Head Jambs Threshold 5/16" x 2-3/4" Tek screws 5/16" x 2-3/4" Tek screws 5/16" x 2-3/4" Tapcons Four anchors 1-1/2" in from each jamb and 3" on center with an additional two anchors 32" in from each jamb through the C-8 steel channel. 5" from the bottom of the jamb and 12" on center up to the horizontal mullion where two screws were located 3" apart above and below the mullion. Eight anchors 6" in from each jamb and 12" on center into the concrete slab. Test unit#3 Location Anchor Description Anchor Location Head 5/16" x 2-3/4" Tek screws 5" from each end and 12" on center Jamb 5/16" x 2-3/4" Tek 5" from the bottom of the jamb and 12" on screws center Threshold 5/16" x 2-3/4" Eight anchors 6" in from each vertical mullion Tapcons 12" on center into the concrete slab.

13 Page 12 of Test Results: The temperature during testing was 78 F. The results are tabulated as follows: Protocol TAS , Static Air Pressure Tests Test Unit #1 Design Pressure: 60.0 psf Title of Test Results Air Infiltration at 1.57 psf (25 mph) 0.18 cfm/ft 2 Air Infiltration at 6.24 psf (50 mph) 0.40 cfm/ft 2 Indicator Reading (inches) Structural Loads 50% of Test Pressure (+45.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set < #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Design Pressure (+60.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set % of Test Pressure (-45.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set

14 Page 13 of Test Results: (Continued) Test Unit #1 (Continued) Design Pressure: 60.0 psf Indicator Reading (inches) Design Pressure (-60.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Water Infiltration 15% Positive Design Pressure (+9.0 psf) See note #1 Note: See Architectural Testing Sketch #1 for indicator locations. Note#1: Water entered in between the right side vertical mullion/door hinge jamb and sill joinery 5 minutes into the test. (Interior view)

15 Page 14 of Test Results: (Continued) Protocol TAS , Static Air Pressure Tests Test Unit #1 (retest) Design Pressure: 60.0 psf Title of Test Results Air Infiltration at 1.57 psf (25 mph) 0.17 cfm/ft 2 Air Infiltration at 6.24 psf (50 mph) 0.39 cfm/ft 2 Indicator Reading (inches) Structural Loads 50% of Test Pressure (+45.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Design Pressure (+60.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set % of Test Pressure (-45.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set

16 Page 15 of Test Results: (Continued) Test Unit #1 (Retest) (Continued) Design Pressure: 60.0 psf Indicator Reading (inches) Design Pressure (-60.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Water Infiltration 15% Positive Design Pressure (+9.0 psf) No Penetration Test Pressure (+90.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Test Pressure (-90.0 psf) #1 #2 #3 #4 #5 #6 Maximum Deflection Permanent Set #7 #8 #9 #10 #11 #12 Maximum Deflection Permanent Set Forced Entry lb Pull Test Pass Notes: Vertical mullions do not meet L/180 for deflection See Architectural Testing Sketch #1 for indicator locations.

17 Page 16 of Test Results: (Continued) Protocol TAS , Impact Test Procedures Missile Weight: 9.25 lbs Missile Length: 8' 1" Muzzle Distance from Test Specimen: 17' 0" Test Unit #1: Impact #1: Missile Velocity: 49.5 fps Impact Area: Left Fixed Light, center of glazing Missile hit target area, fractured the laminated Observations: glass with no penetration Results: Pass Impact #2: Missile Velocity: 50.3 fps Impact Area: Left Fixed Light, upper right corner of the glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Impact #3: Missile Velocity: 50.0 fps Impact Area: Right Fixed Light, lower left corner of the glazing Missile hit target area, fractured the laminated Observations: glass with no penetration Results: Pass Impact #4: Missile Velocity: 49.9 fps Impact Area: Right Fixed Light, center of glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Note: See Architectural Testing Sketch #2 for impact locations.

18 Page 17 of Test Results: (Continued) Protocol TAS , Impact Test Procedures Missile Weight: 9.25 lbs Missile Length: 8' 1" Muzzle Distance from Test Specimen: 17' 0" Test Unit #1: Impact #5: Missile Velocity: 50.0 fps Impact Area: Active door, upper right corner of the glazing Missile hit target area, fractured the laminated Observations: glass with no penetration Results: Pass Impact #6: Missile Velocity: 50.3 fps Impact Area: Active door, center of glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Impact #7: Missile Velocity: 50.1 fps Impact Area: Right vertical mullion, center shot Observations: Missile hit target area, dented the aluminum Results: Pass Impact #8: Missile Velocity: 50.7 fps Impact Area: Center of active door locking stile above the lock. Missile hit target area, dented the aluminum no Observations: disengagement Results: Pass Note: See Architectural Testing Sketch #2 for impact locations.

19 Page 18 of Test Results: (Continued) Protocol TAS , Impact Test Procedures Missile Weight: 9.25 lbs Missile Length: 8' 1" Muzzle Distance from Test Specimen: 17' 0" Test Unit #1: Impact #9: Missile Velocity: 50.8 fps Impact Area: Inactive door leaf, center of bottom rail Observations: Missile hit target area, dented aluminum Results: Pass Impact #10: Missile Velocity: 50.9 fps Center of the horizontal mullion above the double Impact Area: doors Observations: Missile hit target area, dented the aluminum Results: Pass Note: See Architectural Testing Sketch #2 for impact locations Inactive door impact SGP Interlayer Impact #11: Missile Velocity: 50.1 fps Impact Area: Inactive door leaf, lower right corner Missile hit target area,, fractured the laminated Observations: glass with no penetration Results: Pass Impact #12: Missile Velocity: 50.3 fps Impact Area: Active door, center of glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass

20 Page 19 of Test Results: (Continued) Protocol TAS , Impact Test Procedures Missile Weight: 9.20 lbs Missile Length: 7'2" Muzzle Distance from Test Specimen: 17' 0" Test Unit #2: (Double Door with Transom) Impact #1: Missile Velocity: 50.1 fps Impact Area: Active door leaf, upper right corner of the glazing Missile hit target area, Fractured the laminated Observations: glass with no penetration Results: Pass Impact #2: Missile Velocity: 50.3 fps Between the active and inactive door stiles 3" Impact Area: above the lock Observations: Missile hit target area, dented the aluminum Results: Pass Impact #3: Missile Velocity: 50.1 fps Impact Area: Center glazing on the active door Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Impact #4: Missile Velocity: 49.9 fps Impact Area: Center of horizontal mullion Observations: Missile hit target area, dented the aluminum Results: Pass

21 Page 20 of Test Results: (Continued) Test unit#2: (Double Door with Transom) (Continued) Impact #5: Missile Velocity: 50.3 fps Impact Area: Inactive door leaf, upper right corner of the glazing Missile hit target area, Fractured the laminated Observations: glass with no penetration Results: Pass Impact #6: Missile Velocity: 49.9 fps Impact Area: Center glazing on the inactive door Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Impact #7: Missile Velocity: 50.1 fps Impact Area: Inactive door leaf, center of bottom rail Observations: Missile hit target area, dented the aluminum Results: Pass Impact #8: Missile Velocity: 50.0 fps Between the active and inactive door stiles 3" Impact Area: above the lock Observations: Missile hit target area, dented the aluminum Results: Pass Note: See Architectural Testing Sketch #3 for impact locations.

22 Page 21 of Test Results: (Continued) Protocol TAS , Impact Test Procedures Missile Weight: 9.20 lbs Missile Length: 7' 2-1/2" Muzzle Distance from Test Specimen: 17' 0" Test Unit #3: (Double Door) Impact #1: Missile Velocity: 50.3 fps Impact Area: Active door leaf center of glazing Missile hit target area, fractured the laminated Observations: glass with no penetration Results: Pass Impact #2: Missile Velocity: 50.5 fps Impact Area: Active door leaf upper right corner of the glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Impact #3: Missile Velocity: 50.4 fps Impact Area: Inactive door leaf center of the glazing Missile hit target area, fractured the laminated Observations: glass with no penetration Results: Pass Impact #4: Missile Velocity: 50.4 fps Impact Area: Inactive door leaf lower right corner of the glazing Missile hit target area, re-fractured the laminated Observations: glass with no penetration Results: Pass Note: See Architectural Testing Sketch #4 for impact locations.

23 Page 22 of Test Results: (Continued) Protocol TAS , Cyclic Wind Pressure Loading Test Unit #1 Design Pressure: ±60.0 psf Pressure Range psf Number of Cycles POSITIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Permanent Set (inches) Pressure Range psf Number of Cycles POSITIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #7 #8 #9 #10 #11 # to to to to Permanent Set (inches) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #1 for indicator locations.

