22 kv OUT DOOR VACUUM CIRCUIT BREAKER

Size: px
Start display at page:

Download "22 kv OUT DOOR VACUUM CIRCUIT BREAKER"

Transcription

1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATION FOR 22 kv OUT DOOR VACUUM CIRCUIT BREAKER Getco/Engg/TechSpec/22kV/O/D VCB/R1/Nov07

2 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In absence of this, the evaluation shall be carried out accordingly as non-submission of type test reports. 4. The bidder must fill up all the points of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure.

3 QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be FIVE times tender/ bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPP LIED TO ORDER REFEREN CE No. & DATE ITEMS QUANTI TY ORDER FULLY EXECUTED. YES/NO STATUS, IF ORDER UNDER EXECUTION REMAR K e) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / or EN by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification. The type test reports shall not be older than FIVE years and shall be valid up to expiry of validity of offer.

4 SECTION I GENERAL TECHNICAL REQUIREMENTS FOR 22 KV OUT DOOR VACUUM CIRCUIT BREAKER 1.1 SCOPE This section covers the design, manufacture, testing, inspection, supply and delivery of 22 KV Out door Circuit Breakers with associated accessories and complete in all respects specified in the schedule of requirements. 1.2 APPLICABLE STANDARDS Except where specified otherwise in this specification, the circuit breakers shall conform to the requirements of the latest edition of IS /IEC 56. However, in the event the offered breakers confirming to any other standard, salient points of differences between the standard adopted and the standards specified shall be clearly indicated in the offer. 1.3 DRAWINGS As a part of the proposal, the bidder shall furnish the drawings in triplicate incorporating the following particulars for the purpose of preliminary studies. a) Drawing showing the general outline dimensions of circuit breakers, with clear identification of parts / items. b) Drawing showing control cabinets and circuit diagrams for operating mechanism of circuit breakers. c) Compression type terminal connectors for the breakers Within 15 days of receipt of a purchase order, the bidder shall furnish to the purchaser following drawings for the approval of the purchaser.

5 a) Outline dimensional drawings showing all parts / items, transport weight etc. of circuit breaker & its support structure. b) Sectional views showing the general constructional features, Operating mechanism, and extinguishing chambers etc. of circuit breakers. c) Detailed drawings of operating mechanism of circuit breakers. d) Wiring and control diagram. e) Drawings of foundation details, mounting structures, spacing of bolts etc. f) Compression type terminal connectors suitable for (ACSR) panther conductor, with STC rating & bill of material & complete dimensions The bidder may also, submit any other drawings found necessary in addition to the drawings stated above GENERAL DESIGN FEATURES OF CIRCUIT BREAKERS The circuit breaker shall be VCB type. The breakers shall be offered as a complete unit with all piping equipment in place and all internal wiring installed and terminated in the mechanism housing and breaker shall be compete in all respect The circuit breakers shall be capable of rapid and smooth interruption of currents under all conditions completely suppressing all undesirable phenomena even under the most severe and persistent short circuit conditions or when interrupting small currents or leading or lagging reactive currents. The circuit breakers shall be Restrike-Free under all operating conditions. The details of any device incorporated to limit or control the rate of rise of restriking voltage across, the circuit breaker contacts shall be stated. The over voltages caused by circuit breaker while switching inductive or capacitive loads shall not exceed 2.5 times the highest phase to neutral voltage. The actual make and break times

6 for the circuit breakers throughout the ranges of their operating duties shall be stated in the offer and guaranteed The arc quenching chambers shall have devices to ensure almost uniform distribution of voltage across the interrupters Breaking Capacity - The interrupting capacity of the breaker for kilometric faults (short line faults) shall be equal to its interrupting capacity [as per Clause of IS 13118] and shall be stated in the offer. The details of tests conducted for confirming the capability of the breakers under kilometric fault conditions shall be furnished in the offer The circuit breakers shall be designed for interrupting line charging currents without undue rise in the voltage on supply side and without any restrike and without showing signs of undue strain. The guaranteed over voltage which shall not be exceeded while interrupting the line charging currents as specified under the Clause 2.4.(10) Section-II of this specification shall be stated in the offer The circuit breakers shall be capable of interrupting small inductive currents (occurring while switching off unloaded transformer) without giving rise to undue over voltage and without restrikes. The maximum over voltage value which will not be exceeded under such conditions shall be stated in the offer, In case of requirement type test for small inductive current interrupting capacity shall be arranged as per provision of IEC 56 or IS Restriking Voltage - The circuit breakers shall be capable of interrupting the rated power when the restriking voltage has a frequency of not less than 400 Hz and with a restriking voltage having frequency of 2000 Hz. The circuit breakers shall be capable of interrupting atleast 50% of nominal breaking capacity.

