TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
|
|
|
- Walter Marshall
- 9 years ago
- Views:
Transcription
1 Architectural Testing TEST REPORT Report No.: D Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite Panel System AAMA , Voluntary Test and Classification Method for Drained and Back Ventilated Rain Screen Wall Cladding Systems. Classification: V1/W1 Reference must be made to Report No. D , dated 08/29/13 for complete test specimen description and detailed test results.
2 Page 1 of Report Issued To: TFC A Division of Centurion Industries, Inc North Taylor Road Garrett, Indiana Test Laboratory: Architectural Testing, Inc. 849 Western Ave. North St. Paul, Minnesota Project Summary: 3.1 Product Type: Pressure Equalized Rainscreen 3.2 Series/Model: 4 mm Composite Panel System 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test methods. Test specimen description and results are reported herein. 3.4 Test Dates: 08/14/ /16/ Test Record Retention End Date: All test records for this report will be retained until August 29, Test Location: Architectural Testing, Inc. test facility in St. Paul, Minnesota. 3.7 Test Sample Source: The test specimen was provided by the client Representative samples of the test specimen will be retained by Architectural Testing for a minimum of four years from the test completion date. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix A. Any deviations are documented herein or on the drawings. 3.9 List of Official Observers: Name Karl Lips-Eakins Company Architectural Testing, Inc.
3 Page 2 of Test Methods: AAMA , Voluntary Test and Classification Method for Drained and Back Ventilated Rain Screen Wall Cladding Systems. ASTM E , Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen. Testing was conducted at 75 Pa (1.57 psf) positive static air pressure difference. Air Flow Analysis: Testing was conducted at 75 Pa (1.57 psf) positive static air pressure difference to verify "defective" air-water barrier. Testing was conducted at 26 Pa (0.55 psf) positive static air pressure difference to establish the air flow capabilities of the exterior cladding system. Each condition; head, jamb, sill, intermediate vertical and intermediate horizontal were tested by taking the air flow readings of each element to better understand the system's ability to allow for ventilation and the potential for drying. ASTM E , Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform Static Air Pressure Difference. Testing was conducted at both 300 Pa (6.24 psf) and 575 Pa (12.0 psf) positive static air pressure difference for a 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/hr/ft 2. AAMA , Standard Test Method for Water Penetration of Windows, Curtain Walls, and Doors Using Dynamic Pressure. Testing was conducted with a dynamic pressure equivalent of both 300 Pa (6.24 psf) and 575 Pa (12.0 psf) for a 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/hr/ft Test Specimen Description: 5.1 Product Sizes: Overall Area: Width Height 6.1 m² (66.2 ft 2 ) millimeters inches millimeters inches Overall size / Panel size (x4) / /4
4 Page 3 of Test Specimen Description: (Continued) 5.2 Joint Sizes: Width Height Joint Location millimeters inches millimeters inches Head joint /4 3 1/8 Sill joint /4 19 3/4 Horizontal joint /4 13 1/2 Vertical joint /8 5.3 Rain Screen Panel Construction: The wall system consisted of four composite panels that measured 4 mm (0.158") thick. The panels were constructed with a 0.118" thick plastic core and 0.020" thick aluminum interior and exterior skins, adhered to the plastic core. One 90 bend was utilized on all four sides of the panel with a 3/4" return leg. An aluminum extrusion was secured to the interior perimeter of the panel and secured with #6 x 1" screws. Extrusion corners were mitered and joined with a 4" x 4" piece of composite material. Horizontal joints, in the mid-field of the wall system, utilized a bent aluminum flashing to divert water towards the panel. The panels had 1/8" dia. weep holes along the bottom return leg spaced 6" from corners and mid-span. 3" long "F" shaped aluminum extrusions were utilized to secure the panels to the base wall, 2 per side, by fitting into the panel edge and screwed onto studs/sheathing with a #12 x 2" hex head screw. The perimeter of the wall system utilized an "L" shaped aluminum flashing. The intermediate joints of the wall panel system utilized an aluminum composite filler strip that slid into the panel backer extrusion. 5.4 Test Wall Construction: The test wall was constructed of 16 gauge, 6" galvanized steel studs. The steel studs were spaced 16" on center inside a 2x10 wood buck. The stud wall was covered with 1/8" thick clear lexan, sealed and secured to the exterior of the wall to simulate an air/water barrier. A formed aluminum gutter was installed at the base of the acrylic sheet for the purpose of collecting, draining, and measuring the water that contacted the air/water barrier. The wall panel system was installed onto the clear polycarbonate in a manner consistent with normal construction procedures for the system.
5 Page 4 of Test Procedure: Prior to installation of the test specimen, a chamber tare reading was taken to establish the air flow through the buck/chamber arrangement. The clear polycarbonate was calibrated to a pre-determined air leakage rate by drilling 1/8" diameter holes on the backside in a uniform pattern, making sure to create an even pressure drop and leakage rate across the wall and in each quadrant. The test specimen was installed and an air infiltration reading was taken, subtracting the initial tare and air leakage established through the defect holes to obtain a net air infiltration reading through the cladding assembly. Upon completion of the initial air measurements through the specimen, the system was prepared to determine air flow through the cladding elements. Each joint (head, jambs, sill, intermediate horizontal(s), and intermediate vertical) was temporarily sealed using foam blocks and tape as required. A tare reading was performed and each joint was subsequently tested to determine the air flow through each of the various joinery elements. After air flow testing, water penetration testing was initiated. For the water penetration test, the tape was removed from all but the jamb joinery. This process provides for the determination of water penetration through the designed rain screen cladding elements; less the jamb conditions; which were intentionally omitted from the test results as they are considered non-standard conditions. For the purpose of this test, water penetration is considered to be any water that makes contact with the AWB and is either collected in the gutter at the sill, or penetrates the purposely designed defects that were drilled in the AWB. The water was collected, measured by weight, and then converted to a unit of volume in order to draw comparisons between the various pressure levels tested. After the completion of the water testing protocol, the specimen was allowed to sit for several hours at test lab interior ambient conditions. The specimen was later evaluated to determine the amount of residual water that may have remained on the AWB and/or back of the specimen. The purpose of this was to achieve an understanding of the drying capability of the system.
6 Page 5 of Test Results: The temperature during testing was 26 C (78 F). The results are tabulated as follows: Air Leakage (Infiltration per ASTM E 283) (Initial Tare) Pressure Results Allowed Note 75 Pa (1.57 psf) 1.1 L/s (2.23 cfm) 0.15 L/s/m 2 (0.03 cfm/ft 2 ) Report Only 1 Air Leakage (Infiltration per ASTM E 283) (with Defects) Pressure Results Allowed Note 3.5 L/s (7.39 cfm) 1 75 Pa (1.57 psf) Report Only 0.60 L/s/m 2 (0.12 cfm/ft 2 ) 1, 2 Air Leakage (Infiltration per ASTM E 283) (Total with Cladding) Pressure Results Allowed Note 3.5 L/s (7.39 cfm) 1 75 Pa (1.57 psf) Report Only 0.60 L/s/m 2 (0.12 cfm/ft 2 ) 1, 3 Note #1: The calibrated air leakage was achieved by drilling twelve 1/8" diameter holes through the polycarbonate. These holes represent purposely designed defects in the AWB. Note #2: Result includes initial wall tare and deflects which resulted in a leakage of 0.6 L/s/m 2 (0.12 csm/ft²). Note #3: Result includes initial tare, 0.6 L/s/m 2 (0.12 cfm/ft²) of purposely imposed defects and added leakage from wall system installation.
7 Page 6 of Test Results For System Classification: The data compiled during testing for classification purposes is recorded in Tables #1 and #2. Air Leakage (Infiltration per ASTM E 283) (Air Flow Across Cladding) Pressure Results Allowed 26 Pa (0.55 psf) See Table 1 Report Only TABLE #1 Test Results - Air Flow Measurement Across The Cladding Elements Data Head Sill Horizontal Vertical Sum L/s/m² L/s (cfm) (3) (cfm/ft²) (4) L/s (cfm) (1) 7.52 (15.93) 0.99 (2.09) 1.57 (3.33) 2.10 (4.44) (25.79) 1.95 (0.39) L/s/m (cfm/ft) (2) (1.97) 1.43 (0.26) 2.26 (0.41) 3.03 (0.55) Not Required Not Required (1)Data for each element (1) head/sill/horizontal(s)/vertical(s) and expressed as L/s (cfm). (2)L/s (cfm) per lineal ft. of each element - head/sill/horizontal(s)/vertical(s) and expressed as L/s/m (cfm/ft). (3)The sum the total L/s (cfm) from all of the elements. (4)The sum total of (3) divided by the square footage and expressed as L/s/m 2 (cfm/ft²). Used for classification purposes to determine the V-axis (See Charts). Ventilation Classification: V1
8 Page 7 of Test Results For System Classification: (Continued) Static Water Penetration (per ASTM E 331) Pressure Results Allowed 300 Pa (6.24 psf) 575 Pa (12.0 psf) See Table 2 Report Only Dynamic Water Penetration (per AAMA 501.1) Pressure Results Allowed 300 Pa (6.24 psf) 575 Pa (12.0 psf) See Table 2 Report Only Data Liquid ml (oz) (1) ml/m 2 (oz/ft²) (2) TABLE #2 Test Results - Water Collected Off/Through the AWB 577 Pa 300 Pa 577 Pa TTL (12 psf) (6.24 psf) (12 psf) ml (oz.) static dynamic dynamic (3) 300 Pa (6.24 psf) static 0.00 (0.00) 0.00 (0.00) 0.00 (0.00) 0.00 (0.00) 0.00 (0.00) 0.00 (0.00) 3.9 (0.13) <0.01 (<0.01) 3.9 (0.13) Not Required Sum ml/m 2 (oz/ft²) (4) Not Required <0.01 (<0.01) Avg. ml/m 2 (oz/ft²) (5) Not Required <0.01 (<0.01) (1)Results of each water test, expressed as liquid ml (oz). (2)Results of each individual test is divided by the square footage of the specimen and expressed as ml/m 2 (oz/ft²). (3)Sum the results of the four water tests from (1) and express as total ml (oz). (4)The sum per m 2 (ft²) of specimen area. (5)The average ml/m 2 (oz/ft²) for all four tests. Used for classification purposes to determine the W-axis (See Charts. Note: Water contacted the Lexan after splashing off of the intermediate horizontal members. Water Penetration Classification: W1
9 Page 8 of Test Results: Optional Performance Uniform Load Deflection (per ASTM E 330) Pressure Results Allowed Note taken on panel edge Pa (+60.0 psf) Pa (-60.0 psf) 3.8 mm (0.15") 0.3 mm (0.01") Report Only 4, 5 Uniform Load Structural (per ASTM E 330) Pressure Results Allowed Note taken on panel edge Pa (+60.0 psf) Pa (-60.0 psf) <0.3 mm (<0.01") <0.3 mm (<0.01") Report Only 4, 5 Air Leakage (Infiltration per ASTM E 283) (Total with Cladding) Pressure Results Allowed Note 3.5 L/s (7.39 cfm) 1 75 Pa (1.57 psf) Report Only 0.60 L/s/m 2 (0.12 cfm/ft 2 ) 1, 3 Note #4: Loads were held for 10 seconds. Note #5: Tape and film were not used to seal against air leakage during structural testing.
10 Page 9 of Classification Rating: Based on the results of the air flow across the cladding (Table 1) and the water collected through the AWB (Table 2) the system tested achieved a V1/W1 Classification. Chart 1 shown below is used to plot the results of the test. CHART 1: System Classification Chart: (SI Units) V V V V V Ventilation through cladding, L/s/m 2 (for Head, Sill, Cladding, Horizontal & Vertical) V6 V V V V V Classification W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 W11 Water Collected from A/W, ml/m 2 (Average of 4 tests) Note: Upon examination of the specimen several hours after testing, the specimen was found to have allowed for drying and did not trap water.
11 Page 10 of Classification Rating: (Continued) CHART 1: System Classification Chart: (IP Units) Ventilation through cladding, cfm/ft 2 (for Head, Sill, Cladding, Horizontal & Vertical) V11 V10 V9 V8 V7 V6 V5 V4 V3 V2 V Classification W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 W11 Water Collected from A/W, fl oz./ft 2 (Average of 4 tests) Note: Upon examination of the specimen several hours after testing, the specimen was found to have allowed for drying and did not trap water. General Note: This report is not intended as a comprehensive evaluation of the system regarding performance and application to specific buildings. All testing was performed in accordance with the referenced standards.
12 Page 11 of 11 The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Karl A. Lips-Eakins Senior Technician Daniel A. Johnson Director, Regional Operations KLE/jb Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Drawings (2) This report produced from controlled document template ATI 00522, issued 03/30/11.
13 Appendix A Drawings
14 R 1107 NORTH TAYLOR ROAD GARRETT, IN PH. (260) FAX (260) TEST PANEL'S WALL ELEVATION 509 TEST PANELS " = 1' DF A2.0
15 R 1107 NORTH TAYLOR ROAD GARRETT, IN PH. (260) FAX (260) TEST PANEL'S WALL DETAILS 509 TEST PANELS " = 1' DF A4.0
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE Report to: Ceramitex Inc. 520 Clarke Rd. London, Ontario
FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight
FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
PERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
continuing professional education. As such, it construed to be an approval or endorsement by
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window
BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
TEST REPORT. Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California
Architectural Testing TEST REPORT Report No.: A8865.01-301-41 Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California TYPE: Dome Assembly Only SERIES/MODEL: Nano Insulgel - ALT-CM-2-CPM/16 mm CNANO Thermally
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window
Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:
DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
AAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
SECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
Specifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
InsulView Window Installation Instructions
InsulView Window Installation Instructions 1. The entire building is normally sheeted with the 2" 2 ½ OR 3 wall panel and the windows installed at a later time. A window retrofit of an existing building
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
Installer Training and Certification Overview
Installer Training and Certification Overview Outline of This Presentation The Need for a Training Program The History of the Program Details of the Training Program The Certification Process The Need
TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.
PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
Tundra Series Windows January 2016
Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing
PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM
PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Table of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide
VOLUME 1 - WINDOWS AND DOORS Window and Door Selection Guide PART 1 WINDOW SELECTION GUIDE WSG-11 PART 2 - PERFORMANCE SPECIFICATIONS Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized
Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages)
INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates 19501 Biscayne Boulevard, Suite 400 Aventura, FL 33180 Subject: The Nashville Hilton
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing
TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry
Garden Window. Montecito Series Vinyl Garden Window Architectural Manual
Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,
Field Water Testing - Lessons Learned
Quicklinks Lots of Questions - How About Answers Let's Start with the Specifications Test Methods VS. Performance Standard Using the Correct Test Method Conclusion About the Author Compilation of Test
Barewood Octagon and Elongated Windows Installation Instructions
Step-by-step instructions to a beautiful window. Measuring and Installation of your new window from Century Specialty Windows couldn't be easier with our step-by-step instructions. Quality, function and
INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW
Vinyl Windows and Doors Manufactured by Pella Corporation INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW Lea las instrucciones en español en el reverso.
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
PANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window
Windows Curtain Walls Entrances Storefronts Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window Configurations XO OX XOX Fixed Series 3502 retains an AAMA
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING IMPORTANT NOTICES AND INFORMATION Read these instructions in their entirety prior to installing windows. Any local building code requirements
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
Installation Instructions
Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
WINDOW INSTALLATION GUIDE
WINDOW INSTALLATION GUIDE is not responsible for or liable for any use or misuse of the information contained in this window installation guide. Window Installation Guide This guide provides basic information
Scottsdale, Arizona. Presentation by: Hermes Norero, P.E. President and CEO
Scottsdale, Arizona Presentation by: Hermes Norero, P.E. President and CEO Mr. Hermes F. Norero, P.E. is the founder and President of Building Drops. The concept of Building Drops first arose after realizing,
Vinyl Greenhouse Window Page 2 of 6 New Contruction Installation Instructions
New Construction Installation Instructions EPLACEMENT Installation Instructions Page 2 of 6 New Contruction Installation Instructions 1. Frame rough opening equal to window call out size. ough opening
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand [email protected] Florian Speier, Zola Windows [email protected] Paul Grahovac,
DE Frame with C Series Sidelight
TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder
Architectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
INSTALLATION INSTRUCTIONS for Vinyl Windows without Nailing Fin (JII011) ImPOrTANT INFOrmATION & GlOssAry. rough OPeNINGs
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for vinyl windows without a nailing fin (including finless, flush fin and flange). Read these instructions
Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.
Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.
Basement Window Installation Guide Hopper and Sliding
Basement Window Installation Guide Hopper and Sliding americancraftsmanwindows.com Project Requirements: Installation must comply with all applicable building codes. Existing window frame, wall and weatherresistant
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS
Page 1 of 5 SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS Guarda Security Window Screens in this specification are appropriate for use in windows, storefronts, curtain walls, vents, and any other applications
PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims
PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130
Vinyl Brick Mould Field Installation Instructions All Vinyl and Vinyl Clad Windows
Vinyl Brick Mould Field Installation Instructions All Vinyl and Vinyl Clad Windows Viewed from the exterior. IMPORTANT: Please read before you begin installation. TABLE OF CONTENTS AND TOOL / MATERIAL
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
T H E A A M A C E R T I F I C A T I O N P R O G R A M
T H E A A M A C E R T I F I C A T I O N P R O G R A M AAMA STANDS FOR QUALITY Since 1962, AAMA Certification, the original third-party window performance program, has provided manufacturers with the means
INSTALLATION INSTRUCTIONS for Premium Pocket Windows (JII022) IMPoRtaNt INFoRMatIoN & glossary. safety & HaNdlINg
Thank you for selecting JeLd-weN products. Attached are JeLd-weN s recommended installation instructions for pocket (replacement) double-hung, casement, awning, picture or transom windows, designed to
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
INSTALLATION INSTRUCTIONS for Vinyl Patio Doors with Integral Nailing Fin (JII006)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl Patio Doors with nailing fin. Any local building code requirements supersede the recommended
AC-3200 ALUMINUM PLATE SYSTEM (DRY JOINT)
ALUMINUM PLATE SYSTEM (DRY JOINT) C D E G P J L A H M B Q F A B C D E F G H J K L M N P Q R HORIZONTAL JOINT DETAIL VERTICAL JOINT DETAIL COPING DETAIL (1) COPING DETAIL (2) COPING DETAIL (3) OUTSIDE CORNER