Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
|
|
|
- Eugene Evans
- 10 years ago
- Views:
Transcription
1 FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended use there are many features that are built in. For example, walls between areas are sheathed in drywall. The application of drywall to studs as part of a wall can carry a fire-resistance rating when built according to a standard. Likewise, a door and self-closing mechanism may also function as part of the fire separation as long as they are listed and have a fire-protection rating. This is why building permits are required when constructing a building. During the planning stages of a building the process that happens in a building is identified and has to include safety measures for the occupants. In the case where the operation is commercial cooking, a hood and duct system along with suppression systems must be employed. These types of devices must be installed to a standard and be maintained accordingly. In the case where a building s use changes the same systems and equipment must be used specific to the activities. This is why a building permit is required for these circumstances. This is often referred to a change of use. Once the building is occupied the systems and equipment must be maintained. If left unchecked each of these systems will not continue to function as designed. It is the application of the Ontario Fire Code that requires the regular check, inspection or testing of the fire protection systems, measures and equipment. Below is a list of some of the systems, measures and equipment common to most retirement homes, care occupancies and care and treatment occupancies: Smoke Alarms Fire safety Plan Exit Lights Portable Fire Extinguishers Fire Hose Cabinets Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more Commercial Cooking Suppression System Elevators Emergency Lighting Doors and Walls Records The following pages are a schedule of maintenance common to most retirement homes, care occupancies and care and treatment occupancies. These requirements are for convenience only. For accurate information please refer to your approved fire safety plan. It is important to note that if you have a fire safety plan it is a requirement that you know its contents.thoroughly!
2 The Ontario Fire Code requires that checks, inspections, and tests be made of fire protection equipment from time to time. DEFINITIONS: CHECK: TEST: A visual observation to ensure that the device or system is in place and is not obviously damaged or obstructed Operation of the device or system to ensure that it will perform in accordance with its intended operation or function INSPECT: A physical examination to determine that the device or system will apparently perform in accordance with its intended function M - MAINTENANCE PERSONAL S - SUPERVISORY STAFF C - CONTRACTED OUT TO QUALIFIED PERSON(S) O - OTHER (SPECIFY) NOTE: Records of all Tests and Inspections must be kept for a period of two (2) years and made available to the fire department upon request. DAILY DESCRIPTION/ITEM REFERENCE PERSON 1. Exit lights should be checked to ensure that they have not been damaged and that they are illuminated M or S 2. Fire Alarm System, AC Power lamp and Trouble Signal must be checked 3. Voice Communication System, AC Power Lamp and Signal must be checked 4. Temperature of Fire Pump Rooms must be checked M or S M or S M or S 5. Tank Heating equipment and Water Temperature must be checked for Fire Protection Water tanks M or S
3 WEEKLY DESCRIPTION/ITEM REFERENCE PERSON 1. Check Hoods, Filters and Ducts in Ventilation Systems subject to the accumulation of combustible deposits M or S 2. Check the Sprinkler System control valves are open and properly supervised 3. Check that Dry Pipe Sprinkler Air Pressure is being maintained 4. Inspect valves controlling fire protection water supplies 5. Check the water level and pressure for fire protection system pressure tanks 6. Inspect relief values on air and water supplies of Fire Protection tanks 7. Check water level in Fire Pump Reservoirs M or S M or S M or S M or S M or S M or S 8. Inspect and operate all fire pumps Check all components for emergency generator system and operate the generator set under at least 50% of the rated load for 30 minutes M or S M or S
