Data Centre Best Practices Summary
|
|
|
- Byron Price
- 10 years ago
- Views:
Transcription
1 Data Centre Best Practices Summary Delivering Successful Technology Rooms
2 1 END2END s Data Centre Best Practices END2END design Data Centres/Computer Rooms based on 7 major principles: Understanding the Requirement Understanding the IT element and defining the Room Specifications Designing Modular Data Centres Creating Server Room availability by use of levels of Redundancy Creating the Early Warning System Remotely Managing the Data Centre Building with the right components fit for purpose and resilient Documenting the Facility and Training personnel 1.1 Understanding the Requirement Data Centres are often put together because real requirements were never evaluated or understood and without a Requirements Specification how can a design be created to match those needs. Put together Data Centres will never meet goals or expectations and will continually be a source of failure both operationally and commercially. An Analysis of Requirements determines the exact needs ensuring that budgets are spent wisely and that the final Room meets all specifications. There are many Data Centres for example that are wildly over specified just because initial requirements were not properly defined. These Requirements should be ascertained using joint workshops with all relevant parties and look at all aspects from IT estate, commercial considerations, user/customer service levels, operational structure to physical site conditions. 1.2 Understanding the IT Element and defining the Room Specifications Fitting the Data Centre to the IT it will house is one of the most crucial factors in determining the size of the Data Centre and its overall environmental specifications. It involves: 1. Gaining a list of all known IT equipment to be housed in the Server Room, including: o IT equipment manufacturer, model and quantities for each type o o Numbers of racks and types Racking layouts, END2END may have to review this with the customer as racking some equipment (e.g. blade servers) can cause environmental problems. Too many to a cabinet can seriously affect the potential to cool the equipment and overload the local power distribution. 2. Obtaining from the Manufacturers information on: o Heat Emissions o Power Consumption o Maintenance Service Clearances (horizontal and vertical) o Footprints of Racks 3. Obtaining information on use of: o Dual Power supplies o Multiple Network Connections 4. Gathering information on future equipment predictions, including: o Type of kit (any standardisations) o Predicted amount of kit 5. Create and calculate the Room Environmental profile, including: o Maximum number of racks and types o Total Heat and Power figures o Equipment layout (on room floor) taking into account service clearances, optimum cooling layouts and power distribution system o Overall room size requirements, allowing for any environmental equipment, access requirements and health and safety regulations o Room height required including service clearances and optimal cooling requirements o Positioning of air grilles, taking into account inter-rack cooling distribution systems END2END/ Confidential Page 2 of 13
3 1.3 Designing Modular Data Centres Data Centres that operate well do not intermix activities in different areas (e.g. personnel don t live in areas designed for IT equipment or use it as a corridor to get to another area). It s all about designing a layout based on functional elements and then ensuring that processes (including security) reinforce that layout. The diagram on the following page shows the typical types of room and defines their primary and only functionality. Whilst this is a generic layout, the same rules should apply to the design and construction of all Data Centres. No matter what their exact size or shape The rules still apply! END2END/ Confidential Page 3 of 13
4 Plant equipment separated from Server Room, increases space & eases maintenance Isolates engineering & H/W development activities Centralised, monitoring and management. Continually staffed Specialised functions requiring personnel intervention Secure Entry Point Access and delivery area. Easy access but secure Clean area, limited personnel access. Controlled environment, monitored and managed remotely Ensures extraneous materials do not contaminate operational areas Separate area for IT non-server room operations staff Page 4 of 13
5 1.4 The Server Room The Heart of the Data Centre The Server is the real heart of the Data Centre. It houses all of the IT equipment and if designed correctly is a lights out environment. Lights Out really means that there is no real reason for personnel to have to enter the room (apart from new H/W installations) and this should be an objective for all Server Rooms. Personnel entering and working in a Server Room destabilise the environmental conditions and bring contaminants to what should be a clean environment. There are strict rules for positioning of racks and plant equipment and fit for purpose standards for components that have to be adhered to (e.g. Downflow A/C no wall or ceiling mounted units). Also, to ensure that lights out can be truly achieved, the Server Room has to be equipped with a remote capability for monitoring and management. This means that operations personnel do not have to enter the area to manage the Data Centre effectively and that they can, in fact, be located in a different location altogether. Page 5 of 13
6 1.5 Creating Server Room Availability Creating availability and reducing downtime for IT starts with the Environmental Fabric of the Server Room and the design of that fabric will determine the availability that can be expected from it. In Data Centre Design terminology it is about defining the N factor. Note: N stands for Needs and it defines the basic components required to provide environmental services to the Server Room. An N Room will have just what it needs to supply the IT equipment of the Room. END2END have defined 4 levels of Server Room based on the N factor: Level 1 No Redundancy Level 2 Basic Redundancy Level 3 High Redundancy Level 4 Maximum Redundancy The following table defines those Levels in terms of the N factor and the site downtime and availability potentials of the Environmental Fabric of the Room. Level 1 Level 2 Level 3 Level 4 Power Distribution Single Source Single Path Dual Source Single Path Dual Source Dual Path Dual Source Dual Path Component Redundancy N N + 1 N + 1 N + N Site Downtime per annum 18.5 hrs 10.3 hrs 3.2 hrs 0.8 hrs Availability % % % % The trick when designing any Room s Environmental Fabric is to ensure that the cost v benefits analysis is undertaken. As Component Redundancy is increased, so does the cost and there is always a point where extra redundancy adds extra cost but no real extra value. Page 6 of 13
7 The following defines each Level in more detail: Level 1 No Redundancy (N) Single power source with single distribution path No redundant environmental fabric components (N=number required only) All maintenance requires shutdown of the room Failure of any environmental component will cause disruption to IT Operations Level 2 Basic Redundancy (N+1) Dual power source (e.g. backup generator with single distribution path) Redundant Environmental Fabric components (N+1= number required plus one standby) Some maintenance requires shutdown of the room Failure of most individual environmental components will not cause disruption to IT Operations Level 3 High Redundancy (N+1) Dual power source and dual distribution paths Redundant Environmental Fabric components (N+1, number required plus one standby) Maintenance requires minimal shutdown of the room Failure of individual environmental component will not cause disruption to IT Operations Level 4 Maximum Redundancy (N+N) Dual power source and distribution paths Redundant Environmental Fabric components, plus duplicate configurations (N+N = number required duplicated) Maintenance non disruptive IT Operations generally immune to unplanned events or failures Final Note: Remember the Environmental Infrastructure is the foundation for all of the other levels that make up the Availability pyramid. Once the environment is correctly sorted you can then ensure that the other layers can support the service levels you require. Page 7 of 13
8 1.6 Creating the Early Warning System - Monitoring the Data Centre Monitoring the Server Room Environmental Monitoring of all of the factors in a Server Room is essential to ensure that prompt action can be taken when things are beginning to or have gone wrong. On many occasions the signs of potential failure can be spotted and fixed before any actual problem has occurred. This component of the Data Centre is often seen as optional. It is not! It is one of the most important elements that will ensure continued operation of the Centre. Temp/ Humidity Monitorable/ Manageable Rack PDU's Smoke/ Fire Generator A/C UPS Room Environmental Monitoring System Water Leak Temp/ Humidity Rack EMS Door Security A/C Unit/ UPS with SNMP technology SNMP requests/ Traps IP Network SNMP requests/ Traps Environmental Alerting Stations Data Centre Monitoring/ Management Application Central Operations Personnel Security/ On-site personnel Environmental Dashboard Monitoring the Server Room Racks s, SMS messages, etc. As well as monitoring the overall room, it is wise to monitor individual rack environments for power usage (via monitorable PDU s) and for internal temperatures. In fact, Environmental Monitoring Systems should be included to monitor many or all of the following environmental factors: Page 8 of 13
9 1.7 Managing the lights Out Data Centre A lights out Data Centre can only be achieved if a proper Remote Management infrastructure is implemented within the Data Centre, allowing for management of Servers and network equipment to be accessed and controlled Out-of-band. This means that, for instance, servers could be managed at the bios level and even rebuilt totally from a remote location. Usable from anywhere to access the RMI (e.g. airport, home or in the office) Single Web Browser Interface Virtual Presence Interface Remote Operations Personnel Local Media (e.g. CD, USB memory) Remote Management Infrastructure Relevant building blocks installed at beneficial locations within the organisation Remote Server Management Remote Network Equipment Management Remote Virtual Media Usage Remote Power Management Imbedded Technologies Manufacturer specific &Legacy Tools Page 9 of 13