7 The measures adopted for ensuring proper operation at high rate of rise of restriking voltage and for limiting the actual voltage values across the breaks shall be described in the offer. The type characteristics and rating of the resistor used, if any, to shunt the breaker contacts and of the auxiliary switching devices used for interrupting the resistor current shall be clearly stated Recovery voltage and power Factor The circuit breaker shall be capable of interrupting the rated power with recovery voltage equal to the rated maximum line to line service voltage at rated frequency and at a power factor not exceeding The circuit breakers shall also be capable of satisfactory operation even under conditions of phase opposition that may arise due to faulty synchronising. The maximum power which the breaker can satisfactorily interrupt under phase opposition shall be stated in the offer The operating duty of the circuit breaker shall be as specified under Clause (11) section II of specific technical requirement for breakers Temperature Rise The temperature rise and the maximum temperature on any part of the equipments when in service under continuous full load conditions and exposed continuously to the direct sun-rays shall not exceed the permissible limits as per relevant ISS. When the standard specifies the limits of temperature rise, this shall not be exceeded when corrected for the difference between ambient temperature at site and the ambient temperature specified in the relevant specification. The correction proposed shall be stated in offer and shall be subject to the approval of the purchaser General Features of Circuit Breakers The circuit breakers shall be suitable for outdoor operation under the climatic conditions specified in section-ii of this specification.

8 Exposed live parts shall be placed high enough above ground to meet the requirements of local safety codes All similar parts, particularly removable one and shall be interchangeable with one another VCB shall consist of three identical single phase units with common operating mechanism suitable for specified duty. Bidder may give complete constructional details for VCB offered by them. The insulation level of porcelain of the circuit breaker shall be so cocoordinated with that of the equipment that flashover shall occur externally to the equipment Insulation of the Circuit Breaker - The insulation to ground, the insulation between open contacts and the insulation between phases of the completely assembled circuit breaker shall capable of withstanding satisfactorily die-electric test voltages corresponding to BIL specified in Clause SECTION II of this specification i.e. Lightening impulse with stand voltage shall be150 KVP & One minute P.F. withstand voltage shall be 55 KV rms Adequate clearance shall be provided between phase and from phase to ground. The clearance shall be such that the breaker shall withstand the BIL specified under clause no of this specification. The minimum clearance from live parts to ground level shall however be subject to the purchaser s approval Contacts of Circuit Breaker The main contacts shall have adequate area and contact pressure for carrying the rated currents and the short time rated breaking currents of the breaker without excessive temperature rise. Contacts shall have a minimum of movable parts and adjustments. The main contacts shall be first to open and last to close so that burning and wearing of the contact may be negligible. Main contacts shall be of copper. Moving contacts shall have permanent marking or scale. Identification shall be invariably