4 MONTHLY 1. Inspect all doors in Fire Separations M or S 2. Emergency Lighting System, Batteries, Units Lamps to be inspected and tested 3. Conduct fire alarm drills in all Care and Care & Treatment Facilities 4. Inspect all portable Fire Extinguishers 5. Test the building fire alarm system and check all components including standby power batteries 6. Test the Voice Communication Systems M or S M or S M or S (1) M or S M or S 7. Inspect all Fire Hose Cabinets M or S 8. Test the Sprinkler System Alarm M or S 9. Inspect the water level in Gravity Tank Fire Protection Water Tanks 10. Smoke alarms shall be maintained in operating condition M or S M or S
5 EVERY 2 MONTHS 1. Test Sprinkler System Central Station Connections M or S EVERY 3 MONTHS 1. Test Fire Fighter s Elevators for proper operation M or S EVERY 6 MONTHS 1. Inspect fire protection systems for commercial cooking equipment 2. Check and clean crankcase, breathers, governors and linkages on emergency generator sets 3. Conduct inspection and maintenance of special extinguishing system 4. Test gate valve supervisory switches and other sprinkler and fire protection system supervisory devices C & C M, S or C
6 ANNUALLY DESCRIPTION/ITEM REFERENCE PERSON 1. Inspect all Fire Dampers and Fire Stop Flaps M, S or C 2. Inspect all Chimneys, Flues and Flue pipes 3. Inspect disconnect switches for mechanical air conditioning and ventilation systems 4. Carry out Maintenance procedures for Fire Extinguishers 5. Conduct a complete test of the building fire alarm system by qualified personnel 7. Conduct a complete test of the building voice communication system by qualified personnel M, S or C C C C C 8. Inspect all standpipe hose valves C 9. Remove and re-rack all standpipe hose 10. Inspect all exposed sprinkler system pipe hangers C C
7 ANNUALLY DESCRIPTION/ITEM REFERENCE PERSON 11. Check all sprinkler heads C 12. Inspect auxiliary drains (Drums Drips) and dry pipe sprinkler system (Each Fall) 13. Inspect dry pipe valve water priming level 14. Inspect and Lubricate Fire Department Connections 15. Conduct sprinkler system alarm test using the hydraulically most remote test valve C C C C 16. Conduct a dry pipe system trip test C 17. Conduct a main drain flow test of the Sprinkler system water supply 18. Inspect Fire Protection Water supply tanks C C 19. Conduct a Fire Pump Flow Test C 20. Inspect and flow test all fire hydrants C 21. Conduct general engine and generator maintenance and engine tune-ups for emergency generator sets 22. Emergency lighting unit equipment duration test equal to design criteria 23. Smoke alarms shall be maintained in operating condition C M, S or C
8 EVERY 2 1. Inspect all Fire Protection water tanks, connected to a non-potable water supply, for the accumulation of sediment 2. Check valve adjustments and torque heads for emergency generator engines C EVERY 3 1. Clean and service injector nozzles and check value adjustments for emergency generator diesel engines EVERY 5 1. Hydrostatic test of dry standpipe system 2. Inspect fire protection water tank, connected to a potable water supply, for accumulation of sediment 3. Check insulation of generator windings C C
9 EVERY 6 1. Replace the extinguishing agent in dry chemical fire extinguishers C EVERY Conduct Hydrostatic testing of dry chemical and vapourizing liquid fire extinguishers as required C EVERY Inspect dry pipe sprinkler system for pipe obstructions. Flush the system when necessary C Not every facility will have all of these fire protection measures or equipment. This document is provided as a guide only and does not replace the requirements as set out in your approved fire safety plan. It is important that a record be maintained for all tests and inspections for the review of a Chief Fire Official.
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
VOLUNTEER FIRE WARDENS
FIRE PRE-PLAN FACILITIES SERVICES VOLUNTEER FIRE WARDENS & EMERGENCY RESPONSE MEMBERS KEELE CAMPUS & GLENDON CAMPUS Ken Wong, P.Eng. SFPE. Mgr., Building Code / Fire Protection Code Compliance Facilities
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO
S A M P L E FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO This sample Fire Safety Plan can be used to assist in developing a Fire Safety Plan for your building. TABLE OF CONTENTS 1. HUMAN RESOURCES
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature
Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)
1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
Fire Safety Plan (No Fire Alarm System):
Fire Safety Plan (No Fire Alarm System): Fire Safety Plan No Fire Alarm System for: (Business Name) (Business Address) I,, have read and understand my responsibilities under this Fire Safety Plan. Signature
Fire Safety Plan University Stadium
Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:
Emergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
(Single Stage Fire Alarm System)
1 Fire Safety Plan (Single Stage Fire Alarm System) Fire Safety Plan Single Stage Fire Alarm System for: (Business Name) (Business Address) Signature of Individual Responsible For Implementing this Fire
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
Commercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
Inspection, Testing and Preventive Maintenance
Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
PART 1 FIRE SAFETY PLAN
Fire Safety Plan This sample fire safety plan has been developed to help owners and managers of small apartment buildings maintain compliance with Section 2.8 of the B.C. Fire Code. The plan is intended
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES
Insert Picture of Building FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Address: Lock Box Location: Fire Safety Plan Location: Approved: Fire Department (dd /mm/yyyy) Building Owner (dd /mm/yyyy) Reviewed
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
Manual Document Page Issue Date TABLE OF CONTENTS
, Manual USQ #15-1163-D ESHQ 1 of 23 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 2 2.0 IMPLEMENTATION... 2 3.0 STANDARD... 2 3.1 Facility Management Support Requirements... 3 3.2 Fire System Discrepancy
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
Environment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
CHAPTER 35 - FIRE SYSTEMS INSPECTION, TESTING, AND MAINTENANCE (ITM)
CHAPTER 35 - FIRE SYSTEMS INSPECTION, TESTING, AND MAINTENANCE (ITM) A. INTRODUCTION... 1 B. CHAPTER-SPECIFIC ROLES AND RESPONSIBILITIES... 1 1. Building Manager... 1 2. Safety Coordinator... 1 3. Office
Fire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 [email protected] Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1
Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In
Sample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
Trace Electric Trace Fire Protection
ELECTRIC AL FIRE PROTECTION ACTIVE IN THE FOLLOWING AREAS: Multi-Unit Residential Apartment Buildings Industrial Commercial Institutional & Long Term Care Facilities Trace Electric Trace Fire Protection
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
Inspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
F.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
Inspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
TECHNICAL ADVISORY BULLETIN
RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are
CMS/Accreditation Surveys The Physical Environment
CMS/Accreditation Surveys The Physical Environment Critical Aspects for 2013 Presenter Robert H. Bartels, CHFM CHSP CHEP SASHE President Safety Management Services, Inc. A program presented by: SAFETY
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 17-12 Fire Safety Plan The purpose of this bulletin is to assist
FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
Ethanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following
I. Introduction. 10 minutes
I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical
FIRE SAFE PLAN SCARBOROUGH CHINESE BAPTIST CHURCH 3223 KENNEDY ROAD SCARBOROUGH, ONTARIO MIV 4Y4
FIRE SAFE PLAN SCARBOROUGH CHINESE BAPTIST CHURCH 3223 KENNEDY ROAD SCARBOROUGH, ONTARIO MIV 4Y4 Revised April 11, 2011 SCBC File: SCBC Fire Safety Plan - 2011 04 11 REVISED.doc Page 1 TABLE OF CONTENTS
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
PART II: New Construction Inspections and Acceptance Testing Procedures
Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128
CITY OF AUSTIN, TEXAS FIRE PROTECTION CRITERIA MANUAL. Table of Contents. Page Number PREFACE 4
CITY OF AUSTIN, TEXAS FIRE PROTECTION CRITERIA MANUAL Table of Contents Page Number PREFACE 4 SECTION 1 INTRODUCTION 1-2 1.1.0 GENERAL 1-2 1.2.0 USER INFORMATION 1-3 1.3.0 SITE PLAN REVIEW PROCESS 1-3
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
Program No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
KODAK VERSAMARK, INC.
KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF
Fire detection, alarm, and suppression systems are installed to:
Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities
Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
RICHARD IVEY SCHOOL OF BUSINESS
Fire Safety Plan Building Fire Safety Plan for: RICHARD IVEY SCHOOL OF BUSINESS D - 451 August, 2013 Western Fire Safety Plan Table of Contents Section 1. Introduction... 3 2. Contact Information... 6
OSHA Office of Training and Education 1
Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and
Flammable and Combustible Liquids. Slide 1 (of 23)
Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids