Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
|
|
|
- Randall Butler
- 10 years ago
- Views:
Transcription
1 Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
2 Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment 50% Source: EYP Mission Critical Facilities Inc., New York Source: EPA Lawrence Berkeley National Laboratory study on data center power allocation: 46 percent used by IT equipment such as servers 23 percent used by HVAC cooling equipment 8 percent by HVAC fans 8 percent by uninterruptible power supply (UPS) equipment losses 4 percent by lighting 11 percent other uses, e.g., misc. electrical losses, support office area, etc. 2
3 Metrics: PUE, DCiE, and Carbon Footprint PUE = Total Facility Power IT Equipment Power DCiE = IT Equipment Power Total Facility Power x 100% Carbon Emissions (kg) = Source: EYP Mission Critical Facilities Inc., New York Energy (kwh) * Carbon Factor (kg/kwh) Assumptions: 10Mw total, 5 Mw IT, 0.08/kwh, 7x24 operation PUE = 10 Mw/5 Mw = 2.0, DCiE = 50% 8760 hours x 0.08/kwh x 10 Mw = 6.9M annual cost of power Example Carbon Factors: Gas G = 0.19 kg/kwh Coal G = 0.35 kg/kwh CO2 = 8760 hours x 10 Mw x.35 kg/kwh CO2 = 30,660,000 kg (about 6759* cars) *based on ~12k miles and ~4536kg 3
4 Why measure? Because you can t manage what you don t measure How do you know your Data Center PUE? Will you be able to comply to to CRC or ASHRAE future guidelines? How do you know how close you are to tripping a breaker? How do you know if you have the power capacity for more IT equipment? How do you know whether you re over cooling or have hotspots? How do you know the impact of any change? 4
5 The Two Paths to increased power efficiency? Optimizing IT equipment Virtualization decommission servers extra savings on cooling power save mode consolidation upgrade technology batch processing during offpeak Control Test and Dev Servers Optimizing Infrastructure avoid overcooling minimize humidification reduce air mixing via hot/cold air separation blanking plates to minimize recirculation raised floor grommets to reduce bypass airflow optimize floor layout (CFD) closely couple supply and returns to the load 5
6 What do you measure? Measurements for Optimising IT equipment Actual IT Load IT Device Department Application IT Utilisation CPU cycles/power usage Actual Business Benefit Department Allocation Measurements for Optimizing Infrastructure Branch Circuit Monitoring Room Temperature Rack Temperature PuE Airflow Humidity 6
7 Where to measure power 7 Uptime Institute, 4 Metrics That Define Data Center Greenness
8 Where to measure temperature Source: ASHRAE, Thermal Guidelines for Data Processing Environments 8
9 What to look for in a solution Accuracy Real measured data vs. assumptions-based calculations, e.g., kwh Metering optimized for real-world conditions vs. lab Sine wave vs. wave with harmonic distortion Depth of data Just current vs. watts, power factor, voltage Building or UPS level vs. individual outlets and IT devices Open, interoperable with other systems Data is portable via standard protocols Easy to deploy, maintain, use Considerations for monitoring both power and temperature Software to collect, trend, report data Sampling/polling frequency Measurement period Forward looking considerations, e.g., CO2 footprint, bill back 9
10 What to do with the data gathered? Measure PUE and compare DC efficiency against peers Find stranded power and optimize existing power capacity vs. nameplate Temperature Deltas Increase room temperature to reduce electricity costs Bill-back by metering kwh to drive behavior Monitor carbon footprint, prepare for carbon trading Improve manageability of DC, and make smarter decisions 10
11 The roadmap to your PUE IT equipment power measurement from Total facility power measurement from Minimum measurement interval Level 1 Basic Level 2 Intermediate Level 3 Advanced UPS PDU Server Data center input power Data center input less shared HVAC Data center input less shared HVAC plus building, lighting, security Monthly/weekly Daily Continuous Source: greengrid.org 11
