TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION"

Transcription

1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GETCO/E/TS PCBL025/RO DT Page 1 of 18

2 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. However, in the event of partial submission or reports older than specified limit, bidder must submit his confirmation for those type test report/s to be submitted in the event of an order, without affecting delivery schedule, before commencement of supply, free of cost. In absence of this confirmation, the evaluation shall be carried out accordingly as non submission of type test reports. 4. The bidder must fill up all the point of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure. 9. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). Page 2 of 18

3 QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be 7 times tender / bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPLIED TO ORDER REFERENC E No. & DATE ITEM S QUANTI TY ORDER FULLY EXECUTE D. YES/NO STATUS, IF ORDER UNDER EXECUTI ON REMAR K 5) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / or EN by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification, valid for a period of FIVE years from the date of opening of technical bid and shall be valid till expiry of offer. Page 3 of 18

4 TECHNICAL SPECIFICATION FOR 11 / 22 kv XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) 1.1 SCOPE SECTION I This Section of the Specification covers design, manufacturing, testing, packing, supply & delivery of 11 / 22 kv XLPE Dry gas cured insulated power cable for effectively earthed system. 1.2 STANDARDS Unless otherwise specified, the cable shall conform in all respect to IS 7098 (Part-II)-1985 with latest amendment thereof. 1.3 CLIMATIC CONDITIONS The climatic conditions under which cables shall operate satisfactorily are as follows (a) (b) (c) Maximum ambient temperature of air Minimum ambient temperature of air in shade Maximum daily average ambient temperature 0 C 50 0 C 4 0 C 40 (d) Maximum yearly average ambient temperature 0 C 30 (e) Maximum relative humidity % 95 (f) Average number of thunder storm days per annum 15 (g) Average annual rainfall cm 150 (h) Maximum wind pressure Kg/cm (i) Altitudes not exceeding above MSL mtrs (j) (k) Maximum soil temperature at cable depth Maximum soil thermal resistively 1.4 PRINCIPAL PARAMETERS 0 C 30 0 C cm/watt / 22 kv (E) Grade XLPE, 3-Core, power cable shall be of high conductivity, stranded compacted, H.D. aluminum circular shaped conductor with XLPE (cross linked Poly Ethelene) Dry/Gas cured insulation provided with shielding of extruded semi-conducting materials over conductor and XLPE insulation. Each insulated core shall have copper tape screen, laid Page 4 of 18

5 together and provided with common covering of PVC Inner Sheath (Extruded). Overall galvanized steel strip armour and PVC outer sheath shall be provided. The specification for manufacture of cable shall be conforming to IS 7098 (Part-II) 1985 (latest edition) for 11KV (E), 3-phase, 50 Hz. Earthed systems Outer sheath shall be designed to afford high degree of mechanical protection and shall also be heat, oil, chemical and weather resistant, Common acid, alkalis and sealing solution shall not have adverse effect on material of PVC sheath Cable shall be suitable for laying in covered trenches and / or buried underground in outdoor Cable Parameters 11 kv 22 kv (i) Voltage grade (Uo / U) kv 6.35 / / 22 (ii) Cores (Nos) 3 3 (iii) Nominal system voltage kv (iv) Highest system voltage kv (v) System frequency Hz (vi) Variation in frequency % ± (vii) (viii) (ix) (a) Maximum allowable temp. of conductor during continuous normal operation at rated full load current. 0 C (b) Maximum allowable temp. under short circuit condition 0 C 1.2/50 microsecond lightning impulse withstand voltage wave value. kvp 5 Min, Power frequency withstand voltage kv rms (x) System earthling Effectively earthed. 1.5 GENERAL TECHNICAL REQUIREMENTS Conductor The cable conductor shall be made from high conductivity stranded High Density aluminum to form compacted circular shaped conductor having resistance within limits specified in IS 8130/1984 and any latest amendment to it. Page 5 of 18

6 1.5.2 Conductor shield Insulation The conductor having semi-conducting screen shall ensure perfectly smooth profile & avoid concentration of stress. The conductor screen shall be extruded in the same operation as the insulation. The semiconducting polymer shall be cross linked. The XLPE insulation shall be suitable for 11 / 22 kv system voltage and should be manufactured with Dry / Gas curing process. The bidder shall submit the description of dry / gas curing process, with the clear inclusion of equipments / parameters involved. The manufacturing process shall ensure that the insulation shall be free of voids. The insulation shall withstand mechanical and thermal stress under steady state and transient operating conditions. The extrusion method should give very smooth interface between semi-conducting screen and insulation. The insulation of the cable shall be of high standard quality generally conforming to IS 7098 (Part II) 1985 and any latest amendment to it Insulation shield Non-metallic semi-conducting shield shall be provided over the insulation to confine electrical field to the insulation. The insulation shield shall be extruded in the same operation as the conductor shield and the insulation by suitable extrusion process. The XLPE insulation shield shall be of tended type. The copper metallic overlapped tape shield shall be provided Filler and Inner-Sheath Armour The sheath shall be suitable to withstand the site conditions and the desired temperature. It shall be of adequate thickness, consistent quality and free from all defects. The PVC sheath shall be extruded. The material of fillers and inner-sheath shall be compatible with the temperature ratings of the cable and shall have no deterious effect on any other component of the cable. Central PVC filler shall also, be provided with other peripheral PVC fillers to have proper circular section. Armouring of galvanized steel strip shall be provided. The dimensions of steel strips shall be as per latest edition of IS Outer-Sheath Extruded type ST-2 PVC outer-sheath, conforming to IS 5831-(1984) (latest edition) over armouring with suitable additives (to prevent attack by rodents & termites), shall be provided. Page 6 of 18

7 1.5.8 Construction The cable shall have suitable PVC fillers laid up with insulation cores to have subsequently circular cross-section before the inner sheath is applied. The fillers shall be suitable for operating temperature of the cable All materials used in manufacturing of cable shall be new, unused and of finest quality. All materials should comply with the requirements / tests as per applicable IS / IEC specification, Indian Electricity Rules and any other statutory provision of rules & regulations The PVC material used in the manufacture of cable shall be of reputed manufacturer. No recycling of PVC is permitted. The purchaser reserves the right to ask for documentary evidence of the purchase of various materials, (to be used for the manufacture of cable) as per checking of quality control. Quality Assurance plans shall be submitted Current Rating The indicative value of continuous current carrying capacities at Maximum conductor temperature of 90 0 C (for design purpose by field ) of the various sizes of the cables are given below Sr. No. Size of 3 Core Cable (Sq.mm) Continuous Current Carrying Capacity in Amp (For 11 / 22 kv cable) In Ground In air Short circuit ratings of various sizes of 3 core cable calculated for duration of one second at maximum temperature of C, are given below Sr. No. Size of 3 Core Cable (Sq.mm) Conductor short circuit rating in ka (rms) (For 11 / 22 kv cable) Page 7 of 18

8 The current rating shall be based on maximum conductor temperature of 90 0 with ambient site condition specified for continuous operation at the rated current Operation Cable shall be suitable for operation under frequency variation of +3% and voltage variation of +10% to -15% and combined frequency - voltage variation of 10% (absolute sum) Cable shall be suitable for laying in duct or buried underground Cable shall have heat & moisture resistance properties. These shall be of type & design with proven record on distribution network service Length The cable shall be supplied in standard drum length of 300 mtrs. ± 5% tolerance for all the sizes of cable except for 3 C x 240 mm 2 and 3 C x 300 mm 2 size cable. The drum length for 3 C x 240 mm 2 and 3C x 300 mm 2 cable shall be 200 mtrs. ± 5%. Over all tolerance in total quantity of ordered cables shall be + 2% Identification Mark (i) The cable drum shall be printed with information as per cl. 21;2 of IS and ISI Certification mark. Bidder shall submit xerox copy of valid ISI Licenses with technical bid. (ii) 1.6 TESTS (iii) (A) Type Tests For identification of cores, coloured strip of Red, Yellow and Blue colours shall be used for identification of phases. Following details of identification shall be embossed at intervals of length of one meter of cable outer sheath. (a) Name of manufacturer (b) year of manufacture (c) voltage grade (d) Name of purchaser GETCO.. All the cable sizes i.e. items offered should have been fully type tested as per the relevant standards at any Govt. recognized Laboratory. The bidder shall furnish three sets of type test reports along with the offer. The Type test reports shall not be older than FIVE years and shall be valid upto the expiry of validity of offer. For any change in design/type, already type tested and the design / type offered against this specification, the purchaser reserves the right to demand reputation of type tests without any extra cost. Page 8 of 18

9 The purchaser also reserves the right to have tests carried out at his own cost by an independent agency, whenever there is a dispute regarding the quality of supply (B) The following type test reports shall be furnished with the offer (a) Tests on conductor (i) Tensile test (ii) Resistance test (b) Tests for armouring strips / wires. (c) Tests for thickness of insulation and sheath. (d) Physical tests for insulation. (i) Tensile strength and elongation at break. (ii) Ageing in air oven (iii) Hot set (iv) Shrinkage test (v) Water absorption (e) Physical tests on outer seath (i) Tensile strength and elongation at break. (ii) Ageing in air oven (iii) Shrinkage test (iv) Hot deformation (v) Bleeding and blooming test (f) (g) (h) (i) (j) (k) (l) (m) Partial discharge test Bending test Dielectric power factor test i) as a function of voltage ii) as a function of temperature Insulation resistance test (volume resistivity) Heating cycle test Impulse withstand test High voltage test Flammability test Page 9 of 18

10 1.6.2 Acceptance Test The selection of sample pieces for acceptance test shall be from 10% drums of each lot offered for inspection or part thereof. The minimum shall be one drum The following acceptance tests shall be carried out on the selected samples as per IS 7098 (Part-II) (a) (b) (c) (d) (e) (f) (g) (h) Annealing test (for copper) Tensile test (for aluminum) Wrapping test (for aluminum) Conductor resistance test. Test for thickness of insulation and sheath Hot set test for insulation Tensile strength and elongation at break test for insulation and sheath. Partial discharge test (for screened cables only) (i) High voltage test for 4 hours (as per cl. No ) (j) Insulation resistance (volume resistivity) test All the acceptance tests shall be carried out by the firm, in the presence of purchaser s representative at their works. The firm shall give atleast 15 days advance notice to the purchaser to enable him to depute the engineer for witnessing the tests. The test certificates for acceptance tests witnessed by inspecting officer/ engineer shall be submitted for approval before dispatch of material Tests The bidder shall have to submit, well in advance, the test certificates for the following routine test for approval prior to inspection of the materials for the complete lot offered for inspection at a time. (a) (b) (c) Conductor resistance test Partial discharge test High-voltage test for 5 minutes [as per Clause of IS 7098 (Part-II) 1985]. 1.7 STAGE INSPECTION The inspection may be carried out by the purchaser at any stage of manufacture. The successful bidder shall grant free access to the purchaser s representative at reasonable time, when the work is in progress. Inspection and acceptance, of any cables under this specification by the purchaser, shall not relieve the supplier of his Page 10 of 18

11 obligation of supplying cable in accordance with the specification and shall not prevent subsequent rejection, if the cables are found defective The supplier shall keep the purchaser informed in advance about the programme of manufacturing of cables so that arrangement can be made for inspection The purchaser reserves the right to insist for witnessing the acceptance / routing tests of the bought out items. 1.8 DOCUMENTATION The bidder shall furnish following documents alongwith his offer Sectional view, showing the General constructional feature with conductor / conductor screen / insulation / armouring / inner and outer sheath etc Drawing of cable drums with details of material dimension, as per relevant IS and paint etc. shall be submitted All the required type test reports for offered items tested at any Government recognized Laboratory as stated under Clause No (B) Literature, pamphlets etc List of orders (size wise) executed during last five years for supply of specified sizes of XLPE cables, supplied to State Electricity Boards, Private firms & GETCO(formerly GEB) etc. alongwith quantity, value of the orders, year of supply and delivery schedule. List of orders executed and under execution shall be submitted separately. The annual turn over in rupees, of the firms to whom the cables have been supplied during last two years shall be stated. 1.9 PACKING AND FORWARDING The cable shall be wound on wooden drums as per IS and packed in drums suitable for vertical / horizontal transport, as the case may be and shall be suitable to withstand rough handling during transport and outer storage. The outer surface of the drum shall be painted with white aluminum pint. Similarly, the inside surface of drum shall have the protective layer of varnish / paint to protect from white ants & termites The wooden drums shall be reinforced with steel bends and strips for better protection The ends of the cable shall be sealed by means of non-hygroscopic sealing materials. Page 11 of 18

12 1.9.4 The following information may be stenciled on the drum with either water proof ink or oil paint i. Reference of IS / IEC standard. ii. iii. iv. Manufacturer s name or trademark. Type of cable and voltage grade. No. of cores. v. Nominal cross-sectional area of conductor. vi. vii. viii. ix. Cable code. Length of cable on the drum No. of lengths on the drum (if more than one) Direction of rotation of drum (by means of an arrow) x. Position of outer end of cable xi. xii. xiii. xiv. xv. xvi. Gross weight Country of manufacture Year of manufacture Reference of A/T No. & date Property of GETCO Name of consignee and the destination. The drum may also be marked with ISI Certification Mark. Over and above, name plate of aluminium of suitable size and thickness, containing all the above information, shall be fixed on the drum in addition to the painting The firm shall be responsible for any damage to the cables during transit due to improper and inadequate packing. Wherever necessary, proper arrangement for lifting, such as lifting hooks, shall be provided. Any cable found short inside the packing cases shall be supplied by the supplier, without any extra cost Each consignment shall be accompanied by a detailed packing list, containing the following information (a) (b) (c) (d) (e) (f) Name of consignee Details of consignment Destination Total weight of consignment Handling and unpacking instruction Bill of materials, indicating contents of each package. Page 12 of 18

13 1.10 TECHNICAL AND GUARANTEED PARTICULARS The bidder shall furnish all Guaranteed Technical Particulars, as called for, in Appendix - I of this Specification. Particulars, which are subject to guarantee, shall be clearly identified. Offer not containing this information will not be considered for acceptance PERFORMANCE CERTIFICATE Bidders shall also submit performance reports for the specified size of cables supplied to other State Electricity Boards / reputed firms, with the clear indication of the period since when the cables performed satisfactory service LEGIBLE SUBMISSION Only required relevant, legible documents shall be submitted to avoid delay due to back reference. SEAL OF THE FIRM SIGNATURE OF THE BIDDER Page 13 of 18

14 APPENDIX I SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 11 / 22 KV XLPE POWER CABLE GENERAL (To be filled in and signed by the Bidder) Name of Manufacturer Place of Manufacturing Applicable standard IS/IEC Design ambient temperature 0 C Cable particulars, whether, confirmed, as per clause 1.5 of Section I of Technical Specification (Yes/No) Note (Fill up separate column for the following particulars for each type & size of cable) CABLES Voltage grade (Uo / U) Whether suitable for neutral earthed / unearthed System Permissible voltage & frequency variation for satisfactory operation Nos. of cores & size Continuous current carrying capacity For standard condition as per IS 1) In air (Amp.) 2) In ground ( ) 3) In duct ( ) 4) In trench ( ) For site condition 1) In air (Amp.) 2) In ground ( ) 3) In duct ( ) Page 14 of 18

15 4) In trench ( ) CONDUCTOR Material & its applicable IS Shape of conductor Nominal cross section area (mm 2 ) Number of wires per core Nominal diameter & cross section area of each wire used in each core of the conductor CONDUCTOR SCREENING Type Material & its applicable IS Continuous working temp 0 C Nominal thickness (mm) INSULATION Material & its applicable IS Thickness of insulation (mm) a) Between cores b) Between cores & inner sheath Tolerance in thickness (percent) of insulation Diameter of core over insulation (mm) Specific insulation resistance at ninety (90) degree Centigrade (Ohm-Cm) Whether Dry/Gas curing adopted(yes/no) INSULATION SCREENING Page 15 of 18

16 Material & its applicable IS Thickness (mm) 1) Semi-conducting part 2) Metallic part (copper tape) Whether overlapping provided for copper tape Current carrying capacity a) Continuous (Amps.) b) S.C. current duration of 3-Sec. (KA) Diameter of core over screening (mm) Whether insulation screen is removable without the application of heat FILLER Material & its applicable IS Whether suitable for operating temperature of Cable No of fillers provided including central filler INNER SHEATH Yes/ No Material & its applicable IS Extruded or wrapped Thickness (mm) Diameter of cable over inner-sheath (mm) ARMOURING Material & its applicable IS Type of armouring Nos. of strips Page 16 of 18

17 Diameter of cable over armouring Current carrying capacity of armour a) on continuous basis (Amp) b) short circuit current duration of 1 sec (KA) OUTER SHEATH Material & its applicable IS Thickness of sheath Tolerance on thickness of sheath Over all diameter of cable (mm) Scheme for identification CABLE CONSTANT AC resistance per core at operating temp. (Ohm/KM) DC resistance per core at 20 0 C (Ohm/KM) Reactance per core (Ohm/KM) Capacitance per core (Microfarad/ KM) Insulation resistance at 27 0 C (Ohm/ KM) Loss tangent Dielectric constant Maxi. Cable charging current at normal operating voltage (Amp/KM) OTHER PARAMETERS Recommended minimum braiding radius (mm) Page 17 of 18

18 Safe pulling force Cable weight (Kg./KM) CABLE DRUM Net weight of cable (Kg.) Drum weight (Kg.) Shipping weight (Kg.) Whether ISI Mark shall be indicated on drum (Yes/No) Length of cable per drum (Meter) Whether details shall be embossed as stated under Cl of Technical Specification (Yes/No) Whether type test reports submitted, as stated under Cl of Technical Specification (Yes/ No) Whether drawings submitted as specified under Cl of Technical Specification. (Yes/ No) Whether unpriced schedule of offered items submitted with Technical offer. (Yes/ No). Signature of the Bidder Name Designation Date Authorised common rubber Stamp / seal of the bidder Page 18 of 18

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E /TS

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E/TS

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GETCO/E/022TS ISO/R1

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6 DELHI METRO RAIL CORPORATION LIMITED (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III TURNKEY PROJECT OF DESIGN, SUPPLY, LAYING, JOINTING, TESTING AND COMMISSIONING OF

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

CLAMPS CONNECTORS & EQUIPOTENTIAL RING CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under: REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

High Voltage Systems. Today. The history of cables

High Voltage Systems. Today. The history of cables High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

EDS 02-0027 11KV TRIPLEX CABLE

EDS 02-0027 11KV TRIPLEX CABLE THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:

More information

Cables, Cable Laying & Accessories Manual

Cables, Cable Laying & Accessories Manual Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables

More information

VIPERFLEX ELECTRIC CABLE

VIPERFLEX ELECTRIC CABLE VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07

More information

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED

More information

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35 CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv

More information

MEDIUM VOLTAGE CABLES Up to and including 36 KV

MEDIUM VOLTAGE CABLES Up to and including 36 KV MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types

More information

APPLICATION ORIENTED DESIGN OF CABLES

APPLICATION ORIENTED DESIGN OF CABLES APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com

More information

MV CABLE TYPE C 33-226

MV CABLE TYPE C 33-226 MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2

More information

Removal of EP 20 10 00 02 SP High Voltage Cable

Removal of EP 20 10 00 02 SP High Voltage Cable TN 018: 2014 Technical Note For queries regarding this document standards@asa.transport.nsw.gov.au www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:

More information

22 kv OUT DOOR VACUUM CIRCUIT BREAKER

22 kv OUT DOOR VACUUM CIRCUIT BREAKER GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 22 kv OUT DOOR VACUUM CIRCUIT BREAKER Getco/Engg/TechSpec/22kV/O/D VCB/R1/Nov07

More information

International Electrotechnical Commission Standards

International Electrotechnical Commission Standards International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354

More information

Communication, Signal & Data Cables

Communication, Signal & Data Cables Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

INDIAN INSTITUTE OF TECHNOLOGY (BHU) Varanasi

INDIAN INSTITUTE OF TECHNOLOGY (BHU) Varanasi INDIAN INSTITUTE OF TECHNOLOGY (BHU) Varanasi Ref.No.: IIT(BHU)/IPCell/IWD/2014-15/1169 Dated : 13 th January 2015 NOTICE Indian Institute of Technology (BHU) Varanasi invites the sealed quotation for

More information

Contents. All Rights Reserved

Contents. All Rights Reserved Electricity Specification 400C8 Issue 6 October 2015 LV Service Cables Contents 1 Scope 2 Definitions 3 General Requirements for Approvals and Assurance 4 Conditions of Installation 5 Conditions of Operation

More information

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD PROJECT PROFILE ON XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD Prepared by: TRACO CABLE COMPANY LIMITED IV TH FLOOR, KSHB OFFICE COMPLEX PANAMPILLY NAGAR KOCHI-682036 September 2012 PROJECT

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

COATING & WRAPPING OF UNDERGROUND PIPING

COATING & WRAPPING OF UNDERGROUND PIPING CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES Irrigation 1 Coaxial s for T.V/ Satellite Antenna etc 2 Data Transmission s - 4 pair 24 AWG 3 TELEPHONE CABLES Telephone cables CCP-LAP & CCP-LAP-SS

More information

Specification N : NPS - 63/8. Underground Power Cable Covers

Specification N : NPS - 63/8. Underground Power Cable Covers Page No. 1 of 13 Specification N : NPS - 63/8 Underground Power Cable Covers Replaces specification N : NPS - 63/7 Prepared by : A. Lavian Approved by : Dr. N. Grinberg May 2016 Haifa- Israel Page No.

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 4 PAIR UTP CABLE (ENHANCED CATEGORY 5) PVC (CM Grade) Page 1 of 6 1. SCOPE This specification is based on the specifications of UL 444, ANSI/TIA/EIA-568-B.2, UL 1685 and covers

More information

Specializing in the cable business for over 38 years, PT. SUPREME CABLE

Specializing in the cable business for over 38 years, PT. SUPREME CABLE Specializing in the cable business for over 38 years, PT. SUPREME CABLE MANUFACTURING & COMMERCE Tbk. (PT. SUCACO Tbk) has grown steadly to become a largest and leading cable manufacturer, with international

More information

TECHNICAL SPECIFICATION OF VARIOUS EARTH WIRES FOR TRANSMISSION LINES AND SUB STATIONS

TECHNICAL SPECIFICATION OF VARIOUS EARTH WIRES FOR TRANSMISSION LINES AND SUB STATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF VARIOUS EARTH WIRES FOR TRANSMISSION LINES AND SUB STATIONS GETCO/E/TS

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature

More information

MEDIUM VOLTAGE POWER CABLES

MEDIUM VOLTAGE POWER CABLES MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

CABLE ACCESSORIES 110-220 kv

CABLE ACCESSORIES 110-220 kv CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination

More information

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded

More information

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET 1 KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET KI XL - 03 / KI-SC 10 TWO COMPONENT AMBIENT CURABLE POLYETHYLENE COMPOUND FOR INSULATION OF LOW VOLTAGE POWER CABLE DESCRIPTION : KI polyethylene compound

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

Festoon 715 P PUR cable for flexible application in festoon systems

Festoon 715 P PUR cable for flexible application in festoon systems CABLES FOR CRANE AND CONVEYOR APPLICATIONS Festoon 715 P PUR cable for flexible application in festoon systems S AB BRÖCKSKES D-VIERSEN Festoon 715 P 1 x 16.0 mm 2 C Marking for Festoon 715 P 07150162:

More information

I-PEX MHF4 Micro Coaxial Connector

I-PEX MHF4 Micro Coaxial Connector PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: sales@wellshow.com.tw Tel: +886-2-24239376

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Fire Resistant Cables

Fire Resistant Cables 109/4 Fire Resistant Cables SR 114H Standard - SR 114E Enhanced BS 5839-1 BS 7629-1 BS 6387 BS 8434-1/2 BS 6425 BS 7622 EN 50200 World-wide recognized high quality cables Firecel SR114 are used in: Data

More information

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES IEC SYSTEM FO CONFOMITY TESTING AND CETIFICATION OF ELECTICAL EQUIPMENT COMMITTEE OF TESTING LABOATOIES TESTING AND MEASUING EQUIPMENT/ALLOWED SUBCONTACTING Power cables with extruded insulation and their

More information

XLPE Land Cable Systems User s Guide. Rev 5

XLPE Land Cable Systems User s Guide. Rev 5 XLPE Land Cable Systems User s Guide Rev 5 CONTENT XLPE Land Cable Systems Introduction... 3 Design, installation and testing... 4 XLPE cables... 4 Cable accessories... 4 Installation of XLPE cable systems...

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR Standards : CENELEC HD 22.4 NF C 32-102-4 DIN VDE 0282-1 and VDE 0282-4 BS 6007 and BS 6500 IEC 60245-4 Rated voltage Rated voltage: 450/750 V (Use up to

More information

TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)

TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) (SPECIFICATION NO. DIST/MM-II/03/2005) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

100% EMI Emission Containment

100% EMI Emission Containment 100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

LT/HT Power & Control Cables

LT/HT Power & Control Cables LT/HT Power & Control s Catalogue 2014 HT Power s upto 66kV 1.1 kv Power s 1.1 kv Copper Control s ISO-9001/ 14001/18001 Certified Certification Building customer confidence by providing a wide range of

More information

Flexible cables for submersible products

Flexible cables for submersible products Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

Outside Telephone Cable

Outside Telephone Cable Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of

More information

Flexible Control Cables

Flexible Control Cables Works photo: KUKA Flexible Control Cables A Flexible Control Cables Since generations people try to build machines and plants which shall take on different functions. To raise, sink, slide, drill, transport

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

VDE-approved PVC-Control Cables

VDE-approved PVC-Control Cables Works photo: HELUKAEL VDE-approved PVC-Control Cables VDE-approved PVC-Control Cables This certification/licency is issued according to the rules of the HAR Agreement, wherein the certification/ licency

More information

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies www.echtzeit.com e-mobility Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies Special cables for electric vehicles Wittener Straße 271 D-42279 Wuppertal Phone +49(0)202.2681.228 Fax +49(0)202.2681.360

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information

the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables

the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables ABOUT US Since our beginning in 1995, We - MEGHNA INDUSTRIES have been one of the fastest growing manufacturer

More information

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec

More information

WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED. (A Govt of West Bengal Enterprise)

WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED. (A Govt of West Bengal Enterprise) WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED (A Govt of West Bengal Enterprise) Office of the Chief Engineer (Procurement) Regd. Office: Vidyut Bhavan (10 TH Floor), Block- B, Bidhannagar,

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

David O Brien, CMP Products (David.OBrien@cmp-products.com)

David O Brien, CMP Products (David.OBrien@cmp-products.com) David O Brien, CMP Products (David.OBrien@cmp-products.com) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Flygt flexible cables

Flygt flexible cables Flygt flexible cables Contents Standards General SUBCAB 4 Screened SUBCAB 6 Rubber cable type: NSSHÖU-J 7 Screened rubber cable type: NSSHÖU../E + ST 8 FGB screened rubber cable 9 PUR control cable 0 HCR

More information

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69 Ratings TBLE BEC 107. (Continued) ratings for 60/11000 volts grade PILC/SW/PVC cable to BS64/69 CBLES LID IN IR: The ratings given in the foregoing tables are based on an ambient of C. It is recommended

More information

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo Connectors, Clamps, Compensating Devices, Insulators and Safety Equipment for Overhead Catenary Lines RAILWAY CATENARY SYSTEMS Components and Systems for the Electrification of Railway Lines. Welcome to

More information

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide HIGH VOLTAGE XLPE CABLE SYSTEMS Technical User Guide Content 1. General information on High Voltage XLPE Cable Systems 1.1. Introduction 1.2. Cable selection process 1.3. Service life 3 3 3 4 2. Cable

More information

TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH

TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH Rev. 1:2007 TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH Suruhanjaya Komunikasi dan Multimedia Malaysia Off Pesiaran Multimedia, 63000 Cyberjaya, Selangor

More information

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES Quality Reliability Innovation ISO : CERTIFIED BY AFAQ No. QUAL / 7 / 7 a COPPER TELECOMMUNICATION CABLES COPPER TELECOMMUNICATION CABLES CONTENTS 7 NOTICE INTRODUCTION QUALITY ASSURANCE RECOMMENDED ORDERING

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection

Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection Cable Guide Cables, Connectors & Tools for installation of quality networks TRIAX - your ultimate connection A Selection of the best Triax TX Cable range optimised for digital reception Simplification

More information

The Quality Connection. BETAflam Fire Resistant Safety Cables

The Quality Connection. BETAflam Fire Resistant Safety Cables The Quality Connection BETAflam Fire Resistant Safety Cables 2 Contact Consulting and sales Switzerland Phone +41 (0)62 288 82 82 Fax +41 (0)62 288 83 83 sales@leoni-studer.ch www.leoni-infrastructure-datacom.com

More information

PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082

PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 General PTC-resistor temperature sensors (also called PTC-resistors or thermistors) are temperatur dependent semiconductor resistors

More information

TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT

TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT Annexure A Sl.No. Description 1 Scope: The scope cover the design, manufacturing, supply and delivery at GCF Jabalpur on FOR basis

More information