9 and legibly marked on VCB mechanism so that the extent of wear and tear can be measured. Necessary instruction there of shall be furnished on front of panel Operating Mechanism of Circuit Breakers Circuit breakers shall be power operated either by pneumatic mechanism or by a motor compressed spring charging mechanism depending on the type of breaker offered. The mechanism will be trip-free electrically and mechanically. The mechanism shall be strong, quick in action and shall be removable without disturbing other parts of the circuit breakers. All the working parts in the mechanism shall be of corrosion resistant materials and all bearings which require greasing, shall be equipped with pressure grease fittings. The mechanism and breaker shall be such that the failure of any spring will not prevent tripping and will not cause tripping or closing The circuit breakers shall be designed for remote control from the control room and there shall be provision for manual operation of circuit breakers during maintenance and for local tripping and closing by normal means The circuit breaker shall have a mechanical ON-OFF indicator in addition to facilities for remote electrical indicator The operating mechanism along with its accessories shall be mounted in a weather proof cabinet with hinged doors located near the breakers.. The local control switch and the breaker position indicator shall be provided in this cabinet. The control circuit shall be designed to operate on 110 V.D.C. as specified in section-ii of this specification. The closing and opening coils shall be designed to operate satisfactorily at any control voltage from 80% to 115% of the normal voltage. A heater of adequate capacity with thermostat shall be provided in the cabinet to avoid moisture condensation.

10 (a) The terminal block shall of 1.1 KV voltage grade & shall be with stud type connections instead of with screw types connections Auxiliary switches- A minimum number of 6 NC + 6 NO Auxiliary switches contacts shall be provided on each circuit breaker for use in remote indication control scheme of the circuit breakers and for safety interlocking. Special contacts for use with trip coils shall also be provided. Provision shall be made for adding more auxiliary switches, if required. Auxiliary switches shall be placed in weather proof galvanized casing and current rating of switches shall be mentioned in the bid. 1.5 BUSHING & INSULATORS The porcelain insulator used in manufacturing the bushings shall be homogeneous, free from laminations, cavities and other flaws or imperfection that might affect the mechanical or dielectric qualities. All bushings of identical ratings shall be interchangeable. The bushings shall conform to the latest edition of IS 5621 or any other equivalent standard (Latest). The puncture strengths of the bushings shall be greater than their flashover values. The bushings shall be entirely free from external and internal corona. The total minimum creepage distance of the bushings shall be suitable for heavily polluted atmosphere. 1.6 TERMINAL CONNECTORS AND EARTHING TERMINALS Nos. of Compression type terminal connectors per breaker suitable for ACSR PANTHER Conductor shall be supplied and they shall be suitable for both vertical and horizontal connections of the Transmission line conductor or station bus bar. Suitable terminal earth connectors (two Nos.) for earthing connections shall also be supplied. The drawing of this connector shall be submitted. SS bolt for connector shall be provided with two Nos. of SS nuts (including lock nut) & one SS washer. 1.7 TROPICALISATION

11 1.7.1 All control wiring, electric motors and accessories shall be protected against fungus growth and other harmful effects due to tropical environments. 1.8 GALVANISING All ferrous parts of breakers and compressed air plant including bolts, nuts etc. shall be hot-dip galvanised as per latest edition of IS PAINTING Mechanisms, enclosures, cabinets and other metal parts shall be thoroughly cleaned to remove all rust scales, corrosion and other adhering foreign matter, steel surfaces, as far as possible shall be painting with not less than two coats of heat resistant, oil insoluble, insulating varnish light-grey pains as per shade no.631 of IS5 shall be selected to withstand tropical heat and extremes of weather/heavily polluted atmosphere TEST AND TESTS REPORTS Reports of following type tests carried out in Govt. approved laboratory within five years prior to Date of Bid opening and shall be valid up to expiry of validity of offer as per IS for circuit breakers shall be submitted along with the offer (i) Lightening impulse withstand voltage test (ii) Power frequency voltage withstand voltage test. (DRY as well as wet). (iii) Temperature rise test. (iv) Measurement of resistance of main circuit (v) Short time current withstand and peak current with stand Test (vi) Mechanical endurance test (vii) Single phase short circuit test. (viii) Out of phase making and breaking current test. (ix) Capacitor current switching test for isolated neutral capacitor banks. In case of non-submission of some of the type test reports, the bidder shall confirm the submission of same before commencement of supply without affecting delivery schedule of breaker.

12 Routine tests as per the latest edition of IS for circuit breakers shall be carried out on each circuit breaker (in presence of purchaser s representative if degreed by the purchaser) The test reports for type tests and routine tests in respect of associated equipments as motors, instruments, relays etc. as per the latest edition of the relevant IS shall be supplied by the bidder All tests reports for acceptance / routine tests shall be submitted and got approved from the purchaser before dispatching the breaker SPARE PARTS The bidder shall furnish an item wise list and quantity of recommended spare parts, if any, for five years' operation of the air break Isolators, with unit price of each part ERECTION The bidder shall quote for the services of an erection engineer who shall take full responsibility for the erection, testing, and commissioning of the breakers. Skilled labour for erection work will have to be arranged for by the successful bidder. Erector shall bring all special tools and instruments required. Rates of pay, on daily and monthly basis as well as the estimated duration of execution shall be indicated The erection and commissioning of the breaker shall be supervised, if required by the purchaser, through supplier s representative who shall direct the sequence of erection and make necessary adjustments to the apparatus and correct in the field any errors or omissions on the part of the supplier in order to make the breakers and material to function in accordance with the intent of this specification The purchaser shall not be responsible for any damage to the breaker during commissioning if such damages result from faulty or inadequate erection. Purchaser shall provide local workmen as well as ordinary tools and equipments required for erection.

13 Supplier shall not be liable for any loss, damage or injury to property or persons at the installation site unless such damage or injuries are caused by any act or negligence of the supervising erector TECHNICAL & GUARANTEED PARTICULARS The bidder shall furnish all guaranteed technical particulars as called for in section-iv (Schedule- A ) of this specification. Particulars which are subject to guarantee shall be clearly stated offers not containing this information will not be considered. Deviation against any clause of this technical specification shall be clearly described in annexure 12 only INSTRUCTION MANUALS There copies of operation, maintenance and erection manuals in English language shall be supplied one month prior to the dispatch of the circuit breakers. In addition, two copies of the same per sub-station shall be supplied. The manuals shall be bound volumes and shall contain all the drawings and instructions required for erection, operation and maintenance and in addition the following particulars a) Marked erection prints identifying the component parts of the circuit breakers and current transformers as dispatched with the assembly drawings. b) Details dimensions, assembly and description of all the components and catalogues for operation of the circuit breaker and accessories. c) List of recommended spare parts of circuit breaker.

14 SECTION II TECHNICAL SPECIFICATION FOR 22 KV OUTDOOR CIRCUIT BREAKERS SPECIFIC REQUIREMENTS. 2.1 SCOPE This section covers the specific technical requirements, climatic and isocerunic conditions and system particulars for which the circuit breakers shall be offered as per the General Technical Requirements given in Section-I of this specification and the schedule of requirements specified herein for the various sub stations. 2.2 CLIMATIC & ISOCERAUNIC CONDITIONS The climatic conditions under which the breaker shall operate satisfactorily are as follows a) Maximum ambient temperature of air in shade ( 0 C). b) Minimum ambient temperature of air in shade ( 0 C). c) Maximum daily average ambient temperature ( 0 C). d) Maximum yearly average ambient temperature ( 0 C) e) Maximum relative humidity (%). 95 f) Average number of thunderstomn days / annum. 15 g) Average annual rainfall (Cm.) 150 h) Maximum wind pressure (Kg/m2) 150

15 i) Height above mean see level (m). Not exceeding 1000 meters All breakers offered shall be suitable for continuous satisfactory operation at the full rated capacity under the above climatic conditions Since the sub-station may be near seashore or Industrial area, the breaker offered shall be suitable for heavily polluted atmosphere. 2.3 SYSTEM DETAILS i) Nominal system voltage(kv) 22 ii) Maximum rated voltage (KV) 24 iii) Frequency (Hz ) 50 iv) Number of phases 3 v) Neutral Earthing Solidly earthed. vi) Auxiliary power supply 1) 240 Volts 1-φ & 415 Volts 3-φ, 50 Hz A.C., with the variation of frequency 48.5 to 51.5 and voltage +10% & -15% occasionaly. 2) 110 Volts or 220 Volts 2-wire D.C. supply subject to variations of ± 10%. The circuit breakers shall complete with following technical requirements. 11) Number of Poles 3 2) Basic Insulation level