10 1.8 Building with the Right Components This is one of the commonest areas for mistakes to be made. Many environmental components that are used for office space are not suitable for Server Room environments, the problem is that many suppliers do not understand the needs of sensitive and complex IT equipment and, therefore, it s no wonder that the wrong products are specified. The following table describes some of the major components of a Data Centre and the types of products required. Functions and Benefits Component Function Benefits Electrical Switchgear Uninterruptible Power Supply (UPS) Air Conditioning Units Essential Supply PDU (Power Distribution Unit) - Local power distribution boards installed in the Computer Room to support the room. This Essential Load PDU should be fed from a UPS - These can be duplicated to remove possible single points of failure A centralised Uninterruptible Power Supply provides a short term source of power in the event of a power cut. The level of protection is dependant on the amount of battery autonomy installed. If conditioned, it also provides a high degree of filtering on the electrical supply removing noise, surges, sags and transients To give more availability, these can be paralleled in redundant configurations For medium to large Computer Rooms, it is essential to use either: For low density racks, Close Control Down Flow Air Conditioning Units. They utilise the under floor void (plenum) via strategically placed grills to direct cooling precisely to the IT equipment, cooling up to 8kW For high density racks, Chilled Racks/rack heat exchangers, which work on a per rack basis and can cool 15-20kW Provides a single source of all power to the room and ensures that all equipment is fed from a conditioned supply and in dual mode provides protection against single component failure Many intermittent hardware and software errors can be traced directly back to poor quality power supplies. These difficult to trace errors can be completely removed by the addition of a conditioned UPS (beware: some UPS s, do not provide this ability) It also provides (via batteries) a power source in the event of a power failure. This typically provides sufficient time (normally minutes) for a generator to start or for systems to be shutdown correctly. This can save costly hours recovering systems which have crashed Proper temperature and humidity control reduce the MTBF s for IT equipment significantly These units are designed to provide carefully regulated and conditioned air into a room to enable the temperature and humidity to be controlled precisely to meet defined operational specifications They ensure that IT equipment is cooled not just the space in the room Page 10 of 13
11 Functions and Benefits (continued) Component Function Benefits Fire Detection and Suppression Standby Generator Sets Environmental Monitoring Systems (EMS) Security Access Systems Structured Cabling Systems Sensors throughout the Room detect the presence of smoke or fire. In the event of an incident, suppressant gas is released to extinguish the fire. The gas suppressant is stored in bottles in a liquid state ready for release when the system is activated. For modern rooms the gases used are FM200, Inergen or Argonite Generator A standby power source. The generator is powered by either diesel or gas depending on model purchased and is under the direct control of the site AMF Panel The Automatic Mains Failover Switch (also known as a Transfer load Panel) monitors the condition of the power and automatically switches to the best source of power to meet the parameters programmed A modular system designed to actively monitor alerts from environmental components and to generate alarm signals. It can monitor for issues with temperature and humidity, UPS and Air conditioning failures, fire, water leaks. In fact the majority of potential problems Alert signals can be generated in the form of SNMP traps to Network Management stations, to key personnel or SMS messages These provide protection against unauthorised access to the Computer Room and includes security access Systems and CCTV monitoring systems Cat5e, Cat6 or fibre Structured means laid in proper runs (in basketwork) and connected to patch panels with all racks in the Server Room connected back to centralised patch racks Data cabling should be kept separate from power cables (at least 1m apart). Where they have to cross this should be at 90 degrees to prevent electrical interference of the data signals IT equipment is an expensive asset and even a minor fire can cause severe damage. IT equipment can be irreparably damaged by smoke on its own let alone the full effects of a larger blaze A properly configured Generator set provides a site with complete protection against power failure Combined with a UPS, it ensures that downtime due to power outage is zero Computer Rooms are typically lights out environments. Failure of any environmental component can (in a short space of time) become a serious problem (e.g. even small fluctuations in temperature can cause severe failures of servers). Alerting can inform operators of the need to take action, before serious damage occurs Besides the obvious protection against deliberate sabotage, these ensure that numbers of personnel entering the Computer Room are kept to a minimum. Computer Rooms once set up correctly are best left undisturbed. Research shows that Computer Rooms which have a high level of human interaction are far more likely to fail. A good structured cabling system is one where all cables are in predefined runs and are labelled correctly for easy management Patching should be simple and neat and documentation precise If constructing a new Server Room, it is wise to lay all of the data cables required for the future al the same time. Laying extra cabling later is rarely done in a structured manner. Page 11 of 13
12 Functions and Benefits (continued) Component Function Benefits Remote Management Technologies KVM over IP appliances Serial over IP devices for managing network equipment Power cyclable power strips (PDUs) A combination of management technologies mean that all can be managed from anywhere as long as there is a possible IP connection. Page 12 of 13
13 1.9 Documenting the Operational Facility and Training personnel Given that a great Data Centre has been created, it will all come to nothing unless that Environmental Fabric is documented fully and the Operations personnel (responsible for each of the elements) are trained thoroughly. Such documentation covers a wide spectrum of areas, including, but not limited to: Common Naming Conventions - use meaningful naming conventions and stick to them. It s OK to use friendly names such as Gandalf and Skywalker for the first name but these should be accompanied and associated with meaningful codes which should reflect the type of equipment and location These sorts of conventions ensure that finding equipment for engineers and relating logical maps to actual locations will be much easier Operational Manuals the obvious items but they need to be written and integrated with other operational documentation (otherwise they tend to get mislaid) Physical Schematics full electrical, data cabling diagrams etc. Logical Topologies Logical layouts of Systems, Networks and environmental kit with their interconnections. If possible use Network Management type maps on-line, using the naming conventions to map the logical to the physical Physical layouts The Server Room should have a complete physical layout kept of the position of equipment, its function etc tied back to any Asset/Inventory Management system used Physical Equipment labelling often forgotten but labelling ties the piece of equipment shown on a logical map to where it actually resides. This is essential to ensure mistakes are not made by operations or maintenance engineers or time is wasted trying to actually find the right piece of equipment in the right rack Physical Cable labelling often forgotten again but this is even more disastrous. A patch panel whilst allowing flexibility for connecting equipment is potentially a DR causing hazard. Simple rearrangement of a couple of fly leads can bring a Data Centre to its knees and finding what s exactly happened without labelling is like finding a needle in a haystack Installation Planning layouts Ensuring that racks are laid out effectively to ensure optimum operation (e.g. a rack with too much equipment can be impossible to cool properly) Important Note: All of this documentation is really useful but is only of use if it is kept fully up to date (Change and Configuration management are really important) Page 13 of 13
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
Data Centre Services. JT First Tower Lane Data Centre Facility Product Description
JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security
Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description
JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre
DATA CENTER PHYSICAL INFRASTRUCTURE
Is your datacenter running with maximum performance? Datacenter managers have been challenged to maintain or increase availability, maximize efficiency, and optimize the use of existing capacity. However,
Network Router Monitoring & Management Services
Network Router Monitoring & Management Services Get different parameters of routers monitored and managed, and protect your business from planned and unplanned downtime. SERVICE DEFINITION: NETWORK ROUTER
DATA CENTRE DATA CENTRE MAY 2015
DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level
Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
Data Centre. Design and Project Management. from concept to completion
C O N S U L T I N G Data Centre Design and Project Management from concept to completion Computer rooms are the heart of most businesses today. Yet I see so many that have been patched together, are in
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Portable Energy Efficient Data Centre Solution
Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Sovereign. The made to measure data centre
Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011
Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Managing the Data Center One Rack at a Time
Managing the Data Center One Rack at a Time No Limits Software White Paper #6 By David Cole 2013 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Document Details. 247Time Backup & Disaster Recovery Plan. Author: Document Tracking. Page 1 of 12
Document Details Title: Author: 247Time Backup & Disaster Recovery Plan Document Tracking Page 1 of 12 TABLE OF CONTENTS 1 INTRODUCTION... 3 1.1 OVERVIEW... 3 1.2 DEFINED REQUIREMENT... 3 2 DISASTER OVERVIEW...
Colocation. Introduction. Structure of the service. Service Description
Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security
Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net
Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
Future-Proof the Banking and Finance Data Center
Future-Proof the Banking and Finance Data Center Reinier Dungca Rey Perea Marketing Manager, Southeast Asia and North Asia Manager, Local Technical Support Emerson Network Power Emerson Network Power Philippines
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football
Enterprise Remote Monitoring
Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the
Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure
Georgia Tech Aerospace Server French building Server Room Server Room Policy Handbook: Scope, Processes and Procedure Version History Version/Status Release Date Comments 1.1/Draft 1.2 1.3 1.4 1.5 1.6
Tough Decision: On-Line or Line-Interactive UPS?
W H I T E P A P E R Tough Decision: On-Line or Line-Interactive UPS? How to Choose the Right Protection for Your Network Executive Summary In today s data-driven, technology-dependent world, no organization
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 [email protected] www.telecitygroup.se
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Essential NCPI Management Requirements for Next Generation Data Centers
Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Data Center Management
Data Center Management How Cisco IT Operates, Manages, and Protects Its Data Center A Cisco on Cisco Case Study: Inside Cisco IT 1 Overview The Cisco IT Operations Data Center on the San Jose, California
System integration oriented data center. planning. In terms of ATEN's eco Sensors DCIM solution
System integration oriented data center planning In terms of ATEN's eco Sensors DCIM solution 1. Introduction The reliability of an enterprise data center servicing either external or internal clients
Documenting and Managing Infrastructure Connectivity
Documenting and Managing Infrastructure Connectivity David Cuthbertson Square Mile Systems Ltd [email protected] www.squaremilesystems.com Square Mile Background Develop toolsets,
Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive
Co-Location Services Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive optimum performance 24x7. SERVICE
Technical specifications. Containerized data centre NTR CDC 40f+
Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
by Metagyre, Inc. September 27, 2010
NewCo Data Center Assessment by September 27, 2010 Metagyre Account Manager Contact Paul Thompson 1249 NW Arcadia Ct. Suite 300 Poulsbo, WA 98370 voice - 360 697-3386 fax 360 697-6676 [email protected]
MARULENG LOCAL MUNICIPALITY
MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details
South Datacentre Studley
South Datacentre Studley Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. With 15 years of continual operational life, the Studley
Datacentre Reading East 2 Data sheet
Datacentre Reading East 2 Data sheet Data sheet Datacentre Reading East 2 Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the
Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity
Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery
Introducing Tripp Lite s PowerAlert Network Management Software
Introducing Tripp Lite s PowerAlert Network Management Software What Can It Do For You? Improve the accuracy and efficiency of the network operations staff in the context of power and environmental management
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service
vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
National Aluminium Co. Ltd.
National Aluminium Co. Ltd. [NALCO] EXPRESSION OF INTEREST FOR DATA CENTRE CO-LOCATION SERVICES Address for Communication The Project Manager ERP P/1, NALCO BHAWAN NAYAPALLI, BHUBANESWAR 751061 E mail:
Blade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
Standardization and modularity as the foundation of data center UPS infrastructure
ABB White Paper Standardization and modularity as the foundation of data center UPS infrastructure - ABB Power Protection Product Group Doc name: Advantages of modular and standardized UPS Date: 19.11.2013
CONTENTS. Security Policy
CONTENTS PHYSICAL SECURITY (UK) PHYSICAL SECURITY (CHICAGO) PHYSICAL SECURITY (PHOENIX) PHYSICAL SECURITY (SINGAPORE) SYSTEM SECURITY INFRASTRUCTURE Vendor software updates Security first policy CUSTOMER
DATA CENTRE DATA CENTRE
DATA CENTRE DATA CENTRE v. OCT 2014 DJ CENTRAL DJ Central Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level of service
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER
Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Introducing UNSW s R1 Data Centre
Introducing UNSW s R1 Data Centre R1-DC Our New High Density Data Centre Right here Right now - Welcome to our newest UNSW Data Centre R1-DC R1 Location on UNSW Randwick campus. Keeping it in the family
ASX Australian Liquidity Centre. ASXCoLo
ASX Australian Liquidity Centre ASXCoLo Australian Liquidity Centre Location The ASX Australian Liquidity Centre is located at: Gore Hill Business Park 219-247 Pacific Highway Artarmon. NSW, 2064 The location
Server Monitoring & Management Services
Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
BELLE VUE MANCHESTER DATA CENTRE
www.iracknet.com 0843 557 5712 [email protected] www.iracknet.com BELLE VUE MANCHESTER DATA CENTRE 02 BELLE VUE MANCHESTER HIGHLY ADVANCED DATA CENTRE PURPOSE BUILT TO DELIVER UNRIVALLED FLEXIBILITY
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected]. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS [email protected] Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction
Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Rules of Conduct and Safety
Rules of Conduct and Safety ETISALAT DATA CENTER RULES - V2.4 Contents Definitions... 2 Introduction... 3 Safety Instructions... 3 Upon entering the Data Center... 3 Privacy Notice / Camera Surveillance...
minova technology electronics
2015 Telemetry, Remote Monitoring and Control Products & Services Server Room Monitoring Depot & Facility Condition Monitoring Cold Storage, Cold Chain Tracking Metering & Pre-paid Systems Management www.tech.com
AIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
Eni Green Data Center - Specification
Eni Green Data Center - Specification Green IT Adopting the principles of sustainable development is one of the key missions in the field of information technology today. 2% of the world s CO2 emissions
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
Revolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
LDeX Group. Colocation Solutions for High Expectations
LDeX Group Colocation Solutions for High Expectations LDeX1 Units 8 10 The Oxgate Centre, Oxgate Lane, London, NW2 7JA +44 (0)845 370 3510 [email protected] www.ldexgroup.co.uk 5 M VA LDeX1 delivers
Powerful Dedicated Servers
Powerful Dedicated Servers Our dedicated servers offer outstanding performance for even the most demanding of websites with the latest Intel & Dell technology combining unparalleled server specification,
Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions
Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
HealthcareBookings.com Security Set Up
HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of
Frankfurt Data Centre Overview
Technical Services Briefing Document Frankfurt Data Centre Overview Version 2.1 Contents Introduction... 3 TelecityGroup Data Centre in Frankfurt... 4 Data Centre Characteristics... 4 Technologies in Use
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
How To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
Datacentre South Gyle 1 Data sheet
Datacentre South Gyle 1 Data sheet Data sheet Datacentre South Gyle 1 Find us South Gyle Datacentre With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations,
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
How To Use Rittal'S Rizone
RiZone Data Centre Infrastructure Management Enclosures Power Distribution Climate Control IT INFRASTRUcTURe SOFTWARE & SERVICEs RiZone Data Centre Infrastructure Management What can the RiZone Data Centre
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical