Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
|
|
- Gyles Bridges
- 8 years ago
- Views:
Transcription
1 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN
2 Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change. Trademarks Trane, Rover, the Trane logo, are trademarks of Trane in the United States and other countries. All other brands and products referenced in this document are acknowledged to be the trademarks or registered trademarks of their respective holders. Warnings and Cautions. Notice that warnings and cautions appear at appropriate intervals throughout this manual. Warnings are provided to alert installing parties of potential hazards that could result in personal injury or death, while cautions are designed to alert personnel to conditions that could result in equipment damage. Your personal safety and the proper operation of the Trane Rental Services temporary chilled water system depend upon the strict observation of these precautions. Please refer to the Installation Operation Manual (IOM) for all appropriate Warning and Cautions. 2 Rental Services Air Handling Unit CHS-SVN01A-EN Trane All rights reserved
3 Contents Introduction General Information ,000 cfm Air Handling Unit (nom. 25 tons) ,000 cfm Air Handling Unit Fan Curve ,000 cfm Air Handling Unit Drawing ,000 cfm Air Handling Unit w/vfd ,000 cfm Air Handling Unit Fan Curve ,000 cfm Air Handling Unit Drawing Electrical Information Piping Connection Configuration ,000 cfm Unit Piping Manifold ,000 cfm Unit Piping Manifold Duct Configuration Information Controls Information Rigging Guidelines Installation/Startup Guidelines Maintenance Guidelines Decommissioning Guidelines CHS-SVN01A-EN Rental Services Air Handling Unit 3
4 Air Handling Units Introduction This engineering bulletin covers the rental air handling units (AHU) available to rent from Trane Rental Services for temporary cooling solutions. This includes AHU technical information, start-up information, and unit maintenance. The information contained in this bulletin is provided to ensure the safe installation and operation of the equipment and its surroundings. The information provided in this Engineering Bulletin is to be used as a reference for each AHU to aid in determining unit size, power requirements, or lifting requirements. If additional information regarding a particular unit is required, please contact Trane Rental Services. Contact Trane Rental Services Marketing for availability of equipment (including ancillary items: pumps, flexible hose, flexible duct) prior to obtaining a purchase order from the customer. Equipment is available on a first-come, first-serve basis, but can be reserved with a signed rental agreement. Call Rental Services 24 x 7 at (800) for specific questions.! WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Important: All air handlers should be installed per the National Electric Code (NEC) and/or applicable state and local codes. Note: All information contained in this document is for reference only. 4 Rental Services Air Handling Unit CHS-SVN01A-EN
5 Air Handling Units General Information Our rental air handling units are custom Trane air handlers that have been modified for use as rental units. The majority of the modifications are related to framing for rigging purposes, connection of chilled water piping, and temporary duct connection. These air handling units contain only chilled water coils and do not have heating capability. Each unit has been selected for use with 100% outside air. Return plenums are available if required. An MP580 controller with touch screen display and wireless zone sensor is included with each unit. In addition, each unit includes a Trane TR1 variable frequency drive (VFD) that can control the fan motor. For additional information on the unit controls see Controls Information on page 15. CHS-SVN01A-EN Rental Services Air Handling Unit 5
6 10,000 cfm Air Handling Unit General RSAU0025F0 Model Number TCCA Nominal Tonnage tons Water Connection Size in. Victaulic Ambient Operating Conditions F Supply Motor Hp Fused Disconnect Yes Number of Electrical Circuits Discharge Configuration Horizontal Flex Duct Connection Size in round Number of Discharge Air Connections Max Discharge Static Pressure in. ESP Filter Rack (Quantity and size) (4) 24 x 24, (2) 24 x 12 Nominal Air Flow (cfm) ,000 Min/Max Air Flow (cfm) ,000/15,000 Insurance Value $35,000 Selection is required for actual AHU performance. 1 For ambient conditions below 40 F, glycol is recommended. 2 Unit provided with standard 2 filters. Filter rack will accept up to 95% efficient MERV 14 filters. Electrical Data Voltage V 3-phase Frequency Hz Lug(s) can accept wire up to #3 AWG wire Minimum Circuit Ampacity (MCA) amps Maximum Overcurrent Protection (MOP) amps 3 Depending on unit MCA and wire used, multiple wires per phase may be required. For additional electrical information contact Trane Rental Services. Total Cooling Capacity Entering Chilled Water Temperature (F) Outdoor Ambient Temperature (F) 84 db / 77 wb MBh Contact Trane Rental Services for specific selection information. Water Flow Rates Minimum Standard Maximum Coil Flow 70 gpm 151 gpm 400 gpm Pressure Drop 4.61 ft H 2 0 Dimensions and Weights Length Width 4 Height Weight Maximum water side pressure is 150psi (2.31 H20 = 1 psi) 16 ft 0 in 7 ft 4 in 7 ft 6 in 6,000 lbs 4Width includes permanently mounted piping manifold. Lifting Device: Fork Lift or Crane 6 Rental Services Air Handling Unit CHS-SVN01A-EN
7 10,000 cfm Air Handling Unit (nom. 25-tons) 10,000 cfm Air Handling Unit Fan Curve CHS-SVN01A-EN Rental Services Air Handling Unit 7
8 10,000 CFM Air Handling Units 10,000 cfm Air Handling Unit Drawing Note: Drawing should be used for information only as drawing depicts factory unit without rental modifications. 8 Rental Services Air Handling Unit CHS-SVN01A-EN
9 25,000 CFM Air Handling Units General RSAU0062F0 Model Number TCCA Nominal Tonnage tons Water Connection Size in. Victaulic Ambient Operating Conditions F Supply Motor Hp Fused Disconnect Yes Number of Electrical Circuits Discharge Configuration Horizontal Flex Duct Connection Size in. round Number of Discharge Air Connections Max Discharge Static Pressure in. ESP Filter Rack (Quantity and size) (9) 24 x 24, (3) 24 x 12, (3) 12 x 24 Nominal Air Flow (cfm) ,000 Min/Max Air Flow (cfm) ,000/35,000 Insurance Value $45,000 Selection is required for actual AHU performance. 1 For ambient conditions below 40 F, glycol is recommended. 2 Unit provided with standard 2 filters. Filter rack will accept up to 95% efficient MERV 14 filters. Electrical Data Voltage V 3-phase Frequency Hz Lug(s) can accept wire up to /0 AWG wire Minimum Circuit Ampacity (MCA) amps Maximum Overcurrent Protection (MOP) amps 3 Depending on unit MCA and wire used, multiple wires per phase may be required. For additional electrical information contact Trane Rental Services. Total Cooling Capacity Entering Chilled Water Temperature (F) Outdoor Ambient Temperature (F) 84 db / 77 wb MBh Contact Trane Rental Services for specific selection information. Water Flow Rates Minimum Standard Maximum Coil Flow 110 gpm 378 gpm 820 gpm Pressure Drop ft H 2 0 Maximum water side pressure is 150psi (2.31 H20 = 1 psi) Dimensions and Weights Length Width 4 Height Weight 18 ft 2 in 8 ft 6 in 10 ft 1 in 10,500 lbs 4Width does not include field installed piping manifold. Lifting Device: Fork Lift or Crane CHS-SVN01A-EN Rental Services Air Handling Unit 9
10 25,000 CFM Air Handling Units 25,000 cfm Air Handling Unit Fan Curve 10 Rental Services Air Handling Unit CHS-SVN01A-EN
11 25,000 CFM Air Handling Units 25,000 cfm Air Handling Unit Drawing Note: Drawing should be used for information only as drawing depicts factory unit without rental modifications. CHS-PRB009-EN Rental Services Air Handling Unit 11
12 Air Handling Units Electrical Information FIGURE 1 Disconnect FIGURE 2 Emergency stop FIGURE 3 Circuit breaker Each air handling unit (AHU) has an external fused disconnect as shown in Figure 1. In addition to the external fused disconnect each unit has an external start/stop button on the outside of the control cabinet access door (Figure 2) and a circuit breaker inside the control cabinet (Figure 3). Each 10,000cfm unit is provided with a minimum of 50-ft of #8/4 600V electrical cable connected to the external fused disconnect. Each 25,000cfm unit is provided with a minimum of 50-ft of #4/4 600V electrical cable connected to the external fused disconnect. Piping Connection Configuration 10,000 cfm Air Handling Unit (RSAU0025F0 ) Each 10,000 cfm AHU has two 2.5-in threaded inlet chilled water connections and two 2.5-in threaded outlet chilled water connections. Piping Manifold To provide a single chilled water connection point for each 10,000 cfm air handling unit, a piping manifold has been made to connect each unit s chilled water coils. Each 10,000 cfm unit has a manifold that is permanently installed on the unit for flex hose connection (Figure 4). The contents of the drop down kit for the 10,000 cfm units are listed in the bill of material below. The manifold kit will ship in the mixed air chamber and can be accessed through the filter access door. 12 Rental Services Air Handling Unit CHS-SVN01A-EN
13 Air Handling Units Bill of Material for 10,000 cfm Air Handling Unit Piping Manifold QUANTITY DESCRIPTION OF ITEMS Victaulic quick-snap couplings pipe section Victaulic 90 degree elbows FIGURE 4 10,000 cfm unit piping manifold 25,000 cfm Air Handling Unit (RSAU0062F0 ) Each 25,000 cfm AHU has four 2.5-in threaded inlet chilled water connections and four 2.5-in threaded outlet chilled water connections. Piping Manifold To provide a single chilled water connection point for each 25,000 cfm air handling unit, a piping manifold has been made to connect each unit s chilled water coils. Each 25,000 cfm unit has a manifold that must be field installed on each unit for flex hose connection (Figure 5). The contents of the piping manifold kit for the 25,000 cfm units are listed in the bill of material below. The manifold kit will ship in the mixed air chamber and can be accessed through the filter access door. CHS-SVN01A-EN Rental Services Air Handling Unit 13
14 Air Handling Units Bill of Material for 25,000 cfm Air Handling Unit Piping Manifold QUANTITY DESCRIPTION OF ITEMS 2 4 Manifold pipe section 2 4 Victaulic blank off 8 4 Victaulic quick-snap couplings Victaulic quick-snap couplings x 3 flex hose section x 6 pipe section Victaulic 90 degree elbows 2 4 x 6 Victaulic reducers 2 4 x 43 pipe section 4 4 Victaulic 90 degree elbows FIGURE 5 25,000 cfm unit piping manifold Reference the Rental Services hose engineering bulletin, CHS-PRB007-EN, for further information. 14 Rental Services Air Handling Unit CHS-SVN01A-EN
15 Air Handling Units Duct Connection Configuration 10,000 cfm Air Handling Unit (RSAU0025F0 ) Each 10,000 cfm AHU has two 19-in diameter discharge air connections. Each discharge air connection has a manual damper to control air flow. Each connection was made to accept one 20-in diameter flexible duct. 25,000 cfm Air Handling Unit (RSAU0062F0 ) Each 25,000 cfm AHU has four 19-in diameter discharge air connections. Each discharge air connection has a manual damper to control air flow. Each connection was made to accept one 20-in diameter flexible duct. FIGURE 6 Flex Duct Connection Reference the Rental Services flex duct engineering bulletin, CHS-PRB004-EN, for further information. Controls Information All 10,000 cfm and 25,000 cfm rental air handling units come equipped with a Trane MP-580 controller (Figure 7) and Trane TR-1 VFD (Figure 8) mounted in a control cabinet inside the unit. The controller is accessed by opening the external control cabinet door with an emergency stop button. In order for the unit to run using the MP-580 controller and default controls program, the VFD selector switch must be in VFD mode (Figure 9). The unit control program can be accessed using a laptop computer with the Rover service tool software or the unit-mounted stand alone display. The stand alone display is mounted in a sealed cabinet on the front of the unit next to the external disconnect (Figure 10). The operator display touch screen is an intuitive operator interface for monitoring and changing building control functions. With the operator display you can: CHS-SVN01A-EN Rental Services Air Handling Unit 15
16 Air Handling Units FIGURE 7 MP-580 controller FIGURE 8 TR1 VFD FIGURE 9 VFD Selector Switch Choose between constant volume or VAV. Choose specific air flow within specified range. Monitor space temperature, air flow, filter status, etc. Identify and troubleshoot problems. View and reset controller alarms. FIGURE 10 Unit Mounted Display FIGURE 11 Typical Status Screen The operator display includes a 7-day time clock that allows for time-of-day scheduling with two on/off times per day and up to 20 exception schedules per year. Both the 10,000 cfm and 25,000 cfm units can be configured to run based on a specified air flow (CV) or be controlled by space temperature (VAV) using the Rover service tool or the stand alone display. If the unit is configured as CV (or constant volume) the unit air flow can be specified within a certain air flow range. See chart below for air flow range per unit. Unit Nominal Air Flow (cfm) Min Air Flow (cfm) Max Air Flow (cfm) 10,000 8,000 15,000 25,000 15,000 35,000 If the unit is configured as VAV the unit will be controlled by the zone set-point using the wireless zone sensor that is provided with each unit. The wireless zone sensor can be found inside the control cabinet and is strapped in place for shipment. (See BAS- SVX04A-EN for additional information on wireless zone sensor.) 16 Rental Services Air Handling Unit CHS-SVN01A-EN
17 Air Handling Units Rigging Guidelines Each air handling unit has forklift pockets and an overhead lifting frame (Figure 12). Refer to page 5 and page 7 for unit dimensions and weights.! WARNING Heavy Objects! Use a forklift/crane of suitable capacity to move the unit. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage. FIGURE 12 10,000 cfm Unit in Frame CHS-SVN01A-EN Rental Services Air Handling Unit 17
18 Air Handling Units Installation and Startup Guidelines In addition to the startup guidelines below, please refer to startup information contained in the Custom Climate Changer Installation, Operation and Maintenance Manual (CAH-SVX01A-EN), TR1 Series VFD Installation and Operation Manual (TR1- SVX10A-EN), and Wireless Zone Sensor Installation, Operation and Maintenance Manual (BAS-SVX04A-EN). [ ] Install piping manifold supplied with unit and ensure all temporary piping is properly secured. See piping configuration information on page 12. [ ] To avoid flooding of unit interior install the P-trap supplied with unit. The unit P-trap is located in a bin in the mixed air chamber that is accessed through the filter access door. [ ] Close all coil drains. [ ] Install all temporary ductwork and open manual supply dampers. See duct connection configuration information on page 15. [ ] Connect electrical cable supplied with unit to power supply. See electrical information on page 12. [ ] Turn the fused disconnect switch located on the front of the unit to the ON position. [ ] Open the control cabinet door and turn the VFD selector switch to the VFD position. [ ] Make sure all access doors are properly closed. [ ] Using the unit mounted stand alone touch screen display select either CV or VAV. See page 16 for display location and explanation of the CV and VAV options. Note: Power must be supplied to the unit to operate the touch screen display. [ ] If the VAV option is selected remove the wireless zone sensor that is shipped inside the unit control cabinet and locate in the conditioned space. [ ] Pull the red Start/Stop button on the unit control cabinet door to start the unit fan. 18 Rental Services Air Handling Unit CHS-SVN01A-EN
19 Air Handling Units Maintenance Guidelines Please refer to the Custom Climate Changer Installation, Operation and Maintenance Manual (CAH-SVX01A-EN) and Wireless Zone Sensor Installation, Operation and Maintenance Manual (BAS-SVX04A-EN) for any regular unit maintenance. [ ] Monitor differential pressure across the unit filters using the pressure gauge mounted on the outside of the filter access door and change the filters as necessary (see pages 6 and 9 for unit filter rack quantities). Filter status can also be monitored using the stand alone touch screen display mounted in a cabinet on the front of the unit. Decommissioning Guidelines Reference the following guidelines for decommissioning rental AHUs prior to their return at the end of a rental job. Please contact Trane Rental Services at for any additional information. [ ] Press the red Start/Stop button on the unit control cabinet door. Allow enough time for the supply fan to come to a complete stop before opening any unit access doors. [ ] Turn the fused disconnect located on the front of the unit to the OFF position. [ ] Open the control cabinet door and turn the VFD selector switch to the OFF position. [ ] Drain solution from the system. If the system has glycol or other anti-freeze solution, flush hoses, manifold, and coil with water. Note: Local codes and regulations apply for disposal of glycol or anti-freeze solutions. [ ] Remove all external piping, temporary manifold pieces (see piping configuration section on page 12), and P-trap. Return P-trap and temporary manifold pieces to the bin located in the mixed air chamber that is accessed through the filter access door. [ ] Open all coil drains. [ ] Remove all temporary ductwork and close manual supply dampers. [ ] Disconnect electrical cable supplied with the unit from the power supply. [ ] Make sure all access doors are properly closed. [ ] Return additional hose, fittings, or cable (if furnished by Trane Rental Services) to appropriate containers for return shipment. [ ] Notify Trane Rental Services ( ) if unit needs repair or has damage. CHS-SVN01A-EN Rental Services Air Handling Unit 19
20 For more information, contact your local Trane office or us at Literature Order Number CHS-SVN01A-EN Date July 2008 Supersedes Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. New
Rental Services Temporary Cooling - Flexible Water Hose
Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationGreensource iseries HY Model Unitary Air Handler/Fan Coil
Engineering Submittal Sheet Overview Model Nomenclature HY 035 00-1 HY - HYDRONIC AIR HANDLER NOMINAL CAPACITY IN THOUSANDS OF BTUH VOLTAGE DESIGNATION 1 = 208-230/1/60 ELECTRIC HEAT KW 00 - NO ELECTRIC
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationWATER COOLED SELF CONTAINED MODEL LSWU/LSWD WITH IPU2 CONTROL 025-105
WATER COOLED SELF CONTAINED AIR CONDITIONING UNITS INSTALLATION, OPERATION AND MAINTENANCE Supersedes 145.05-NOM5 and 145.05-NOM6 Form 145.05-NOM7 (412) 035-22910-007 WATER COOLED SELF CONTAINED MODEL
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationTECHNICAL MANUAL GDS8 & GHS8
TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as
More information48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationWater Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationInstallation Instructions
05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:
More informationDehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
More informationF9MXE. Product Specifications
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationCooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in
More informationOperational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationVertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
More informationAir Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
More informationM7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
More informationCooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
More informationARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
More informationCooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
More informationOPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
More informationSplit System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationTWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationConvection Ovens. BX Classic. Models BX4 / FG 189C, BX4-6040 / FG 158C, BX10 / FG 180C. Operator's Manual
Convection Ovens BX Classic Models BX4 / FG 189C, BX4-6040 / FG 158C, BX10 / FG 180C Operator's Manual Belshaw Bros., Inc. 814 44 th Street NW, Suite 103 Auburn, WA 98001 USA Phone: 206-322-5474 Fax: 206-322-5425
More informationCEILING CASSETTE DUCTLESS SYSTEM
CEILING CASSETTE DUCTLESS SYSTEM INSTALLATION MANUAL Models: CAS12HP230V1AC -12,000 BTUH CAS18HP230V1AC -18,000 BTUH CAS24HP230V1AC - 24,000 BTUH Thank you for choosing the Gree Ceiling Cassette for your
More informationXV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.
Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent
More informationInstalling the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationModel 1210C Battery Powered Pump Shown. Description
12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationAIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency
FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant
More informationCEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
More informationService Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
More informationUSER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA
USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your
More informationAIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
More informationXV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE
UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB
More information36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
More informationPACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS SERVICE INSTRUCTIONS AMANA REFRIGERATION, INC., AMANA, IOWA 52204 MANUFACTURING NUMBERS COVERED IN THIS MANUAL SEE MODEL AND MANUFACTURING NUMBERS
More informationSplit System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
More informationG26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
More informationUse & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
More informationMobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
More informationPortable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
More informationHP ProLiant DL380 G6 Carrier-Grade Server Read Before Install
HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3 Copyright 2009, 2012 Hewlett-Packard Development Company,
More informationInstallation Instructions
Installation Instructions Accessory Ultraviolet (UV) Germicidal Lamp 1 & 2 Lamp Models 115-v & 208/230-v UV Lamp C03009 Fig. 1 Two Lamp Model UV Lamp NOTE: Read the entire instruction manual before starting
More informationCE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
More informationAIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
More informationVariable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
More informationG9MXE. Product Specifications
Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)
More informationCentrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
More informationVision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems
Vision Engravers and Routers PRE-Installation Guide Revised: 8/19/2015 Vision Engravers and Routers PRE-Installation Guide All rights reserved. No parts of this work may be reproduced in any form or by
More informationTMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationWON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
More informationPre-installation Manual. CONCEPT Processor 305 DW / 405 DW / 505 DW 505 DW XP
Pre-installation Manual CONCEPT Processor 305 DW / 405 DW / 505 DW 505 DW XP Pre-installation Manual CONCEPT Processor 305 DW / 405 DW / 505 DW / 505 DW XP T11336 Edition AA, April 2013 This book has
More informationMovinCool Office Pro Series. The Portable Spot Cooling Solution
MovinCool Office Pro Series The Portable Spot Cooling Solution The Office Pro 2002 American Standard Inc. All rights reserved Losing Is Not An Option With The Office Pro Series. The loss of data and equipment
More informationCTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual
CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual Goodway Technologies Corporation 420 West Avenue Stamford, CT 06902-6384 (203)359-4708 Sales: 1-800-333-7467 Customer Service: 1-800-370-2855
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
More informationPlease also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk
1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance
More informationYour safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
More informationGCS16 GCS20 WARNING CAUTION
Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat
More informationPortable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
More informationOperational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationFTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationSplit System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
More informationKESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850
INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationAluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
More informationInstallation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
More informationSINGLE PACKAGE VERTICAL AIR CONDITIONERS
SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,
More informationModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60
ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner
More informationCAB LCAB HACAB RMP/AMP CC CY/YY RVP CUSTOM CU
GENERAL PURPOSE (ORDINARY) LOCATION Custom Controls provides the petro-chemical and offshore industries with HVAC equipment of the highest quality and reliability on the market at an economical price.
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationSERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
More informationcatalog Single Package Vertical Air Conditioners and Heat Pumps
catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationNSN 4120-01-21 4-3692
*TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21
More informationService Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007
Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations
More informationCoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
More informationSunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationMACBlower Model Number: MAC40R MAC60R MAC80R MAC100R. MAC120R MAC150R MAC 200R Serial # www.macblowers.com
MACBlower Model Number: MAC40R MAC60R MAC80R MAC100R MAC120R MAC150R MAC 200R Serial # Fuji Clean USA 41-2 Greenwood Road Brunswick, Maine 04011 207-406-2729 www.macblowers.com MACBlowers The Intelligent
More information