12 Intelligent rack PDUs new options to measure at the rack for Infrastructure and IT Optimization What can be done with latest intelligent rack power strips? Outlet-level metering to measure device PDU-level metering to measure circuit Temp/Humidity sensors to measure rack environment Thresholds, alerting and notifications Trending and reporting over time Remote switching via IP Standards-based protocols offer easy integration to existing systems Secure Integration with IT Management Systems 12
13 Raritan s project Benefits of Granular Power Measurement in a typical small size company data center Aim: Implement full measurement systems to improve efficiency Location: Raritan Production Data Center New Jersey Process steps Establish baseline Survey nameplate data and take point measurements for all 68 servers First CFD run for baseline Deploy real-time power data collection tools to replace nameplate data. Dominion PX rack PDU: measure and record instantaneous, max, min and avg power for each IT device Measure the branch circuit level power for all infrastructure Deploy temperature sensors 2 per rack 1 for data center room and outside Intake and output of each CRAC Deploy data collection system Raritan Power IQ management software data collection Analyze measured data Conclusions published in Raritan s white paper Power Moves Take action to improve efficiencies and continue to monitor 13
14 What we found Calculating Raritan s PUE 71% of the total average power consumption was used for critical IT equipment 55 percent for servers alone 29% for support services like cooling and lighting Total Power = Support Infrastructure (5.625 kw) + Critical Load (13.68 kw) = 19.3 kw Raritan PUE = 1.4 DCiE= 71%( 1/PUE) 14
15 What we found..nameplate vs. Actual Power Draw Actual consumption much lower than nameplate Consumption varies widely by device/application Average consumption for all devices 39% of nameplate Average max consumption for all devices 48% of nameplate Room for optimization on low end for improving efficiency High end allows room for improving reliability Opportunity to Improve Efficiency Opportunity to Improve Reliability Source: Raritan data center, Feb
16 Analysis and lessons The spread between nameplate and actual emphasizes the need to measure and not wholly rely on de-rated averages. We now understand our power use patterns over time day/month and ultimately season Our PUE was better than we dared assume = 1.4 = 19.3KW/13.7KW? Small business sweating the assets cooling not over engineered! Smaller Rooms engineered to fit limited expansion planned for We don t need to add more servers! Found 45 low utilized or idle devices for possible consolidation/vm We can improve utilization of existing power Average load of all equipment was 38% vs. nameplate We found 8 devices running above 80% of nameplate which we should investigate to improve reliability and reduce risk We had a baseline from which to compare and optimize 16
17 Actions Taken Increased computer room thermostat temperature from 20 C to 23 C. Implemented a virtualization project. Removed 7 servers from the IT environment (7 of 68) Participation in the U.S. Environmental Protection Agency (EPA) ENERGY STAR study by providing our data on a monthly basis. Achieved an 8% saving in total power The Green Grid is assisting the U.S. Environmental Protection Agency (EPA) in developing an ENERGY STAR rating for data center infrastructure. The EPA is collecting data on energy use and operating characteristics from a large number of existing data centers, including both stand-alone facilities and those located in offices and other building types. The collection of sufficient data from data center operators is critical to the development of an ENERGY STAR rating for data center infrastructure. 17
18 Do we stop here? We have understood our use of cooling is relatively efficient and have granular measures and notifications in place that would allow us to increase operating temperature further if we wanted We have accurate data collection to properly assess replacement free cooling options and fully understand payback We are collecting highly granular data on our 61 remaining devices/platforms regarding power used vs. utilisation. We understand the platforms that have idle power performance and will move to replace with better performers with clear ROI at the appropriate time.
19 Thank You
Data Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Data Center Infrastructure Management: How to Optimize Data Center Operations
Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE [email protected] General Manager Raritan, Inc. Question of the Day Question: Would any CFO run
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
EO 13514 and Smart Federal Government Data Center Management
1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Power Management. Raritan Description. http://www.raritan.com/products/power-management/
Raritan Description Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, our hardware
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant [email protected] PANDUIT You Can t Manage What You Don t Measure:
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
EO 13514 and Smart Federal Government Data Center Management
EO 13514 and Smart Federal Government Data Center Management 2011 Raritan Inc. Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Data Center Leadership In the DOE Better Buildings Challenge
Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack An all-in-one solution for efficient data center management, spanning facilities, networking
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
General Recommendations for a Federal Data Center Energy Management Dashboard Display
General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
CenterMind P+ Solution for efficient power management
CenterMind P+ Solution for efficient power management Overview Over last decade DC become significant power consuming facilities Information Technology Equipment (ITE) continue to increase computing capabilities
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Data Center Infrastructure Management (DCIM) Demystified
software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
How High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009
IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities
DATA CENTERS: AN ACCOUNT OF FEDERAL INITIATIVES AND DATA CENTER ASSESSMENTS FOR FACILITY MANAGERS. David Cosaboon, LEED AP O+M
P a g e 1 DATA CENTERS: AN ACCOUNT OF FEDERAL INITIATIVES AND DATA CENTER ASSESSMENTS FOR FACILITY MANAGERS David Cosaboon, LEED AP O+M Facility Engineering Associates, P.C. 12701 Fair Lakes Circle, Suite
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Harmonizing Global Metrics for Data Center Energy Efficiency
Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology
Improving Data Centers Energy Reliability & Efficiency. December 2015
Improving Data Centers Energy Reliability & Efficiency December 2015 Background The challenges Alternative solutions SATEC approach Advantages Cases Summary Data Centers Energy Challenges Worldwide Data
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
8 Intelligent PDUs. Intelligent Power Distribution Units for Data Centers
BRC_PDU_US_B_BRC_IcePack 4/30/13 11:31 AM Page 2 8 Intelligent PDUs Intelligent Power Distribution Units for Data Centers Intelligent Power Distribution Units Siemon s line of intelligent PDUs provide
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Mejora la Eficiencia Operativa en Centros de Datos
Mejora la Eficiencia Operativa en Centros de Datos Marco Antonio Damián Data Center Specialist Panduit Data Center Operational Efficiency Operational Efficiency is done through: Cabinets and racks Cable
Management and Wireless in the Data Center
SOLUTIONS BRIEF Management and Wireless in the Data Center High Performance Wireless Networks Management and Wireless in the Data Center Worldwide demand for new and more powerful IT-based applications,
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Zen Internet Case Study
Zen Internet Case Study About Zen Internet Zen Internet is an independent Internet Service Provider (ISP) that offers a full range of data, voice, and hosting services to businesses and residential users
DATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
Implement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators
Implement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators Awareness of environmental protection issues, has many industry types focusing and pursuing
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
One unbelievable solution for rack-level data center power management. Sentry Power Manager. Solutions for the Data Center Equipment Cabinet
One unbelievable solution for rack-level data center power management. Sentry Power Manager Solutions for the Data Center Equipment Cabinet Sentry Power Manager. The most comprehensive and affordable rack-level
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Best Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Reducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress
Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress Dan Azevedo, Symantec Jon Haas, Intel Jud Cooley, Sun Microsystems, Inc. Mark Monroe, Sun Microsystems, Inc. Pam
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
The necessary convergence of IT and Facilities
The necessary convergence of IT and Facilities Bringing the two groups together under one unified process By Dr. Kenneth Uhlman Director of Data Center Business Development Eaton Corporation Abstract Many
Includes customer case study. February 28, 2013
Advances in Wire-Free Power and Environmental Monitoring in the Data Center Open Architecture API Integration capabilities offer the ultimate flexibility when using intelligent cabinet PDU Technology/
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Australian Government Data Centre Strategy 2010-2025
Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework
Cheat Sheets to Data Center Infrastructure Management
^ Business-wise, Future-drivenTM Cheat Sheets to Data Center Infrastructure Management The Brands You Trust. Table of Contents Introduction...3 How DCIM helps operations...4 How DCIM helps planning...5
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution