Current Transformer (CT) Selection Guide
|
|
|
- Rose Collins
- 10 years ago
- Views:
Transcription
1 Current Transformer (CT) Selection Guide Article ESA-1008D December 5, 2014 Contents 1 Introduction Extending CT leads Selecting the mechanical dimension of the CT Selecting the current rating of the CT Revenue Grade CTs Direct Current CTs phase inverter notes Page 1 of 10
2 7 Appendix Standard 0.4" CT dimensions Standard 0.75" to 2.00" CT dimensions High Accuracy 0.75" CT dimensions DC CT dimensions CT part numbers Page 2 of 10
3 1 Introduction This guide is intended to help you select the right quantity and type of current transformers (CTs) needed for an egauge installation. A typical egauge installation will measure multiple amperage inputs from CT sensors. The CT sensors are installed around the current carrying conductors of the load or generation source you wish to monitor. CTs can be used to monitor the main utility feed conductors for a facility or residence, conductors that feed sub panels, and individual circuit conductors such as pumps, motors, air conditioning, car chargers, and lighting loads. CTs can also be used to monitor conductors from generators as well as renewable energy systems such as solar PV systems, wind generators and hydro power systems. Split-phase loads (eg, 120V residential outlet, phase-to-neutral) require a single CT 2 phase loads ( single phase ) require 2 CTs. See footnote 1 3 phase loads require 3 CTs Example: a split phase 240V electric water heater: one CT can be used on the phase, that amperage reading can be applied to the other voltage in the configuration section of egauge installation. Most residential 240V PV inverters are also balanced, but not 3 phase inverters. Some loads such as HVAC systems and dryers are not balanced and will always require a CT on each phase. Facility main feeds and sub panel feed are also not balanced. CTs are available in a number of different physical sizes. The inner diameter ID of the CT must be large enough to fit around the conductive wire you wish to monitor. The outer dimensions must be small enough to work inside the circuit panel or switch gear. egauge offers these examples as a reference. The nature of the current in an appliance should be verified by a qualified electrician or via the appliance documentation before ordering. Picking the type of CT involves selecting the mechanical dimension and the current rating (in Amps). 1.1 Extending CT leads Split core CTs can be extended with appropriately rated 2 twisted pair wire to cover much longer distances. STP (shielded twisted pair) is recommended, as it will reduce noise and interference. If you need to extend a CT wire farther than approximately 100 ft, contact egauge support to see if a custom factor will be necessary in your software settings. Appropriately rated CATV Ethernet cable can be used to extend up to 4 CTs. 1 If a load is balanced (meaning the same current is flowing across all phases), then a single CT can be used to measure one amperage. egauge can be configured to apply the amperage reading to the second phase, as long as egauge has a voltage reference to each phase in the system. See configuration example 2.9 Appliances in the configuration guide for more details. 2 The insulation rating of the wire must be at least the maximum voltage of the system. For example, 340V rated insulation for a 120/240Vrms split phase system (240 x 2) or 680V insulation for a 480Vrms service. Page 3 of 10
4 2 Selecting the mechanical dimension of the CT CTs are available in a number of different physical sizes. The inner diameter ID of the CT must be large enough to fit around the conductive wire you wish to monitor. The outer dimensions must be small enough to work inside the circuit panel or switch gear. CT diameter: Wire Size: 0.4" #14 to #2 AWG 0.75" 1/0 to 4/0 AWG 1.25" 250 to 400 MCM 2.0" 400 to 750 MCM Table 1: General sizing guidlines 6" Rogowski coil rope CTs are good for bus bar and parallel feed conductors (or any installation with limited space, assuming the current does not drop below 25A or go above 4800A and there is adequate space for the rope in the panel). 3 Selecting the current rating of the CT CTs are available with in a wide amperage range from 20A to 4800A. An easy way to select the amperage needed is to match the breaker or disconnect rating that you or measuring with the CT you choose. For example if you are monitoring a 50A circuit, then a 50A CT would be appropriate. If you have a 15Amp breaker, then the closest larger rated CT, a 20A CT, should be used. The CTs and egauge will not be damaged if the amperage on the measured conductor exceeds the rating of the CT, within reasonable limits. If the circuit or service is determined to have a maximum amperage that is well below the rated breaker ampacity, you may choose a lower amperage CT. Example: a typical residential service is rated for 200A with 2 phases feeding the home. Although the service is rated to have up to 200A on a single phase at any given moment, the reality may be that neither phase will pull over 100A ever. In this situation 2 100A CTs would work. egauge offers this examples as a reference. The nature of the current should be verified by a qualified electrician before ordering. Split core CTs are available with set amperage ratings. The load you wish to monitor should fall within the range from 10% to 100% of the CT being used to monitor that current. CTs can not be used to monitor currents above their rating. Example: a 50A CT would be a good choice to monitor a load that is typically between 5 and 50A. Accuracy begins to diminish when a current is below 10% of the CT rating. The 6" Rope CT has excellent performance from 50A to 4800A. Page 4 of 10
