Facilities Instructions, Standards, and Techniques Volume 4-1B. Maintenance Scheduling for Electrical Equipment
|
|
|
- Christal Cross
- 10 years ago
- Views:
Transcription
1 Facilities Instructions, Standards, and Techniques Volume 4-1B Maintenance Scheduling for Electrical Equipment U.S. Department of the Interior Bureau of Reclamation Denver, Colorado January 2012
2 REPORT DOCUMENTATION PAGE Form Approved OMB No Public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing this collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden to Department of Defense, Washington Headquarters Services, Directorate for Information Operations and Reports ( ), 1215 Jefferson Davis Highway, Suite 1204, Arlington, VA Respondents should be aware that notwithstanding any other provision of law, no person shall be subject to any penalty for failing to comply with a collection of information if it does not display a currently valid OMB control number. PLEASE DO NOT RETURN YOUR FORM TO THE ABOVE ADDRESS. 1. REPORT DATE (DD-MM-YYYY) January 17, REPORT TYPE Final 3. DATES COVERED (From - To) Implementation Date: January 1, TITLE AND SUBTITLE 5a. CONTRACT NUMBER FIST 4-1B, Maintenance Scheduling 5b. GRANT NUMBER 5c. PROGRAM ELEMENT NUMBER 6. AUTHOR(S) Bureau of Reclamation Hydropower Technical Services Group Mail Code Denver, Colorado 7. PERFORMING ORGANIZATION NAME(S) AND ADDRESS(ES) Hydropower Technical Services Group, Bureau of Reclamation Denver Federal Center P.O. Box Denver CO SPONSORING / MONITORING AGENCY NAME(S) AND ADDRESS(ES) Power Resources Office Bureau of Reclamation Mail Code PO Box Denver CO DISTRIBUTION / AVAILABILITY STATEMENT Available from the National Technical Information Service, Operations Division, 5285 Port Royal Road, Springfield, Virginia d. PROJECT NUMBER 5e. TASK NUMBER 5f. WORK UNIT NUMBER 8. PERFORMING ORGANIZATION REPORT NUMBER FIST 4-1B 10. SPONSOR/MONITOR S ACRONYM(S) DIBR 11. SPONSOR/MONITOR S REPORT NUMBER(S) 13. SUPPLEMENTARY NOTES 14. ABSTRACT This document establishes minimum recommended practices for maintenance of electrical equipment in Bureau of Reclamation hydroelectric power and large pumping plants. Included in this document are recommended maintenance activities, maintenance intervals, and references. 15. SUBJECT TERMS Electrical equipment, maintenance scheduling, maintenance, annunciators and alarms, arresters, batteries, bushings, buswork, enclosures, insulators, power cables, circuit breakers, carbon dioxide systems, coupling capacitors, overhead cranes, hoists, elevators, emergency lighting, governors, motors, relays, generators 16. SECURITY CLASSIFICATION OF: 17. LIMITATION OF ABSTRACT a. REPORT UL b. ABSTRACT UL c. THIS PAGE UL UL 18. NUMBER OF PAGES 67 19a. NAME OF RESPONSIBLE PERSON Power Resources Office 19b. TELEPHONE NUMBER (include area code) (303) Standard Form 298 (Rev. 8/98) Prescribed by ANSI Std
3 Facilities, Instructions, Standards, and Techniques Volume 4-1B Maintenance Scheduling for Electrical Equipment Hydroelectric Research and Technical Services Group U.S. Department of the Interior Bureau of Reclamation Denver, Colorado January 2012
4 Disclaimer This written material consists of general information for internal use only by Bureau of Reclamation operations and maintenance staff. Information contained in this document regarding commercial products or firms may not be used for advertising or promotional purposes and is not to be construed as an endorsement or deprecation of any product or firm by the Bureau of Reclamation.
5 Acronyms and Abbreviations ac alternating current AVR automatic voltage regulator CARMA Capital Asset and Resource Management Application CCVT coupling capacitor/voltage transformer CO 2 carbon dioxide dc direct current DGA dissolved gas analysis EHV extra high voltage EPSS emergency power standby systems FIST Facilities Instructions, Standards, and Techniques GSU generator step-up HECP Hazardous Energy Control Program hp horsepower HVDC high voltage direct current hipot high potential tests IR infrared kv kilovolt kva kilovoltampere O&M operations and maintenance PEB Power Equipment Bulletin PI Polarization Index PO&M Power Operation and Maintenance PPE personal protective equipment PSS power system stabilizer RCM reliability centered maintenance Reclamation Bureau of Reclamation RSHS Reclamation Safety and Health Standards SCADA Supervisory Control and Data Acquisition UPS uninterruptable power supply V volt Vac volts alternating current Vdc volts direct current % percent > greater than < less than iii
6
7 Table of Contents Page Acronyms and Abbreviations... iii 1. Introduction Maintenance Maintenance Schedules and Documentation Job Plan Templates Power O&M Forms... 4 Electrical Equipment Maintenance Schedules Annunciators and Alarms General Maintenance Schedule for Annunciators/Alarms Arresters General Maintenance Schedule for Arresters Batteries, Battery Chargers, and Battery Monitoring Systems General Maintenance Schedule Flooded, Wet Cell, Lead Acid Batteries Maintenance Schedule Valve Regulated, Lead Acid (Gel Cell) Batteries Maintenance Schedule Vented Nickel Cadmium Batteries Maintenance Schedule Battery Chargers Maintenance Schedule Battery Monitoring System Bushings General Maintenance Schedule for Bushings Buswork, Enclosures, and Insulators General Maintenance Schedule for Buswork, Insulators, and Enclosures 5 15 Kilovolts (kv) Power Cables Energized at 2 kv and Above General Maintenance Schedule for Power Cables Carbon Dioxide Systems General v
8 Table of Contents (continued) Page 8.2 Maintenance Schedule for CO 2 Systems Circuit Breakers General Molded Case Breaker Maintenance Schedule Low Voltage (600 Volts [V] and Less [480 V] Draw Out and Fixed Air Circuit Breaker Maintenance Schedule Medium Voltage ( kv Rated) Air and Air Blast Breaker Maintenance Schedule Medium Voltage (601 15,000 Vac) Vacuum Breaker Maintenance Schedule Medium and High Voltage SF 6 Breaker Maintenance Schedule Medium and High Voltage Oil Breakers Maintenance Schedule Control Circuits General Maintenance Schedule for Control Circuits Coupling Capacitors General Maintenance Schedule for Coupling Capacitors Overhead Cranes, Hoists, Elevators General Maintenance for Elevators Maintenance Schedule for Cranes and Hoists Startup and Daily Inspections Overhead Distribution Lines General Maintenance Schedule for Overhead Distribution Lines Electrical Drawings General Emergency Lighting General Maintenance Schedule for Emergency Lighting Exciters and Voltage Regulators General Maintenance Schedule for Exciters and Voltage Regulators vi
9 Table of Contents (continued) 17. Facility Equipment Ratings and Protective Relaying Reviews General Maintenance Schedule for Facility Equipment Ratings Review Protective Relay Settings Review Arc Flash Hazard Analysis Fire Detection and Alarm Systems General Maintenance Schedule for Fire Detection and Alarm Systems Blackstart Generators General Testing Schedule for Blackstart Generators Engine Generators General Maintenance Schedule for Engine Generators Generators and Large Motors General Maintenance Schedule for Generators and Large Motors Governors General Maintenance Schedule for Governors Motors (< 500 hp) General Maintenance Schedule for Motors Personal Protective Equipment General Maintenance Schedule for Personal Protective Equipment/ Hot Line Tools Potheads General Maintenance Schedule for Potheads Relays and Protection Circuits General Calibration and Maintenance Relay Functional Test Protection Circuit Functional Testing Page vii
10 Table of Contents (continued) Page 26.2 Maintenance Schedule for Electromechanical Relays Maintenance Schedule for Solid-State Relays Maintenance Schedule for Microprocessor Relays Maintenance Schedule for Lockout Relays Maintenance Schedule for Protection Circuits SCADA Systems General Input and Output Circuit Functional Testing Maintenance Schedule for SCADA Systems Security Systems General Maintenance Schedule for Security Systems Switches, Disconnect Medium and High Voltage General Maintenance Schedule for Disconnect Switches Switchyard/Substation Ground Connections General Maintenance Schedule for Switchyard/Substation Ground Connections Switchyards, Substations, and Transmission Lines General Maintenance Schedule for Switchyards and Substations Maintenance Schedule for Transmission Lines Thermographic Maintenance (Infrared Scanning) General Transducers/Meters/Switches General Maintenance Schedule for Transducers/Meters/Switches Transformers General Instrument Transformers General Maintenance Schedule for Instrument Transformers Transformers Rated Less Than 500 kva General Maintenance Schedule for Transformers Rated Less Than 500 kva viii
11 Table of Contents (continued) Page 34.4 Dry-Type Power Transformers Rated 500 kva and Larger General Maintenance Schedule for Dry-Type Power Transformers Oil-Filled Power Transformers Rated 500 kva and Larger General Maintenance Schedule for Oil-Filled Power Transformers Transformer Fire Suppression Systems General Maintenance Schedule for Transformer Fire Suppression Systems Calibration of Test Equipment General Maintenance Schedule for Calibration of Test Equipment ix
12
13 1. Introduction The recommended intervals listed in this document will supersede all intervals within existing Facilities, Instructions, Standards, and Techniques (FIST) and Power Equipment Bulletins (PEB) documents. s within the maintenance schedules identify appropriate FIST volumes and PEBs for the established electrical maintenance practices. FIST volumes are available on the World Wide Web. Power Equipment Bulletins are available only to Bureau of Reclamation (Reclamation) personnel and may be found on the Intranet. Frequencies stated by this FIST are based on a standard time-based maintenance 1 scheduling system for which all maintenance activities will be performed. It does not address followup work generated by preventive maintenance activities. The adoption of other techniques must be implemented via a variance. These other techniques must be consciously chosen, technically sound, effectively implemented, and properly documented. The alternative to a time-based maintenance program includes a condition-based maintenance program or a reliability-centered maintenance (RCM) based program that may justify longer (or shorter) time intervals. FIST procedures, practices, and schedules that appear in black bold and bracketed text are considered Reclamation standard practice. FIST procedures, practices, and schedules that appear in red bold and bracketed text are related to compliance issues, such as safety (Occupational Safety and Health Administration) or reliability (North American Electric Reliability Corporation) and cannot be varied from. s, listed in the tables, are recommended maximum times between maintenance cycles. Variation from the adopted Reclamation standard practice is acceptable provided that an approved variance exists. Variances only are required when an alternative practice, procedure, or schedule does not meet the maximum time intervals listed within the Reclamation standard. Procedures, practices, and schedules that are in plain text are suggested, not a minimum operations and maintenance (O&M) activity level. Variations from suggested procedures, practices, and schedules do not require a variance. Reclamation standard practices, including recommended intervals defined in FIST volumes, are based on power industry best practices, published standards, and Reclamation s experience maintaining equipment in hydroelectric powerplants (defined within as Reclamation Best ). This FIST volume includes references to other published FISTs and PEBs that may contain further instruction. 1 FIST 6-2 for other maintenance approaches. 1
14 To access Reclamation s FIST volumes: Printed FIST volumes: Reclamation offices: Phone: Mail: Power Resources Office All others, contact National Technical Information Service: Internet: Phone: Mail: National Technical Information Service 5301 Shawnee Rd. Alexandria, VA Digital FIST volumes in pdf: Maintenance Equipment and situations vary greatly, and sound engineering and management judgment must be exercised when applying these recommendations. It should not be the sole source of information used in conducting maintenance activities. Other sources of information should be consulted (e.g., manufacturer s recommendations, unusual operating conditions, personal experience with the equipment, etc.) for references associated with these maintenance schedules. Performing maintenance on electrical equipment can be hazardous. Electrical and mechanical energy can cause injury and death if not managed properly. All maintenance activity must be conducted in accordance with FIST 1-1, Hazardous Energy Control Program (HECP), and Reclamation Safety and Health Standards (RSHS). 1.2 Maintenance Schedules and Documentation Complete, accurate, and current documentation is essential to an effective maintenance program. Whether performing preventive, predictive, conditionbased, or reliability-centered maintenance, keeping track of equipment condition and maintenance performed and planned is critical. Critical equipment is defined in the Reclamation Standards Asset and Maintenance Management Glossary of Terms (Document Control No
15 001). This standard defines critical equipment as any system, asset, or component whose failure could cause: 1. A loss of ability to convey water or the shutdown or load reduction of power generation 2. Loss of transmission capability or reduction in capacity 3. Serious personnel injury or violation of a safety regulation 4. An environmental hazard resulting in harm to the public, environment, or damage to public property Maintenance schedules contained in this volume should be used as the basis for establishing a local maintenance program. This schedule states frequencies as multiyear, annually, monthly, weekly, etc. Weekly: Calendar week (Sunday to Saturday) Monthly: Calendar month (first day through the last day of the month) Quarterly: A calendar quarter consisting of 3 calendar months Semi-annually: Six calendar months Annually: A calendar year (January 1 through December 31) Multiyear: Multiple calendar years (e.g., 5-year January 1, 2011, through December 31, 2015) It is up to the individual office to document the tolerances associated with these stated frequencies. Many offices use the concept of a maintenance season to describe the timeframe for performing maintenance scheduled on an annual interval. A maintenance season will be considered the period of time from October 1 of the current year through May 31 of the following year. 1.3 Job Plan Templates Existing job plans created by the various facilities are available in the Capital Asset and Resource Management Application (CARMA ) to use as templates. Local development of complete job plans that match maintenance requirements can be expedited by using these as templates. 3
16 1.4 Power O&M Forms Power O&M (PO&M) forms have been updated and placed on the Intranet for facility use in documenting maintenance. These forms can be filled out online and printed or printed and completed by hand. PO&M forms are available at select Power O&M Forms from the menu on the left or from the Reclamation forms Web site at Word format files of the forms can be acquired from the Hydroelectric Power Technical Services Group at , if modification for specific facility use is desired. 4
17 Electrical Equipment Maintenance Schedules 2. Annunciators and Alarms 2.1 General The maintenance schedule for annunciator and alarms only pertains to circuits associated with critical equipment as defined in section 1.2 of this document. Annunciators and alarms provide essential plant condition status information to O&M personnel. Two aspects must be considered: 1. Correct operation of annunciator and alarm devices 2. Integrity of the annunciator and alarm circuits 2.2 Maintenance Schedule for Annunciators/Alarms [Operational test] [Weekly] PEB 43 [Functional test] [2 years] PEB 43 5
18 3. Arresters 3.1 General Lightning or surge arresters provide protection for important equipment from high energy surges. These arresters are static devices that require fairly infrequent maintenance. Most maintenance must take place while the associated circuit is de-energized. However, crucial visual inspections and infrared (IR) scans can take place while energized. 3.2 Maintenance Schedule for Arresters [Visual inspection] [Semi-annually] PEB 44 [Clean insulator and check integrity of connections] [Insulation test] (Doble test power frequency dielectric loss, direct current [dc] insulation resistance, power factor) [6 years] PEB 44 [6 years] PEB 44 6
19 4. Batteries, Battery Chargers, and Battery Monitoring Systems 4.1 General Battery systems provide last resort power for performing communication, alarm, control, and protective functions (relaying and breaker tripping) when other sources of power fail. Battery system maintenance should have highest priority. Computerized, online battery monitoring systems can be installed to supplement a maintenance program and reduce costs. Battery chargers require regular maintenance as well. 4.2 Maintenance Schedule Flooded, Wet Cell, Lead Acid Batteries [Battery float voltage (charger meter)] [Weekly] FIST 3-6, section 1.3.A [Visual inspection] [Monthly] FIST 3-6, section 1.7 [Check accuracy of charger meter] [Monthly] FIST 3-6, section 1.3.D [Cell float voltage pilot cells with meter] [Monthly] FIST 3-6, section 1.3.E [Cell float voltage all cells] [Quarterly] FIST 3-6, section 1.3.F [Specific gravity pilot cells] [Monthly] FIST 3-6, section 1.4.A [Specific gravity (10 percent [%] of all cells)] [Quarterly] FIST 3-6, section 1.4.B [Specific gravity all cells] [Annually] FIST 3-6, section 1.4.C [Temperature (pilot cell)] [Monthly] FIST 3-6, section 1.5.A [Temperature (10% of all cells)] [Quarterly] FIST 3-6, section 1.5.B [Connection resistance (this may be checked by IR scan while loaded)] [Annually] FIST 3-6, section 1.6.B [Capacity testing] [5 years] 1 FIST 3-6, section 3.2 [Safety equipment inspection] [Monthly] FIST 3-6, sections 1.7.A and 8 1 [Annually if capacity less than 90%.] 7
20 4.3 Maintenance Schedule Valve Regulated, Lead Acid (Gel Cell) Batteries [Battery float voltage (charger meter)] [Weekly] FIST 3-6, section 5.7.B [Visual inspection] [Monthly] FIST 3-6, section 5.6 [Check accuracy of charger meter] [Monthly] FIST 3-6, section 5.7.E [Cell float voltage pilot cells with meter] [Monthly] FIST 3-6, section 5.7.D [Cell float voltage all cells] [Semi-annually] FIST 3-6, section 5.7.F [Temperature (all cells)] [Quarterly] FIST 3-6, section 5.8.B [Connection resistance (25% of all connections)] [Connection resistance (all connections)] [Quarterly] [Annually] FIST 3-6, section 5.10.B FIST 3-6, section 5.9.C [Internal resistance of all cells] [Quarterly] FIST 3-6, section 5.10.B [Capacity testing] [Annually] FIST 3-6, section 5.11.B [Safety equipment inspection] [Monthly] FIST 3-6, sections 5.6 and Maintenance Schedule Vented Nickel Cadmium Batteries [Battery float voltage (charger meter)] [Weekly] FIST 3-6, section 6.6.A [Visual inspection] [Monthly] FIST 3-6, section 6.11.A [Check accuracy of charger meter] [Monthly] FIST 3-6, section 6.6.D [Cell float voltage pilot cells with meter] [Quarterly] FIST 3-6, section 6.6.E [Cell float voltage all cells] [Semi-annually] FIST 3-6, section 6.6.F [Temperature (pilot cell)] [Quarterly] FIST 3-6, section 6.7A [Specific gravity all cells] [5 years] FIST 3-6, section
