Data Centre Efficiency and the Limitations of PuE
|
|
|
- Sabina Evans
- 9 years ago
- Views:
Transcription
1 Data Centre Efficiency and the Limitations of PuE Ian F Bitterlin PhD BSc(Hons) DipDesInn MCIBSE MIET MBCS MBIFM Chief Technical Officer Prism Power Ltd, Watford, UK
2 Prism Power Limited delivers high integrity Critical Power Solutions. This document is one in a series of white papers prepared by Prism Power. If you would like further information, please contact Prism Power on +44 (0) or visit Copyright 2009 Prism Power Limited. All rights reserved. The information contained in this document represents the current view of Prism Power Limited on the issues discussed as of the date of publication. Because Prism Power Limited must respond to changing market conditions, it should not be interpreted to be a commitment on the part of Prism Power and Prism Power cannot guarantee the accuracy of any information presented after the date of publication. This white paper is for information purposes only. Prism Power Limited makes no warranties, express or implied, in this document. Prism Power Limited may have patents, patent applications, trademark, copyright or other intellectual property rights covering the subject matter of this document. Except as expressly provided in any written licence agreement from Prism Power Limited the furnishing of this document does not give you any licence to these patents, trademarks, copyrights or other intellectual property. Prism Power Limited registered in England and Wales number Head office: Prism Power Limited, Caxton Court, Caxton Way, Watford Business Park, Watford, Hertfordshire WD18 8RH
3 Introduction Even before electrical energy costs started to climb in 2001 data-centre designers were thinking about the relationship between the power consumed by the IT hardware itself and the total power absorbed by the containment facility. The driver for that process in the dot.com boom was the apparent shortage of power capacity in various internet-hub locations such as London, Dublin, Amsterdam, Paris and Frankfurt and the desire to maximise the power available for the IT hardware. The thrust of the thinking then, as now, was 1 focussed on the Coefficient of Performance of the cooling system and the power required to recharge the UPS after an outage. At that time the IT hardware costs and the facility construction costs were dominant and the concentration was on the space efficiency; the ratio of raised floor area to total built area. However, since the dot.com crash in 2001 key drivers have influenced the discussions around efficiency : Construction costs have only risen with inflation IT hardware costs have fallen dramatically per unit of performance Energy costs have generally doubled and are continuing to rise far ahead of inflation Grid capacity has become more difficult to source Corporate entities have adopted green as a mantra Data-centre vendors all want to parade their green-credentials Power costs have become the largest item in the OpEx budgets of data-centre owners and, for the first time, now exceed the IT hardware cost over its average service-life of 3-4 years. This has resulted in the pursuit (both real and spun) for higher efficiency, sustainable, green designs. PuE, DCiE et al The basis of most improvement programmes involves the old adage you can t control what you don t measure so the development of a common measurement tool for data-centre energy efficiency has been 2 high on many agendas. Despite their various heritages all of the definitions come down to some form of the relationship between IT power and total site power taken from the electrical grid. The most commonly accepted definitions are the PuE (Per Unit Efficiency) and the DCiE (Data Centre Index of Efficiency): PuE is the Site power divided by the IT power. E.g. Typically ranges from a good 1.6 to a poor 3 so that 1 is (unobtainable) perfection and the number gets larger as the efficiency gets worse DCiE is the inverse of PuE, therefore the output ranges from 0.6 to 0.3 with the numerical result getting smaller as the efficiency declines 1 2 The mechanical cooling system does the job of capturing the heat generated by the IT equipment and transferring it to the outside for rejection. The Coefficient of Performance (CoP) expresses the efficiency of that process. E.g. If it takes 400W of power to remove 1000W of heat the CoP is 0.4 or 40%
4 There is still debate about how the two input power are measured (and where) but there is general agreement that the method is valid and valuable if carried out on a single facility to monitor progress between phases of improvement. For example a particular facility might be measured for IT power (the sum of all the PDU inputs) and total mains power just before a phased programme of works such as: Blanking plates, hole-stopping & remove redundant under-floor cables to manage air-flow Hot-aisle/cold-aisle layout implementation with cold-aisle (or hot-aisle) containment Raised room set-point temperature with raised chilled-water temperatures Implementation of free-cooling equipment At the end of each work-phase a re-measurement and resultant new PuE calculation will be a very useful exercise indeed it will also provide data for the facilities EU Energy Efficiency rating. In this respect (using PuE or DCiE) as a measurement of relative improvement the process is a relevant and valuable tool. There are however some basic flaws even at the lowest level: A data-centre with a large office (for Disaster Recovery for example) as part of the facility will have any efficiency gains within the data-centre masked in the roll-up of the site numbers and appear to have a high PuE (poor) unless the data-centre load can be measured in isolation A data-centre which uses other forms of energy (other than mains electricity) will appear to have a very good PuE. For example: Cooling systems powered by natural gas (absorption chillers) can have a PuE below 1.2 because nowhere in the PuE calculation is the energy content of the natural-gas On-site photovoltaic solar panels (for small facilities) On-site production of electricity & heat via co-generation, particularly using sustainable fuels such as bio-diesel, wood-chip, straw or municipal waste A data-centre with free-cooling installed can be measured in winter and then compared with summer a measurement probably showing a marked improvement A lightly loaded facility (perhaps new) will appear to have a very poor PuE which will increase as the load grows with no improvement action on the part of the operator The measurement and calculation of PuE is in the hands of the facility owner/operator and, so far, there is no regulatory certification body, and so, just like Income Tax, self-certification is open to individual interpretation. 3 Black-box thinking? Having established that the use of PuE is a valid (and valuable) tool for measuring progress in a particular facility we have now to turn to its principle flaw. 3 Power Distribution Units in the data-room
5 For a corporate entity the whole issue of energy efficiency can be viewed two ways: Improving energy efficiency saves money and happens to be green and, as long as it does save money, we want to be green We want to be green, even at a premium capital cost So far, in the UK and USA at least, most businesses fall into the first category even to the extent that a Return-on-Investment of longer than 2 years for higher cost capital plant will often be rejected. However, there is a growing desire to appear green, driven by cost saving and, as the cost of energy spirals upwards, this will increase. But what does green really mean? It means sustainability in particular, for power, it means no (or lower) carbon footprint. However there are three steps to sustainability that have to be taken in precise order and efficiency is the second step, not the first: 1. Reduce the consumption of the process 2. Improve the efficiency of the process 3. Source the energy from sustainable (renewable) sources In this way it can be seen that building an inefficient data-processing facility and powering it from local hydro-power is not truly sustainable it is better considered to be a waste of a valuable carbon-free resource. So, to be truly green and sustainable we need to address the matter of the load consumption before we worry about the efficiency. It is not within the scope of this paper or the electrical system designer to be concerned about the value and content of the data being processed that is far more philosophical discussion about modern society so we have to accept that the electrical input to the load is our starting point. The power consumed by a micro-processor based load falls into three segments The power consumed by the core of the micro-processor, typically W each The power dissipated by the on-board power supply, typically 30-50W per processor The power required to drive the cooling fans to enable the heat to be rejected, typically 20-30W per processor In this way we can see that each core consumes between W. Add all the processors up in a fully populated blade server chassis (often >30 cores), along with the usual hard-drive motors and controllers, and it is easy to reach 5kW for a server in a 7U space. Of course, every Watt that enters the load terminals is rejected as heat and so it is possible to criticise the concept of PuE because it ignores the fundamental efficiency of the load itself. It would be more logical (but extremely difficult) when calculating the PuE to consider the power consumed by the cores and take the power-supply losses and fan power as part of the site-power in that way the pressure for high efficiency would be extended to the switched-mode power-supply and the internal cooling. That said, 4 4 Also has the undesirable characteristic of consuming >70% of the maximum power when inactive
6 it could also be considered that the performance of the micro-processor itself (in terms of instructions/ second/watt etc) is a fundamental part of the evaluation process. The immediate conclusion is that PuE ignores the efficiency of the load, but shouldn t. Since low-power cores are available, along with high-efficiency power-supplies and variable speed low-power fans, this omission is fundamental. The client should start with low-power high-efficiency servers and then proceed to considering the facility s PuE but he/she will never be praised for the substantially lower power consumption of their data-centre because the PuE will ignore that extra effort and, usually, investment. An holistic view of energy consumption As we have seen in the previous section it is not just the part of the electrical energy stack that the PuE methodology covers that matters not forgetting the input of other fuels like natural-gas for chillers etc. The diagram, below, illustrates where the majority of the losses occur in a data centre. Whilst the PuE covers only 54% of the whole energy stack between power-station and IT load terminals we should be aware of the elements that can vary widely and dramatically affect the overall picture: The chip-set itself; with low-power chips now available and more forecast down to 40% of current power-draw The on-board switched-mode power-supply; improving from 60% to 85% efficient The mechanical cooling system; here shown totalling 30% (CoP = 0.6) but often as high as 50% for poorly designed air-flow and can be as lower than 20% (CoP = 0.4) Whilst it is good that the PuE captures the mechanical cooling system the load itself can be halved by careful selection and specification of hardware.
7 Redundancy and the problems of partial load It will be of no surprise to the engineering designer that it is not possible to construct commercially attractive plant that does not have peak efficiency at a particular load and this certainly applies to datacentre plant such as UPS, chillers, room air-conditioning units, IT hardware power-supplies etc. Most plant is designed to run near peak efficiency usually in the upper quartile of load. However data-centres have two features that result in low loads on the critical equipment: They are rarely fully loaded for the majority of their service lives They are designed for reliability with high levels of redundancy built-in to avoid down-time The combination of both factors often leads to loads on plant of less than 15% - where no plant is energy efficient. For example take a Tier IV UPS system with A+B paths and 2+1 redundancy in each path. At a room load of 40% each UPS module runs at less than 14%. Compare this to a Tier I system (single path with no redundancy) of the same capacity the UPS runs at 40% load, not an ideal set-point but at least 20%age points better in operating efficiency. Maybe unsurprisingly are we to infer that high-reliability (via redundancy) is the enemy of high-efficiency and, hence, of PuE? Conclusion: There is danger in PuE becoming a marketing tool for facilities Like the exaggerated claims for Tier Classification (all self-certified) the claims for PuE (or DCiE) have started to appear in sales-pitches for data-centre space. So the following caveats should be considered: These claims are made for centres not yet built and must assume that the centres will be >75% occupied from the day the doors open. The PuE of a new centre will be poor until the systems are loaded up Using PuE as a yard-stick to compare different locations is highly dubious You cannot compare the PuE of a Tier I facility with a Tier IV (or Tier II or III). If you do then you will accept that energy efficiency overrides reliability and availability in your data-centre It is a valid tool for recording improvements in one centre but even then is open to abuse and misinterpretation Always start with selecting energy-efficient IT hardware with low-power micro-processors
8 Ian F Bitterlin PhD BSc(Hons) DipDesInn MCIBSE MIET MBCS MBIFM Chief Technical Officer Prism Power Ltd, Watford, UK e. [email protected]
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Design Best Practices for Data Centers
Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
Datacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power
THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected]
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
The Effect of Data Centre Environment on IT Reliability & Energy Consumption
The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental
AIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
The Business Case Annual fuel cost savings of 26% worth more than 28,000 Annual fuel savings of 1.3million kwh Annual CO2 savings of over 245 tonnes
North Lanarkshire Council The Business Case Annual fuel cost savings of 26% worth more than 28,000 The Sir Matt Busby Sports Complex is an important local facility for the people of Bellshill, North Lanarkshire.
A Market Transformation Programme for Improving Energy Efficiency in Data Centres
A Market Transformation Programme for Improving Energy Efficiency in Data Centres Paolo Bertoldi, European Commission Joint Research Centre ABSTRACT The European Code of Conduct for Data Centres is a voluntary
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
How To Find A Sweet Spot Operating Temperature For A Data Center
Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Energy saving technology to deliver the fastest returns. Top 10 energy saving options
Energy saving technology to deliver the fastest returns Top 10 energy saving options How can you increase efficiency, reduce costs and cut your carbon emissions? Unstable energy prices, increased costs,
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: [email protected] www.itisltd.com Introducing Computational
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy
Existing and proposed metrics to provide effective understanding and reporting of data centre energy Liam Newcombe Data Centre Specialist Group 1 Introduction... 2 2 Summary... 6 3 Overview of metrics...
The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric
Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Energy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
Data Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration
Using Simulation to Improve Data Center Efficiency
A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience
Electrical Efficiency Modeling of Data Centers
Electrical Efficiency Modeling of Data Centers By Neil Rasmussen White Paper 113 Executive Summary The conventional models used to estimate electrical efficiency of data centers are grossly inaccurate
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
TelecityGroup plc. Outstanding data centres. Expertise you can trust.
TelecityGroup plc Outstanding data centres. Expertise you can trust. ABOUT TELECITYGROUP 2 / About TelecityGroup TelecityGroup is Europe s leading provider of premium carrier-neutral data centres. Helsinki
Saving Energy For Your Organisation. Top 10 energy saving tips
Saving Energy For Your Organisation Top 10 energy saving tips How can you increase efficiency, reduce costs and cut your carbon emissions? The UK s Climate Change Act (2008) sets a legally-binding target
Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.
Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10
Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10 Issue August 2007 Contents Executive Summary 2 Blade for Blade, Power is the Same 3 PAN Lowers Power by Reducing Server/CPU Count
Heating, ventilation and air conditioning zone controls
Technology information leaflet ECA762 Heating, ventilation and air conditioning zone controls A guide to equipment eligible for Enhanced Capital Allowances Contents Introduction 01 Background 01 Setting
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Common mistakes in datacentre planning
Common mistakes in datacentre planning White Paper Last edited: March 2013 Document Control Document Information Title Author Common mistakes in datacentre planning Nick Ewing This document is based upon
HOW TO SELECT GREEN TECHNOLOGIES IN A HARBOUR SETUP
HOW TO SELECT GREEN TECHNOLOGIES IN A HARBOUR SETUP E-Harbours towards sustainable, clean and energetic innovative harbour cities in the rth Sea Region ACKNOWLEDGEMENT This report has been realised with
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Gas Absorption Heat Pumps. Future proofing your heating and hot water
Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How
DC Pro Assessment Tools. November 14, 2010
DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory [email protected] 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
Greener Pastures for Your Data Center
W H I T E P A P E R Greener Pastures for Your Data Center 2 Executive Summary Following a green path, once a concept relegated to a small group of environmentalists and the U.S. Environmental Protection
THE NEXT GREEN THING. How Teliti International will help clean up our information and shape the future of green data centres in Malaysia
THE NEXT GREEN THING How Teliti International will help clean up our information and shape the future of green data centres in Malaysia 2 THE FUTURE OF GREEN DATA CENTRES IN MALAYSIA T he industrial revolution