International Standards for Data Centre Electrical Design. Developed from The Uptime Institute & TIA942 concepts
|
|
|
- Gerald Pope
- 10 years ago
- Views:
Transcription
1 International Standards for Data Centre Electrical Design Developed from The Uptime Institute & TIA942 concepts
2 Benchmarking Data-Centre Quality There has long been the need to be able to measure the quality of a critical facility The quality is usually expressed as Availability of the IT functionality of the facility in terms of number-of-nines - e.g. Three Nines = 99.9% Availability - Note that several engineered and human systems have to contribute to the whole facility and its IT functionality, including the IT hardware and software itself At this top-level nines are usually applied over 5-10 years - e.g % over 5 years = one failure event lasting ~4 hours - It should never be assumed to cover multiple failure events - It should never be assumed to span only one year
3 How good is 99.9%? 44 minutes of unsafe drinking water per month 3 crash-landings per week at Heathrow 3,000 letters lost by The Post Office, every hour 2,000 surgical mistakes in the NHS, every week 9,000 incorrect banking debits per hour 32,000 missed heartbeats, per person, per year - Not all in one go, please. UK numbers
4 Availability Nines: A measure of quality? MTBF 10 years 1 month 1 day MDT 1 hour 30 seconds 1 second Availability % % % Four-Nines = OK? But do you really want a failure every day? In reality it s worse. Assuming the system recovery time is 6 hours: MDT 6+1 hours 6h+30s 6h+1s Availability % 99.17% 74.99%
5 20ms power events in 12 months? How many computer crashes will you accept? Availability Nines MDT 20ms failures 99.0% hrs 15,768, % hrs 1,576, % 4 53 min 157, % min 15, % sec 1, % sec % ms % ms 2 The Nines cannot be applied to power over a single year! Better to use MTBF/MDT for one failure event
6 Site/IT functionality and Availability Your mission critical hardware can only deliver its maximum potential if the whole facility works - Connectivity - Power - Cooling - Fire detection, alarm and suppression - EPO - Maintenance and emergency intervention - Security, internal and external, physical and software attack - Human Error, Systems Training & Facility Management - External disasters earthquake, hurricane, flood, fire.. air-crash
7 The Uptime Institute The Uptime Institute [1] has, for more than 10 years, sponsored research and practical studies into data centre design, operation and resultant resilience and developed a Tier Classification to describe and differentiate facilities from an availability standpoint A White Paper [2] from the Institute (authors of which include the originator of dual power supplies in IT equipment and the Tier system itself) is the basis of this review of the facility and operational concepts The Uptime Institute is a commercial organisation and the guidelines it created are not in the form of a technical standard. However much of the principles and details have been incorporated in TIA-942 (see next slide) [1] The Uptime Institute, Building 100, 2904 Rodeo Park Drive East, Santa Fe, NM 87505, USA [2] Title: Industry Standard Tier Classifications Define Site Infrastructure Performance, Turner, Seader & Brill, The Uptime Institute, Inc
8 American ANSI/TIA Standard In the absence of any more definitive standards ANSI/TIA Telecommunications Infrastructure Standard for Data Centers Telecommunications Industry Association - Standards and Technology Dept, 2500 Wilson Boulevard, Arlington, VA 22201, USA - Follows the same Tier I-IV format and draws heavily on The Uptime Institute publications but extends the detail, especially in connectivity Entirely a USA centric ANSI specification, so can only be used as a guide in other territories - EN/BS etc Specifically for telecom related data-centre environments <2700W/m 2
9 Tier Classification Tier I to IV The classification system takes into account that at least 16 major M&E systems contribute to the overall IT availability (such as fire alarms, EPO etc) - Tier IV represents 99.99% site availability (measured over five years) with the critical systems loaded to a maximum of 90% Each and every sub-system has to meet this table:
10 Site Availability Vs System Availability 16 major sub-systems contribute to TUI Tier Classification To reach a Tier Classification requires all 16 to achieve... Interesting to note: 5xNines UPS = Tier III
11 Tier IV the ultimate in resilience? Fault Tolerant: A site that that can sustain at least one unplanned worst-case infrastructure failure with no critical load impact Concurrently Maintainable: A site that is able to perform planned maintenance activity without shutting down the critical load - Note that it is acceptable that the fault tolerance level will be reduced during maintenance or after the first fault Tier IV Classification only applies to dual power supply loads where complete functionality is obtained with either power supply fed and where the two inputs, in normal operation, share the power demand, as defined by The Uptime Institute s own specification [1] A technical and philosophical argument reigns about Static Transfer Switches for single-cord loads in Tier IV designs - Is that Tier III.5 or IV.5? [1] Title: Fault Tolerant Power Compliance Specifications, v2.0, see
12 Electrical Single Line Diagrams There is no compunction on the designer to strictly follow the designs derived from the Tier Classifications. In many cases compromises will have to be made - The benchmarking function of the Tier system then provides a useful yardstick to measure a system against In the rest of this presentation we only refer to the Electrical systems, just one of the 16+ engineered systems that are required to achieve a Classification rating A particular facility s Tier rating is the lowest of all its system Tier Classifications - Tier IV power +Tier III all other + Tier II cooling = Tier II Facility
13 Tier I = majority of critical power systems A basic single-bus critical power system suitable for single-corded IT loads There is no specific redundancy called for, although it can be argued that the standby generator set is redundant for the grid supply Although only N is specified, the designer should avoid multiple components in powerparallel configuration as it drastically reduces the potential Availability, i.e. N=1 is best Maintenance generally involves supplying the load with non-ups power and an annual load shut-down Availability of Power at load typically 99.95%* *Over 5 years operation
14 Tier II increasing levels of redundancy A single-bus power system suitable for both single-corded loads Redundancy is called for in the standby generator installation to reduce the chance of failure-to-start, but not the mains supply N+1 is specified for the UPS so a high degree of maintenance can be concurrent Load bank connections are mandatory Availability at load typically 99.98%* *Over 5 years operation
15 Tier II with dual-cord loads A single-bus power system suitable for both single and dual-corded loads Redundancy is called for in the standby generator installation to reduce the chance of failure-to-start, but not the mains supply N+1 is specified for the UPS so a high degree of maintenance can be concurrent Load bank connections are mandatory Dual-corded loads (expected minority) should be fed by separate A+B PDU s whilst only the singlecorded loads should be fed via STS s (performing a maintenance function rather than Availability enhancement Note the option of a B UPS, practical when dualcord loads are few Availability at load typically 99.98%* *Over 5 years operation
16 Tier III more redundancy + segregation A dual-bus power system suitable for both single and dual-corded loads Redundancy is called for in the mains supply and the standby generator sets. These must be compartmentalised for lower common mode failure, fire etc N+1 is specified for the UPS so a high degree of maintenance can be concurrent Dual-corded loads should be fed by separate A+B PDU s whilst only the single-corded loads should be fed via STS s (performing a maintenance function rather than Availability enhancement) Note the ability of a rapid upgrade to a B UPS and Tier IV (but don t forget the other systems) An important extra here is the Load Bus Synchronisation. When the STS s can have UPS power on one input and the generator supply on the other it is essential (for the load) to have the two supplies within 30 Availability of Power at the load typically 99.99%
17 Tier IV the Uptime purists configuration Segregation
18 Load isolation breaker and N+? To be able to run the load via the bypass and test the UPS system as a parallel group is a very attractive and useful operational/maintenance feature - The load isolation breaker enables that function Generally that means that between the PDU and the output bus of the UPS system there are at least two MCCB s or ACB s in series - Typical MTBF published at 250,000h (28.5y) with maintenance - Two in series = 125,000h MTBF This negates the advantage of applying any reliability enhancement strategy using N+(more than 1)
19 Distribution limits the UPS Availability Utility/Generator Feed Input Switchboard Maintenance Bypass Output Switchboard Typically 250,000h MTBF each Two in series = 125,000h MTBF N+2 (or higher) UPS does not improve things Bus-voltage Availability depends upon these two switches Single-bus maximum MTBF = 125,000h (14 years), 8h MDT A = 99.99% Dual-bus maximum MTBF = 110,000 years, A = 8xNines
20 N+1 redundant UPS architecture: N? % Redundancy 50% Redundancy 25% Redundancy 600kVA Load 2x 600kVA modules 3x 300kVA modules 4x 200kVA modules R = 10* R = 7 R = 5 Day One only Day One to Two Day One to Three Highest UPS CapEx Scope for load shrink High scope for load shrink High risk of partial load Medium risk of partial load Low risk of partial load High load step Medium load step Low load step 1200kVA of batteries 900kVA of batteries 800kVA of batteries 25% space saving 33% space saving Lower battery CapEx etc *Based on Reliability (R) of a single module = 1
21 Limitation of N in N+1 systems As N grows the potential MTBF of the system decreases (see graph) A 5+1 limit is sensible - Potential MTBF x 0.333r - Doesn t fall too far during N operation - With module of 35,000h and mains of 100h MTBF, A=7xNines at bus which equates to 5xNines at UPS output *
22 Tier Classification is more than just power To truly achieve a Tier Classification means ticking-the-box in 16 subgroups and one of the most important is timely, skilled and proper maintenance capabilities on site - Human error remains the largest contributor group to mission failure, most often when responding to alarms in complex systems The level of cover and skills in site personnel is a major hurdle - 24x7 staffing, factory trained in every product on site, an effective BMS alarm response plan backed up by a 4 hour site response with parts and service engineer to ensure a very high first-time-fix rate For the power system the best (and only cost effective?) solution is to use 24x7 remote monitoring with trained service personnel - Detect and respond before the site personnel - Diagnose alarm and set in motion the right engineer with the right parts
23 Any combination of MTBF/MTTR = Answer
24 Tier I & II can wait for a service engineer
25 Tier III & IV can t
26 Tier IV The Uptime Institute, original version Complete physical segregation of the two power supplies from the grid to the dual-corded load a true Dual-Bus system - 2x(N+1) in every system, maximum 90% load - Concurrent maintenance possible without load shut down and without losing N+1 redundancy - Needs two grid sub-stations (they will be on the same MV-ring or diverse MV-radials) and diverse cable routes into the site - Two mechanical load power switchboards in dual-bus - Note that many engineers question having N+1 on both A & B buses ONLY dual-corded loads - No STS s, no common point of failure except the grid and the load - Simple to operate (idiot proof), fault tolerant, hence reliable With care in design, installation, operation and maintenance, % power Availability possible
27 Not all loads are dual-corded, <30%? Not all loads are dual-corded - Power transparent switching via STS s is a great maintenance tool - Feeding dual-corded loads via STS s reduces Availability to that of the STS itself and negates the principle of dual-bus segregation Classic Tier IV but with STS s for single-corded loads - Essential to have Load Bus Synchronisation Three PDU s in the data-room - A fed from UPS-A for one feed of the dual-cord loads - B fed from UPS-B for the second feed of the dual-cord loads - A/B with STS fed from UPS-A & B for single-cord loads
28 Tier III.5 or IV.5? That is the question!
29 Tier IV requires uninterruptible cooling Even though the TIA-942 specification limits itself to 2700W/m 2 and TUI Tier IV refers to 1560W/m 2 as the limit across a large space they call for uninterruptible cooling for Tier IV The trend for ever-higher IT cabinet loads is well known and single hot-spots as high as 20-30kW/m 2 are no longer rare events making uninterruptible cooling essential E.g. When a 13kW loaded IT cabinet loses all cooling supply the ambient temperature rises from 22 C to 35 C in under 20s (0.65 K/s) - Interesting to note the specified rate-of-change-of-temperature limit in TIA-942 = 5 K/hour ( K/s)
30 The only solution to high W/m 2 = UPS? Three steps to achieve continuous cooling - Keep the air moving, server fans are often sufficient, obtain generator power after seconds and, preferably, have high floor-to-ceiling heights - Keep the fluids moving via UPS driven redundant pumping and, wherever possible, apply Chilled-Water-Storage - If CWS is not practical then power the compressors and heat rejection plant with UPS, retaining 100% cooling capacity on a continuous basis The power required for the cooling system is typically 40% of the kw IT load (10% pumps, 30% compressors) Most engineers would prefer to keep the IT and mechanical loads separate so, separate UPS systems
31 UPS driven cooling alternative solution The mechanical cooling load is predominately motors and variable speed drives, not requiring the high-fidelity voltage and frequency control normally provided by UPS Generic computer grade series-on-line UPS has energy efficiency of 93% to 94% Optionally, Eco-Mode can be selected and the UPS system will operate at >98% - ready to switch back into series-online mode in <0.5ms The 4-5% delta (with no degradation in power for the mechanical load) will save ~2% of the data-centre kwh and carbon emissions, at no additional capital expenditure
32 Eco-Mode = 100% CapEx payback in 2 years
33 System Load Vs Bus-A and Bus-B Load Total load will probably peak at 80% capacity (TierIV=90%) Typically 30% single-cord loads will be present - Worst-case balance 1/3 rd to 2/3 rd on A/B system Typical Bus loads of a fully loaded system are then 36% and 44% of rated capacity (for 99.95% per year) N+1 topology: The higher the N, the higher the module load
34 Partial load efficiency becomes crucial 25-30% load efficiency point is critical in Tier IV Above example: At 25% load = 8% efficiency delta
35 New energy storage developments Vs Tiers? Flywheels, as a battery substitute, always reduce power efficiency - Autonomy 5-15 seconds of flywheel Vs minutes of battery - Smaller footprint although <2% of stored energy - Higher capital cost typically 3-8 times that of an equivalent power battery - UPS system is 100% dependent upon the diesel-engine starting reliability - N+1 generators will need special treatment on paralleling-time Low speed flywheels (steel rotor, bearing load relief via magnetics) - Standby losses x20 that of battery float power (+10kW higher losses per MVA) Medium speed (steel rotor, bearing load relief via magnetics) - Routine bearing changes largely offset battery replacement costs - Standby losses x15 that of battery float power (+8kW higher losses per MVA) High speed (steel or composite rotor, active magnetic bearings) - Standby losses x2 that of battery float power (+1kW higher losses per MVA) - Complex, hence lower potential reliability (not predictability) than a battery - Low power module ratings make high-power data-centre application uneconomic
36 Other contenders in the green debate? Compressed Air Storage - Takes up 200% more floor area than an equivalent VRLA battery - High CapEx, US$1m/MW x10 cost of equivalent VRLA - Higher maintenance costs than VRLA - High standby losses - 35MWh/year higher than battery float power Hydrogen Fuel Cells - Are they a replacement for the generator rather than the battery? - Typically -48V output, needs an energy-bridge to cover starting time - Green? 50% thermal efficiency but what source the fuel? - High CapEx, US$2m/MW x10 cost of diesel genset - Low power ratings for data-centre (but well proven at 10kW) - Embryonic technology for UPS systems, either H-gas or Methanol-Water
37 Secure Power, Always Ian F Bitterlin PhD BSc(Hons) DipDesInn MCIBSE MIET International Sales Director Contact details Tel: +44 (0) E mail: [email protected] Web:
38 Unique to TIA in the detail Tier IV has to have impedance-based battery monitoring systems TIA-942 says that when a system (A or B) is shut down for routine maintenance then the maintenance bypass should be energised by a UPS supply - Not to rely on the dual-corded loads to operate with one feed dead? - TIA-942, Page 123, RH column UPS Maintenance Bypass Arrangement A third UPS (C) system? Space hungry, 0.05% utilisation and a poor return on investment - Chloride solution (red-line on diagram) Cross-feed the output of each UPS system to the maintenance bypass of the alternate system Manual control, padlocked and interlocked isolators, break-before-make, no hot-transfer, no point of common coupling in an auto-mode, sync-check blocking relays across breakers = safe
39 Tier IV+STS s + bypass detail from TIA-942
Designing Fault-Tolerant Power Infrastructure
Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
Building a Tier 4 Data Center on a Tier 1 Budget
Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Capgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
DISTRIBUTED REDUNDANCY:
DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Sovereign. The made to measure data centre
Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA
Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
BICSI 002 / TIA 942 / Uptime
BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM
NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
Diesel Rotary UPS reliability and process availability
Diesel Rotary UPS reliability and process availability Availability in datacenter UPS infrastructures compared Summary The typical characteristics of a DRUPS system are advantageous for the reliability
Data Center Site Infrastructure Tier Standard: Topology
U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th
Data centre experts. Advanced power protection for data centres
Data centre experts Advanced power protection for data centres A robust power protection strategy is critical to successful data centre operations. Uninterruptible Power Supplies Limited (UPSL), a Kohler
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
Data Center Site Infrastructure Tier Standard: Topology
U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West
CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers
CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth
Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
Data Centre Efficiency and the Limitations of PuE
Data Centre Efficiency and the Limitations of PuE Ian F Bitterlin PhD BSc(Hons) DipDesInn MCIBSE MIET MBCS MBIFM Chief Technical Officer Prism Power Ltd, Watford, UK www.primpower.co.uk Prism Power Limited
CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Designed for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
South Datacentre Studley
South Datacentre Studley Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. With 15 years of continual operational life, the Studley
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
A Quick Primer on Data Center Tier Classifications
A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute
UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 [email protected]
UPS Topologies & Architectures Don Lemmon Tubbesing Solutions (214) 690-6866 [email protected] Tubbesing Solutions & Tubbesing Solutions Mike Farrell Mobile No. (214) 355-0493 Tubbesing Solutions Portfolio
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Isolated-Parallel UPS Configuration
Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well
Strategic Data Centre Site Profiles. Data Centre Co-Location London East
Strategic Data Centre Site Profiles Data Centre Co-Location London East Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 5 Contents 1. LONDON EAST...3 1.1 LOCATION...3 1.2 TECHNICAL
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group
Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green
An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green Biography Kenny Green is Technical Support Manager for Uninterruptible Power Supplies Ltd. He is a graduate of Imperial
Redundancy and Reliability for an HPC Data Centre
Available online at www.prace-ri.eu Partnership for Advanced Computing in Europe Redundancy and Reliability for an HPC Data Centre Erhan Yılmaz* 1 Ladina Gilly** 2 * National High Performance Computing
Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM
Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Power protection for data centers
Power protection for data centers Power protection for data centers Data centers are major power users, with larger installations consuming tens of megawatts. As customers are often highly reliant on the
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
plantemoran.com {Data center. } Design standards
plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the
Uptime Institute Tier Standard for Data Centers Facts vs. Myths and Misconceptions
Uptime Institute Tier Standard for Data Centers Facts vs. Myths and Misconceptions Presented by Kenneth ( Ken ) Brill, Founder Uptime Institute [email protected] Agenda Introduction to Tiers Benefits
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
Data Centre Best Practices Summary
Data Centre Best Practices Summary Delivering Successful Technology Rooms 1 END2END s Data Centre Best Practices END2END design Data Centres/Computer Rooms based on 7 major principles: Understanding the
High-Availability Power Systems, Part II: Redundancy Options
Liebert July 2003 High-Availability Power Systems, Part II: Redundancy Options SUMMARY High-Availability power systems require Reliability, Functionality, Maintainability, and Fault Tolerance. A few UPS
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute
Tier Classification of Data Centres Eric Maddison Senior Consultant, The Uptime Institute Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993
CHICAGO S PREMIERE DATA CENTER
CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
RIELLO ELETTRONICA. Master HP
RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES
Increased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
Technical specifications. Containerized data centre NTR CDC 40f+
Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION
Galaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements
The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced
IT S TIME TO EXPECT MORE FROM AN ENERGY STORAGE SOLUTION
S U P E R I O R F L Y W H E E L E N E R G Y S T O R A G E S O L U T I O N S IT S TIME TO EXPECT MORE FROM AN ENERGY STORAGE SOLUTION POWER. REDEFINED. VYCON FLYWHEEL TECHNOLOGY APPLICATIONS: BACKUP GENERATOR
UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN
Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF
Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net
Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet
Eaton 93PM UPS Where aesthetics meet intelligence.
Brochure 100 kw Eaton 93PM UPS Where aesthetics meet intelligence. 93PM features and benefits The Eaton 93PM UPS combines unprecedented and reliability with eye-catching design. A space-saving, flexible
Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date
Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理 1 Agenda 1 2 3 相 UPS 總 覽 Introduction & Overview of 3 Phase UPS 理 解 客 戶 最 大 的 考 量 點 Understanding Top Customer Concerns 3 Galaxy VM 關 鍵 技 術 創
Automation's Modular Containerized Datacenter Solutions
SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
World s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity
Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Evaluating the Opportunity for DC Power in the Data Center
A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Scalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
ATS - Automatic Changeover
ATS - Automatic Changeover Manufacturers of Electrical Switchgear Choosing an Automatic Transfer System Switchgear Systems offer a variety of solutions for multiple supply switching needs. As well as our
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Tier Classifications Define Site Infrastructure Performance
W h i t e P a p e r Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, PE, John H. Seader, PE, Vince Renaud, PE, and Kenneth G. Brill Table of Contents Executive Summary...
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected]
Common mistakes in datacentre planning
Common mistakes in datacentre planning White Paper Last edited: March 2013 Document Control Document Information Title Author Common mistakes in datacentre planning Nick Ewing This document is based upon
Cisco Nexus 7000 Series Power Supply Modules
Cisco Nexus 7000 Series Power Supply Modules Product Overview The Cisco Nexus 7000 Series Power Supply Modules (Figures 1 and 2) deliver fault tolerance, high efficiency, load sharing, and hot-swappable