PERFORMANCE TEST REPORT
|
|
|
- Andrew Edwards
- 9 years ago
- Views:
Transcription
1 PERFORMANCE TEST REPORT CCLW JOB # DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA PH: Fax:
2 MOCK UP DEESCRIPTION The scope of the mock-up specimen for testing was one (1), shop glazed unitized wall system consisting of three (3) modules in width by two (2) modules in height of a custom curtain wall system with 1 3/16 glazing. The mock up measured overall 12-6 wide by 22 high. For a complete description and framing details, see drawings, sheets 1-41, at end of this report. The report is not complete unless drawings marked and stamped by the laboratory are included. All references to positive pressures are considered inward acting and negative is outward. The mock up was tested in accordance with each applicable AAMA and ASTM standard. TEST EQUIPMENT The specimen was installed into a test chamber constructed of structural angles, beams, and columns covered with steel and plywood bulkheads, accessible through a bulkhead door. Air infiltration was measured with a Meriam laminar flow element and a Dwyer electronic manometer. Water was applied from a vertical spray rack mounted 22 to 24 from the specimen. The rack was equipped with swirl-type nozzles spaced two (2) feet on center, vertically and horizontally, which delivered five (5) gallons of water per hour per square foot of wall frontal area. Dynamic winds were generated by a Curtis Wright 3350 radial aircraft engine with a three (3) bladed propeller, 14-5 diameter, which formulates typical and atypical wind conditions. Pressure differentials were measured with a Dwyer electronic manometer (DM-2). The pressure differential between the exterior and interior of the chamber was created by a positive and negative blower system. WITNESSED BY (all or partial) Katherine Miller Anurag Jain Ryan Burke Michael Hathhorn Scott Acevedo Eric Thatcher Eric Schroter David Mirelez Cassie Harker Nancy Bjurstrom Glenn Allen Subir Ghosh Jack W. Jackson Chad C. Jackson EHDD Architecture Weidlinger Associates, Inc. Simpson, Gumpertz & Heger, Inc. Guarantee Glass, Inc. Guarantee Glass, Inc. Advanced Glazing Systems, LLC Advanced Glazing Systems, LLC Advanced Glazing Systems, LLC Construction Consulting Laboratory West Construction Consulting Laboratory West PAGE 2 of 7
3 FORMAL TEST SEQUENCE SEPTEMBER 19, 2008 The weather conditions at 9:30 AM were 72 F, 44% RH, calm winds and a clear sky. PRELOAD To set the specimen for testing, a positive pressure differential of 15.0 psf, 50% of design load, was applied to the specimen while exhausting air for the air infiltration test. It was held for ten seconds and then reduced to 6.24 psf to complete the air test. There was no indication of failure. AIR INFILTRATION TEST per ASTM E The exterior of the wall area was sealed with a visqueen material and tape. The exterior face of the specimen was then subjected to a positive static pressure differential of 6.24 psf. This infiltration reading represented the amount of air infiltration through the chamber (tare). The visqueen was removed and another reading was recorded at 6.24 psf pressure differential representing the amount of air infiltration through the wall specimen and the chamber (gross). Subtracting the first reading from the last yields the net air infiltration through the specimen. Air infiltration shall not exceed 0.06 cfm per square foot of wall area. Net allowable based on measurements was 20.4 cfm total. (12.5 x 22 = 274 s/f x 0.06 = 16.4 cfm total. : Specimen passed. The Titon trickle vents were taped over and not included in the air infiltration readings. Net air infiltration was measured at 6.2 cfm total. STATIC WATER PERATION TEST per ASTM E Water was applied to the exterior face of the specimen, at a minimum rate of five (5) gallons per hour per square foot of wall frontal area, in such a way as to completely cover the exterior face of the specimen. At the same time, a positive differential static pressure of 15.0 psf was applied to the face of the specimen. The application of pressure and water was maintained for a period of fifteen (15) minutes, with observers viewing the interior of the specimen. Water leakage is defined as uncontrolled water infiltrating the system or appearing on systems normally exposed interior surfaces from sources other than condensation. Water controlled by flashing and gutters that is drained back to the exterior and cannot damage adjacent materials or finishes is not water leakage. : Specimen passed. There was no water leakage. PAGE 3 of 7
4 DYNAMIC WATER PERATION TEST per AAMA The specimen was subjected to a dynamic wind load pressure equivalent of 15.0 psf (76.5 mph wind speed) only, with a water application of five (5) gallons per hour per square foot of wall frontal area for duration of fifteen (15) minutes. There shall be no uncontrolled water leakage, same as the static water test above. Specimen passed. The Titon trickle vents were opened during the dynamic water test to demonstrate that the vent is weatherproof during a rain storm. There was no water leakage noted. UNIFORM STRUCTURAL DESIGN ASTM E The test specimen was subjected to a positive load of 15.0 psf. The pressure was held for ten (10) seconds and released. Indicators were set. The test specimen was subjected to a positive load of 30.0 psf, held for ten (10) seconds and released. Indicators were read and data was recorded. The blower system, along with the measuring equipment, was then reversed. The test specimen was subjected to a negative load of 22.5 psf. The pressure was held for ten (10) seconds and released. Indicators were set. The test specimen was subjected to a negative load of 45.0 psf, held for ten (10) seconds and released. Indicators were read and data was recorded. At design load, limit deflection of framing members, in a direction normal to wall plane, to. Specimen passed. All measured structural spans complied with specified criteria. See elevation drawing for dial indicator locations. See Charts #1 and #2 on page 6 for deflection and permanent set results (reference bold number xx/xx for deflection/permanent set) REPEAT AIR INFILTRATION TEST per ASTM E Similar procedure and same criteria as previous air infiltration test. (allowed 16.4 cfm) Specimen passed. Gross leakage was measured and compared to the gross leakage obtained at start of testing. With the wall and chamber wet and the windows adjusted, the difference was 4.0 cfm less. This indicates that there was no detrimental change in the air infiltration due to the structural design load tests. The Titon trickle vents remained taped. PAGE 4 of 7
5 REPEAT STATIC WATER PERATION TEST per ASTM E Same procedure and same criteria as previous static water penetration test. Specimen passed psf: There was no water leakage noted. UNIFORM STRUCTURAL PROOF LOAD TEST per ASTM E The test specimen was subjected to a positive load of 22.5 psf (75% design load). The pressure was held for ten (10) seconds and released, with indicators then set to zero. The test specimen was subjected to a positive load of 45.0 psf (150% design load), held for ten (10) seconds and released. Indicators were read and all data recorded. The blower system along with the measuring equipment was reversed. The test specimen was subjected to a negative load of psf (75% design load). The pressure was held for ten (10) seconds and released, with indicators set to zero. The test specimen was subjected to a negative load of 67.5 psf (150% design load), held for ten (10) seconds and released. Indicators were read and all data recorded. No failures or permanent set in excess of L/1000 is allowed. Specimen passed. All measured structural spans complied with specified criteria. See elevation drawing for dial indicator locations. See Charts #3 and #4 on page 7 for deflection and permanent set results (reference bold number xx/xx for deflection/permanent set). END OF TESTING PAGE 5 of 7
6 STRUCTURAL INGS 100% DESIGN LOAD CCLW REPORT NO: CHART 1 OF 4 TEST PRESSURE = 30.0 PSF POSITIVE 1 VERT. MULL 02/PMU_4.02 BOTTOM 10/ ANCH- 2 VERT. MULL 02/PMU_4.02 (3) STK JT BOT 10/ VERT. MULL 02/PMU_4.02 (2) STK JT TOP 17/ VERT. MULL 02/PMU_4.02 (1&5) MID 33/00 25/ VERT. MULL 02/PMU_4.02 TOP 07/ ANCH- 6 HORZ. MULL 18/PMU_3.06 MID 03/01 03/ VISION GLASS 1 3/16 INSUL CENTER 21/01 21/ CHART 2 OF 4 TEST PRESSURE = 45.0 PSF NEGATIVE 1 VERT. MULL 02/PMU_4.02 BOTTOM 04/ ANCH- 2 VERT. MULL 02/PMU_4.02 (3) STK JT BOT 03/ VERT. MULL 02/PMU_4.02 (2) STK JT TOP 06/ VERT. MULL 02/PMU_4.02 (1&5) MID 27/01 21/ VERT. MULL 02/PMU_4.02 TOP 08/ ANCH 6 HORZ. MULL 18/PMU_3.06 MID 04/01 04/ VISION GLASS 1 3/16 INSUL CENTER 34/00 34/ INGS ARE IN HUNDRETHS OF INCH DEFL. LIMIT = INGS ARE DEFLECTION/PERMANENT SET PAGE 6 of 7
7 STRUCTURAL INGS 150% PROOF LOAD CCLW REPORT NO: CHART 3 OF 4 TEST PRESSURE = 45.0 PSF POSITIVE 1 VERT. MULL 02/PMU_4.02 BOTTOM 14/ ANCH- 2 VERT. MULL 02/PMU_4.02 (3) STK JT BOT 17/ VERT. MULL 02/PMU_4.02 (2) STK JT TOP 36/ VERT. MULL 02/PMU_4.02 (1&5) MID 57/02 44/ VERT. MULL 02/PMU_4.02 TOP 12/ ANCH 6 HORZ. MULL 18/PMU_3.06 MID 04/01 04/ VISION GLASS 1 3/16 INSUL CENTER 28/01 28/ CHART 4 OF 4 TEST PRESSURE = 67.5 PSF NEGATIVE 1 VERT. MULL 02/PMU_4.02 BOTTOM 05/ ANCH- 2 VERT. MULL 02/PMU_4.02 (3) STK JT BOT 04/ VERT. MULL 02/PMU_4.02 (2) STK JT TOP 07/ VERT. MULL 02/PMU_4.02 (1&5) MID 52/02 40/ VERT. MULL 02/PMU_4.02 TOP 20/ ANCH 6 HORZ. MULL 18/PMU_3.06 MID 05/01 05/ VISION GLASS 1 3/16 INSUL CENTER 49/01 49/ INGS ARE IN HUNDRETHS OF INCH PERM. SET LIMIT = L/1000 INGS ARE DEFLECTION/PERMANENT SET PAGE 7 of 7
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
continuing professional education. As such, it construed to be an approval or endorsement by
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Architectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE Report to: Ceramitex Inc. 520 Clarke Rd. London, Ontario
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
SECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION AND FORENSIC INVESTIGATION OF BUILDING LEAKAGE
WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION FORENSIC INVESTIGATION OF BUILDING LEAKAGE F RANCESCO J. SPAGNA, PE; SIMPSON GUMPERTZ BRON S. BUCHBERG, PE HEGER, INC. 41 Seyon Street,
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
Field Water Testing - Lessons Learned
Quicklinks Lots of Questions - How About Answers Let's Start with the Specifications Test Methods VS. Performance Standard Using the Correct Test Method Conclusion About the Author Compilation of Test
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
Scottsdale, Arizona. Presentation by: Hermes Norero, P.E. President and CEO
Scottsdale, Arizona Presentation by: Hermes Norero, P.E. President and CEO Mr. Hermes F. Norero, P.E. is the founder and President of Building Drops. The concept of Building Drops first arose after realizing,
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Specifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
Installer Training and Certification Overview
Installer Training and Certification Overview Outline of This Presentation The Need for a Training Program The History of the Program Details of the Training Program The Certification Process The Need
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
resist water infiltration and avoid water damage to buildings.
INTRODUCTION Uncontrolled water penetration through the building façade, exterior walls, and especially fenestrations (windows) results in billions of dollars of damage in the con struction industry every
Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
CH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
The minimum reinforcement for the stem wall is the placement of:
PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20
Lighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: [email protected] Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract
Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
Lighthouse Engineering, L.L.C.
Monday, May 07, 2012 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:
SECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.
ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
1. Concrete: T W L / 27 = Concrete C.Y. Multiply Feet Thickness x Feet Width x Feet Length / 27 = Cubic Yards.
Formulas: Formula Letters: H= Height BCY = Bank Cubic Yards L= Length CCY = Compact Cubic Yards P= Perimeter LCY = Loose Cubic Yards LF = Linear Feet or Lineal Feet BF = Board Foot or Feet SF = Square
Code of Standard Practice for Timber Frame Structures
TFEC 2-2013 Code of Standard Practice for Timber Frame Structures August 2013 Preface This Code is intended to represent a reasonable consensus of what constitutes ordinary and acceptable practice within
After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS
PART 1 GENERAL SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS 1.1 SUMMARY A. Optically clear dual reflective, neutral sputtered and aluminum metallized polyester film for solar control. 1.2 RELATED
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
Impact-Resistant Windows and Sliding Glass Doors
Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
BECx& Building Airtightness. Presented by: Eric Amhaus Principal
BECx& Building Airtightness Presented by: Eric Amhaus Principal The Building Enclosure 2007 study: out of 17,000 construction defect claims, 69% result of moisture related defects in building enclosure
IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2014-023-S2 AWNING WITH FIXED WINDOW PROTOTYPE TEST to AS2047-1999. for. Finesse Window Systems Australia
IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2014-023-S2 AWNING WITH FIXED WINDOW PROTOTYPE TEST to AS2047-1999 for Finesse Window Systems Australia November 2014 Accreditation No. 2371 Accredited for compliance
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
CHAPTER 24 GLASS AND GLAZING
CHAPTER 24 GLASS AND GLAZING SECTION 2401 GENERAL 2401.1 Scope. The provisions of this chapter shall govern the materials, design, construction and quality of glass, lighttransmitting ceramic and light-transmitting
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Approval Standard for Class 1 Exterior Wall Systems
Approval Standard for Class 1 Exterior Wall Systems Class Number 4881 November 2007 2007 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that the
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures R. A. Van Straaten 1, G. A. Kopp 2, J. F. Straube 3 1 Research Lab for Better Homes, University of Western
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,