Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
|
|
|
- Gregory Lyons
- 10 years ago
- Views:
Transcription
1 Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited
2 At the completion of this unit you shall be able to: 1. Utilize section Z of the Safety and Health Hazard Inspection Program Checklist to identify compliant and non-compliant safety behaviors. 2. Identify areas of concern requiring immediate action to mitigate or prevent a possible injury. Please use Slide Show to properly view this presentation!
3 Let s start with a discussion of Electrical Safety.
4 Whenever you work with electrical devices there is a risk of electrical hazards, especially electrical shock. Risks are increased at maintenance and construction sites because many jobs involve electric power tools. Coming in contact with an electrical voltage can cause current to flow through the body, resulting in electrical shock and burns. Serious injury or even death may occur. Electricity has long been recognized as a serious workplace hazard, exposing employees to electric shock, electrocution, burns, fires, and explosions. In 1999, for example, 278 workers died from electrocutions at work, accounting for almost 5 percent of all on-the-job fatalities that year, according to the Bureau of Labor Statistics. What makes these statistics more tragic is that most of these fatalities could have been easily avoided.
5 When an electrical shock enters the body it may produce different types of injuries. Electrocution results in internal and external injury to body parts or the entire body often resulting in death. After receiving a jolt of electricity all or part of the body may be temporarily paralyzed and this may cause loss of grip or stability. A person may also involuntarily move as a result of receiving an electrical shock, resulting in a fall. Internal or external burns may result from contact with electricity.
6 For this reason we inspect and verify the safety of our electrical equipment in our offices, shops, and posts.
7 Section Z deals with the Electrical wiring methods, components and equipment for general use.
8 This section consists of up to 13 items. Let s look at these more closely.
9 1. Junction, switch, and outlet boxes have all openings covered. 2. Extension cords are not used as a substitute for permanent, fixed wiring. 3. Flexible cords and cables are in good condition and properly routed to prevent physical damage and eliminate tripping hazards. 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain) inch working space is maintained in front of electrical panels. Panel schedules are clearly legible and up-to-date.* 6. Electrical disconnects are labeled to identify the equipment it controls, or so located that its purpose is evident.* 7. Insulation on wiring is in good condition. 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. * 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). * 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. * 11. Electrical rooms or enclosures containing live parts/conductors operating at greater than 600 volts are locked and labeled Danger High Voltage. * 12. Holes through which conductors pass will not cause damage to conductor.
10 1. Junction, switch, and outlet boxes have all openings covered. Junction, switch, and outlet boxes are designed to have their covers on them and any other holes that could allow a finger to contact live electrical parts guarded.
11 1. Junction, switch, and outlet boxes have all openings covered. Junction, switch, and outlet boxes are designed to have their covers on them and any other holes that could allow a finger to contact live electrical parts guarded. Underneath these covers are live electrical parts that can cause injury.
12 1. Junction, switch, and outlet boxes have all openings covered. A compliant rating would indicate that all holes were sealed and all covers in place.
13 1. Junction, switch, and outlet boxes have all openings covered. A non compliant rating would indicate that the covers were missing, broken, or that cable holes ( knockouts ) were missing that could allow contact with exposed electrical parts.
14 2. Extension cords are not used as a substitute for permanent, fixed wiring. Extension cords are found in many work locations at this project. Using an extension cord is convenient, but if misused, can create unsafe conditions. Potential hazards include fires from overloaded cords, electrical shock from worn or damaged cords, and trip and fall accidents from unsecured cords. According to the National Electrical Safety Foundation, extension cords should be used only on a temporary basis.
15 2. Extension cords are not used as a substitute for permanent, fixed wiring. Generally, if an extension cord is plugged in for >90 days it is considered permanent wiring and as such is a violation of the electrical code and Project Policy.
16 2. Extension cords are not used as a substitute for permanent, fixed wiring. A compliant rating on this item would indicate that all extension cords found were not being used as a permanent wiring methods.
17 2. Extension cords are not used as a substitute for permanent, fixed wiring. A non compliant rating would indicate that the extension cord had been there for some time and was being used in lieu of permanent wiring methods.
18 3. Flexible cords and cables are in good condition and properly routed to prevent physical damage and eliminate tripping hazards. Extension cords allow us to provide power to the tools and equipment that have cords that are too short. Unfortunately cords on the ground can create tripping hazards as well as create an opportunity for failure of the electrical sheathing (insulation) of the cord. For this reason we require that cords be routed properly.
19 3. Flexible cords and cables are in good condition and properly routed to prevent physical damage and eliminate tripping hazards. A compliant rating would indicate that the extension cords were protected from damage and were not creating a tripping hazard.
20 3. Flexible cords and cables are in good condition and properly routed to prevent physical damage and eliminate tripping hazards. Non compliant rating would indicate that the cords were located where they could be damaged or they could trip someone.
21 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain). The supply of readily available electrical outlets is inadequate in some buildings, especially older ones. To meet power supply needs, extension cords or surge protected power strips are often interconnected, or daisy chained, to readily provide more outlets and/or to reach greater distances.
22 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain). Another common solution is to create a mixed daisy chain, interconnecting extension cords and power strips. However, interconnecting these devices is a violation of Occupational Safety and Health Administration (OSHA) regulations and the National Electrical Code because doing so can cause them to become overloaded, leading to their failure and a possible fire.
23 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain). A compliant rating would indicate that the power strips in use were plugged directly into an permanently wired receptacle, did not connect to another strip or surge suppressors or use an extension cord.
24 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain). A non compliant rating would indicate that the power strips/suppressors were daisy chained.
25 4. Multi-outlet power strips/surge protectors properly connected (no daisy chain). A non compliant rating would indicate that the power strips/suppressors were daisy chained. Also, it would indicate that the power strips weren t being used correctly in other ways as well. Multiple issues here, but the strips are not being used iaw with the manufacturers instructions!
26 5. 36-inch working space is maintained in front of electrical panels. Panel schedules are clearly legible and up-to-date. The minimum requirements for both access and working space for electrical equipment used on circuits 600 volts nominal or less are 30 inches wide and 3 feet deep. Equipment examples include panelboards, switches, circuit breakers, controllers, and controls on heating and air-conditioning equipment. This area cannot be used for storage.
27 5. 36-inch working space is maintained in front of electrical panels. Panel schedules are clearly legible and up-to-date. Also included in this item is the requirement that each panel clearly state what circuits are fed by each breaker. This is called the schedule. Schedule
28 5. 36-inch working space is maintained in front of electrical panels. Panel schedules are clearly legible and up-to-date. A compliant rating would indicate that the access to these disconnects, panel boards, and breaker boxes were clear of nonelectrical equipment. These would include boxes, brooms, garbage cans, chairs, etc. Also the schedule was legible and up to date showing the loads that were served by each breaker.
29 5. 36-inch working space is maintained in front of electrical panels. Panel schedules are clearly legible and up-to-date. A non compliant rating would indicate that the access to these disconnects, panel boards, and breaker boxes were not clear of non-electrical equipment or the schedule was missing or was illegible.
30 6. Electrical disconnects are labeled to identify the equipment it controls, or so located that its purpose is evident. The purpose of this item is to ensure that equipment disconnects are either clearly marked as to the equipment they serve or it is obvious which equipment they serve. An example of obvious would be a disconnect for a machine that is mounted on the machine or the cable connecting the disconnect is obviously going into only that machine.
31 6. Electrical disconnects are labeled to identify the equipment it controls, or so located that its purpose is evident. A compliant rating would indicate that the disconnects were either marked for the equipment they served or they were obvious in their location and function.
32 6. Electrical disconnects are labeled to identify the equipment it controls, or so located that its purpose is evident. A non compliant rating would indicate that the disconnects were either marked for the equipment they served or they were obvious in their location and function. No label???
33 7. Insulation on wiring is in good condition. The purpose of this item is to check on the condition of the insulation on wires of equipment being used. It is not intended as an full scope electrical inspection but rather a visual check on the condition of the electrical cordage being used.
34 7. Insulation on wiring is in good condition. Obviously if you observe a wiring system such as this you ll want to the let the facility manager and your safety professionals know as soon as possible.
35 7. Insulation on wiring is in good condition. Generally, you need to look for damaged cords;
36 7. Insulation on wiring is in good condition. Generally, you need to look for damaged cords; modified plugs
37 7. Insulation on wiring is in good condition. Generally, you need to look for damaged cords; modified plugs obvious improper wiring methods
38 7. Insulation on wiring is in good condition. Generally, you need to look for damaged cords; modified plugs obvious improper wiring methods illegal 3 prong adaptors (suicide plugs).
39 7. Insulation on wiring is in good condition. If you find that the cordage and electrical installations are in good condition then you would rate the item as compliant. Otherwise you would need to rate the item as non compliant or less, ensure that the comment section was filled out, and in all the examples given ensure that the facility manager was informed and took action immediately.
40 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use.
41 Electrical Wiring Methods, Components and Equipment for General Use 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. * Electrical equipment needs to be approved and rated for the environment it is located in. Major incidents have happened in facilities where the equipment was either not approved for use in that environment or had degraded to where it was not longer safe.
42 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. When we talk about electrical equipment in wet areas we mean equipment that will not short to ground or if there is a problem with the device it is designed with safeguards to protect the operator of the equipment from shock. These protections include GFCI s, double insulation, and water proof/weather proof installations.
43 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. We also are concerned that the electrical equipment is appropriate for any hazards that may be present. The Codes and Standards have requirements that electrical equipment in locations of explosive gas, dust, or liquids but be rated for that purpose. Imperial Sugar Factory Georgia, after recent sugar dust explosion.
44 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. A compliant rating would indicate that the electrical equipment was installed correctly and was for the environment it was located in.
45 8. Electrical equipment installed or used in wet or hazard class locations is approved for such use. A compliant rating would indicate that the electrical equipment was installed correctly and was for the environment it was located in. A non compliant rating would indicate that the electrical equipment was not approved for that location. An outside receptacle not protected from the weather.
46 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). Space heaters are used for augmentation of existing heating systems in many of our buildings. These heaters are of many different types and use many different types of energy to create heat. Of concern in this item are the safety of electric space heaters that are used by our personnel.
47 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). If these heaters are not used properly or are not of the correct and listed type then a fire can happen. The photo on the right shows a space heater that had combusible material placed to close to it. Subsequently a fatal fire occurred.
48 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). Must have a tip-over shutdown feature. If a space heater is knocked over, the unit must automatically shut off.
49 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). Must be UL (Underwriters Laboratory), or other Nationally recognized testing laboratory approval (NRTL), and must be labeled accordingly.
50 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). A compliant rating would indicate that the space heater had met these requirements and was being safely used.
51 9. Space heaters are approved by a Nationally Recognized Testing Laboratory (NRTL). A non compliant rating would indicate that the heater was not listed or was not in a safe condition. Flammables within 3
52 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. The purpose of this item is to ensure that personnel are protected from hazards of exposed electrical parts (> 50 VAC to ground) during both maintenance and normal operations. There are two types of hazards we guard against.
53 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. The first is to guard against the possibility of arc flash during maintenance/operations of the equipment with their covers off. Flash Protection Boundary distance from an arc source within which an employee may receive a second degree burn from an electrical arc flash The Flash Protection Boundary is 4 feet for energized electrical equipment up to 600 volts unless otherwise calculated.
54 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. Access into this barrier requires that only qualified persons wearing the prescribed arc flash PPE may approach. The perimeter of this area must be marked so that no unsuspecting employee may enter the area and be at risk.
55 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. The second type of electrical hazard we try to protect against is the possibility of electrical shock. Guarding is provided by locating the energized equipment in rooms, vaults, enclosures, etc, only accessible to qualified persons. We place components in enclosures (panels) that require tools to access the live parts.
56 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. We also can protect exposed live electrical equipment by location on a suitable balcony, gallery, or platform and arranged so as to exclude unqualified persons. We also can guard by elevation a minimum of 8 feet or more above the floor or other working surface. For exposed movable conductors (like on cranes) we require a minimum of 10 feet elevation to protect workers.
57 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. In order to protect personnel from accidental shock there is a 3 ½ foot approach distance from exposed (unguarded) electrical components. This area is restricted to only qualified persons or persons under the direct supervision of qualified person. This is called the limited approach boundary (LAB). If the conductor is an exposed movable conductor then the LAB is 10 feet.
58 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. A compliant rating would indicate that either there were no exposed energized electrical wires, there were sufficient barriers, or there was sufficient boundaries in place to prevent accidental contact.
59 10. Warning signs and/or physical barriers are used to keep unauthorized employees a safe distance from exposed energized electrical equipment/parts above 50 volts. A non compliant rating would indicate there were conditions that could lead to accidental contact with live electrical conductors. Multiple hazards!!
60 11. Electrical rooms or enclosures containing live parts/conductors operating at greater than 600 volts are locked and labeled Danger High Voltage. This item is to ensure that non qualified personnel do not have access to intermediate or high voltage equipment (>600 VAC) This is not a requirement for lower voltage systems (<600 VAC) where building occupants' are expected to have access to low voltage disconnects.
61 11. Electrical rooms or enclosures containing live parts/conductors operating at greater than 600 volts are locked and labeled Danger High Voltage. A compliant rating would indicate that these locations were locked.
62 11. Electrical rooms or enclosures containing live parts/conductors operating at greater than 600 volts are locked and labeled Danger High Voltage. A compliant rating would indicate that these locations were locked. Note these locations also have to be marked as DANGER High Voltage as well.
63 11. Electrical rooms or enclosures containing live parts/conductors operating at greater than 600 volts are locked and labeled Danger High Voltage. A non compliant rating would indicate that these locations were not locked and were accessible to non qualified personnel. Open Door/Unlocked/Unattended
64 12. Holes through which conductors pass will not cause damage to conductor. This item is to ensure that cords and wires going through holes in desks, walls, panels, etc. are protected from cutting and abrasion from sharp edges. Grommets (a desk grommet shown here), stuffing tubes and other devices are used to protect electrical conductors.
65 12. Holes through which conductors pass will not cause damage to conductor. A compliant rating would indicate that the conductors were protected from cutting and abrasion.
66 12. Holes through which conductors pass will not cause damage to conductor. A non compliant rating would indicate that the conductors were not protected from cutting and abrasion.
67 If at any time you have any questions about how to fill out the form or about the items on the form please contact your project OS&H group.
68 Thank you for your time and desire to help us have a safer workplace
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Electrocution Hazards
Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents
Extension Cord Safety Policy
NATIONAL HIGH MAGNETIC FIELD LABORATORY Operated by Florida State University, University of Florida, Los Alamos National Laboratory Florida State University, 1800 East Paul Dirac Drive, Tallahassee, Florida
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
Cal/OSHA Guide to. Electrical Safety. Cal/OSHA Consultation Service Research and Education Division of Occupational Safety and Health
Cal/OSHA Guide to Electrical Safety Research and Education Division of Occupational Safety and Health This guide is not meant to be either a substitute for or a legal interpretation of the occupational
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
Dining Services OSHA Safety Training Program TRAINING RECORD
Dining Services OSHA Safety Training Program TRAINING RECORD Employee Title: This record documents the safety training received by Dining Services employees, including student employees, as required by
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
MANCON Human Resources Workers Compensation 757-457-9312 or 888-892-0787 ext 312 or [email protected]
POLICIES AND PROCEDURES SAFETY MANUAL SAFETY TRAINING Employee Safety Training Maintenance SAFETY TRAINING FOR MANCON EMPLOYEES IN MAINTENANCE/MACHINERY POSITIONS MANCON employees perform a variety of
OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Instructions: This checklist
0150506194 C Limited 2nd through 5th Year Functional Parts Warranty During the 2nd through 5th year,haier will provide functional parts which prove to be defective due to workmanship
OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING
OWNER S MANUAL BIG BEAR VORTEX FAN MODEL #BB-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING PLEASE READ AND SAVE THESE INSTRUCTIONS - 2 - INTRODUCTION TO THE BIG
INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010
ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken
Why Construction Workers are Getting Electrocuted
Why Construction Workers are Getting Electrocuted Michael McCann, PhD, CIH Director of Safety and Ergonomics The Center to Protect Workers Rights [email protected] Causes of Death in Construction, 1992-98
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
Laboratory Safety Guideline Electrical Safety
Introduction The typical laboratory contains a wide variety of electrically-powered equipment including stirrers, shakers, pumps, hot plates, heaters, power supplies, ovens, and electrophoresis equipment.
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK
FIREPLACE HEATER FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK If you have any questions about the operation of your fireplace heater, please contact Crane Customer Care. Toll Free: 888-599-0992
Massachusetts FACE Occupational Fatality Report
Massachusetts FACE Occupational Fatality Report Massachusetts Department of Public Health Occupational Health Surveillance Program Fatality Assessment and Control Evaluation Project Apprentice Electrician
LABORATORY SAFETY INSPECTION CHECKLIST
LABORATORY SAFETY INSPECTION CHECKLIST As part of EH&S's laboratory safety survey program, we have compiled a list of the most common safety problems. This is not a list of every possible hazard, but can
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put it into perspective: Electrocutions can be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, injure 1,400 people, and account
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
B-AIR BLOWER CUB POWER MODEL # CP-1
OWNER S MANUAL B-AIR BLOWER CUB POWER MODEL # CP-1 INTRODUCTION OPERATION SAFETY SERVICE WARRANTY CONTACT SPECIFICATIONS TROUBLESHOOTING READ AND SAVE THESE INSTRUCTIONS INTRODUCTION TO B-AIR CP-1 YOUR
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
Electrical safety and you
Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are
Electrical Safety in the Workplace
Electrical Safety in the Workplace NFPA 70 E Presented by Sabine Mueller What Made Sabine Choose Such a DRY Topic? Ulterior Motive Metso Mueller Engineering has been visiting many scrap yards two or more
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Electrical Hazards. Power Tools. Extension Cords
Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED
Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
2008 Eaton Corporation. All rights reserved.
FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical
Help protect your home, possessions and family.
Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
MODULE 1 INTRODUCTION TO ELECTRICAL SAFETY
INTRODUCTION TO ELECTRICAL SAFETY At the end of this module, you will be able to Recognize key statistics relating to electrical injuries. Recognize OSHA regulations and other standards relating to electrical
100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work
Definitions 100% Rule Work on or near energized parts must be performed only after all participating qualified electrical workers are in 100% agreement on the work to be completed, on the sequence in which
Roadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716
BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: [email protected] www.juicegoose.com 06-06 CONGRATULATIONS
Electrical Safety Program
California State University-Fullerton 800 N. State College Blvd. Fullerton, CA 92831 Prepared by: Paul A Zoubek, CSP, CIH President/Principal Consultant Zoubek Consulting, LLC 3737 Granada Ave. San Diego,
LOS ANGELES UNIFIED SCHOOL DISTRICT DIVISION OF ADULT AND CAREER EDUCATION SAFETY TEST FOR ELECTRICIAN PROGRAM
LOS ANGELES UNIFIED SCHOOL DISTRICT DIVISION OF ADULT AND CAREER EDUCATION SAFETY TEST FOR ELECTRICIAN PROGRAM Service Area: Industry Sector: Energy, Environment & Utilities Class Teacher (Please Print)
Dielectric Withstand Testing in a Production Environment
Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
working surface can be a potential fall hazard.
OSHA s Focus Four Mitigating Jobsite Hazards By Pete Rice, CSP, CIH, REHS Construction is among the most dangerous industries in the country. In 2010, data from the Bureau of Labor Statistics (BLS) indicate
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series
Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Operating Instructions WARNING CONCERNING THE REMOVAL OF COVER: CAUTION: TO PREVENT THE RISK OF ELECTRIC
IMPORTANT SAFETY RULES TO FOLLOW
WARNING FLOOR & CARPET CLEANER Any piece of equipment can be dangerous if not operated properly. YOU are responsible for the safe operation of this equipment. The operator must carefully read and follow
This material was produced under grant number SH-17792-08-60-F-48 Occupational Safety and Health Administration, U.S. Department of Labor.
Big Four Construction Hazards: Fall Hazards This material was produced under grant number SH-17792-08-60-F-48 Occupational Safety and Health Administration, U.S. Department of Labor. It does not necessarily
Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards
Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on
Job Hazard/Safety Analysis For the Office Worker
Job Hazard/Safety Analysis For the Office Worker 1 INTRODUCTION Job Hazard/Safety Analysis for the Office Worker is a partial list of known task performed by the professional office worker. We have placed
Article 10 - ADMINISTRATIVE SECTION
Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the
Vilter motor starter solutions The NEW industry standard in motor starter packages
Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.
SALISBURY ASSESSMENT SOLUTIONS
SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessments - Electrical Safety Training Arc Flash Risk Assessments - Power Systems
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other
2012 NFPA 70E. Ten Most Important Changes. John A. DeDad
2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 [email protected] Abstract The 2012 Edition of NFPA 70E, Standard for
CONTROL OF HAZARDOUS ENERGY (Lockout Tagout)
CONTROL OF HAZARDOUS ENERGY (Lockout Tagout) Many workplace accidents are caused by machinery that accidentally becomes activated while being serviced or maintained. This accidental activation is called
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
Wilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions
Wilo SP Series Submersible Sump Pumps ECS ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc