How To Test For An Architectural Test
|
|
|
- Garey Hodge
- 5 years ago
- Views:
Transcription
1 Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System Door Openings This report contains in its entirety: Cover Page: 1 page Report Body: 8 pages Test Equipment: 1 page Sketches: 2 pages Drawings: 16 pages Report No.: Test Dates: 12/17/08 Through: 06/10/09 Report Date: 12/07/09 Expiration Date: 06/10/ Massaro Blvd Tampa, FL phone: fax:
2 Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS 3010 Rice Mine Road Tuscaloosa, Alabama Report No.: Test Dates: 12/17/08 Through: 06/10/09 Report Date: 12/07/09 Expiration Date: 06/10/13 Project Summary: Architectural Testing, Inc. was contracted by Coral Architectural Products to perform testing on one Series/Model PW 256, aluminum impact resistant curtain wall system with door openings. The samples tested met the performance requirements set forth in the referenced test procedures for a ±3828 Pa (±80.0 psf) Design Pressure with missile impacts corresponding to Missile Level D and Wind Zone 4. Test specimen description and results are reported herein. The samples were provided by the client. Test Procedures: The test specimens were evaluated in accordance with the following: ASTM E , Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials. ASTM E , Standard Specification for Performance of Exterior Windows, Glazed Curtain Walls, Doors and Storm Shutters Impacted by Wind Borne Debris in Hurricanes. Test Specimen Description: Series/Model: PW 256 with Door Openings Product Type: Aluminum Impact Resistant Curtain Wall System with Entrance Door Overall Size: 3531 mm (139") wide by 3810 mm (150") high Door Leaf Size (2): 908 mm (35-3/4") wide by 2419 mm (95-1/4") high Door Leaf Daylight Opening Size (2): 667 mm (26-1/4") wide by 2076 mm (81-3/4") high 2250 Massaro Blvd Tampa, FL phone: fax:
3 Architectural Testing Page 2 of 8 Test Specimen Description: (Continued) Fixed Daylight Opening Above Door Size: (47-1/4") high 1880 mm (74") wide by 1200 mm Top Right Fixed Daylight Opening Size: 1461 mm (57-1/2") wide by 1200 mm (47-1/4") high Lower Right Fixed Daylight Opening Size: (94-3/4") high 1461 mm (57-1/2") wide by 2407 mm Finish: All aluminum was mill finished. Glazing Details: The fixed lites utilized a 9/16" thick glazing fabricated from two sheets of 1/4" heat strengthened glass separated by 0.075" Vanceva interlayer. The lites were exterior glazed onto a Dow 995 silicone bedding and secured in place with aluminum pressure plates. The fixed lites of glass utilized a 3/4" glazing bite. Aluminum mull caps were added to the exterior. Weatherstripping: Description Quantity Location 0.270" backed by 1/4" 1 Row Perimeter of the door frame stop hollow vinyl bulb gasket 0.115" by 7/16" kerf-mounted 2 Rows Length of the active door leaf woven weatherstrip Frame Construction: The frame was constructed of extruded aluminum. The corners were coped, butted, sealed and secured with three #14 x 1" hex head screws located through the jambs into the head and sill screw boss. Door Panel: Door panel Series 381 was only utilized as a filler for the frame. A 2" x 2" x 1/4" by 2' long aluminum angle was utilized at the top and bottom of the door frame to secure the doors in place to the frame and threshold.
4 Architectural Testing Page 3 of 8 Test Specimen Description: (Continued) Screen Construction: No screen was utilized. Hardware: No hardware was utilized. Drainage: No drainage was utilized. Reinforcement: The intermediate vertical mullion utilized a full-height 4-1/2" x 1-7/8" x 1/4" steel "C" channel with a 3-3/4" wide by 3/4" thick flat bar welded to the "C" channel. It was secured with #8 x 3" bolts through the aluminum mullion located 1" from head, sill and horizontal mullion. Installation: The system was secured to an 8" steel "C" channel. The door to jamb was secured to the channel with 1/2"-13 x 4-1/2" bolts located 2-1/2", 45-1/2", 50-1/2", 67-1/2" and 98-1/2" from the bottom. The head utilized 1/2"-13 x 2" bolts 6" from each end and 4" each side of the vertical mullion. The sill utilized two 1/2"-13 x 2" bolts located 6" from the jamb and 6" from the vertical mullion.
5 Architectural Testing Page 4 of 8 Test Results: The following results have been recorded: ASTM E 1886, Large Missile Impact Conditioning Temperature: 26.6 C (80 F) Missile Weight: g (9.2 lbs) Missile Length: 2.4 m (8' 0") Muzzle Distance from Test Specimen: 5.18 m (17' 0") Test Unit #1 Impact #1: Missile Velocity: 15.4 m/s (50.4 fps); orientation within ±5 of vertical Impact Area: Center of the vertical mullion Observations: Missile hit target area, dented the aluminum mullion cap with no other damage. Results: Pass Impact #2: Missile Velocity: 15.5 m/s (50.8 fps); orientation within ±5 of vertical Impact Area: Center of the horizontal mullion above the double door assembly. Observations: Missile hit target area, dented the aluminum mullion cap and fractured the fixed lite above, with no other damage. Results: Pass Note: See Architectural Testing Sketch #1 for impact locations.
6 Architectural Testing Page 5 of 8 Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #1 Design Pressure: ±3828 Pa (±80.0 psf) Pressure Range Pa (psf) 766 to 1914 (16 to 40) 0 to 2297 (0 to 48) 1914 to 3062 (40 to 64) 1149 to 3828 (24 to 80) Pressure Range Pa (psf) 1149 to 3828 (24 to 80) 1914 to 3062 (40 to 64) 0 to 2297 (0 to 48) 766 to 1914 (16 to 40) Number of Cycles POSITIVE PRESSURE Average Maximum Deflection at Indicator mm (inch) Cycle Time (seconds) #1 #2 #3 #4 #5 # (0.19) 5.84 (0.23) 6.86 (0.27) 8.13 (0.32) 3.30 (0.13) (0.59) (0.65) (0.79) (0.96) 6.60 (0.26) (0.57) (0.71) (0.86) (1.03) 7.87 (0.31) 9.14 (0.36) (0.42) (0.51) Permanent Set (0.32) (0.28) (0.60) (0.74) (0.87) (1.04) 8.13 (0.32) 8.63 (0.34) 9.40 (0.37) (0.42) (0.47) 9.40 (0.37) NEGATIVE PRESSURE Average Number of Maximum Deflection at Indicator mm (inch) Cycle Time Cycles (seconds) #1 #2 #3 #4 #5 # (0.99) (0.74) (0.20) (0.38) (0.98) (0.38) (0.83) (0.62) (0.18) (0.31) (0.83) (0.37) (0.49) (0.35) (0.09) (0.17) (0.48) (0.09) (0.34) (0.23) (0.05) (0.09) (0.31) (0.06) Permanent Set (0.10) (0.04) (0.01) (0.04) (0.08) (0.02) Observations: No additional damage was observed. Result: Pass Note: See Architectural Testing Sketch #2 for indicator locations.
7 Architectural Testing Page 6 of 8 General Note: Upon completion of testing, the specimens met the requirements of Section 7 of ASTM E Test Equipment: (See Appendix A) Cannon: Constructed from steel piping utilizing compressed air to propel the missile Missile: 2x4 Southern Pine Timing Device: Electronic Beam Type Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein. List of Official Observers: Name William Smith Sr. William Smith Jr. Jack Hook Scott Parker Don Beltz John McClane Company Impact Glazing Consultants Impact Glazing Consultants Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc.
8 Architectural Testing Page 7 of 8 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. John C. McClane Laboratory Manager Joseph A. Reed, P.E. Director - Engineering and Product Testing JCM:ck/cmd Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Test Equipment (1) Appendix-B: Sketches (2) Appendix-C: Drawings (16)
9 Architectural Testing Page 8 of 8 Revision Log Rev. # Date Page(s) Revision(s) 0 12/07/09 N/A Original report issue This report produced from controlled document template ATI 00165, revised 03/05/09.
10 Architectural Testing Appendix A Test Equipment Instrument Manufacturer Asset # Transducer Celesco Transducer Celesco Transducer Celesco Transducer Celesco Transducer Celesco Transducer Celesco Control panel Architectural Testing, Inc Cannon Architectural Testing Inc Temperature/ Barometer Davis Instrument
11 Architectural Testing Appendix B Sketches
12
13
14 Architectural Testing Appendix C Drawings
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight
FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13
AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window
BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window
Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized
TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:
TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing
TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.
PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report
SECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
Installation Detailed installation instructions are provided which should be strictly followed.
Specification System 6 The Metal Technology Thermally-Broken Vertical Slide Window has been designed in such a way that its'attractive and clean lines will enhance all types of residential and commercial
TEST REPORT. Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California
Architectural Testing TEST REPORT Report No.: A8865.01-301-41 Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California TYPE: Dome Assembly Only SERIES/MODEL: Nano Insulgel - ALT-CM-2-CPM/16 mm CNANO Thermally
PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM
PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700
Specifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims
PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
Glossary. 1/3 1/3 1/3 - Configuration of a vent-fixed-vent (xox) window in which the vents and fixed panel are equal sizes
Glossary 1/3 1/3 1/3 - Configuration of a vent-fixed-vent (xox) window in which the vents and fixed panel are equal sizes 1/4 1/2 1/4 - Configuration of a vent-fixed-vent (xox) window in which the vents
SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR1 Teutonic Outswing Vinyl Entrance Door
ACOUSTIC Page of 5 9/8/204 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323
SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door
ACOUSTIC Page of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323 South th
PERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window
Windows Curtain Walls Entrances Storefronts Series 3502 Thermal Series 3902 Fixed Thermal 3 1 4 Architectural Grade Horizontal Sliding Window Configurations XO OX XOX Fixed Series 3502 retains an AAMA
n Three 4 x 4 butt hinges per door - prevents wracking and assures smooth positive operation n Heavy duty 16 gauge steel frame
Weather Fin and bulb help keep bad weather outside and good air inside Windows: n Many light kits are available 1-LU 4 X 48 1-LE 16 X 16 1-LA 20 X 24 1-LI 20 X 24 1-B 22 X 36 1-LW 16 X 16 W/GRID 9-LB 22
Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows
Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Series 2050 Garden Window The Series 2050 standard garden window has an outstanding reputation for its distinctive design and excellent
WINDOW PANNING AND TRIMS
OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.
Scottsdale, Arizona. Presentation by: Hermes Norero, P.E. President and CEO
Scottsdale, Arizona Presentation by: Hermes Norero, P.E. President and CEO Mr. Hermes F. Norero, P.E. is the founder and President of Building Drops. The concept of Building Drops first arose after realizing,
CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
Residential Garage Door Terminology
A Air Infiltration: The leakage or passage of air through a door system Anodize: A hard non-corrosive oxide film on the surface of aluminum Astragal: A compressible or deformable seal provided on the bottom
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"
TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405
SECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401
BASIC FIRE DOOR REQUIREMENTS SHEET NO. 401 Fire door openings are classified by their locations in the building. The location determines the length of exposure protection required, based on the potential
Garden Windows Builders Vinyl
TABLE OF CONTENTS Specifications... 8-2 QuickSpecGuide... 8-3 Elevations/Sizes: 1/4 Scale GardenUnits... 8-4 Grille Patterns... 8-5 SectionDetails: 6 Scale... 8-6 December 2008 JELD-WEN reserves the right
Installation Instructions
Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate
Garden Window. Montecito Series Vinyl Garden Window Architectural Manual
Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,
WHI TEST REPORT #630-104800 FIRE RATED DOORS
8000 Whitepine Rd. Richmond, VA 23237 Tel: 800-446-7325 Fax: 800-448-2908 E-mail: [email protected] WHI TEST REPORT #630-104800 FIRE RATED DOORS REPORT OF TEST OF GASKETING FOR RESISTANCE TO AIR
Table of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide
VOLUME 1 - WINDOWS AND DOORS Window and Door Selection Guide PART 1 WINDOW SELECTION GUIDE WSG-11 PART 2 - PERFORMANCE SPECIFICATIONS Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
Casement/Awning Window Parts Reference Catalog
Casement/Awning Window Parts Reference Catalog (Includes Miscellaneous Parts for Eyebrow Casement and Garden Bay Windows) #1028654 (Revised 03/02) Weather Shield Mfg., Inc. Medford, WI 54451 715/748-2100
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
Wind Mitigation Inspection
[email protected] Tampa Bay Area: SW & Central Florida: (813) 368-6407 (239) 896-3986 Wind Mitigation Inspection VonHaase, Dale 4585 Bowen Bayou Road Sanibel, FL 33957 5/6/2013 Note to Policyholder:
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
Impact-Resistant Windows and Sliding Glass Doors
Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they
SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning
ACOUSTIC Page 1 of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning Prepared for: Koble & Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 1323 South 11th Avenue Wausau,
STANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
Andersen Clad Inswing Entry Doors (2001 to Present)
Andersen Clad Inswing Entry Doors (2001 to Present) What s in This Section Clad Inswing Entry Doors Page 3 Part Illustrations 3 Parts Illustration - Single Door 3 Parts Illustration - Double Door 4 Parts
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
CLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
Sample Calculations...V-CR-12. Door and Window Typical Combinations... V-CR-12 Horizontal and Vertical Typical Combinations...
SECTION DIRECTORY General Information Definitions...V-CR- Design Considerations...V-CR- Composite Configurations...V-CR-4 Design Considerations and Examples for Typical Window and Door Combinations...V-CR-5
RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com
SERIES 900 CASEMENT WINDOW Page 1 of 6 RAM Industries 8600 Commerce Park Dr Houston, TX 77036 Tel: 281-495-9056 Fax: 281-495-6778 www.ramwindows.com SPECIFICATION GUIDE SERIES 900 CASEMENT WINDOW RAM Industries
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
DE Frame with C Series Sidelight
TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder
2.02. Specifications. General. Products. Execution. Offset Pivots P-694 Top and Bottom Pivots
2.02 Standard Specifications General Entrances Description Furnish all necessary materials, labor and equipment for the complete installation of aluminum entrance doors, door frames and hardware as shown
Quality Building Products for over 50 Years
Light Commercial Quality Building Products for over 50 Years Harvey Building Products is a leading manufacturer and distributor of high quality building products. We manufacture a complete line of superior
MANCHESTER SERIES(SGD-R35) SLIDING GLASS DOOR 5 5/8 FRAME DEPTH
MANCHESTER SERIES(SGD-R35) SLIDING GLASS DOOR 5 5/8 FRAME DEPTH FEATURES 1.) Available Configurations -Sliding Glass Door -Geometric shapes -OX, XO, OXO, OXXO, XOO, OOX (as viewed from exterior) 2.) Main
CLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
Window Glass Design 5 According to ASTM E 1300
A User s Guide to: Window Glass Design 5 According to ASTM E 1300 A product of: 1 Table of Contents Table of Contents List of Figures Chapter 1: Window Glass Design 5 1.1 Introduction 1.2 Features ii iv
Installation Window Building In Details
Installation Window Building In Details INSTALLATION Photo courtesy of Rowe Aluminium DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 INSTALLATION Installation Replaces: Scale: NOT TO SCALE Vantage snap-on couplers
glass & Glazing Products
glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
NanaWall SL73 - Thermally Broken Aluminum Framed Hurricane Rated Folding System with Miami Dade County, Florida NOA
NanaWall SL73 - Thermally Broken Aluminum Framed Hurricane Rated Folding System with Miami Dade County, Florida NOA ❶ PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: Sliding/folding aluminum and glass
K. D. FRAME ASSEMBLY FOR CLOSED STEEL STUD WALLS...Ins 10. FRAME INSTALLATION DETAILS FOR CLOSED STEEL STUD WALLS...Ins 11
K. D. FRAME ASSEMBLY FOR MASONRY WALLS...........................Ins 2 FRAME INSTALLATION DETAILS FOR MASONRY WALLS......................Ins 3 INSTALLING EXISTING MASONRY WALL ANCHORS IN FRAME..................Ins
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Evidence of Performance Resistance to wind load Watertightness Air permeability
Evidence of Performance Resistance to wind load Watertightness Air permeability Test Report 102 43093/1e Client Product YILDIZPEN PLASTIK SAN. VE TIC. LTD. STI. A.O.S.B 10039 Street No:18 Çigli Izmir Turkey
T H E A A M A C E R T I F I C A T I O N P R O G R A M
T H E A A M A C E R T I F I C A T I O N P R O G R A M AAMA STANDS FOR QUALITY Since 1962, AAMA Certification, the original third-party window performance program, has provided manufacturers with the means
SERIES 238 WINDOWS. NOTE: Read instructions completely before attempting any installation.
1 Installation Instructions SERIES 238 WINDOWS Page 2: Page 3-4: Page 5: Page 6: Page 7: Opening Preparation and Wood Buck Installation Installation Instructions for Series 238 WINDOWS Figure 1: Buck preparation
Important Information for Installer & Homeowner
Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
Variety of Control Options Control is possible via wall switches, remote control systems or integration into building management systems.
Breezway Altair Powerlouvre Window 35 Breezway Altair Powerlouvre Window The Powerlourve Window motor is neatly concealed within the Easyscreen TM Frame or the Component Powerlouvre Head Section. Automated