16 1) 1.2/50 Microsecond impulse withstand voltage (KVP) ) On Minute Power Frequency withstand voltage (KV rms). 55 3) Rated normal current (Amps.) a) Rated symmetrical breaking capacity at highest system voltage. (MVA) 4) Rated short circuit breaking capacity KA (rms.) 5) Rated duration of short circuit seconds. 6) Total break time for any current upto the rated breaking current cycles ) Closing time. Not more than 10 cycles. 8) Rated characteristics for short line faults 9) Rated transient recovery voltage for terminal fault. 10) Rated line charging current breaking capacity (Amps.) 11) Rated short circuit making current KAP. As per Clause of IS 13118/IEC-56. As per Clause of IS 13118/IEC ) Rated operating duty Sec-Co-3 Min. Co.

17 13) Total creepage distance for heavily polluted atmosphere (mm ) ) Type of circuit breaker Vacuum 2.5 EARTH QUAKE & WIND DESIGN LOADS Each circuit breaker including its supporting structure shall be designed to withstand required earthquake acceleration of 0.08 x 2 g and with wind loads of 150 Kg/m2 on the projected area (non-simultaneous) without damage to component parts and without impairment of operation.

18 APPENDIX - I BIDDING SCHEDULES (TO BE FILLED IN & SIGNED BY THE BIDDER) SCHEDULE A GUARANTEED TECHNICAL PARTICULARS FOR 66KV CIRCUIT BREAKERS 1. Name of Manufacturer 2. Type Designation 3. Governing Standard 4. Rated Voltage (KV) 5. Maximum continuous rated service voltage (KV) 6. Frequency (Hz) 7. Operating duty cycle 8. Nominal current rating (Amps.) Under standard condition. (Amp) Under site condition (Amp). Derating factor, if any for site conditions. 9. Short time current rating (KA) for 3 seconds

19 10. Maximum temperature / rise over ambient temp. due to rated current in main contacts measured after breaking test. ( 0 C) 11. Rated short circuit breaking current Rated short circuit current (AC component) (KV rms). Percentage DC component Assymetrical breaking current (including DC component (KA rms). Rated symmetrical breaking capacity in MVA FOR MOCB & FOR SF6 CB 12. Making capacity (KA Peak) 13. Total breaking time (Milliseconds) a) For interruption of 10% of the rated capacity. b) For interruption of 30% of the rated capacity. c) For interruption of 60% of rated capacity. d) For interruption of the full rated capacity. 14 Arcing time ( Milli seconds ) 15. Making time (Milli seconds)

20 16. Minimum reclosing time at rated interrupting capacity from the in fault of the trip coil inrgisation (Milli-second) 17. A) Minimum dead time a) 3 phase reclosing (Milli seconds). b) Limit of adjustment of dead time for 3-phase reclosing. B) Whether restrike free and trip free. (IS/IEC applicable may be stated). 18. Rate of rise of restriking voltage for 100%, 50% & 30% rated capacity a) Amplitude factor (max) b) Phase factor (max) c) Natural Frequency (Hz) d) Rated of rise of restriking voltage (V/Micro Sec)(max) 19. Maximum interrupting capacity under phase opposition condition (MVA). 20. Maximum line charging current breaking capacity without over voltage exceeding 2.5 neutral voltage (Amps.)

21 21. Maximum line charging current breaking capacity corresponding over-voltage recorded a) On supply side. b) On line side. 22. Maximum cable charging current breaking capacity & corresponding over-voltage recorded in test. a) On supply side. b) On line side. 23. Maximum shunt capacitor Bank switching capacity (MVA) 24. Maximum breaking capacity on kilometric fault (MVA) 25. Maximum over-voltage on switching transformers on no load & the charging current. 26. Dry 1 Minute power frequency test withstand voltage, for complete circuit breaker Between line & Grounded parts (KV rms) Between line with breaker contacts open (KV rms)

22 27. Wet 1-minute power frequency withstand voltage for complete circuit breaker a) Between line terminal & grounded parts (KV rms) b) Between terminals with breaker contacts open (KV rms.) /50 Micro-second wave lightening impulse withstand test voltage for complete circuit breaker a) Between line terminal and ground (KV peak) b) Between terminal with circuit breaker contacts open (KV peak). SUPPORTING INSULATORS 29. Make & Type 30. Insulation Class 31. Visible Corona discharge voltage 32. Wet 1-minute power frequency f1ashover voltage (KV rms). 33. Dry 1-minute power frequency f1ashover voltage (KV rms) /50 micro-second impulse f1ashover voltage (in KV peak)