24 Page 23 of Test Results: (Continued) Protocol TAS , Cyclic Wind Pressure Loading Test Unit #1 Design Pressure: ±60.0 psf Pressure Range psf Number of Cycles NEGATIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Permanent Set (inches) Pressure Range psf Number of Cycles NEGATIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #7 #8 #9 #10 #11 # to to to to Permanent Set (inches) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #1for indicator locations.

25 Page 24 of Test Results: (Continued) Protocol TAS , Cyclic Wind Pressure Loading Test Unit #2 Design Pressure: ±60.0 psf Pressure Range psf Number of Cycles POSITIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Pressure Range (psf) Number of Cycles Permanent Set (inches) POSITIVE PRESSURE Average Cycle Maximum Deflection at Indicator (inches) Time (seconds) #7 #8 # to to to to Permanent Set (inches) Observations: About 300 cycles into the 50% to80% of the positive pressures the upper right corner impact area on the active door leaf deglazed from the door top rail. The door was boarded up and the testing was continued, No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #5 for indicator locations.

26 Page 25 of Test Results: (Continued) Protocol TAS , Cyclic Wind Pressure Loading Test Unit #2 Design Pressure: ±60.0 psf Pressure Range psf Number of Cycles NEGATIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Permanent Set (inches) Pressure Range (psf) Number of Cycles NEGATIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #7 #8 # to to to to Permanent Set (inches) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #5 for indicator locations

27 Page 26 of Test Results: (Continued) Protocol TAS , Cyclic Wind Pressure Loading Test Unit #3 Design Pressure: ±60.0 psf Pressure Range psf Number of Cycles POSITIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Permanent Set (inches) Pressure Range psf Number of Cycles NEGATIVE PRESSURE Average Maximum Deflection at Indicator (inches) Cycle Time (seconds) #1 #2 #3 #4 #5 # to to to to Permanent Set (inches) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #6 for indicator locations

28 Page 27 of Test Equipment Cannon: Constructed from steel piping utilizing compressed air to propel the missile Missile: 2x4 Southern Pine Timing Device: Electronic Beam Type Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers, 9.0 Laboratory Compliance Statements: The following are provided as required by the protocols for the testing reported herein. Upon completion of testing, specimens tested for TAS met the requirements of Section 1626 of the Florida Building Code, Building (2010) Upon completion of testing, specimens tested for TAS met the requirements of Section 1620 of the Florida Building Code, Building (2010). Upon completion of testing, specimens tested for TAS met the requirements of Section 1626 of the Florida Building Code, Building (2010) Sentry Glass interlayer only. Tape and film were used to seal against air leakage during structural testing. opinion, the tape and film did not influence the results of the test. In our

29 Test Report No.: B Page 28 of 28 The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimens can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. John C. McClane Laboratory Manager Shawn G. Collins, P.E. Manager-Regional Operations JCM:sgc:asm Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Sketches (3) Appendix-B: Drawings (14) This report produced from controlled document template ATI 00501, issued 06/10/11.

30 Appendix A Sketches

31 # * * INDICATES AN FBC SECTION 1626 REQUIREMENT INDICATOR LOCATION INDICATES IMPACT SEQUENCE INDICATES LARGE MISSILE IMPACT LOCATION INDICATOR AND L.M.I LOCATIONS SCALE:NTS Architectural Testing

32 # * * INDICATES AN FBC SECTION 1626 REQUIREMENT INDICATOR LOCATION INDICATES IMPACT SEQUENCE INDICATES LARGE MISSILE IMPACT LOCATION INDICATOR AND L.M.I LOCATIONS SCALE:NTS Architectural Testing

33 # * * INDICATES AN FBC SECTION 1626 REQUIREMENT INDICATOR LOCATION INDICATES IMPACT SEQUENCE INDICATES LARGE MISSILE IMPACT LOCATION INDICATOR AND L.M.I LOCATIONS SCALE:NTS Architectural Testing

34 Appendix B Drawings

35

36

37

38

39

40

41

42

43

44

45

46

47

48

How To Test For An Architectural Test

How To Test For An Architectural Test Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07

More information

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom

More information

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,

More information

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13

More information

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration

More information

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report

More information

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed

More information

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01

More information

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)

More information

SECTION 6. Glass Storefront Doors:

SECTION 6. Glass Storefront Doors: SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01

More information

Glossary. 1/3 1/3 1/3 - Configuration of a vent-fixed-vent (xox) window in which the vents and fixed panel are equal sizes

Glossary. 1/3 1/3 1/3 - Configuration of a vent-fixed-vent (xox) window in which the vents and fixed panel are equal sizes Glossary 1/3 1/3 1/3 - Configuration of a vent-fixed-vent (xox) window in which the vents and fixed panel are equal sizes 1/4 1/2 1/4 - Configuration of a vent-fixed-vent (xox) window in which the vents

More information

Important Information for Installer & Homeowner

Important Information for Installer & Homeowner Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side

More information

Scottsdale, Arizona. Presentation by: Hermes Norero, P.E. President and CEO

Scottsdale, Arizona. Presentation by: Hermes Norero, P.E. President and CEO Scottsdale, Arizona Presentation by: Hermes Norero, P.E. President and CEO Mr. Hermes F. Norero, P.E. is the founder and President of Building Drops. The concept of Building Drops first arose after realizing,

More information

n Three 4 x 4 butt hinges per door - prevents wracking and assures smooth positive operation n Heavy duty 16 gauge steel frame

n Three 4 x 4 butt hinges per door - prevents wracking and assures smooth positive operation n Heavy duty 16 gauge steel frame Weather Fin and bulb help keep bad weather outside and good air inside Windows: n Many light kits are available 1-LU 4 X 48 1-LE 16 X 16 1-LA 20 X 24 1-LI 20 X 24 1-B 22 X 36 1-LW 16 X 16 W/GRID 9-LB 22

More information

SERIES 238 WINDOWS. NOTE: Read instructions completely before attempting any installation.

SERIES 238 WINDOWS. NOTE: Read instructions completely before attempting any installation. 1 Installation Instructions SERIES 238 WINDOWS Page 2: Page 3-4: Page 5: Page 6: Page 7: Opening Preparation and Wood Buck Installation Installation Instructions for Series 238 WINDOWS Figure 1: Buck preparation

More information

DE Frame with C Series Sidelight

DE Frame with C Series Sidelight TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window

Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window Windows Curtain Walls Entrances Storefronts Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window Configurations XO OX XOX Fixed Series 3502 retains an AAMA

More information

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court

More information

SECTION 08560 SERIES 1500 VINYL PATIO DOORS

SECTION 08560 SERIES 1500 VINYL PATIO DOORS SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish

More information

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product

More information

Clad Direct Glaze Window Installation Instructions

Clad Direct Glaze Window Installation Instructions Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

WINDOW PANNING AND TRIMS

WINDOW PANNING AND TRIMS OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.

More information

Garden Window. Montecito Series Vinyl Garden Window Architectural Manual

Garden Window. Montecito Series Vinyl Garden Window Architectural Manual Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,

More information

Residential Garage Door Terminology

Residential Garage Door Terminology A Air Infiltration: The leakage or passage of air through a door system Anodize: A hard non-corrosive oxide film on the surface of aluminum Astragal: A compressible or deformable seal provided on the bottom

More information

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001) Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions

More information

Window Glass Design 5 According to ASTM E 1300

Window Glass Design 5 According to ASTM E 1300 A User s Guide to: Window Glass Design 5 According to ASTM E 1300 A product of: 1 Table of Contents Table of Contents List of Figures Chapter 1: Window Glass Design 5 1.1 Introduction 1.2 Features ii iv

More information

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40 TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized

More information

Impact-Resistant Windows and Sliding Glass Doors

Impact-Resistant Windows and Sliding Glass Doors Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they

More information

City of San Diego, CWP Guidelines

City of San Diego, CWP Guidelines PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,

More information

Garden Windows Builders Vinyl

Garden Windows Builders Vinyl TABLE OF CONTENTS Specifications... 8-2 QuickSpecGuide... 8-3 Elevations/Sizes: 1/4 Scale GardenUnits... 8-4 Grille Patterns... 8-5 SectionDetails: 6 Scale... 8-6 December 2008 JELD-WEN reserves the right

More information

Assessing Curtain Walls

Assessing Curtain Walls Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building

More information

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401 BASIC FIRE DOOR REQUIREMENTS SHEET NO. 401 Fire door openings are classified by their locations in the building. The location determines the length of exposure protection required, based on the potential

More information

2.02. Specifications. General. Products. Execution. Offset Pivots P-694 Top and Bottom Pivots

2.02. Specifications. General. Products. Execution. Offset Pivots P-694 Top and Bottom Pivots 2.02 Standard Specifications General Entrances Description Furnish all necessary materials, labor and equipment for the complete installation of aluminum entrance doors, door frames and hardware as shown

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

INSTALLATION INSTRUCTIONS for Vinyl Windows without Nailing Fin (JII011) ImPOrTANT INFOrmATION & GlOssAry. rough OPeNINGs

INSTALLATION INSTRUCTIONS for Vinyl Windows without Nailing Fin (JII011) ImPOrTANT INFOrmATION & GlOssAry. rough OPeNINGs Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for vinyl windows without a nailing fin (including finless, flush fin and flange). Read these instructions

More information

Specifying Windows. Performance Standards

Specifying Windows. Performance Standards 1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

WINDOW REPAIR MANUAL & REFERENCE GUIDE

WINDOW REPAIR MANUAL & REFERENCE GUIDE WINDOW REPAIR MANUAL & REFERENCE GUIDE TABLE OF CONTENTS DOUBLE HUNG & SINGLE HUNG PARTS 4-5 CASEMENT PARTS 6 SCREEN PARTS 7-8 HOW TO REMOVE TILT-IN SASH 9 HOW TO REMOVE A BALANCE 10 HOW TO INSTALL BALANCE

More information

Heavy Glass Frameless Shower Door With Return Panel

Heavy Glass Frameless Shower Door With Return Panel 202 Anderson Ave., elvue, KS 66407 Phone: 800-669-9867 Fax: 800-393-6699 www.onyxcollection.com Heavy Glass Frameless Shower Door With Return Panel Full Showers with Return ench Seat with Return FRLSDRPL-0116

More information

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Introduction...COMB-2 Design Considerations and Examples...COMB-3 SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant

More information

Sun Windows General Information Sun New Construction Window Installation Instructions

Sun Windows General Information Sun New Construction Window Installation Instructions Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten

More information

CLEAR-DIVISIONS APERTO

CLEAR-DIVISIONS APERTO CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the

More information

CLEAR-DIVISIONS VARIOFOLD

CLEAR-DIVISIONS VARIOFOLD CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the

More information

4 5/16 Subframe Installation

4 5/16 Subframe Installation 4 5/16 Subframe Installation The subframe system is a great installation tool for installing windows in masonry conditions. Typically subframes are used in masonry openings so that windows can be anchored

More information

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

WHI 90-Minute Rated Veneered Door Frame Installation Instructions No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,

More information

Strength, Style and Security for your home and family

Strength, Style and Security for your home and family Strength, Style and Security for your home and family NEW and IMPROVED DOORS 2013 John Cannon Homes, Inc. The Amarina Why Sentinel Impact Resistant Windows and Doors? Sentinel by CGI has received the prestigious

More information

HMMA 810 HOLLOW METAL DOORS HOLLOW METAL MANUAL -87 NAAMM STANDARD FOURTH EDITION METAL DOORS & FRAMES NAAMM 2 NAAMM 2 METAL DOORS & FRAMES

HMMA 810 HOLLOW METAL DOORS HOLLOW METAL MANUAL -87 NAAMM STANDARD FOURTH EDITION METAL DOORS & FRAMES NAAMM 2 NAAMM 2 METAL DOORS & FRAMES HOLLOW METAL MANUAL NAAMM STANDARD HMMA 810-87 8d METAL DOORS & FRAMES NAAMM 2 87 HOLLOW METAL HOLLOW METAL DOORS FOURTH EDITION NAAMM 2 87 8d METAL DOORS & FRAMES A Division of NATIONAL ASSOCIATION OF

More information

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit. Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden

More information

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit. Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden

More information

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.

More information

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357

More information

K. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11

K. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11 K. D. FRAME ASSEMBLY FOR MASONRY WALLS...........................Ins 2 FRAME INSTALLATION DETAILS FOR MASONRY WALLS......................Ins 3 INSTALLING EXISTING MASONRY WALL ANCHORS IN FRAME..................Ins

More information

Replacement Installation Instructions

Replacement Installation Instructions Sliding Door Replacement Installation Instructions Please make sure you have: Fixed 1 - Operating (X) Panel (Glazing Bead Inside, Roller Adjustment Holes Outside) 1 - Fixed (O) Panel (For 3-Panel doors,

More information

Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions

Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Y Parts Included: Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Tools Required: Power Driver Drill Bit (Determined by fastener) Driver Bit (Determined by fastener)

More information

AAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure

AAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U

More information

JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs

JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition

More information

WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:

WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,

More information

RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com

RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com SERIES 900 CASEMENT WINDOW Page 1 of 6 RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com SPECIFICATION GUIDE SERIES 900 CASEMENT WINDOW RAM Industries

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows

Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Series 2050 Garden Window The Series 2050 standard garden window has an outstanding reputation for its distinctive design and excellent

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art

Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art D O O R F R A M E S Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art D O O R F R A M E S Eggers Industries

More information

Installation Guide for Andersen Architectural Wood Inswing Entry Doors

Installation Guide for Andersen Architectural Wood Inswing Entry Doors Installation Guide for Andersen Architectural Wood Inswing Entry Doors Congratulations! You have just purchased one of the many fine Andersen products. Proper assembly, installation and maintenance are

More information

Wind Mitigation Inspection

Wind Mitigation Inspection tpatrick@ispects.me Tampa Bay Area: SW & Central Florida: (813) 368-6407 (239) 896-3986 Wind Mitigation Inspection VonHaase, Dale 4585 Bowen Bayou Road Sanibel, FL 33957 5/6/2013 Note to Policyholder:

More information

Andersen Clad Inswing Entry Doors (2001 to Present)

Andersen Clad Inswing Entry Doors (2001 to Present) Andersen Clad Inswing Entry Doors (2001 to Present) What s in This Section Clad Inswing Entry Doors Page 3 Part Illustrations 3 Parts Illustration - Single Door 3 Parts Illustration - Double Door 4 Parts

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

Therma-Tru Slim-Line Sliding Patio Door. Assembly and Installation

Therma-Tru Slim-Line Sliding Patio Door. Assembly and Installation Therma-Tru Slim-Line Sliding Patio Door Assembly and Installation Read all instructions before starting. Builder or subcontractor, please forward these instructions to the homeowner. The applicable standards

More information

SECTION 08460 AUTOMATIC SLIDING DOOR SYSTEMS. A. Automatic sliding doors with operator and motion/presence sensor control device.

SECTION 08460 AUTOMATIC SLIDING DOOR SYSTEMS. A. Automatic sliding doors with operator and motion/presence sensor control device. SECTION 08460 AUTOMATIC SLIDING DOOR SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Automatic sliding doors with operator and motion/presence sensor control device. 1.2 RELATED SECTIONS A. Section 08400

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Premier & Deluxe 3-Season Room Sliding Glass Door

Premier & Deluxe 3-Season Room Sliding Glass Door DTSSGD-11 Premier & Deluxe 3-Season Room Sliding Glass Door Installation Instructions Screen Door Seal Left Side Track Top Track Assembly Right Side Track Right Side Trim Sliding Glass Door Sliding Screen

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence

CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story)

More information

INSTALLATION INSTRUCTIONS for Vinyl Patio Doors with Integral Nailing Fin (JII006)

INSTALLATION INSTRUCTIONS for Vinyl Patio Doors with Integral Nailing Fin (JII006) Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl Patio Doors with nailing fin. Any local building code requirements supersede the recommended

More information

Installation Detailed installation instructions are provided which should be strictly followed.

Installation Detailed installation instructions are provided which should be strictly followed. Specification System 6 The Metal Technology Thermally-Broken Vertical Slide Window has been designed in such a way that its'attractive and clean lines will enhance all types of residential and commercial

More information

Casement/Awning Window Parts Reference Catalog

Casement/Awning Window Parts Reference Catalog Casement/Awning Window Parts Reference Catalog (Includes Miscellaneous Parts for Eyebrow Casement and Garden Bay Windows) #1028654 (Revised 03/02) Weather Shield Mfg., Inc. Medford, WI 54451 715/748-2100

More information

Astragal: a vertical member placed at the meeting edges of a double door to provide a weather seal and may be used to anchor the fixed door.

Astragal: a vertical member placed at the meeting edges of a double door to provide a weather seal and may be used to anchor the fixed door. Window and Door Dictionary AAMA: American Architectural Manufacturers Association. A national trade association that establishes voluntary standards for the window, door, and skylight industry. Ambient

More information

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4 x 4 and 5 x 5 PVC Porch Posts with Aluminum Reinforcing TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry

More information

PERFORMANCE TEST REPORT

PERFORMANCE TEST REPORT PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789

More information

Installation Instructions

Installation Instructions Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate

More information