21 Maintenance Schedule Vented Nickel Cadmium Batteries (continued) [Retorque intercell connections] [Annually] FIST 3-6, section 6.4.A [Capacity testing] [5 years 1 ] FIST 3-6, section 6.9.B [Safety equipment inspection] [Monthly] FIST 3-6, sections 1.7 and [Annually if capacity less than 90%.] 4.5 Maintenance Schedule Battery Chargers [Check each charger and verify that charger will hold the load] [Check float and equalize charge settings] [Quarterly] [Annually] Reclamation Standard Reclamation Standard [Check and clean enclosures] [Annually] Reclamation Standard [Check connection integrity] [Annually] Reclamation Standard 4.6 Maintenance Schedule Battery Monitoring System [Inspect unit for indication of power failure or alarms] [Verify monitoring system battery float voltage] [Verify monitoring system cell voltages to manual readings at the battery cells] [Verify monitoring system overall battery current] [Verify monitoring system cell connection resistance] [Verify monitoring system battery room temperature] [Weekly] PEB 49 [Annually] PEB 49 [Annually] PEB 49 [Annually] PEB 49 [Annually] PEB 49 [Annually] PEB 49 9
22 Maintenance Schedule Battery Monitoring System (continued) [Verify cell temperature monitoring system equipment 1 ] [Verify cell fluid level monitoring system equipment 1 ] [Verify specific gravity monitoring system cell equipment 1 ] [Annually] PEB 49 [Annually] PEB 49 [Annually] PEB 49 1 [These functions must be tested if present and used to assist in the maintenance of the battery system.] 10
23 5. Bushings 5.1 General Bushings are critical components of medium and high voltage circuit breakers and transformers. Bushing maintenance usually is conducted at the same time maintenance is performed on the circuit breaker or transformer, or at least during an outage on that equipment. 5.2 Maintenance Schedule for Bushings Refer to the circuit breaker and transformer maintenance sections of this document for bushing maintenance requirements. 11
24 6. Buswork, Enclosures, and Insulators 6.1 General Buswork conducts current from one part of the powerplant or switchyard to another. Buswork usually is constructed of flat or round copper or aluminum busbar and can be either isolated-phase or nonsegregated. Except for infrared scanning, bus maintenance must be conducted de-energized. Standoff buswork insulators provide isolation of live power circuits from ground and other circuits. Failure of insulators will cause a power system fault and a forced outage. 6.2 Maintenance Schedule for Buswork, Insulators, and Enclosures 5 15 Kilovolts (kv) [Check integrity of connections] [6 years] Reclamation Standard [Check and clean enclosures] [6 years] Reclamation Standard [Insulation test] (Hipot or Doble test power frequency dielectric loss, dc insulation resistance, power factor) [6 years] Reclamation Standard 12
25 7. Power Cables Energized at 2 kv and Above 7.1 General Periodic maintenance tests are needed during the life of the cable to determine whether or not there has been significant insulation deterioration due to operational or environmental conditions. The maintenance schedule for power cables only pertains to cables associated with critical equipment as defined in section 1.2 of this document. High potential tests (hipot) effectively reduce inservice failures from faults of the cable or its accessories. When done properly, maintenance tests can detect problems in cables that are approaching failure without accelerating the deterioration process. Except for infrared scanning, de-energize the cable circuit before maintenance. For assistance in determining appropriate test methods and voltage levels for a specific cable installation, contact the Hydroelectric Power Technical Services Group ( ) at Maintenance Schedule for Power Cables [Insulation test] (DC ramp test) [5 years] FIST 3-1, sections 21 and 49 [Insulating oil dissolved gas analysis (DGA), physical, and chemical tests] [Annually] Reclamation Standard 13
26 8. Carbon Dioxide Systems 8.1 General Carbon dioxide (CO 2 ) systems provide fire suppression for generator and large motor windings. These systems consist of CO 2 storage bottles or tanks, piping and valves, and electrical control systems. 8.2 Maintenance Schedule for CO 2 Systems CAUTION: CO 2 is dangerous and costly to replace. Take care to avoid inadvertent CO 2 discharge during maintenance and testing. [Visual inspection and check gauges] [Weekly] FIST 5-12, section 15 [Weigh CO 2 bottles] [Semi-annually] FIST 5-12, section 12.2 [Function check controls] [Annually] FIST 5-12, section 15, table 2 [Operate routing valves] [Overall CO 2 system functional test] [Cylinder hydrostatic test] [Visually inspect and functional test CO 2 discharge warning beacons and alarms] [Annually and after painting] FIST 5-12, section 15, table 2 [5 years] FIST 5-12, section 15, table 2 [12 years] [Any discharged cylinder not hydrostatically tested in the past 5 years must be tested prior to refill.] FIST 5-12, section 15, table 2 [Annually] FIST 5-12, section 15, table 2 14
27 9. Circuit Breakers 9.1 General Circuit breakers interrupt electrical current to stop power flow both for switching operations and during fault conditions. The maintenance schedule for molded case circuit breakers only pertains to breakers associated with critical equipment as defined in this document. Molded case circuit breakers located in low voltage distribution panels are typically 125 to 250 volts direct current (Vdc); 120, 208, 240, 277, and 480 volts alternating current (Vac); or used for control, protection, and auxiliary power. These molded case breakers should not be loaded more than 80% of the rated value unless the breaker is specified as a continuous type capable of being loaded to 100%. As well as low voltage drawout and fixed air circuit breakers, 480-Vac power type molded case circuit breakers can be located in motor starter cabinets, motor control centers, station service switchgear, or similar power distribution enclosures and auxiliary power panels. Breakers in this category or class usually have some type of adjustable trip capabilities. Adjustable settings for this class of breaker may have single trip adjustments, multiple trip adjustments, or solid-state tripping devices and modules. Final time delays and trip settings need to be coordinated closely with the specific equipment it is trying to protect. Settings should be verified by the Electrical Design Group of the Denver Technical Service Center. Medium voltage circuit breakers generally are located in station-service metal clad switchgear or in separate enclosures as unit breakers. Examples are 4,160-Vac station service and and 13.8-kV unit breakers. These breakers may be air, air blast, vacuum, or SF 6. High voltage circuit breakers are located in separate breaker enclosures, either indoors or outdoors. These are oil, air-blast, or SF 6 breakers. Examples are 115- and 230-kV breakers located in the switchyard. Extra high voltage (EHV) circuit breakers are not addressed in this FIST volume. the manufacturer s instruction books. Most breaker maintenance (except infrared scanning) must be performed with equipment de-energized. 15
28 9.2 Molded Case Breaker Maintenance Schedule [Exercising by hand] [6 years] PEB 45 [Routine Maintenance Tests] [6 years] FIST 3-16, section 2.2 PEB Low Voltage (600 Volts [V] and Less [480 V] Draw Out and Fixed Air Circuit Breaker Maintenance Schedule [Preventive maintenance and inspection] [3 years 1 ] FIST 3-16, section 3.1 [Insulation test] [5 years] FIST 3-1, section 4 [Overcurrent fault trip testing and verify settings] [3 years] Reclamation Standard 1 [Breaker should be inspected after interrupting fault current.] 9.4 Medium Voltage ( kv Rated) Air and Air Blast Breaker Maintenance Schedule [Inspection] [Annually] FIST 3-16, section 4.3 [Preventive maintenance] [3 years] FIST 3-16, section 4.3 [Overcurrent trip settings and testing; test all trips] [Contact resistance measurement] [Breaker timing (Motion analyzer)] [Insulation test] (hipot or Doble test power frequency dielectric loss, dc insulation resistance, power factor) [3 years] PEB 47 [3 years] PEB 47 [3 years] PEB 47 [3 years] PEB 47 16
29 9.5 Medium Voltage (601 15,000 Vac) Vacuum Breaker Maintenance Schedule [Record operations counter] [Monthly] FIST 1-11 [Inspection] [Annually] FIST 3-16, sections 4.1 and 4.5 [Preventive maintenance] [3 years] FIST 3-16, sections 4.1 and 4.5 [Insulation test] (alternating current (ac) hipot or Doble test power frequency dielectric loss, dc insulation resistance, power factor) [Contact resistance measurement] [3 years] FIST 3-16, section 4.5 [3 years] FIST 3-16, section 4.5 Breaker timing (motion analyzer) 6 years Reclamation Standard 9.6 Medium and High Voltage SF 6 Breaker Maintenance Schedule [Preventive maintenance (external inspection)] [Record gas pressure and temperature; compare with tolerances and prior readings] [Annually] FIST 3-16, section 5 (needs to be revised) [Monthly] FIST 3-16, section 5 (needs to be revised) [Record operations counter] [Monthly] FIST 3-16, section 5 (needs to be revised) [Visual inspection] [Monthly] FIST 3-16, section 5 (needs to be revised) [Check contact wear] [6 years] FIST 3-16, section 5 (needs to be revised) [Check foundation, grounds, paint] [Check external screws, bolts, electrical terminals tight] [6 years] FIST 3-16, section 5 (needs to be revised) [Annually] FIST 3-16, section 5 (needs to be revised) 17
30 Medium and High Voltage SF 6 Breaker Maintenance Schedule (continued) [Contact resistance test] [6 years] FIST 3-16, section 5 (needs to be revised) [Insulation test] (hipot or Doble test power frequency dielectric loss, dc insulation resistance, power factor) [6 years] FIST 3-16, section 5 (needs to be revised) [Motion analysis] [6 years] FIST 3-16, section 5 (needs to be revised) [Moisture test on gas] [6 years] FIST 3-16, section 5 (needs to be revised) [Verify operation and calibration of temperature and pressure switches and gauges] [Check lube points, heater operation, tightness of terminals, linkages, screws, bolts, latch, linkage, operating mechanism adjustments] [Overhaul breaker with new seals, contacts, nozzles] [6 years] FIST 3-16, section 5 (needs to be revised) [6 years] FIST 3-16, section 5 (needs to be revised) [10 years] FIST 3-16, section 5 (needs to be revised) 9.7 Medium and High Voltage Oil Breakers Maintenance Schedule [Preventive maintenance] [3 years] FIST 3-16, section 4.4 PEB 47 [Visual inspection] [Weekly] FIST 3-16 PEB 47 [Insulation test] (hipot or Doble test - power frequency dielectric loss, dc insulation resistance, power factor) [3 years] FIST 3-2 FIST 3-16 PEB 47 [Contact resistance] [3 years] FIST 3-16 PEB 47 [Breaker timing (motion analyzer)] [Insulating oil, DGA, and dielectric strength] [3 years] FIST 3-16 PEB 47 [Annually] FIST 3-16 PEB 47 18
31 10. Control Circuits 10.1 General The maintenance schedule for control circuits only pertains to circuits of critical equipment as defined in section 1.2 of this document. Control circuits (usually 125 Vdc, 250 Vdc, or 120 Vac) provide the path for all control functions for major equipment in the powerplant. Reliability of these circuits is paramount. Although tested during commissioning, these circuits can become compromised over time through various means: Modifications and construction work that unintentionally break circuit integrity or introduce wiring errors Age, misuse, and inadvertent damage or deterioration of wiring and connections rendering the system nonfunctional Verifying the integrity of the control devices and interconnecting wiring requires a functional test of these circuits. Functional testing of control circuits may be considered completed in the course of normal plant operation. However, control circuits that rarely are used should be functionally tested on a periodic basis Maintenance Schedule for Control Circuits [Functional test control circuits] [2 years] PEB 43 19
32 11. Coupling Capacitors 11.1 General Coupling capacitor/voltage transformers (CCVTs) are instrument transformers that provide a path for communications, metering, control, and relaying equipment without allowing power system frequency energy to pass. These are static devices requiring relatively little maintenance. Except for infrared scanning, maintenance must be conducted with equipment de-energized. This equipment normally is oil-filled and must be checked for oil leaks Maintenance Schedule for Coupling Capacitors [Visual inspection] [Annually] Reclamation Standard [Insulation test] (Doble test for oilfilled only) [6 years] FIST
33 12. Overhead Cranes, Hoists, Elevators 12.1 General Cranes, hoists, and elevators are important to the O&M of the facility. Proper maintenance of cranes and hoists will ensure they are ready for service, which will reduce time and cost of maintaining other equipment Maintenance for Elevators Maintaining elevators is important to the convenience and safety of staff, visitors, and the public. Also, elevators must be inspected periodically by a certified elevator inspector. Maintenance of these types of equipment is important to the safety of everyone. Elevators are required by State law to be certified by a Statelicensed inspector annually in most States. Elevator maintenance is not covered in this document; for complete requirements for required maintenance, see FIST 4-1A, section 6.14, and FIST Maintenance Schedule for Cranes and Hoists Mechanical maintenance of cranes, hoists, and elevators is covered in FIST 4-1A, Maintenance Scheduling of Mechanical Equipment. Only the electrical components are covered here. The definitions and table below are excerpted from the electrical portions of FIST 4-1A. For complete requirements and references, see FIST 4-1A, sections 6.2, , and Startup and Daily Inspections [On each shift, before operating the crane, the operator shall perform the following operations on the electrical controls: Test all controls. Any controls that do not operate properly should be adjusted or repaired prior to the start of any operation. Verify operation of the primary upper-limit switch. The trip setting of the primary upper limit switches shall be checked under no load conditions by inching the block into the limit (running at low speed).] 21
34 Maintenance [Inspect and clean electromagnetic braking system] [Inspect, insulation test, and clean motors] [Annually] [Annually] s FIST 4-1A, section FIST 4-1A, section [Inspect and clean controllers] [Annually] FIST 4-1A, section [Inspect and clean resistor bank] [Inspect and verify settings of hoist-limit devices] [Inspect and torque bridge and trolley conductors and collectors] [Annually] [Annually] [Annually] FIST 4-1A, section FIST 4-1A, section FIST 4-1A, section
35 13. Overhead Distribution Lines 13.1 General Distribution lines carry midvoltage electrical power. The maintenance and inspection of distribution lines and their components are required Maintenance Schedule for Overhead Distribution Lines [Visual inspection] [Semi-annually] Reclamation Standard [Inspect wood poles and crossarms] [12 years 1 ] FIST If minor decay is noted, 6 years. 23
36 14. Electrical Drawings 14.1 General Electrical drawings, especially one-line, switching diagrams, control and protection schematics, and wiring diagrams, are the most important references for the safety and O&M of a facility. Ideally, these drawings will be kept current with all modifications and replacements to plant equipment. Every effort must be made to keep electrical drawings of critical equipment up to date and should be accessible to all O&M personnel to avoid risk to equipment and staff. Critical equipment is defined in section 1.2 of this document. The following drawings should be kept current and available: Critical control and protection schematics Critical wiring diagrams One-line, three-line, tripping, switching diagrams Relay data sheets 24
37 15. Emergency Lighting 15.1 General Reliable plant emergency lighting is essential for personnel safety Maintenance Schedule for Emergency Lighting [Functional test (30 seconds)] [Monthly] PEB 34 [Functional test (1½ hours)] [Annually] PEB 34 25
38 16. Exciters and Voltage Regulators 16.1 General Exciters and voltage regulators comprise excitation systems that provide appropriate direct current excitation for the field of generators and synchronous motors. Excitation systems may be rotating or static Maintenance Schedule for Exciters and Voltage Regulators Components of excitation systems (e.g., transformers, circuit breakers, protective relays, annunciators, and buswork) require maintenance similar to that described in like sections of this document. Exciter and voltage regulator manufacturer s instructions may recommend supplemental maintenance tasks. Automatic voltage regulator (AVR) performance testing ( alignment ) is a specialty, requiring specialized training and unique equipment as well as knowledge of current power system stability requirements. It is recommended that performance testing be performed by qualified personnel. The Hydroelectric Power Technical Services Group ( ) at has qualified staff to perform these tests. [Visually inspect and clean exciter and voltage regulator] [Annually] Reclamation Standard [Voltage regulator model validation] [AVR and power system stabilizer (PSS) performance testing] [5 years] Reclamation Standard [5 years] FIST 1-11, sections and
39 17. Facility Equipment Ratings and Protective Relaying Reviews 17.1 General Facility equipment conditions tend to change over time. A periodic review of these conditions and settings for both normal operation and maximum fault conditions is necessary to ensure management awareness of current plant status and capabilities. For assistance in performing the facilities equipment ratings and protective relay reviews, contact the Hydroelectric Power Technical Services Group ( ) at A Facility Equipment Rating Review is an evaluation of the loading and protective capabilities of all equipment listed below. The Facility Equipment Rating Review shall include the following: Verification of equipment ratings and load requirements and identification of the greatest load limiting component. As stated above, this review must include the complete powertrain and shall include any equipment limitations as well as turbine limitations. Fault current analysis and verification of interrupting capabilities of all protective equipment Maintenance Schedule for Facility Equipment Ratings Review [Arresters] [5 years] Reclamation Standard [Buswork] [5 years] Reclamation Standard [Power cables 5 kv and above] [5 years] Reclamation Standard [Breakers molded case] [5 years] Reclamation Standard [Breakers low voltage (600 V and below) draw out air] [Breakers medium voltage ( kv) air and air blast] [5 years] Reclamation Standard [5 years] Reclamation Standard 27
40 Maintenance Schedule for Facility Equipment Ratings Review (continued) [Breakers medium voltage ( kv) vacuum] [Breakers medium and high voltage SF 6 ] [Breakers high voltage (greater than [>] 15 kv) oil] [5 years] Reclamation Standard [5 years] Reclamation Standard [5 years] Reclamation Standard [Coupling capacitors] [5 years] Reclamation Standard [Distribution lines] [5 years] Reclamation Standard [Fuses] [5 years] Reclamation Standard [Personal protective grounds] [5 years] Reclamation Standard [Switches, disconnects medium and high voltage] [Transformers station and distribution (less than 500 kilovoltamperes [kva])] [5 years] Reclamation Standard [5 years] Reclamation Standard [Transformers instrument] [5 years] Reclamation Standard [Transformers dry type power (500 kva and larger)] [Transformers oil-filled power] [5 years] Reclamation Standard [5 years] Reclamation Standard [Transmission lines] [5 years] Reclamation Standard [Facility energy source for blackstarting the unit] [5 years] Reclamation Standard 28
41 17.3 Protective Relay Settings Review [Protective Relay Settings Review] [5 years] Reclamation Standard 17.4 Arc Flash Hazard Analysis [Arc Flash Hazard Analysis] [5 years] FIST
42 18. Fire Detection and Alarm Systems 18.1 General Fire detection and alarm systems provide indication and warning of fire in the facility. They are crucial to safety of personnel and the public. Correct operation also may minimize damage to equipment by an early response. Regular maintenance of systems in unstaffed facilities is particularly important because O&M staff usually is not present to detect problems Maintenance Schedule for Fire Detection and Alarm Systems [Visual inspection batteries] [Lead acid battery 30-minute discharge and load voltage test] [Nickel cadmium battery 30-minute discharge and load voltage test] [Visual inspection of detection and control equipment (fuses, interfaces, lamps, light emitting diodes, primary power supply)] [Monthly] [Semi-annually] [Annually] [Annually] Reclamation Standard Reclamation Standard Reclamation Standard Reclamation Standard [All circuits functional test] [Annually] Reclamation Standard [Fire extinguisher visual inspection] [Fire extinguisher maintenance] [Monthly] FIST 5-2, section 3.3 [Annually] FIST 5-2, section
43 19. Blackstart Generators 19.1 General Upon complete loss of the power system (blackout), it will be necessary to establish initial generation and begin system restoration at select powerplants. Initiating (main unit) generators are referred to as system blackstart generators and are designated as such in system blackstart restoration plans. They must be able to self-start without any source of offsite electrical power and maintain adequate voltage and frequency while energizing isolated transmission facilities and auxiliary loads of other generators Testing Schedule for Blackstart Generators [Each unit tested to verify it can start and operate without being connected to the system] [3 years] Reclamation Standard 31
44 20. Engine Generators 20.1 General Engine generators that feed critical equipment at powerplants, dams, and other water-related facilities are crucial to the continued operation of these facilities during the loss of the normal power source. The maintenance schedule for engine generators only pertains to those generators associated with critical equipment as defined in section 1.2 of this document. Engine generators must be maintained and tested regularly to ensure they will perform as expected. Engine generators provide essential power to supply critical loads in the event of loss of the normal power source. Spillway or outlet gates/valves may need to be operated for water release purposes with engine generator power. Powerplant critical loads such as sump pumps, fire pumps, and battery chargers also are dependent on reliable power. Engine generators also may be used to power unit auxiliaries and the generator excitation system for blackstart generators assigned to restore the power system after a blackout Maintenance Schedule for Engine Generators [Inspect all emergency power standby systems (EPSS) components] [Inspect and maintain generator set battery] [Exercise generator sets per PEB 28 for a minimum of 30 minutes] [Electrically operate transfer switch in both directions] [Manually exercise circuit breakers] [Operate EPSS at available load for assigned class duration or minimum of 4 hours] [Weekly] PEB 28 [Weekly] PEB 28 [Monthly] PEB 28 [Monthly] PEB 28 [Annually] PEB 28 [2 years] PEB 28 32
45 21. Generators and Large Motors 21.1 General Generators produce electrical energy from mechanical power transmitted from the turbine. Large motors drive pumps to move water. Generators and large motors included in this section are synchronous machines performing the primary function of the power or pumping plant. Small motors are covered in Section 23, Motors (less than [<] 500 horsepower [hp]) Maintenance Schedule for Generators and Large Motors [Visual inspection] [Weekly] Reclamation Standard [Visual inspection and preventive maintenance] [Thrust and upper guide bearing insulation test] [Stator winding and core physical inspection] [Stator winding insulation test] (hipot or Doble test power frequency dielectric loss, dc insulation resistance, power factor) [5 years] Reclamation Standard [Annually] FIST 3-11 [5 years] Reclamation Standard [5 years] FIST 3-1 [Rotor physical inspection] [5 years] Reclamation Standard [Rotor insulation test] [5 years] PEB 29 Stator winding wedge tightness measurements Performed after rotor is removed (particularly if unit has been in operation for years without rewedging) FIST 3-1, section 2 33
46 22. Governors 22.1 General Governors control generator power and frequency output by regulating water flow to the turbine. Governors may be mechanical type or electrohydraulic type having electronic controls. New digital governors substitute digital control circuits for analog electronic controls of older electrohydraulic governors. Governor manufacturer s instructions may recommend supplemental maintenance tasks. Mechanical governor maintenance is fully described in FIST 2-3, Mechanical Governors for Hydraulic Units. Mechanical maintenance requirements for all types of governors are identified in FIST 4-1A, Maintenance Scheduling for Mechanical Equipment. The electrical maintenance schedule below supplements these mechanical maintenance requirements Maintenance Schedule for Governors [Visually inspect and clean governor control systems and cabinets] [Annually] Reclamation Standard [Governor model validation 1 ] [5 years] Reclamation Standard [Control system alignment 1 ] [5 years] FIST 2-3, section 7 1 The Hydroelectric Power and Technical Services Group ( ) at has qualified staff to perform a control system alignment. 34
47 23. Motors (< 500 hp) 23.1 General Motors of this type drive pumps, valves, gates, and fans. They are usually induction motors and are generally less than 500 hp but may be somewhat larger. Critical motors should be tested routinely. The maintenance schedule for motors (< 500 hp) only pertains to those associated with critical equipment as defined in section 1.2 of this document Maintenance Schedule for Motors [Visual/physical inspection] [Annually] Reclamation Standard [Insulation resistance test] [Annually] FIST 3-4, section
48 24. Personal Protective Equipment 24.1 General Personal protective equipment (PPE) is used by maintenance workers to provide protection from hazardous electrical energy. Integrity of this equipment is paramount; therefore, maintenance should be scheduled and accomplished similar to equipment maintenance Maintenance Schedule for Personal Protective Equipment/ Hot Line Tools [Personal protective grounds visual inspection] [Personal protective grounds dc millivolt drop test] [Hot stick visual inspection and cleaning] [Hot stick electrical withstand test] [Gloves, sleeves, leather protectors, blankets, insulating mats, voltage test indicators, insulated and insulating hand tools visual inspection] [Before each use] FIST 5-1; FIST 3-29 [Annually 1 ] FIST 5-1; FIST 3-29 [Before each use] FIST 5-1; FIST 3-29 [Annually 1 ] FIST 5-1; FIST 3-29 [Before each use] FIST 5-1; FIST 3-29 [Gloves air test] [Before each use] FIST 5-1; FIST 3-29 [Insulated gloves electrical withstand test] [Blankets and sleeves electrical withstand test] [Voltage test indicators, insulated and insulating hand tools visual inspection] [Voltage test indicators calibration and certification] [Semi-annually 1 ] FIST 5-1; FIST 3-29 [Annually 1 ] FIST 5-1; FIST 3-29 [Before each use] FIST 5-1; FIST 3-29 [Annually 1 ] FIST 5-1; FIST Test as service conditions require based on events that may have adversely affected the PPE s integrity. 36
49 25. Potheads 25.1 General Potheads provide mechanical support and electrical insulation for cables. Insulating capability of these devices is important to prevent a fault and resulting forced outage. Potheads, being an integral part of a cable, generally are tested when the cable is tested Maintenance Schedule for Potheads [Visual inspection for leaks, cracks] [Insulation test] (Doble ac loss measurement (hot collar) or dc ramp with cable [Annually] FIST 3-1, section 46 [5 years] FIST 3-1, section 46 37
50 26. Relays and Protection Circuits 26.1 General Protective relays provide critical protection functions for all types of plant equipment associated with power generation and power delivery. The protective devices must operate during abnormal plant operating conditions and, in most instances, are the last line of defense to protect equipment from a catastrophic failure. It is critical, then, that these protective devices function properly to adequately protect the associated piece of equipment and that adjustments and calibrations are routinely conducted to eliminate the possibility of the protective device misoperation. Therefore, it is imperative to conduct periodic maintenance testing to validate that the operational parameters of the functional protective device are properly set and coordinated. Protective relays currently in use within Reclamation include electromechanical, solid-state, and microprocessor-based packages. The protection relays contained within this FIST section also shall include the lockout relay to ensure that the proper operational and functional testing of the device and associated control circuits is performed on a regular maintenance interval as prescribed in the associated table. Calibration and maintenance recommendations differ from type to type because of the different design and operating features of the protective device Calibration and Maintenance This process usually includes removing the relay from service to a test environment. Injecting current and/or voltage into the relay and observing the response according to the manufacturer s test procedure verifies the recommended settings. Calibration of electromechanical relays is recommended frequently since operating mechanisms can wear and get out of adjustment. Calibration of solid-state and microprocessor-based relays is recommended less frequently since there are fewer ways for them to get out of calibration Relay Functional Test This process verifies that the protective outputs of the relay (e.g., contact closures) actually operate as intended. This can be accomplished as part of the calibration procedure in most cases, but relay functional testing should be verified according to the prescribed maintenance schedule associated with the particular type of relay being tested Protection Circuit Functional Testing Protective relays operate into protection circuits to accomplish the desired protective action. Similar to control circuits, protection circuit integrity may be compromised by construction, modifications, deterioration, or inadvertent damage. A compromised protection circuit may not provide 38
51 the system and plant protection desired. Periodic functional testing is recommended to ensure the integrity of protection circuits. This process verifies that the entire protective trip path from protective relay through circuit breakers (or other protective equipment) is intact and functional. This requires actually operating the entire circuit to verify correct operation of all components Maintenance Schedule for Electromechanical Relays [Calibration maintenance] [2 years] FIST 3-8, section 12.1 [Relay functional test] [2 years] FIST 3-8, section Maintenance Schedule for Solid-State Relays [Check for relay power supply indicating light] [Weekly] FIST 3-8, section 13.3 [Calibration maintenance] [2 years] FIST 3-8, section 13.1 [Relay functional test] [2 years] FIST 3-8, section Maintenance Schedule for Microprocessor Relays [Check for relay trouble light] [Weekly] Reclamation Standard [Relay functional test 1 [6 years] FIST 3-8, section 14.2 Monitored 2 ] [Relay functional test 1 Unmonitored 2 ] [4 years] FIST 3-8, section Relay functional testing of microprocessor relays shall include the testing of the digital and analog inputs and outputs. 2 Monitored A microprocessor relay is considered unmonitored unless facility monitoring meets all the following requirements: - Real time monitoring and alarm of the relay internal self-monitoring alarm - Real time monitoring and alarm for dc supply or power supply failure - Monitoring of trip coil continuity (either real time or via red light check interval) - If applicable, monitoring of protection telecommunication system (real time or periodically per test interval) - Monitoring dc battery voltage (real time or per test interval) - Verification of relay inputs and outputs (real time or per test interval) 39
52 26.5 Maintenance Schedule for Lockout Relays [Coil continuity red light check] Clean and lubricate (removable cover type only) [Contact operation functional tests] [Daily] FIST 1-11, section 7.3; FIST 3-8, section years PEB 6 FIST 3-8, section 9.2 [2 years] PEB 6 FIST 3-8, section Maintenance Schedule for Protection Circuits [Protection circuit functional tests] [2 Years] FIST 3-8, section 9 40
53 27. SCADA Systems 27.1 General Supervisory Control and Data Acquisition (SCADA) systems are computer-based, real-time control systems. Theses SCADA systems are used to monitor and control water and power operations at a variety of Reclamation facilities. These systems operate continuously and, in many ways, are self-diagnosing; but some maintenance and testing of these devices are necessary to ensure system integrity and identify potential failures. As well, circuits that are infrequently used may require periodic functional testing to ensure they will be operational when the need arises. Although the SCADA FIST 3-33 covers requirements for management, operational, maintenance, and technical support training and documentation requirements, the section listed below will focus only on the requirements associated with maintenance and general operational inspections Input and Output Circuit Functional Testing The functional testing process (also considered points checks) verifies the correct operation of all components within the circuit path. Therefore, functional testing requires activation of an initiating device (in the field), monitoring of the point into the SCADA system for correct operation, and activation of the correct SCADA output point as anticipated Maintenance Schedule for SCADA Systems [Lamp integrity tests] [Monthly] Reclamation Standard [Enclosure physical inspections] [Monthly 1 ] Reclamation Standard [Circuit functional tests (all inputs and outputs)] [SCADA power supplies and uninterruptible power supply [UPS] systems 2 ] [2 years] Reclamation Standard [3 years] Reclamation Standard [Communications testing 3 ] [6 years] Reclamation Standard 1 Physical inspection may be required more often if the SCADA equipment is located in areas that would warrant a more frequent inspection schedule. 2 Station battery systems used to supply power to the SCADA system and equipment shall be tested according to FIST 3-6, Storage Batteries Maintenance and Principles. 3 Communications systems associated with the SCADA system shall be tested in conjunction with the circuit functional tests (points checks) to test all input and output points. 41
54 28. Security Systems 28.1 General The goal of this section is not to duplicate requirements for physical security addressed in other Reclamation plans, documents, or policies but rather to identify and document requirements and procedures to properly operate and maintain the security equipment at Reclamation facilities. Security systems at powerplants are critical for protection of Reclamation personnel, the public, and facility equipment. Most security systems are site specific, including many different manufacturers of cameras, receivers, card key systems, gates, gate controls, and other types of equipment. These systems operate continuously and, in many ways, are self-diagnosing; but some maintenance and testing of equipment associated with these systems are necessary to ensure system integrity and identify potential failures. As well, circuits that are infrequently used may require periodic functional testing to ensure they will be operational when the need arises. Therefore, it is imperative that personnel at each plant understand and follow standard operating procedures and instructions for maintenance and testing the particular installed equipment Maintenance Schedule for Security Systems [Visually inspect and clean all security system control cabinets and camera equipment] [Annually] Reclamation Standard [Alarm circuit functional tests] [Annually] Reclamation Standard [Vehicle barrier and gate control functional tests] [Key card control circuit functional tests] [Camera and monitor control circuit functional tests] [Security system power supplies and UPS systems 1 ] [Annually] [Annually] [Annually] [3 years] FIST 3-6 Reclamation Standard Reclamation Standard Reclamation Standard 1 Station battery systems used to supply power to the security system and equipment shall be tested according to FIST 3-6, Storage Batteries Maintenance and Principles. 42
55 29. Switches, Disconnect Medium and High Voltage 29.1 General When open, disconnect switches permit isolation of other power system components, thus, facilitating safety during maintenance procedures. Disconnect switches may be manually or motor operated and, in some cases, may integrate fuse protection. Preventive maintenance shall be considered synonymous with any type of general maintenance, major maintenance, or overhaul functions to be performed on the equipment Maintenance Schedule for Disconnect Switches [Visual inspection] [Semi-annually] Reclamation Standard [Preventive maintenance] [6 years] Reclamation Standard 43
56 30. Switchyard/Substation Ground Connections 30.1 General Grounding is an essential part of protecting staff and equipment from high potential caused by electrical faults. Grounding conductors of switchyard equipment and gate structures are subject to failure due to corrosion, loose connections, and mechanical damage. Grounding also may be compromised during equipment addition and removal or other construction type activities. Verifying grounding system integrity through periodic testing is an important maintenance activity. The Hydroelectric Power and Technical Services Group ( ) at has qualified staff to perform ground system testing Maintenance Schedule for Switchyard/Substation Ground Connections [Visual/physical inspection] [Annually] PEB 26 [Grounding electrode and substation/switchyard grid tests] [6 years] Reclamation Standard [Ground loop impedance test] [6 years] Reclamation Standard 44
57 31. Switchyards, Substations, and Transmission Lines 31.1 General Switchyards, substations, and transmission lines are used to deliver high voltage electrical power Maintenance Schedule for Switchyards and Substations [Visual inspection] [Semi-annually] Reclamation Standard [Vegetation management] [Annually] Reclamation Standard 31.3 Maintenance Schedule for Transmission Lines [Visual inspection] [Semi-annually] Reclamation Standard [Vegetation management] [Annually] Reclamation Standard 45
58 32. Thermographic Maintenance (Infrared Scanning) 32.1 General Throughout this FIST volume, infrared scanning is recommended as a regular maintenance procedure. Infrared scanning and analysis have become an essential diagnostic tool throughout all industries and have been used in Reclamation to detect many serious conditions requiring immediate corrective action. Several forced outages already have been avoided. Infrared scanning is nonintrusive and is accomplished while equipment is in service. It can be used not only for electrical equipment but also to detect mechanical and structural problems. Therefore, IR scanning is recommended as a regularly scheduled maintenance procedure. Effective IR scanning and analysis require the following: The scanning equipment (IR camera and accessories) must be high quality and correctly maintained and calibrated. The IR camera operator should be trained on use of the equipment. The IR system operator should document results of problems found. Arresters Annually Reclamation Standard Flooded, wet cell, lead acid batteries cells and connections Valve regulated, lead acid (gel cell) batteries cells and connections Vented nickel cadmium batteries cells and connections Battery chargers cables and connections if visible Annually Quarterly Annually Annually Reclamation Standard Reclamation Standard Reclamation Standard Reclamation Standard Fuse Annually Reclamation Standard Buswork and enclosures 5 15 kv if visible Annually Reclamation Standard Buswork insulators if visible Annually Reclamation Standard 46
59 Thermographic Maintenance (Infrared Scanning) (continued) Medium and high voltage cables solid dielectric and oil-filled if visible Annually Reclamation Standard Coupling capacitors if visible Annually Reclamation Standard Molded case feeder and critical control and protection breakers if visible Low voltage (600 V and less [480 V]) draw out air breaker if visible Medium voltage ( kv rated) air and air blast breaker - if visible Medium voltage (601 15,000 Vac) vacuum breaker if visible Medium and high voltage SF 6 breaker if visible High voltage (> 15,000 Vac) oil circuit breaker if visible Annually Annually Annually Annually Annually Annually Reclamation Standard Reclamation Standard Reclamation Standard Reclamation Standard Reclamation Standard Reclamation Standard Exciters and voltage regulators Annually Reclamation Standard Commutator and brushes Annually Reclamation Standard Fuses Annually Reclamation Standard Motors (< 500 hp) Annually Reclamation Standard Switches, disconnect medium and high voltage Annually Reclamation Standard Station/distribution transformers less than 500 kva Annually FIST
60 Thermographic Maintenance (Infrared Scanning) (continued) Instrument transformers Annually FIST 3-30 Dry-type power transformers 500 kva and larger Annually FIST 3-30 Oil-filled power transformers Annually FIST 3-30 Electrical connections Annually Reclamation Standard Switches (disconnect) Annually Reclamation Standard Switchgear Annually Reclamation Standard Transmission lines Annually Reclamation Standard Distribution lines Annually Reclamation Standard 48
61 33. Transducers/Meters/Switches 33.1 General Transducers convert electrical and mechanical data into electrical signals that may be used as inputs into monitoring systems. The accuracy and reliability of transduced signals are of extreme importance when used for metering, alarm, control, and protective functions. Examples of transduced data include: Bearing oil level or temperature read by a meter or scanning equipment Megawatt or megavars as input to the SCADA system Meters indicate, and sometimes record, electrical and mechanical quantities. Some meters also transmit stored data to SCADA or other systems. The accuracy and reliability of meter indication are important to ensure correct power and water systems operation. Switches can be actuated by a number of different devices including, but not limited to, pressure, flow, temperature, position, etc. These switches can be used in protection, control, or alarm circuits. The accuracy and reliability of these switches are important to ensure correct power and water systems operation Maintenance Schedule for Transducers/Meters/Switches [Test and calibrate] [3 years] Reclamation Standard 49
62 34. Transformers 34.1 General Transformers convert electrical power from one voltage level to another. Transformer reliability is essential to the continued delivery of the facility s services Instrument Transformers General Instrument transformers convert power system level voltages and currents to levels safe to feed meters and other low voltage and current devices. Voltage or potential transformers generally have output in the 240/120-Vac range, while current transformers have output in the 1- to 5-ampere range. Voltage transformers may be integral to other equipment or stand alone. Typically, current transformers are integral to other equipment (circuit breakers, transformers) but occasionally may be stand alone (e.g., 500-kV switchyard at Grand Coulee). Over the course of time, instrument transformers (particularly current transformers) may become overburdened with the addition of more devices in the secondary circuit. This may lead to saturation during a fault that may cause the relay to misoperate. Periodical measuring of the secondary burden and comparing it to the rated burden will indicate if this is a problem. Instrument transformer secondary wiring always should be checked for integrity after any work that may have disrupted these circuits. Oil-filled instrument transformers may fail catastrophically and cause hazards to workers if not maintained properly. Any oil leak should trigger immediate Doble testing and replacement planning Maintenance Schedule for Instrument Transformers [Visual inspection] [Annually] Reclamation Standard [Burden measurements] [6 years] FIST 3-8, section 5.1 [Insulation test if oil-filled] (Doble test power frequency dielectric loss, dc insulation resistance, power factor) [6 years] Reclamation Standard [Current transformer excitation test] [6 years] FIST 3-8, section 6 50
63 Maintenance Schedule for Instrument Transformers (continued) [Verify that acceptable instrument transformer output signals are received at the protective relay] [Instrument transformer secondary grounding and insulation resistance tests] [6 years] FIST 3-8 [6 years] FIST 3-8, sections 5.2 and Transformers Rated Less Than 500 kva General Station and distribution transformers generally operate at relatively low voltages and power ratings. They provide step-down power to supply plant auxiliary loads for example, a 480- to 240/120-Vac transformer that supplies power to auxiliary lighting panels. The maintenance schedule for transformers rated less than 500 kva only pertains to transformers associated with critical equipment as defined in section 1.2 of this document Maintenance Schedule for Transformers Rated Less Than 500 kva [Insulation test if oil-filled] (Doble test power frequency dielectric loss, dc insulation resistance, power factor) [5 years] FIST 3-30 [DGA if oil-filled] [Annually] FIST Dry-Type Power Transformers Rated 500 kva and Larger General Dry-type power transformers are air cooled and have no liquid insulation. Typical applications include station service and excitation system transformers. The maintenance schedule for dry-type power transformers rated 500 kva and larger only pertains to transformers associated with critical equipment as defined in section 1.2 of this document. 51
64 Maintenance Schedule for Dry-Type Power Transformers [Visual inspection/cleaning] [Annually] FIST 3-30 [Check fan operation] [Annually] FIST 3-30 [Clean fans and filters] [Annually] FIST 3-30 [Insulation test] (Megger or hipot test) [5 years] Reclamation Standard 34.5 Oil-Filled Power Transformers Rated 500 kva and Larger General Oil-filled power transformers rated 500 kva and above generally deliver power to and from the main units of the facility for example, generator step-up transformers. These transformers usually are located outside the building in a transformer bay or in a switchyard Maintenance Schedule for Oil-Filled Power Transformers [Transformer physical inspection] [Annually] FIST 3-30 [Bushings visual inspection] [Quarterly] FIST 3-30 [Bushings visual inspection] [5 years] FIST 3-30 [Bushings check oil level] [Weekly] FIST 3-30 [Bushings cleaning] [5 years] FIST 3-30 [Transformer and bushings Insulation test] (Doble test power frequency dielectric loss, dc insulation resistance, power factor) [5 years] FIST 3-2 FIST 3-30 [Transformer excitation current test] [5 years] FIST
65 Maintenance Schedule for Oil-Filled Power Transformers (continued) [Insulating oil DGA, physical, and chemical tests] [Annually] FIST 3-30 [Cooling fans inspect and test] [Annually] FIST 3-30 [Oil pumps and motors inspect and test] [Annually] FIST 3-30 [Heat exchangers inspect] [Annually] FIST 3-30 [Conservator and bladder inspect] [Top oil and winding thermometer inspection] [Top oil and winding thermometers calibration] [5 years] FIST 3-30 [Annually] FIST 3-30 [5 years] FIST 3-30 [Oil level indicator operation] [5 years] FIST 3-30 [Pressure relief device] [5 years] FIST 3-30 [Sudden pressure relay] [5 years] FIST
66 35. Transformer Fire Suppression Systems 35.1 General Reclamation generator step-up (GSU) transformers normally contain thousands of gallons of flammable transformer oil. Reclamation requires fire suppression for mineral oil-filled GSU transformers Maintenance Schedule for Transformer Fire Suppression Systems [Visual inspection] [Annually] FIST 3-32, section 10 [Functional test fire suppression system] [Annually] FIST 3-32, section Calibration of Test Equipment 36.1 General It is critical to ensure the proper operation and calibration of test equipment per the manufacturer s recommended schedule. If test equipment has not been calibrated to ensure accurate performance, then it may not be reliable to perform these critical functions accurately. Test equipment includes all equipment that is used to check the calibration or proper operation of other equipment. Calibration is required per the recommended interval in table 36.2 for equipment used to take measurements for test results to show compliance with regulatory requirements. These measurements need to be traceable to National Institute of Science and Technology (NIST) standards. Best practice recommends that instruments used to verify accuracy of plant equipment should be calibrated in accordance with the manufacturer s recommendations. Most manufactures recommend sending test equipment back to the manufacturer for calibration. However, this may not be necessary. For example, a craftsman can verify the accuracy of a relay test set with a calibrated multimeter or similar device to compare the output voltages and currents of the relay test set to the reading of the meter. The craftsman must use a multimeter or similar device that has been calibrated within the required interval. Such test procedures and/or equipment calibration certificates should be documented and filed for future reference. 54
67 36.2 Maintenance Schedule for Calibration of Test Equipment [Calibrate test equipment 1 ] [Annually 2 ] Reclamation Standard [Verify accuracy of test equipment] [Annually] Reclamation Standard 1 It is only necessary to calibrate equipment required to verify the accuracy of a test instrument. A test instrument that cannot be verified as accurate by other equipment must be calibrated according to table If the equipment manufacturer recommends a longer interval, a variance documenting this fact can be put in place to extend the calibration interval. 55
Facilities Instructions, Standards, and Techniques Volume 4-1B Revised November 2005. Maintenance Scheduling for Electrical Equipment
Facilities Instructions, Standards, and Techniques Volume 4-1B Revised November 2005 Maintenance Scheduling for Electrical Equipment U.S. Department of the Interior Bureau of Reclamation Denver, Colorado
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
Operation, Maintenance, and Field Test Procedures for Protective Relays and Associated Circuits
Facilities Instructions, Standards, and Techniques Volume 3-8 Operation, Maintenance, and Field Test Procedures for Protective Relays and Associated Circuits Previously Titled: Field Testing Procedures
The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities
Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING
SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standby generators. 2. Automatic Transfer Switches (ATS). 3. System start-up services. 4.
Best Practice Catalog Generator Switchgear
Best Practice Catalog Generator Switchgear Revision 2.0, 8/23/2012 Prepared by MESA ASSOCIATES, INC. Chattanooga, TN 37402 and OAK RIDGE NATIONAL LABORATORY Oak Ridge, Tennessee 37831-6283 managed by UT-BATTELLE,
DISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.
SAFETY Industrial DESCRIBE hazards and precautions taken to avoid injury in the workplace. Example #1: All of the following are common PPE used to perform maintenance activities EXCEPT: a. Safety Glasses
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing
Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
ELECTRICIAN TRADE REGULATION
Province of Alberta APPRENTICESHIP AND INDUSTRY TRAINING ACT ELECTRICIAN TRADE REGULATION Alberta Regulation 274/2000 With amendments up to and including Alberta Regulation 122/2014 Office Consolidation
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Prime Power Services, Inc. Georgia, Carolinas 800 741 0128. NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010
Prime Power Services, Inc. Georgia, Carolinas 800 741 0128 NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010 NFPA Disclaimer The views and opinions expressed in this seminar are purely
Test Code: 8094 / Version 1
Blueprint Electromechanical Engineering Technology PA Test Code: 8094 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information Electromechanical Engineering Technology PA Blueprint
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Air Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
On-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
I. R. D. T INSTITUTE OF RESEARCH DEVELOPMENT AND TRAINING
I. R. D. T INSTITUTE OF RESEARCH DEVELOPMENT AND TRAINING SYLLABUS SIX MONTHS FULL TIME Repair and Maintenance of Electrical gadgets EFFECTIVE FROM:- UNDER DEVELOPMENT Prepared By: Curriculum Development
City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1
2015 July 17 and Testing, ROPEC Page 1 PART 1 GENERAL 1.1. Scope.1 Equipment replacement and testing for a 44 kv 4.16kV/600V substation: a. Replacement of Insulators as indicated on the drawings in Appendix
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Flood Checklist ACTION TO BE TAKEN BEFORE THE FLOOD SEASON
Flood Checklist The following may serve as a checklist when preparing for a flood. This checklist should be tailored to processes/operations, flood protection equipment and flood potentials at your specific
SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding
Annex-A TECHNICAL SPECIFICATION
Annex-A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 0.4kV (2,000kVA) DIESEL GENERATOR 1 1.0 SCOPE This specification covers the requirements of design, manufacture, delivery
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
Practical Transformers: Operation, Maintenance and Testing
Practical Transformers: Operation, Maintenance and Testing YOU WILL GAIN: 4 hour live, practical online course Saturday, 2 nd May, 2015 8.00AM WST; 10.00AM AEST An understanding of the fundamental theory
Predictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
Federal Wage System Job Grading Standard for Powered Support Systems Mechanic, 5378. Table of Contents
Federal Wage System Job Grading Standard for Powered Support Systems Mechanic, 5378 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 GRADES... 2 TITLES... 3 HELPER AND INTERMEDIATE JOBS... 3 NOTE
Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
Facilities Instructions, Standards, and Techniques Volume 3-32. Transformer Fire Protection
Facilities Instructions, Standards, and Techniques Volume 3-32 Transformer Fire Protection U.S. Department of the Interior Bureau of Reclamation Denver, Colorado January 2005 REPORT DOCUMENTATION PAGE
C.I.8.2 Offsite Power System. C.I.8.2.1 Description
C.I.8 Electric Power The electric power system is the source of power for station auxiliaries during normal operation, and for the reactor protection system and ESF during abnormal and accident conditions.
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
Distribution Voltage Regulators
Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
ECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI
1 Vision 2050 An Asset Management Strategy Jaclyn Cantler Manager, Transmission Planning, PHI 2 Agenda Case for Change About Vision 2050 Status Closing System Design Cybersecurity Interface with distributed/dispersed
Dielectric Withstand Testing in a Production Environment
Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you
EVANS ENTErprises, Inc.
EVANS ENTErprises, Inc. Since 1954 THE LEADER IN ELECTRO-MECHANICAL SALES, SERVICE AND INTERGRATION Our Mission Our purpose at Evans Enterprises is to serve customers by providing increased value of product
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic