CRITICAL POWER MONITORING CPM20/CPM21 DETAILS
|
|
- Meagan Dean
- 8 years ago
- Views:
Transcription
1 CRITICAL POWER MONITORING CPM20/CPM21 DETAILS The Starline Critical Power Monitor (CPM) is a distributed data acquisition system that enables Current and Power monitoring in busway systems. Each phase and neutral may be monitored independently. The CPM may be incorporated at a power feed point or directly into a plug-in unit. CURRENT TRANSFORMERS Current transformers (CT s) are supplied and calibrated with the unit for installation onto the customer-supplied feeder cables. Sense leads from the CT s connect to the Meter. METER MODULES Each unit is calibrated for accuracy within 1% to meet ANSI Revenue Grade Standards. CPM20 - BASIC PACKAGE Provides current measurements and alarms of up to 3 circuits. Includes Ethernet and Modbus ports; supports wireless option. CPM21 ENHANCED PACKAGE Provides current and voltage inputs, monitoring Current, Voltage, Power, Power Factor, Frequency, Apparent Power, Energy kwh, Reactive Power, Temperature, Neutral current, Power Min. and Max. DISPLAY (OPTIONAL) The bright LCD touch screen displays all basic power measurements and alarms. Touch screen provides limited configuration and control. Large format display is easily readable at a distance. COMMUNICATION Ethernet and Modbus RTU ports are standard. Ethernet port provides an Embedded Web (html) Interface & supports SNMP. Wireless mesh network interface is optional, providing true versatility in the busway environment. The Power monitor can be used to manage and maximize power distribution within a three phase power system. It can be employed as a component to help balance three phase power distribution between each phase. This assures accuracy within power usage calculations; increase efficiency by reducing wasted power on incoming power and/or neutral lines, and enables a user to fully utilize the power supplied to them. POWER FEED MONITORING CPM incorporated in or near the power feed unit provides load monitoring of the entire run of busway. Used in conjunction with BMS systems to ensure busway is not overloaded as well as for general power management. Typically uses the CPM21 Enhanced package with display. BRANCH CIRCUIT MONITORING CPM incorporated into each plug-in unit monitors individual branch circuits. Used in conjunction with BMS system for general power management and revenue purposes at the rack or circuit level. Typically uses the CPM20 basic unit for most efficient cost and packaging. Monitors up to 3 circuits. BUILDING MANAGEMENT INTERFACE Starline CPM is easily interfaced with BMS systems. Many BMS systems offer drivers for use with the Starline CPM. Contact your BMS supplier or Starline Engineering for more information. MONITOR PART NUMBER (Appends to Base Unit p/n as required) (Base Unit) - M21(xx)(yyy)/(z) No. of circuits (1-4) Max Amps/circuit(60,250,400) R: Remote Communications W: Wireless Communications DR or DW: with Display M20 or M21
2 POWER FEED UNIT with CPM Monitor End Feed with Installed Standard End Power Feed units connect to the male end of the Busway. Factory assembled unit consists of a 12 X 16 X 5 in. steel junction box, with removable sides, connected to a 1 foot section of Busway. The assembly includes connection lugs, ground lug and shrink tubing for wires up to 300 MCM. End Feed units for connection to female Busway ends are also available. Integral CPMs (M20/M21) installed in the End Feed provide power monitoring and alarms. Nuisance tripping may be avoided using the current information to protect against overloading phases. The monitors also assist in balance the three phase loads. A buzzer is provided that activates at 80% of full load. This level may be changed in the field using the embedded webpage. R versions provide remote communication functions, W provides wireless, DW include both local display and wireless and DR both local display and remote Special need power feed units for confined spaces that may be found in Mission Critical Data Centers can also be designed and fabricated, requiring minimum quantities. STANDARD END FEED (x = 20 or 21, yy = R, W, DW, or DR) EF225-4-Mxyy225/4 EF100N-4-Mxyy100/4 EF100NG-4-Mxyy100/4 EF225G-4-Mxyy225/4 MALE END FEED EF225-4M-Mxyy225/4 EF100N-4M-Mxyy100/4 EF100NG-4M-Mxyy100/4 EF225G-4M-Mxyy225/4 MALE RIGHT LID END FEED EF225-4MR-Mxyy225/4 EF100N-4MR-Mxyy100/4 EF100NG-4MR-Mxyy100/4 EF225G-4MR-Mxyy225/4 STANDARD LEFT LID END FEED EF225-4L-Mxyy225/4 EF100N-4L-Mxyy100/4 EF100NG-4L-Mxyy100/4 EF225G-4L-Mxyy225/4 RS-485 Ethernet Page 12.33
3 POWER FEED UNIT with CPM Monitor End Feed with Installed Standard End Power Feed units connect to any Busway section. Factory assembled unit consists of a 12 X 17 X 10 in. steel junction box, with removable sides, connected to a 1 ft section of Busway. Ground and connection lugs for wires up to 500 MCM are included. Reverse End Feed units for connection to opposite end of Busway sections are also available. (See B400 pages.) Integral CPMs (M20/M21) installed in the End Feed provide power monitoring and alarms. Nuisance tripping may be avoided using the current information to protect against overloading phases. The monitors also assist in balance the three phase loads. A buzzer is provided that activates at 80% of full load. This level may be changed in the field using the embedded webpage. R versions provide remote communication functions, W provides wireless, DW include both local display and wireless and DR both local display and remote Special need power feed units for confined spaces that may be found in Mission Critical Data Centers can also be designed and fabricated, requiring minimum quantities. STANDARD END FEED (x = 20 or 21, yy = R, W, DW, or DR) EF400-4-Mxyy400/4 EF400N-4-Mxyy400/4 EF400G-4-Mxyy400/4 EF400NG-4-Mxyy400/4 REVERSE END FEED EF400-4R-Mxyy400/4 EF400N-4R-Mxyy400/4 EF400G-4R-Mxyy400/4 EF400NG-4R-Mxyy400/4 REVERSE LEFT RS-485 LID END FEED EF400-4R-L-Mxyy400/4 EF400N-4R-L-Mxyy400/4 EF400G-4R-L-Mxyy400/4 EF400NG-4R-L-Mxyy400/4 STANDARD RIGHT LID END FEED EF400-4-RT-Mxyy400/4 EF400N-4-RT-Mxyy400/4 EF400G-4-RT-Mxyy400/4 EF400NG-4-RT-Mxyy400/4 RS-485 Ethernet Page 12.44
4 OUTLET BOX UNIT for Power Feed Current Monitoring Outlet Box with Installed An M20/M21 E12 plug-in unit is installed within 100 ft of the Busway power feed. Current Transformers (CT) are installed around the feed wires and then cabled to the Outlet Box. The paddle head may be rotated in the field to change the facing of the unit. M20/M21 CPMs provide the current level and alarm status for each phase and neutral. Nuisance tripping may be avoided using the current information to protect against overloading phases. The monitors also assist in balance the three phase loads. A buzzer is provided that activates at 80% of full load. This level may be changed in the field using the embedded webpage. R versions provide remote communication functions, W provides wireless Catalog No. Description Weight OB60E12-M20R60/3-4 CURRENT MONITOR UNIT, 60A/3P, RS lb OB100CE12-M21R100/4-4 CURRENT MONITOR UNIT, 100A/4P, RS lb OB100AE12-M21R100/4-4 CURRENT MONITOR UNIT, 100A/4P, RS lb OB100NE12-M21R100/4-4 CURRENT MONITOR UNIT, 100A/4P, RS lb OB100NGE12-M21R100/4-4 CURRENT MONITOR UNIT, 100A/4P, RS lb OB225E12-M21R225/4-4 CURRENT MONITOR UNIT, 225A/4P, RS lb OB225GE12-M21R225/4-4 CURRENT MONITOR UNIT, 225A/4P, ISO GND. 5.0 lb OB400E12-M21R400/4-4 CURRENT MONITOR UNIT, 400A/4P, RS lb OB400GE12-M21R400/4-4 CURRENT MONITOR UNIT, 400A-4P, ISO GND. 5.0 lb OB225E12-M21R425/4-4 SPLIT NEUTRAL CF M4, ABC: 225A, N: 400A 5.0 lb Options: - Replace R with W for wireless communication. - Replace M20 with M21 for Power monitoring. - replace -4 with -3 for 3-Pole units Page 12.5
5 CIRCUIT BREAKER UNIT for Branch Circuit Monitoring Circuit Breaker Unit with Installed Critical Power Monitor The Branch Circuit Current Monitoring Unit has the capability of monitoring a maximum of 4 single phase receptacles or a one 3-phase receptacle. The monitor has 4 channels available. Solid core current transformers (CT) are installed around the phase wires in the plug-in unit. R versions provide remote communication functions, W provides wireless, DW include both local display and wireless and DR both local display and remote Communications Ethernet and Modbus RTU ports are standard. Ethernet port provides an Embedded Web (html) Interface & supports SNMP. Wireless mesh network interface is optional, providing true versatility in the busway environment. See Power Monitoring pages for more details. Catalog No. Description CB100NHE28-L M20R30/3 CBM225GE28-(2)L630-4-M20R30/2 CBM225GE25-(4)L630-4-M20R30/4 CB400NGHE28-L M20R30/3 CKT. BKR. UNIT W/RECEPTS L1530, 22K CKT. BKR. UNIT W/RECEPTS - (2) L630 CKT. BKR. UNIT W/RECEPTS - (4) L630 CKT. BKR. UNIT W/RECEPTS L1530 CBDC225E28-X-L2130C-4-M20R30/3 CKT. BKR. DROP CORD UNIT W/CONN BODY - L2130C Options: - Replace R with W for wireless communication. - Replace M20 with M21 for Power monitoring.
Application Note: Monitoring Branch Circuit Loads in Critical Facilities
Application Note: Monitoring Branch Circuit Loads in Critical Facilities Description of application: The AcquiSuite data acquisition server (DAS) from Obvius is used to monitor the electrical loads and
More informationEnergy Savings in the Data Center Starts with Power Monitoring
Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.
More informationPower Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
More informationPanorama Electricity meters For reliable values of energy consumption
Panorama Electricity meters For reliable values of energy consumption Why measure Electrical Energy Energy cost is on the rise. It is therefore in the interest of both private and commercial customers
More informationHow To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
More informationA project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
More informationAPI Marine. BMS Presentation. Ballast Measurement Systems
API Marine BMS Presentation Ballast Measurement Systems BMS4 Typical Configuration BMS4 Typical Configuration BMS4 Extended Configuration BMS4 System (24 tanks) Air regulator Terminal block Drain/Air Filter
More informationPower & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
More informationApplication/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
More informationEnergy Management Solutions
Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic
More informationInstallation Guide Solar Connect-11
Installation Guide Solar Connect-11 Version 1.1 Contents Important Product Information 3 System Registration Form 4 Solar Connect-11 Overview 5 Internet & Power Connections 6 Single Phase CT Connections
More informationAPC 3Phase Power Distribution
APC 3Phase Power Distribution North American 3 Phase Business Development Team All content in this presentation is protected 2008 American Power Conversion Corporation Objectives Understand the entire
More informationSimple Electrical Utility Cost Allocation Solutions
Simple Electrical Utility Cost Allocation Solutions PowerLogic High Density Metering Advanced Submetering and Multi-Tenant Metering Buildings Retail Multi Residential DATA CENTER SOLUTIONS For More Information:
More informationEaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
More informationSOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationED1259R5 Updated April 2011 For latest specs visit www.legrand.us/wiremold
Rack Power Distribution Solutions for IT/Network Environments Wiremold Power Commander Power Distribution Units offer comprehensive power distribution solutions for IT environments from networking solutions
More informationRack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
More informationElectrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
More informationFeatures. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
More informationData Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
More informationSmart-UPS On-Line 230 V
Smart-UPS On-Line 230 V Unity output power factor single-phase, double-conversion online UPS with advanced management features A versatile UPS developed for unstable power conditions worldwide Smart-UPS
More informationOptimizing Rack Power Distribution
Optimizing Rack Power Distribution Best practices for selecting the right rack power distribution unit for your environment By Joe Skorjanec Product Manager Eaton Executive summary With information increasingly
More informationLTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
More informationELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
More informationCurrent Transformer (CT) Selection Guide
Current Transformer (CT) Selection Guide Article ESA-1008D December 5, 2014 Contents 1 Introduction.............................................. 3 1.1 Extending CT leads.......................................
More informationOVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
More informationProduct Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com
Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer
More informationLimited Service Fire Pump Controllers Features
Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers
More informationin widespread use with Simplex sister Company, Simplex Onsite, providing nationwide load bank rentals.
600KW - 1250KW Overview Integrated design, load module, trailer, reels, cam-lock style connections, digital control High capacity, 600-1250kw Dual voltage: 208-240/416-480vAC Digital load control, 5 kw
More informationPower Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
More informationRELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
More informationIntelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
More informationApplications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
More informationIndustrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
More informationEnergy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management
Energy Depot GmbH Delivering Solutions for Energy Management PRODUCT AND APPLICATION GUIDE Total Monitoring Solution for PV SOLAR LOGGER & ANALYSIS DC STRING MONITORING Residential Comprehensive Solar
More informationABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw
Solar inverters ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw PV energy, combined with energy storage systems, can help increase self-consumption and energy selfsufficiency*. One of the biggest challenges
More informationTypes of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
More informationPower Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
More informationMTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
More informationRack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
More informationBest Practices Guide for Obvius Data Acquisition Products
Best Practices Guide for Obvius Data Acquisition Products Part I: Background/general information Obvius LLC provides industry-leading products for cost effective data gathering, storage and communications.
More informationPacket Power. Data Center Solutions. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution. Data Center Monitoring Made Easy
Data Center Solutions Packet Power for Data Centers Packet Power provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility
More informationEVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001 2014 Class 2800 CONTENTS Description............................................ Page 2 Outdoor
More informationOVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
More informationDigital I/O: OUTPUT: Basic, Count, Count+, Smart+
Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ The digital I/O option port in the 4-Series provides us with 4 optically isolated inputs and 4 optically isolated outputs. All power is supplied externally.
More informationSmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
More informationTAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line
More information10 Port L2 Managed Gigabit Ethernet Switch with 2 Open SFP Slots - Rack Mountable
10 Port L2 Managed Gigabit Ethernet Switch with 2 Open SFP Slots - Rack Mountable StarTech ID: IES101002SFP The IES101002SFP 10-port Ethernet switch delivers flexibility and control of your network by
More informationBrochure. Electricity meters For increased awareness
Brochure Electricity meters For increased awareness Strike the perfect balance with EQ meters In the World Energy outlook for 2012 the International Energy Agency (IEA), states: A significant share of
More information8 Intelligent PDUs. Intelligent Power Distribution Units for Data Centers
BRC_PDU_US_B_BRC_IcePack 4/30/13 11:31 AM Page 2 8 Intelligent PDUs Intelligent Power Distribution Units for Data Centers Intelligent Power Distribution Units Siemon s line of intelligent PDUs provide
More informationNEW. Solar-Log & GE Meter Residential Solar PV Monitoring & Metering Built into a Single Device
NEW Solar-Log & GE Meter Residential Solar PV Monitoring & Metering Built into a Single Device Wireless Residential PV Monitoring Solar-Log & GE Meter - Highlights Solar-Log 350 & GE Meter Solar-Log Dashboard
More informationIP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
More informationCable Specifications. T3 Trunk Cabling APPENDIX
APPENDIX B This appendix contains details on the MGX 8230 cabling. It includes the following sections: T3 Trunk Cabling Frame Relay Cabling DC Power Cabling AC Power Cabling Control and Clock Cabling External
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationProducts and solutions for pumping, irrigation and piping
Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric
More informationPower-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationMINIMAT-EC-Servo Screwdriver Spindles
Screwdriving technology Automation Air motors Air tools Screwdriver Spindles electric MINIMAT-EC-Servo Screwdriver Spindles Maximum Flexibility and process Control Straight Spindle Form - Torque range
More informationscalable data centre energy management solution
scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology
More informationProduct Information Sheet UH36 Hi Pot Tester
Product Information Sheet UH36 ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: info@etl-prueftechnik.de Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet: www.etl-prueftechnik.de
More informationElectro-Magnetic Flowmeters COPA-XT 2-Wire DT43
Data Sheet Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43 2-Wire Operation Significantly reduces installation costs when compared to a traditional 4-wire magmeter. ±0.5% of rate system accuracy. Patented
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationHow can a charging station for electric vehicles be set up simply and safely?
SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,
More informationCS-24HEK4B3H2 (Master) CL-24HEK4B3H2 (Expansion) Key Features. Inputs
CS-24HEK4B3H2 (Master) CL-24HEK4B3H2 (Expansion) The Server Technology Smart PDU provides local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis
More informationCommunicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
More informationNational Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
More informationIntesisBox Modbus Server SAMSUNG Air Conditioners
IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,
More informationProduct overview. 2000 mm. 100 mm
Panel mounted electronic multi-circuit heat-tracing control, monitoring and power distribution system Product overview CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE
More informationUSB 3.0 Cables. Color. Black Black Black Black Black 3021003-03 3021009-06 3021015-10 3021021-16 3021027-16. Black Black Black Black Black
USB.0 CableS USB.0 and backwards compatible for USB.0 and. Supports high speed, 480Mbps Twisted-pair construction reduces cross talk to ensure error free transfer USB A male to USB B male 00-0 007-0 0-09-
More informationEnergy Communication Unit (ECU)
Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.8) ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2 2.0 Installation...
More informationModel #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
More informationServer Technology, Inc.
Server Technology, Inc. The Top 10 things every data center manager should know about power White Paper STI-100-014 2012-April Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United
More informationMeasurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219
Siemens AG 2010 Flow Measurement Overview The transmitter is available in an IP67/NEMA X/6 enclosure and is designed for use in the flowmeters series: SONOKIT (1- or 2-track) FUS380 (2-track) FUE380 (2-track)
More informationSmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
More informationAdvantages of Wire- Free Power Monitoring in the Data Center
Advantages of Wire- Free Power Monitoring in the Data Center Using PIPS (Per Inlet Power Sensing) and POPS (Per Outlet Power Sensing) CDU Technology with RF Code s Wire- Free Solutions February 3, 2011
More informationRemote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
More informationEATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual
More informationSmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
More informationTruPower-Portable-500W. Solar Starter kit
TruPower-Portable-500W Solar Starter kit This Solar starter kit is an easy to use solar power supply system that is the complete solution for all your solar power needs. It is a solar generator that converts
More informationCurrent Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
More informationMAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
More informationOPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
More informationUser Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters
SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm
More informationD. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
More informationIntelligent Power Distribution
Eaton epdu Intelligent Power Distribution Maximise and manage your rack power Eaton epdus Managed epdus Advanced Monitored epdus Managed epdus offer data centre managers maximum functionality and flexibility,
More information4-Port 10/100Mbps with PoE + 1-Port 100FX Industrial Ethernet Switch Wide Temperature
4-Port 10/Mbps with + 1-Port FX Industrial Ethernet Switch Wide Temperature 15 F Fiber Optic Link Capability for Flexible Distance Extension The series equips one Base-FX port that provides more flexibility
More informationCurrent Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
More informationAutomatic AES Change-Over
Automatic AES Change-Over Thank you for choosing a GHIELMETTI product. We are convinced that your choice will prove to be a wise and worthy decision for many years to come. Your GHIELMETTI product has
More informationDistributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
More informationLow Voltage Products
Low Voltage Products ABB Power Quality Filters: The most efficient solution for active filtering of harmonics, smooth reactive power compensation and load balancing. Enabling trouble-free and efficient
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationSECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM
WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power
More informationMicrocor Wireless Transmitter (MWT)
Rohrback Cosasco Systems, Inc. Microcor Wireless Transmitter (MWT) Features: Highly Secure and Reliable Self Organizing Wireless Mesh Network High Resolution Metal Loss Measurement for all process environments
More informationPacket Power. Data Center Solutions. Packet Power. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution
Data Center Solutions for Data Centers provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility operations. Gain
More informationZlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
More informationIFS SP-PoE Splitter User Manual
IFS SP-PoE Splitter User Manual P/N 1069176-EN REV 1.01 ISS 01JUL10 2011 UTC Fire & Security. All rights reserved. Content Overview 2 Package contents 2 Introduction 3 Product Specifications 3 Hardware
More informationAIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More information