23 35. Total creep age distance for heavily polluted atmosphere 36. Minimum clearance in air a) Between phases (mm) b) Live parts & earth (mm) Live parts to ground level (mm). 37. No. of poles per circuit breaker 38. Breaks per pole Nos. 39. Total length of breaks per phase (mm) Type of main contacts Material of main contacts 42. Whether main contacts silver plates (Yes/No) 43. Thickness of silver coating on main contacts (mm). 44. Contact pressure on main contacts (Kg/M2). 47. Type of auxiliary switches 48. Material of switch contacts 49. Whether contacts silver plates (Yes/No.)

24 50. No. of auxiliary switch contacts operating with all three poles of breaker a) Which are closed when breaker is closed. b) Which are open when breaker is closed 51 No. of spare auxiliary switch contacts operating a) Which are closed when breaker is closed. b) Which are open when breaker is closed. 52. No. of operations possible without maintenance At full rated interrupting capacity. At 50% of rated interrupted capacity At 100% of rated current At 50% of rated current. 53. Details of foundation

25 54. Type of operating mechanism (motor operated spring charged). a) Opening b) Closing c) Control voltage aux. 55. Tripping & closing circuit voltage (V). 56. Power required for trip coil (in watts). 57. Power required for closing coil (in watts). 58. Weight of 3-φ breaker complete with operating mechanism, supporting, insulators, frame work etc. 59. Impact loading for foundation design to include dead load plug impact value on opening it maximum interrupting rating in terms of equivalent static load. 60. Weight of heaviest package (Kgs) space requirements (Length, Width, Height).

26 61. DETAILS OF VACUUM a) Quantity of vacuum per C.B. (bars) b) Standard applicable for vacuum SEAL OF THE FIRM SIGNATURE OF TENDERER Note 1) Instead of giving reference of drawing No./ IS Literature etc. actual values / figures must be furnished wherever required otherwise it will be completed to consider that the details in GTP are not furnished & technical Bid will be evaluated accordingly. 2) The tenderer should furnish the various make for bought out items wherever required in GTP instead of indicating or its equivalent.

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES

22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 22 kv ISOLATORS & ISOLATOR CUM EARTHING SWITCHES GETCO/E/022TS ISO/R1

More information

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under: REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION

TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara 390 007 TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GETCO/E/TS PCBL025/RO DT.07-03-2008

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

CLAMPS CONNECTORS & EQUIPOTENTIAL RING CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

TECHNICAL SPECIFICATION OF 132 KV SF6 CIRCUIT BREAKER

TECHNICAL SPECIFICATION OF 132 KV SF6 CIRCUIT BREAKER GUJARAT STATE ELECTRICITY CORPORATION LTD. THERMAL POWER STATION SIKKA TECHNICAL SPECIFICATION OF 132 KV SF6 CIRCUIT BREAKER SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E /TS

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT

GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GENERAL: 1. The selection of switchgear for switching the capacitors should be done carefully. The circuit breaker

More information

33kV SF6 CIRCUIT BREAKERS

33kV SF6 CIRCUIT BREAKERS BIDDING DOCUMENT FOR SUPPLY OF 33kV SF6 CIRCUIT BREAKERS NIT NO. AEGCL/MD/SS 142 PRICE: Rs 500.00 26 MAIN CONTENTENTS Notice Inviting Tenders Section-1 Section-2 Section-3 Section-4 Section -5 Section

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E/TS

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Contact expansion modules

Contact expansion modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules CHIEF EN TERPRISES INC. M a s t e r I n t e r n a t i o n a l D i s t r i b u t o r Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules M AS TER IN

More information

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Disconnectors and Earthing Switches 36 kv up to 800 kv

Disconnectors and Earthing Switches 36 kv up to 800 kv Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information