5 4 Revenue Grade CTs High-accuracy split-core CTs are available. The Accu-CTs come in 50A, 100A, and 200A. All are 0.75" Accu-CTs have an error of.2% from 1% to 100% of their rated current. Accu-CTs can be paired with any egauge main unit. For revenue grade readings, all conductors must be monitored, including single-phase (phase-to-phase) balanced and unbalanced loads. For best accuracy, pair the Accu-CT with an egauge device with the 0.5% certificate report. The total system (egauge meter and CTs) will have an error no greater than 0.5%. This pairing meets the ANSI C % accuracy class. Pair the Accu-CT with a non-certificate, 1.0% egauge, and the result will be a system with no greater than a 1% error. This pairing meets the ANSI C12.1 accuracy class. 5 Direct Current CTs DC (direct current) CTs are available for use with the egauge to monitor DC amperage sources. These CTs must be modified by egauge to be supported and require an external 12Vdc power source. A power supply for the CT is included. Solid-core DC CTs have a.79 window. Power on the conductor to monitor must be disabled, disconnected, and then threaded through the CT window. Split-core DC CTs have a 1.2 window. It is not necessary to disconnect the monitored conductor when adding the CT. 6 3-phase inverter notes For PV inverters with 3 phase outputs, 3 CTs are recommended. When inverters are not producing (in standby-mode, such as during night), they consume a small amount of power. 3-phase inverters have been seen not to consume the same amount on each phase during this mode, so using a single CT will cause anomalous behavior in the graph which can show as night time generation or over-consumption. Further, some brands of 3-phase inverters don t produce on all 3 phases in certain circumstances. In this case, a single CT would give erroneous readings and would not be accurate. Page 5 of 10
6 7 Appendix 7.1 Standard 0.4" CT dimensions Figure 1: SCT0400-xxx dimensions Part Number A B C D E SCT0400-xxx 1.56" 1.00" 0.40" 1.00" 1.05" Table 2: SCT0400-xxx dimensions Page 6 of 10
7 7.2 Standard 0.75" to 2.00" CT dimensions Figure 2: CT dimensions between 0.75" and 2.00" Part Number A B C D E SCT0750-xxx 2.00" 2.10" 0.67" 0.75" 0.75" SCT1250-xxx 3.25" 3.35" 1.06" 1.25" 1.25" SCT2000-xxx 4.75" 5.00" 1.20" 2.00" 2.00" Table 3: CT dimensions between 0.75" and 2.00" Page 7 of 10
8 7.3 High Accuracy 0.75" CT dimensions Figure 3: Accu-CT dimensions. Note Accu-CTs are hinged, not fully-removable Page 8 of 10
9 7.4 DC CT dimensions Figure 4: CR5220 DC CT dimensions. Split-core DC CTs are hinged, not fully-removable Page 9 of 10
10 7.5 CT part numbers Standard Split-core CTs: Current Rating 0.40" ID 0.75" ID 1.25" ID 2.00" ID 5A SCT A SCT SCT A SCT SCT A SCT SCT A SCT SCT A SCT A SCT SCT A SCT SCT SCT A SCT SCT A SCT SCT A SCT A SCT Rope CTs (8 foot leads): Current Rating 6" Rope ID: A RCT-1800-COIL High Accuracy CTs: Current Rating 0.75" ID 50A ACT A ACT A ACT Table 4: Part numbers for available CTs Page 10 of 10
Voltage Drop (Single-Phase)
Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage
Figure. 1 - Split Phase 240/120V circuit (180 phase shift)
This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase
Solar monitoring gateway quick start guide
Instructional Leaflet I70002E LGATE101-1B LGATE101-1A LGATE101-5B LGATE101-5A Contents Description Page General................................. 2 Information collection sheet............... 2 Quick reference
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
DANGER! HIGH VOLTAGE HAZARD
WattNode Pulse kwh Transducer Connection Instructions For use with HOBO H21, H22, U30, UX90, and UX120 series data loggers, and HOBO data nodes Applies to these WattNode Pulse kwh Transducers: Onset Part
SolarEdge Export Limitation Guide
SolarEdge Export Limitation Guide Europe and APAC Version 2.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in
Installation Guide Solar Connect-11
Installation Guide Solar Connect-11 Version 1.1 Contents Important Product Information 3 System Registration Form 4 Solar Connect-11 Overview 5 Internet & Power Connections 6 Single Phase CT Connections
Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide
Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management
Ontario Electrical Safety Code 25 th Edition/ 2012
Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and
NEW. Solar-Log & GE Meter Residential Solar PV Monitoring & Metering Built into a Single Device
NEW Solar-Log & GE Meter Residential Solar PV Monitoring & Metering Built into a Single Device Wireless Residential PV Monitoring Solar-Log & GE Meter - Highlights Solar-Log 350 & GE Meter Solar-Log Dashboard
4KVA/5KVA Parallel Installation Guide
4KVA/5KVA Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 4 units. The supported maximum
CURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright
* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2
COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and
Request for Proposals for Photovoltaic System Installation
Request for Proposals for Photovoltaic System Installation Presented by: Prepared by: Location: Contact: Date: Capitol Hill Housing Foundation Bonneville Environmental Foundation, Renewable Energy Group
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20
USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure
Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations
Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where the power generated by the solar panel (panels) runs an
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the
Generator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
Current Transformers
Supersedes December 2002 General Description Eaton s low voltage current transformers are available in both solid core and split core designs. Engineered for electronic metering applications, all solid
CA-6050 Solar Power Unit. User Guide. Designed to work with the Norsonic range of sound level meters to provide a DC supply in remote locations.
CA-6050 Solar Power Unit User Guide Designed to work with the Norsonic range of sound level meters to provide a DC supply in remote locations. 1 Contents Introduction... 2 Components... 3 Solar Array Case...
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
Current Cost TREC Current Cost ENVI Current Cost EnviR SmartNow Solar Monitoring Kit
Installation Guidelines Products Covered: Current Cost TREC Current Cost ENVI Current Cost EnviR SmartNow Solar Monitoring Kit This document is for the use of Qualified Electricians and Electrical Contractors
DC disconnects for solar photovoltaic installations. Connecting the. power of the sun
DC disconnects for solar photovoltaic installations Connecting the power of the sun Solar energy is heating up Interest in renewable energy sources has never been greater, and the fastest growing of these
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction
SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to
Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)
February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,
Transfer Switch 30 Amps STS-30. Manual. Please read this manual before operating your transfer switch
Transfer Switch 30 Amps STS-30 Owner's Manual Please read this manual before operating your transfer switch Section 1 Introduction Function of a Transfer Switch In case of failure of the main AC power
User Manual of Grid Tie Inverter with Limiter
User Manual of Grid Tie Inverter with Limiter Grid Tied Inverter With Limiter (GTIL) 1 www.chinesegrid.com 2014-8-1 All rights reserved Why we produced the GTI-L --- It is in response to the overwhelming
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
INSTALLER S INSTRUCTIONS FOR TRI-METRIC Battery system monitor, Models TM-2030-RV and TM-2030-A. Contents
INSTALLER S INSTRUCTIONS FOR TRI-METRIC Battery system monitor, Models TM-2030-RV and TM-2030-A revised January26, 2016 IMPORTANT: The wiring installation for this meter, especially the shunt installation
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
Additional Solar System Information and Resources
Additional Solar System Information and Resources Background information a. Roughly 400 schools in NJ already have solar systems, producing more than 91 MW, out of approximately 2500 K- 12 schools in NJ.
CRITICAL POWER MONITORING CPM20/CPM21 DETAILS
CRITICAL POWER MONITORING CPM20/CPM21 DETAILS The Starline Critical Power Monitor (CPM) is a distributed data acquisition system that enables Current and Power monitoring in busway systems. Each phase
How To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Investor day. November 17, 2010. Power business Julio Rodriguez Executive Vice President
Investor day November 17, 2010 Power business Julio Rodriguez Executive Vice President Power: Business strategic domain Centralized generation Residential Residential Industries Non Residential Transmission
ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS
Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
46120-F0 Solar Energy Training System
46120-F0 Solar Energy Training System LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 06/2016 Table of Contents General Description 2 List of Equipment 2 List of Manuals 3 Table of Contents of
Sense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.
Sense Components Sense monitor Antenna assembly External mounting kit Current sensors Download the Sense app. Go to sense.com/app Power cable Technical Specifications Sense is a home energy monitoring
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
Multi Media Cable Tester TM-901N/TM-902/TM-903
Multi Media Cable Tester TM-901N/TM-902/TM-903 User Manual HB2TM9020010 TENMARS ELECTRONICS CO., LTD Table of Contents 1 Introduction... 1 2 Safety Precaution... 1 3 The verifier does the following:...
Model CFA-24 Transparent Cable Farm Automation Switch
Model CFA-24 Transparent Cable Farm Automation Switch Ideal for Broadband Forum s ID-337 G.fast Certification and TR-249 VDSL2 Vectoring Testing High performance transparent solution designed to automate
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
MicroFIT Connection Application Guidelines
MicroFIT Connection Application Guidelines These guidelines serve to ensure the efficient processing and implementation of your project. Please read and follow them carefully and completely in order to
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking
TECHNICAL BRIEF M250 Microinverter System Installation Planning The M250 Microinverter The Enphase M250 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60-cell
Feed systems. Effective handling
Feed systems Effective handling THE WAY TO MAKE IT OPTIMIZED The latest generation of automatic wire processing machines operates at high rates of acceleration and speed. This places maximum demands on
User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1
User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...
Services. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
MIDNITE SOLAR AND SOLAR WASHINGTON
MIDNITE SOLAR AND SOLAR WASHINGTON CHARGE CONTROLLERS 30 amp MPPT with load control for small systems, boats and RV s THE KID THE KID LED MODES The KID has a three LED bar graph plus four status LEDs that
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
M-Bus Network Installation Notes
M-Bus Network Installation Notes 1 M-Bus Network Installation Notes This manual explains how to calculate the maximum M-Bus cable length depends on technical parameters of used cable and number of M-Bus
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.
ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.com On-Site Power System Specialists: Photovoltaics, Wind Turbine
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: [email protected] www.juicegoose.com 06-06 CONGRATULATIONS
LocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.
SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
MechoNet TM Network Interface (MNI) Specification Submittal
MechoNet TM Network Interface (MNI) Specification Submittal Models MechoNet Network Interface: MNI RJ (RJ45 Motor Ports): Stock No.: IMNI 0001 TP AS (US version) Stock No.: IMNI 0004 TP AS (UK version)
Communication Setup Application Note
Communication Setup Application Note This Application Note describes how to install and set up communication between the inverter and the SolarEdge Monitoring Server. This document contains the following
Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure
Summary Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure This is a general procedure on how to replace Pathfinder 48-10kW shelf with a Cordex 3.6kW shelf. Part Numbers 010-567-20
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Freedom SW Sine Wave Inverter/Chargers
TM RESET GEN SUPPORT Freedom SW 3K2K InvChg Install Guide.book Page i Wednesday, October 9, 2013 1:32 PM TM Freedom SW 3012 shown. FREEDOM SW 3012 FREEDOM SW 3012 FREEDOM SW 3012 FREEDOM SW 3012 Freedom
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
Parallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
AJ s Technical Tips: Designing a Small Solar PV System Part IV; Selecting Wires for the System
AJ s Technical Tips: Designing a Small Solar PV System Part IV; Selecting Wires for the System A little while back Simon Nyukuri of Kitale wrote to ask me about sizing wires and cables for solar PV systems.
Introduction. Page 2 / 9
Installation Manual English, US, version 1.1, as of November 13th, 2015 2015 Smappee NV. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE
Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of
MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03
MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE USER GUIDE Document reference : 9010709-03 If you have questions about the MDM192 or desire assistance, contact ETIC TELECOMMUNICATIONS at the following
SUFFOLK COUNTY CODE OF RULES GOVERNING RESTRICTED LICENSED ELECTRICIAN S
SUFFOLK COUNTY CODE OF RULES GOVERNING RESTRICTED LICENSED ELECTRICIAN S Including: 1. Heating, Ventilating and Air Conditioning (HVAC) 2. Irrigation Systems 3. Oil and Gas Burning Equipment 4. Signs and
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
Duke Energy Carolinas. Inverter Based Generation Interconnection
Duke Energy Carolinas Inverter Based Generation Interconnection Options for Non-Residential Service Customers Table of Contents Rider NM and Rider SCG: Net Metering Single Phase PV System Typical 120/240V
Voltage Drop. Voltage Drop 1
Voltage Drop The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences. Qualified person is defi ned in Article 100 of
ALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
Monitoring solar PV output
Monitoring solar PV output Introduction Monitoring of your solar PV output is useful to see the actual outputs. This can be measured from the inverter and/or mains using current clamps or pulse meters