Technical catalog - Edition SACE Tmax PV Adaptability, versatility and complete freedom continue
|
|
|
- Anis Hoover
- 9 years ago
- Views:
Transcription
1 Technical catalog - Edition 205 SCE Tmax PV daptability, versatility and complete freedom continue
2 SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors The Tmax PV line of IEC switch-disconnectors and UL switch-disconnectors and molded case circuit-breakers expands upon Tmax T Generation s history of offering complete adaptability, versatility and freedom for any type of application. Using the Tmax PV line, the customer is able to select the most appropriate device for any Solar PV need. Under IEC , Tmax PV offers switch-disconnectors to meet standard 00V DC applications. In addition, it offers the versatility of extended capacities to 500V DC for the increasingly demanding solar applications of today s market. Finally, connection jumpers are an available option for the IEC switch-disconnectors to increase safety and ease of installation. Tmax utomatic Circuit-breakers according to IEC up to 000V DC are available as a special version of the standard Tmax line. Information about that range can be found in the Tmax technical catalogue. Common data Operating temperature [ C] -25 C + C Storage temperature [ C] -40 C + C Numbers of poles 4 Version fixed ltitude derating ltitude [mt] In [%] Ue [%] SDC20054D0203 BB catalogue
3 Under UL 489B, Tmax PV offers adaptability in the form of the availability of both switch-disconnectors and molded case circuit-breakers. Multiple formats allows for the ability of a uniform end product and shared accessories. In addition, BB offers connection jumpers as a mandatory accessory to Tmax PV UL. The jumpers provide simple, safe use and ensured compliance to new UL regulations. Common data Operating temperature [ C] -25 C + C Storage temperature [ C] -40 C + C Numbers of poles 3-4 Version fixed ltitude derating ltitude [mt] In [%] Ue [%] BB catalogue SDC20054D0203 3
4 SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors Thanks to the extremely low short-circuit current generated by PV panels, the use of molded-case switch-disconnectors is widely adopted both in combiner boxes and in the DC side of the inverters: Molded case switch-disconnectors up to 00V DC in compliance with IEC Electrical charachteristics Tmax PV switch-disconnectors in compliance with the IEC TD/PV T3D/PV T4D/PV T5D/PV T6D/PV T7D/PV ) Rated service current in category DC22 B, Ie () Number of poles (No.) Rated service voltage, Ue 00V DC 00V DC 00V DC 00V DC 00V DC 00V DC Rated impulse withstand voltage, Uimp (kv) Rated insulation voltage, Ui (V) 50V DC 50V DC 50V DC 50V DC 50V DC 50V DC Test voltage at industrial frequency for minute (V) Rated short-circuit making capacity, switch-disconnector only, Icm (k) Rated short-time withstand current for s, Icw (k) Versions F F F F F F Standard terminals FC Cu FC Cu F F F F Mechanical life (No. Operations) Electrical life 00V DC) (No. Operations) * 500* 500* 500* Basic dimensions W (mm/in) 02/ / / / / /.02 54/6.06 (manual) D (mm/in) /2.76 / / / / /7.0 (motorized) H (mm/in) 30/5.2 50/ / / / /0.55 Weight (with standard terminals only) (kg/lbs).2/2.65 2/ / /9.5 2/26.46 ) installation in vertical position only * openings with SOR or UVR 2.5/27.56 (manual) 4/30.86 (motorized) Molded case switch-disconnectors up to 500V DC in compliance with IEC Electrical charachteristics Tmax PV switch-disconnectors in compliance with the IEC T4D/PV-E T5D/PV-E T7D/PV-E ) Rated service current in category DC22, Ie () Number of poles (No.) Rated service voltage, Ue 500V DC 500V DC 500V DC Rated impulse withstand voltage, Uimp (kv) Rated insulation voltage, Ui (V) 500V DC 500V DC 500V DC Test voltage at industrial frequency for minute (V) Rated short-circuit making capacity, switch-disconnector only, Icm (k) Rated short-time withstand current for s, Icw (k) Versions F F F Standard terminals F F F Mechanical life (No. Operations) Electrical life 500V DC) (No. Operations) 000* 000* 500* Basic dimensions W (mm/in) 40/ / /.02 D (mm/in) 03.5/ / /7.0 H (mm/in) 205/8,07 205/ /0.55 Weight (with standard terminals only) (kg/lbs) 3.05/6.72 3,5/9.5 4/30.86 ) installation in vertical position only * openings with SOR or UVR 4 SDC20054D0203 BB catalogue
5 Molded case switch-disconnectors up to 000V DC in compliance with UL 489B Electrical charachteristics Tmax PV UL switch-disconnectors TN-D/PV T4N-D/PV T5N-D/PV T6N-D/PV T7N-D/PV ) Frame size () Rated service current () Number of poles (No.) Rated service voltage (V) 000V DC 000V DC 000V DC 000V DC 000V DC Short-circuit current withstand (k) Magnetic override (k) Versions F F F F F Connections* Jumpers Jumpers Jumpers Jumpers Jumpers Terminals provided with Jumper kit l -ES l-ef l-f Mechanical life (No. Operations) Electrical life 000V DC) (No. Operations) ** 500** 500** 500** Basic dimensions W (mm/in) 02/ /4.3 40/ / /.02 D (mm/in) / / / / /7.0 H (mm/in) 30/ / / / /0.55 Weight (with standard terminals only) (kg/lbs).2/ / /7.7 2/ /30.86 ) installation in vertical position only * Selection of one of the jumper connection options is mandatory for Tmax PV UL ** openings with SOR or UVR Whenever a consistent short-circuit current can be found (like in recombiner boxes), 000V DC automatic circuit-breakers are available in the Tmax range. Below is the UL489B automatic circuit-breaker offering: Molded case circuit-breakers up to 000V DC in compliance with UL 489B Electrical charachteristics Tmax PV UL MCCBs T4N/PV T5N/PV T6N/PV Frame size () Rated service current () Number of poles (No.) Rated service voltage (V) 000V DC 000V DC 000V DC Short-circuit interrupting 000V DC (k) Trip Unit TMD/TM TMF/TM TM Versions F F F Standard terminals F F F Connections* Jumpers Jumpers Jumpers Terminals provided with Jumper kit l l--es l-ef Mechanical life (No. Operations) Electrical life 000 VDC) (No. Operations) 000** 500** 500** Basic dimensions W (mm/in) 05/4.3 40/ /.02 D (mm/in) 03.5/ / /4.07 H (mm/in) 205/ / /0.55 Weight (with standard terminals only) (kg/lbs) 2.35/ /7.7 2/26.46 * Selection of one of the jumper connection options is mandatory for Tmax PV UL ** openings with SOR or UVR BB catalogue SDC20054D0203 5
6 SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors The UL circuit-breaker range is divided into three different frames, T4, T5 and T6, with an application range from 40 to 800 and breaking capacities up to 0k at 000V DC. The circuit-breakers are fitted with thermal magnetic trip units and are used for protection of direct current in solar networks. They allow the protection against overload with a thermal device that uses the bimetal technique, and protection against short-circuit with a magnetic device. The range of T4, T5 and T6 circuit-breakers for photovoltaic applications includes the following: - T4 (up to 50) circuit-breakers equipped with TMD thermal magnetic trip units with adjustable thermal threshold (I = 0.7 x In) and fixed magnetic threshold (I3 = 0 x In). - T4, T5 and T6 circuit-breakers equipped TM thermal magnetic trip units with adjustable thermal threshold (I = 0.7 x In) and adjustable magnetic threshold (I3 = 5 0 x In). Only for T5 225, 250 and 300 a special TMF trip unit is given: this TMF unit has fixed thermal threshold and adjustable magnetic threshold as indicated in the dedicated table (I3= ). The magnetic threshold for Tmax T4, Tmax T5 and Tma T6 is affected by a corrective factor of 5% because the TMD and TM releases were originally calibrated to be used in C networks. The curves for the PV line are shown below. T5/PV UL - Magnetic Threshold In I xIn xIn xIn xIn T4N/PV UL 200 In = t [s] T5N/PV UL 400 In = 225, 250, 300, t [s] I3 = 5,75,5 x In I3 = 5,75,5 x In x I T6N/PV UL 600 In = t [s] x I T6N/PV UL 800 In = t [s] I 3 = 5,75...,5 x In 0 - I 3 = 5,75...,5 x In x I x I 6 SDC20054D0203 BB catalogue
7 BB jumpers for pole-to-pole connection are the tested solution for a simplified and safe installation. s already mentioned, another innovation of the Tmax PV series is the possibility of accessorizing the breakers and switch-disconnectors with suitable jumpers. Tmax PV are 3 or 4 pole breakers: in order to break the direct current is necessary to put these poles in series on one, or both, the polarities. Jumpers between poles are therefore necessary: for example a (PS = Poles in Series) jumper kit puts all 4 poles of a breaker in series on one polarity. One jumper kit ordering code includes, 2 or 3 jumpers, plus required lugs and accessories if needed. The jumpers are realized with or without heat sinks, depending on the breaker frame and regulating standard, and UL and IEC kits for the same frames can be different. Jumper kits are divided into two versions: one for cabling all the poles on one single polarity (identified as or 3PS) and one for dividing the poles on both polarities (identified as 2+2PS or 2+PS). BB catalogue SDC20054D0203 7
8 Quick reference tables Tmax PV offers a wide choice of terminals for connection with busbars and cables. In the following tables, all the different options (related to the pole connections) are given: Tmax PV switch-disconnectors up to 00V DC in compliance with IEC IEC MCS Configuration & Supply EF l HR ES F Size T (60 ) lower upper - lower Compatible Standard Supply Not Compatible Compatible Not Compatible Not Compatible - upper T3 (200 ) lower upper - lower Compatible Standard Supply Compatible Not Compatible Not Compatible Compatible - upper 8 SDC20054D0203 BB catalogue
9 Tmax PV switch-disconnectors up to 00V DC in compliance with IEC IEC MCS Configuration & Supply EF l HR ES F Size T4 (250 ) lower upper - lower Compatible Compatible Compatible Not Compatible Not Compatible Standard Supply - upper T5 (500 ) lower upper - lower Compatible Compatible Not Compatible Not Compatible Not Compatible Standard Supply - upper BB catalogue SDC20054D0203 9
10 Quick reference tables Tmax PV switch-disconnectors up to 00V DC in compliance with IEC IEC MCS Configuration & Supply EF l HR ES F Size T6 (800 ) lower Compatible upper Not Compatible - lower Not Compatible Compatible Not Compatible Not Compatible Standard Supply Compatible - upper Not Compatible T7 (600 ) lower Compatible * Compatible upper Compatible Not compatible - lower Compatible Not compatible Standard Supply Not compatible Compatible - upper Not compatible Not compatible * Vertical (VR) terminals can be used too 0 SDC20054D0203 BB catalogue
11 Tmax PV switch-disconnectors and automatic circuit-breakers up to 000V DC in compliance with UL 489B UL MCS and automatic circuit-breakers Configuration & Supply EF l ES F Size T (00 ) lower upper - lower Not compatible Standard supply Not compatible Not compatible Not compatible - upper T4 (200 ) 2+ - lower 3PS - lower Not compatible Not compatible Included with jumpers kit Not compatible Not compatible 3PS - upper BB catalogue SDC20054D0203
12 Quick reference tables Tmax PV switch-disconnectors and automatic circuit-breakers up to 000V DC in compliance with UL 489B UL MCS and automatic circuit-breakers Configuration & Supply EF l ES F Size T5 ( ) 2+ - lower 3PS - lower Not compatible Included with jumpers kit "lug type" * Included with jumpers kit "lug type" ** Included with jumpers kit "busbar type" Not compatible 3PS - upper T6 (800 ) lower - lower Included with jumpers kit "busbar type" Not compatible Included with jumpers kit "lug type" Not compatible Not compatible * T5 300 and 400 only ** T5 225 and 250 only 2 SDC20054D0203 BB catalogue
13 Tmax PV switch-disconnectors and automatic circuit-breakers up to 000V DC in compliance with UL 489B UL MCS and automatic circuit-breakers Configuration & Supply EF l ES F Size T7 (000 ) lower upper - lower Not compatible Not compatible Included with jumpers kit "lug type" Not compatible Included with jumpers kit "busbar type" - upper BB catalogue SDC20054D0203 3
14 Quick reference tables Tmax PV switch-disconnectors up to 500V DC in compliance with IEC IEC 500V DC MCS Configuration & Supply l F Size T lower upper - lower Compatible Compatible Standard Supply - upper T upper Compatible Not compatible Standard Supply T upper lower * Not compatible Compatible Standard Supply - lower * (*) Valid only when 250 jumpers are used 4 SDC20054D0203 BB catalogue
15 Derating Temperature perfomances of Tmax PV at temperatures other than 40 C and for different altitude are reported in the following tables: TD/PV IEC T3D/PV IEC T4D/PV IEC F- T5D/PV IEC F- Temperature [ C] I [] Temperature [ C] I [] Temperature [ C] I [] Temperature [ C] I [] T6D/PV IEC F-l T7D/PV 250 IEC F-l Temperature [ C] I [] Temperature [ C] I [] T7D/PV 600 IEC F-l Temperatura [ C] I [] Sum-Up table for temperature derating Temperature [ C] / In [] TD/PV IEC T3D/PV IEC T4D/PV IEC T5D/PV IEC T6D/PV IEC T7D/PV 250 IEC T7D/PV 600 IEC BB catalogue SDC20054D0203 5
16 Derating Derating T MCS PV UL Derating T4 MCS PV UL Derating T5 MCS PV UL Derating T6 MCS PV UL Derating T7 MCS PV UL With 40 C Cables With 40 C Cables With 40 C Cables With 40 C Cables With 40 C Cables Derating T4 PV UL (MCCB) With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T5 PV UL (MCCB), 225 version With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T5 PV UL (MCCB), 250 version With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T5 PV UL (MCCB), 300 version With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T5 PV UL (MCCB), 400 version With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T6 PV UL (MCCB), 600 version With 40 C Cables refer to page 7 for cable dimensions With 50 C Cables refer to page 7 for cable dimensions Derating T6 PV UL (MCCB), 800 version Test performed by busbars Sum-Up table for temperature derating UL switch-disconnector Temperature [ C] / In [] T T4 T5 T6 T UL automatic circuit-breakers: 40 C cables Temperature [ C] / In [] T4 T5 T UL automatic circuit-breakers: 50 C cables Temperature [ C] / In [] T4 T5 T SDC20054D0203 BB catalogue
17 Wiring Please note that for UL MCCBs two deratings are given, according to UL489B: one when 40 C cables are used, and one when 50 C cables are used. Cables dimensions are given by UL489B. Below, please find the relevant cabling info: Wire options for Tmax PV - UL T 00 mbient temp 40 C 50 C In () required wires (number x section) required wires (number x section) 00 x 3 WG x /0 WG T4 200 mbient temp 40 C 50 C In () required wires (number x section) 40 x 8 WG x 6 WG 50 x 8 WG x 4 WG 80 x 4 WG x 2 WG 00 x 3 WG x /0 WG 25 x WG x 2/0 WG 50 x /0 WG x 3/0 WG 200 x 3/0 WG x 300 kcmil T5 400 mbient temp 40 C 50 C In () required wires (number x section) 225 x 4/0 WG x 350 kcmil 250 x 250 kcmil x 400 kcmil 300 x 350 kcmil 2 x 3/0 WG x 3/0 WG or x 500 kcmil 2 x 300 kcmil T6 600 mbient temp 40 C 50 C In () required wires (number x section) x 350 kcmil 3 x 300 kcmil T7 000 mbient temp 40 C 50 C In () required wires (number x section) x 400 kcmil 4 x 400 kcmil BB catalogue SDC20054D0203 7
18 Power Losses and Insulation Distances When a current passes through a molded case circuit-breaker or switch-disconnector, it dissipates heat. The Tmax series is well known for having very few power losses. Below, please find a table with information for both UL and IEC power losses. Type Trip Unit Version In () P (W/pole) T MCS UL 00 7,5 IEC 60 5 T3 MCS IEC T4 MCS UL 200 8,9 IEC TMD UL 40 3,8 50 3,9 TM UL 80 6,4 00 7,6 25 7, T5 MCS UL IEC TM UL T6 MCS UL UL IEC 48 TM UL T7 MCS UL IEC B METLLIC FRME C IEC Insulation distances for installation in metallic cubicle [mm] B [mm] C [mm] With jumpers No jumpers With jumpers No jumpers With jumpers No jumpers TD/PV T3D/PV T4D/PV T4D/PV-E T5D/PV T5D/PV-E ,5 22,5 22,5 22,5 T6D/PV T7D/PV T7D/PV-E 250 T7D/PV 600 T7D/PV-E UL489 Insulation distances for installation in metallic cubicle [mm] B [mm] C [mm] TN-D/PV T4N-D/PV T4N/PV T5N-D/PV T5N/PV T6N-D/PV* T6N/PV* T7N-D/PV * switchgear protruded 35 mm Insulation distances in air between two Tmax PV with jumpers put side by side* [mm] IEC UL T T T T T T * insulation distances can be reduced using suitable insulation barriers between breakers UL489B cubicle dimensions for Tmax PV H [mm] W [mm] D [mm] T/PV UL T4/PV UL T5/PV UL T6/PV UL T7/PV UL SDC20054D0203 BB catalogue
19 Dimensions TD/PV ccording to IEC solution, terminals for Upper Supply solution, Terminals for Upper Supply Upper supply Upper supply UPPER SUPPL FcCU EF HR UPPER SUPPL FcCU EF HR HR HR 7Nm 7Nm EF Ø8,5 Ø 6.2 EF Ø 6.2 7Nm Ø8.5 7Nm FC Cu FC Cu 7Nm ,5 2x2 7Nm 38, 0, , 0, solution, Lower Supply solution, Lower Supply LOWER SUPPL LOWER SUPPL * FcCU EF HR * FcCU EF HR * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from below. BB catalogue SDC20054D0203 9
20 Dimensions T3D/PV solution, Upper Supply Upper supply F EF l UPPER SUPPL F COMPRTMENT DEPTH PROFONDIT' QUDRO 03 EF FC Cul Ø 0 Ø Nm 85mm ccording to IEC solution, Lower Supply F EF l LOWER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top 20 SDC20054D0203 BB catalogue
21 solution, Upper Supply Upper supply F EF l UPPER SUPPL F COMPRTMENT DEPTH PROFONDIT' QUDRO EF FC Cul Ø Nm 85mm Ø solution, Lower Supply F EF l LOWER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top BB catalogue SDC20054D0203 2
22 Dimensions T4D/PV - T4D/PV-E ccording to IEC solution, Lower Supply UP TO 00V F l 85mm 2 EF LOWER SUPPL T4D/PV-E only UP TO 500V F = = max 9, Ø (max) l 85mm EF Ø solution, Upper Supply T4D/PV-E only UP TO 00V UP TO 500V Upper supply Upper supply F l 85mm 2 EF UPPER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top 22 SDC20054D0203 BB catalogue
23 solution, Lower Supply UP TO 00V F l 85mm 2 EF LOWER SUPPL T4D/PV-E only UP TO 500V F = = 59.5 l 85mm 2 EF max 9, Ø (max) Ø Ø solution, Upper Supply T4D/PV-E only UP TO 00V UP TO 500V Upper supply Upper supply F l 85mm 2 EF UPPER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top BB catalogue SDC20054D
24 Dimensions T5D/PV ccording to IEC solution, Upper Supply Upper supply F EF UPPER SUPPL F EF max Ø Ø COMPRTMENT DEPTH PROFONDIT' QUDRO x Ø x Ø Nm solution, Lower Supply F EF LOWER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top 24 SDC20054D0203 BB catalogue
25 solution, Upper Supply Upper supply F EF UPPER SUPPL F EF max Ø x Ø COMPRTMENT DEPTH PROFONDIT' QUDRO Nm solution, Lower Supply F EF LOWER SUPPL * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top BB catalogue SDC20054D
26 Dimensions T5D/PV-E ccording to IEC Configurations without jumpers Upper supply ONL F UPPER SUPPL ONL F FC Cu 86 46,5 46,5 46,5 max 35 ø 0, ,5 5 0 max 28 Nm ,5 46,5 46,5 8 Nm 34, ,5 25 Nm max 86,25 02, ,2 2,7 5,5 86,25 59, ,5 34,25 86,25 05 _ >3 40 _ <2 69,75 _ > _ <2 ø2,5 ø2,5 40 Jumper examples Example with jumper ( Upper Supply) 28 Nm 26 SDC20054D0203 BB catalogue
27 62.5 solution, Upper Supply Upper supply ONL F UPPER SUPPL ONL F max , x Ø COMPRTMENT DEPTH PROFONDIT' QUDRO 40 2x Ø Nm BB catalogue SDC20054D
28 8 8 Dimensions T6D/PV ccording to IEC solution, Lower Supply F l EF LOWER SUPPL F = = ø 6 9 Nm l EF 20 Ø ø solution, Upper Supply Upper supply F l UPPER SUPPL 28 SDC20054D0203 BB catalogue
29 solution, Lower Supply F l EF LOWER SUPPL F = = ø Nm 6 l EF 20 Ø ø Ø solution, Upper Supply Upper supply F l UPPER SUPPL BB catalogue SDC20054D
30 Dimensions T7D/PV - T7D/PV-E ccording to IEC Configurations without jumpers (cables) F T7D/PV 8 Nm T7D/PV-E M T7D/PV M 458 = = Upper Supply = = 05 2 l (4 x 240 mm ) T7D/PV 43 Nm T7D/PV-E M T7D/PV M UP TO 500V UP TO 500V Lower Supply 8 Nm 458 = = = = ø2. 5 UP TO 500V UP TO 500V CON MOSTRIN WITH FLNGE SENZ MOSTRIN WITHOUT FLNGE T7D/PV 4 47 T7D/PV M T7D/PV-E M Nm SDC20054D0203 BB catalogue
31 Configurations with jumpers (possible solutions) UPPER SUPPL EF l F F l EF 00 V 00 V 500 V 500 V 250 LOWER SUPPL 600 VR HR ES EF l F F l EF ES HR VR 00 V 00 V 500 V 500 V 250 UPPER SUPPL 600 EF F F EF 00 V 00 V 500 V 500 V LOWER SUPPL ES EF l F F l EF ES 00 V 00 V 500 V 500 V BB catalogue SDC20054D0203 3
32 25 44 Dimensions T7D/PV ccording to IEC LOWER SUPPL UPPER SUPPL LOWER SUPPL ES EF Nm Nm ø 5 = = = ø F 480 FC Cu l 2 (4 x 240 mm ) T7D/PV Nm = = = = T7D/PV M T7D/PV-E M 28 ø2.5 CON MOSTRIN SENZ MOSTRIN WITH FLNGE WITHOUT FLNGE T7D/PV 4 47 T7D/PV M 64 T7D/PVE- M Nm HR VR 25 5 ø = = = 20 = ø 5 * UPPER SUPPL - ccording to scheme K, terminals configurations must be symmetrical respect to x-x CB axis 32 SDC20054D0203 BB catalogue
33 LOWER SUPPL UPPER SUPPL LOWER SUPPL ES EF Nm Nm ø ø F FC Cu l 2 (4 x 240 mm ) T7D/PV T7D/PV-E M T7D/PV M Nm = = = = 43 Nm CON MOSTRIN SENZ MOSTRIN WITH FLNGE WITHOUT FLNGE T7D/PV 4 47 T7D/PV M T7D/PV-E M ø2.5 * UPPER SUPPL - ccording to scheme K, terminals configurations must be symmetrical respect to x-x CB axis BB catalogue SDC20054D
34 Dimensions T/PV ccording to UL 489B Jumper Kit TN-D/PV- for connection grounded system wiring, lower supply Jumper Kit TN-D/PV-B for connection B ungrounded system wiring, lower supply Connection Connection B LOWER SUPPL " 0.55" 36.42" " 0.98" 0.98" 38..5" " " 0.6" 0.04" " 0.44" 7 2.8" (see fig.h) " 7Nm 62 lb in LOWER SUPPL " 0.55" 36.42" " 0.98" 0.98" 38..5" " " 0.6" 0.04" " 0.44" 7 2.8" (see fig.h) " 7Nm 62 lb in Jumper Kit TN-D/PV- for connection grounded system wiring, upper supply Jumper Kit TN-D/PV-B for connection B ungrounded system wiring, upper supply UPPER SUPPL Upper supply* Connection UPPER SUPPL Upper supply* Connection B * Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top. 34 SDC20054D0203 BB catalogue
35 Dimensions T4/PV ccording to UL 489B 3PS LOWER SUPPL " " 35.38" Jumper Kit T4N/PV- for connection grounded system wiring 3PS, lower supply " 35.38" " 35.38" Connection 3PS 50mm² 85mm² l 2PS+ LOWER SUPPL " " 35.38" Jumper Kit T4N/PV-B for connection B ungrounded system wiring 2PS+, lower supply Connection B 2PS " 35.38" " 35.38" 50mm² 85mm² l " " S S " ".38" " " " 3 0.2" 0.04" R " 09/4.29" R S 50 mm 2 85 mm ".38" " 0.75" " Jumper Kit T4N/PV- for connection grounded system wiring 3PS, upper supply " ".38" " " " 3 0.2" 0.04" R " 09/4.29" R S 50 mm 2 85 mm ".38" " 0.75" " Jumper Kit T4N/PV-B for connection B ungrounded system wiring 2PS+, upper supply Upper supply Connection 3PS l 2PS+ UPPER SUPPL NOT VILBLE 3PS UPPER SUPPL Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top Le uniche configurazioni utilizzabili sono quelle riportate in questo documento. The configurations here represented are the only ones available. BB catalogue SDC20054D
36 Dimensions T5/PV ccording to UL 489B Jumper l Kit T5N/PV UL- for connection grounded system wiring 3PS, lower supply 225 Jumper l Kit T5N/PV UL-B for connection B ungrounded system wiring 2PS+PS, lower supply 225 3PS LOWER SUPPL + 3PS " " Ø " 32.26" 2PS+PS LOWER SUPPL 2PS+PS " " Ø " 32.26" " ".83" " " 46.8" " = =.83" " " 46.8" " " " ".83" " " 3 0.2" ".52" " COMPRTMENT DEPTH PROFONDIT' QUDRO " ".83".83" " " " 3 0.2" 0.04" 38.49" " PROFONDIT' QUDRO COMPRTMENT DEPTH " + 3PS UPPER SUPPL - UPPER SUPPL NOT VILBLE Upper supply 3PS 36 SDC20054D0203 BB catalogue
37 Jumper l Kit T5N/PV UL- for connection grounded system wiring 3PS, lower supply 250 Jumper l Kit T5N/PV UL-B for connection B ungrounded system wiring 2PS+PS, lower supply 250 3PS 2PS+PS 3PS LOWER SUPPL " 27 " Ø " " 2PS+PS LOWER SUPPL " 27 " Ø " " " ".83" " " 46.8" " = =.83" " " 46.8" " " " " " ".83" " " 3 0.2" ".52" " COMPRTMENT DEPTH PROFONDIT' QUDRO " ".83".83" " " " 3 0.2" 0.04" 38.49" " PROFONDIT' QUDRO COMPRTMENT DEPTH " + 3PS UPPER SUPPL - UPPER SUPPL NOT VILBLE Upper supply 3PS BB catalogue SDC20054D
38 Dimensions T5/PV ccording to UL 489B 3PS LOWER SUPPL " " Jumper Kit T5N/PV UL- for connection grounded system wiring 3PS, lower supply x Ø 2.5 3PS 0.85" ".83" " 56,5 2.22" " 28." " 46.8" " " Jumper Kit T5N/PV UL-B for connection B ungrounded system wiring 2PS+PS, lower supply PS+PS LOWER SUPPL " = =.83" + 2PS+PS - 56,5 2.22" " 28." " 46.8" 2 x Ø " " " ".83" " " 3PS UPPER SUPPL " " 25.52" 0.98" " COMPRTMENT DEPTH PROFONDIT' QUDRO " - Ø " " ".83".83" " " " 3 0.2" 0.04" " 0.98" " PROFONDIT' QUDRO COMPRTMENT DEPTH " Ø " Upper supply 3PS UPPER SUPPL NOT VILBLE Ø5.5 (M5) 0.22" ".83" = = = = WITH FLNGE CON MOSTRIN (mm) WITHOUT FLNGE SENZ MOSTRIN WITH FLNGE CON MOSTRIN (inch) WITHOUT FLNGE SENZ MOSTRIN 5 B " 4.53" 4.2" 4.2" C " 2.38" " = = " = = 2 Nm 7. lb in = = B C Label that indicates type of jumper kit installed on breaker only for Ø5.5 (M5) 0.22" 38 SDC20054D0203 BB catalogue
39 Busbar Jumper ES Kit T5N/PV UL- for connection grounded system wiring 3PS, lower supply Busbar Jumper ES Kit T5N/PV UL-B for connection B ungrounded system wiring 2PS+PS, lower supply 3PS LOWER SUPPL 3PS ES " 40.57" Ø 0.43" 2PS+PS LOWER SUPPL 2PS+PS ES " 40.57" Ø 0.43" " = " = " Ø 0.43" " " " 46.8" " = " = " " " " 46.8" " " B " " " 3.22" 3 0.2" 0.04" " " " PROFONDIT' QUDRO COMPRTMENT DEPTH " " 2.27" " " Ø 0.43" 3.22" 3 0.2" " COMPRTMENT DEPTH PROFONDIT' QUDRO " 3PS UPPER SUPPL NO! OK B + - 3PS B ES Upper supply UPPER SUPPL NOT VILBLE BB catalogue SDC20054D
40 Dimensions T6/PV 600 ccording to UL 489B LOWER SUPPL Jumper Kit T6N/PV- for connection grounded system wiring, lower supply l LOWER SUPPL Jumper Kit T6N/PV-B for connection B ungrounded system wiring, lower supply l " " " " " " " 6 4.6" " 48.89" 2.76" " 2.76" 2.76" " " " " " " " " " = = 9 3.6" " " " " " 05 4." " " " 44.73" " " = = " 8 7." 05 4." 44.73" 2.8" " 2.8" 2.8" 280 " " 3 0.2" " " 6 6.3" " " 280 " " 2.76" " " " 6 6.3" " " Ø9 0.75" " Ø9 0.75" " 600 3x300 Kcmil " 600 3x300 Kcmil " 44.73" " 44.73" UPPER SUPPL NOT VILBLE UPPER SUPPL NOT VILBLE 40 SDC20054D0203 BB catalogue
41 Dimensions T6/PV 800 ccording to UL 489B solution, terminals for Lower Supply solutions, terminals for Lower Supply EF EF LOWER SUPPL LOWER SUPPL 2.8" " 2.8" 2.8" " " 6 4.6" " " 2.8" " 2.8" 2.8" " " 6 4.6" " " " " " " " " " " " " 05 4." 284.2" " " " 5.3 " 44.73" " " " " " " " 284.2" " 44.73" 05 4." 279 " Ø4 0.6" " " " " 6 6.3" " 279 " 50 2" Ø4 0.6" " " " " 6 6.3" " " Ø 4 0.6" " Ø 4 0.6" " " 50 2" 50 2" UPPER SUPPL NOT VILBLE UPPER SUPPL NOT VILBLE BB catalogue SDC20054D0203 4
42 Dimensions T7/PV ccording to UL 489B Upper supply UPPER SUPPL Connection l F Upper supply UPPER SUPPL Connection B l F LOWER SUPPL LOWER SUPPL * Connection l F * Connection B l F 42 SDC20054D0203 BB catalogue
43 Kit T7N-D/PV- for connection grounded system wiring l - Example for Upper Supply Kit T7N-D/PV-B for connection B ungrounded system wiring l - Example for Upper Supply " " " " " " 43 Nm 380 lb in " " " " 43 Nm 380 lb in " " " " " " " " " " 2.76 " 2.76 " 2.76 " " CON MOSTRIN WITH FLNGE SENZ MOSTRIN WITHOUT FLNGE mm 65 in 6.50" 6.69" 2.76 " 2.76 " 2.76 " " CON MOSTRIN WITH FLNGE SENZ MOSTRIN WITHOUT FLNGE mm 65 in 6.50" 6.69" F - Example for Upper Supply F - Example for Upper Supply " " " " " " " " " " " " " " " " 2.76 " 2.76 " 2.76 " " CON MOSTRIN WITH FLNGE SENZ MOSTRIN WITHOUT FLNGE mm in 4.9"...6.5" 6.69" 2.76 " 2.76 " 2.76 " " CON MOSTRIN WITH FLNGE SENZ MOSTRIN WITHOUT FLNGE mm in 4.9"...6.5" 6.69" * LOWER SUPPL - ccording to indicated schemes, terminals configurations must be symmetrical respect to x-x CB axis BB catalogue SDC20054D
44 Codes Tmax PV IEC 00V & 500V switch-disconnectors Breakers Code Description SD06986R TD/PV 60 4p F FC Cu 00V DC SD069822R T3D/PV 200 4p F FC Cu 00V DC SD069823R T4D/PV 250 4p F F 00V DC SD069824R T5D/PV 500 4p F F 00V DC SD069825R T6D/PV 800 4p F F 00V DC SD069826R T7D/PV 250 4p F F 00V DC SD069827R T7D/PV 250 4p F F M 00V DC SD069828R T7D/PV 600 4p F F 00V DC SD069829R T7D/PV 600 4p F F M 00V DC SD073559R T4D/PV-E 250 4p F F 500V DC SD076898R T5D/PV-E 500 4p FF 500V DC SD073560R T7D/PV-E 250 4p F F M 500V DC SD07356R T7D/PV-E 600 4p F F M 500V DC Kit Jumpers Code Description SD069876R KIT 2 JUMPER 2+2PS TD/PV 60 4p SD069877R KIT 3 JUMPER TD/PV 60 4p SD07662R KIT 2JUMPER U 2+2PS T3D/PV 200 SD07663R KIT 3JUMPER U T3D/PV 200 SD0454R KIT 2JUMPER U 2+2PS T4D/PV 250 SD0455R KIT 3JUMPER U T4D/PV 250 SD0456R KIT 2JUMPER U 2+2PS T5D/PV 500 SD0457R KIT 3JUMPER U T5D/PV 500 SD076899R KIT 2JUMPER U 2+2PS T5D/PV-E V DC SD049R KIT 2JUMPER U 2+2PS T6D/PV 800 SD0492R KIT 3JUMPER U T6D/PV 800 SD0429R KIT JUMPER U 2+2PS T7D/PV 250 SD043R KIT JUMPER U 2+2PS T7D/PV 600 SD0430R KIT JUMPER U T7D/PV 250 SD0432R KIT JUMPER U T7D/PV 600 Tmax PV can be accessoried with Tmax series accessories, except for the following exceptions: Frame size TD PV T3D PV T4D PV T5D PV T6D PV T7D PV T7D PV M Incompatibilities Interlocks, KLC, PLL Interlocks, KLC, PLL Interlocks Interlocks Interlocks Interlocks Interlocks ccessories part number, wirings and data can be found in the Tmax IEC Technical Catalogue and Tmax UL489 Technical Catalogue. 44 SDC20054D0203 BB catalogue
45 Tmax PV UL489B 000V switch-disconnectors & automatic circuit-breakers Breakers Code Description SD0004R TN-D/PV 00 MCS UL 4p F FC Cu 000V DC SD0460R T4N-D/PV 200 MCS UL 3p F F 000V DC SD046R T4N/PV 200 UL TMD 40 3p F F 000V DC SD0462R T4N/PV 200 UL TMD 50 3p F F 000V DC SD0463R T4N/PV 200 UL TM p F F 000V DC SD0467R T4N/PV 200 UL TM p FF 000V DC SD0468R T4N/PV 200 UL TM p FF 000V DC SD0469R T4N/PV 200 UL TM p FF 000V DC SD04R T4N/PV 200 UL TM p FF 000V DC SD07989R T5N/PV 250 UL TMD p FF 000V DC SD079820R T5N/PV 225 UL TMD p FF 000V DC SD07988R T5N/PV 300 UL TMD p FF 000V DC SD0472R T5N/PV 400 UL TM p FF 000V DC SD047R T5N-D/PV 400 MCS UL 3p F 000V DC SD0493R T6N-D/PV 600 MCS UL 4p F F 000V DC SD0494R T6N-D/PV 800 MCS UL 4p F F 000V DC SD0495R T6N/PV 800 UL TM p FF 000V DC SD0496R T6N/PV 800 UL TM p FF 000V DC SD0448R T7N-D/PV 000 MCS UL 4p F F M 000V DC Kit Jumpers Code SD0424R SD0425R SD0483R SD0484R SD0485R SD0486R SD0487R SD0488R SD074504R SD074505R SD07982R SD079823R SD079824R SD079825R SD0499R SD0500R SD050R SD0502R SD045R SD0452R SD08762R SD08763R Description KIT 2 JUMPER 2+2PS TN-D/PV-B 00 UL 4p KIT 3 JUMPER TN-D/PV- 00 UL 4p KIT JUMPER 2+PS T4N/PV-B 00 UL 3p KIT JUMPER 2+PS T4 PV-B 200 UL 3p KIT 2 JUMPER 3PS T4N/PV- 00 UL 3p KIT 2 JUMPER 3PS T4 PV- 200 UL 3p KIT JUMPER 2+PS T5 PV-B 400 UL 3p cables KIT 2 JUMPER 3PS T5 PV- 400 UL 3p cables KIT JUMPER 2+PS T5 PV-B 400 UL 3p busbars KIT 2 JUMPER 3PS T5 PV- 400 UL 3p busbars KIT JUMPER 2+PS T5 PV-B 225 UL 3p KIT JUMPER 2+PS T5 PV-B 250 UL 3p KIT 2 JUMPER 3PS T5 PV- 225 UL 3p KIT 2 JUMPER 3PS T5 PV- 250 UL 3p KIT 2 JUMPER 2+2PS T6 PV-B 600 UL 4p KIT 3 JUMPER T6 PV- 600 UL 4p KIT 2 JUMPER 2+2PS T6 PV-B 800 UL 4p KIT 3 JUMPER T6 PV- 800 UL 4p KIT 2 JUMPER 2+2PS T7N-D/PV-B 000 UL 4p cables KIT 3 JUMPER U T7N-D/PV- 000 UL 4p cables KIT 2 JUMPER 2+2PS T7N-D/PV-B 000 UL 4p busbars KIT 3 JUMPER U T7N-D/PV- 000 UL 4p busbars Tmax PV can be accessoried with Tmax series accessories, except for the following exceptions: Frame size TD PV T3D PV T4D PV T5D PV T6D PV T7D PV T7D PV M Incompatibilities Interlocks, KLC, PLL Interlocks, KLC, PLL Interlocks Interlocks Interlocks Interlocks Interlocks ccessories part number, wirings and data can be found in the Tmax IEC Technical Catalogue and Tmax UL489 Technical Catalogue. BB catalogue SDC20054D
46
47
48 Contact us BB SCE division of BB S.p.. L.V. Breakers Via Pescaria, Bergamo Phone: Fax: The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice. Copyright 205 BB. ll rights reserved. SDC20054D Stay tuned. Discover more by visiting the webpages reserved to Tmax PV and be always up-to-date with the latest edition of the catalogue.
General information Circuit breakers for power distribution T1 T3
Circuit breakers for power distribution T1 T3 T1 T2 T3 T1 1P T1 T2 T3 UL 489 CSA C22.2 Frame size A 100 100 100 225 Number of poles Nr 1 3, 4 3, 4 3, 4 Rated voltage AC (50-60 Hz) V 277 600Y / 347V 480
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Technical catalogue - Ordering Codes. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated
Technical catalogue - Ordering Codes SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated New SACE Tmax XT. Simply XTraordinary. Today a highly advanced range of circuit-breakers
Tmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
Manual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility
SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
Technical catalog. FORMULA UL New low voltage molded case circuit breakers up to 250A. Power and productivity for a better world TM
Technical catalog FORMULA UL New low voltage molded case circuit breakers up to 2A Power and productivity for a better world TM Index Main characteristics 1 Circuit breakers for power distribution 2 Accessories
Breaking and protection devices
Breaking and protection devices 05 POWER GUIDE 2009 / BOOK 05 INTRO The purpose of selecting a protection device is to perform two essential functions: to protect people and to protect trunking, while
White paper. ABB solutions for switching and protection of low speed wind turbines
White paper ABB solutions for switching and protection of low speed wind turbines ABB solutions for switching and protection of low speed wind turbines Index 1 Introduction...2 2 Full converter configuration...4
The complete range of consumer switchboards and switchgear
Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial
ZS10 Screw Clamp Terminal Block
Technical Datasheet 1SNK 161 004 D0201 ZS10 Screw Clamp Terminal Block Feed-through Catalogue Page 1SNK 161 004 S0201 10 mm² 6 AWG 8 mm 0.315 in Spacing Features and Benefits 53 2.09" Save space by connecting
Emax DC. Annex to the technical catalogue. Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications
Annex to the technical catalogue Emax DC Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications 1SDC200012D0201 Index SACE Emax DC automatic circuit-breakers...
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil
Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
Brochure April 2012. Moulded-case circuit-breakers overview SACE Tmax
Brochure April 0 Moulded-case circuit-breakers overview SACE Tmax A single family of moulded-case circuit-breakers up to 00 A Tmax moulded-case circuit-breakers guarantee an extremely high performance
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
Thermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES
The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions
Circuit Breakers. Next Generation of Protection Capabilities
Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
VL circuit breakers. Information guide. www.usa.siemens.com/circuitbreakers
VL circuit breakers Information guide www.usa.siemens.com/circuitbreakers Table of contents Technical data 2 8 DG 150A frame 9 14 FG 250A frame 15 20 JG 400A frame 21 26 LG 600A frame 27 32 MG 800A frame
EPL225 Series. 225 Watts. www.xppower.com. AC-DC Power Supplies. Models & Ratings. Summary
225 Watts 50 W Convection/ 225 W Forced-cooled Ratings 2 by 4 Footprint Low.26 Profile 2 V Fan Output High Efficiency, up to 95% ITE & Medical pprovals High Power Density Less than 0.5 W No Load Input
FUSERBLOC. 20 to 1250 A Manual operation. 142 General Catalogue 2011-2012 SOCOMEC. Fuse combination switches
FUSERBLOC Fuse combination switches appli_8_a fuser_548_a cat fuser_59_a cat fuser_52_a cat 2 to 25 A Manual operation Function FUSERBLOC are manually operated multipolar fuse combination switches. They
Index. 17 - Molded case circuit breakers. Molded case circuit breakers. Tmax UL489B Photovoltaic circuit breakers...17.67-17.70
Molded case circuit breakers Index Molded case circuit breakers - Molded case circuit breakers Formula...1 -.10 General information Introduction...1 Circuit breakers for power distribution...2 explanation...3
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)
Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of
Tmax. Molded case circuit breakers. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]. Tmax.
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
The power distribution board that sets new standards
SIVACON The power distribution board that sets new standards SIVACON S4 safe, cost-efficient and flexible Answers for infrastructure. Contents We support you with system 04 05 Maximum safety is our top
ZS6-S Screw Clamp Terminal Blocks Disconnect with blade
Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
ZS25 Screw Clamp Terminal Blocks Feed-through
Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
Catalogue May 2015. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole
Catalogue May 2015 EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Contents Introduction 1 Overview 1-pole 2 Overview 2-pole 3 Overview 3-pole 4 Overview 4-pole 5 Electronic Fuse Monitoring 6 Busbar
Catalog. Modular DIN rail components Installation contactors
Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation
NEXT SOLUTION EXPERT SOLUTION EXCELLENT SOLUTION. Super Solution
NEXT SOLUTION EXPERT SOLUTION EXCELLENT SOLUTION Super Solution Low voltage circuit breakers Susol LV circuit breakers Super Solution Contents Overview Electrical characteristics Trip units Accessories
Catalog January. Heavy industrial power applications Motor contactors and starters
Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type
Low voltage circuit breakers. Working with trip characteristic curves
Low voltage circuit breakers Working with trip characteristic curves Index 1. Introduction... 2 2. Main Definitions... 3 3. ABB Low Voltage Circuit Breakers complying with the Standards UL 489 and UL
Technical catalogue - 2015.10. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A
Technical catalogue - 2015.10 SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A Construction Characteristics 1 The SACE Tmax XT Ranges 2 Accessories 3 Characteristic Curves and Technical
ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket
Technical Datasheet SNK636D00 Catalogue Page SNK636S00 ZS-SF-T Screw Clamp Terminal Blocks For x 0 and x fuses - with test socket - Protect your circuit with x and x0 fuse terminal blocks (fuse not supplied
Tmax. Technical catalogue. Low voltage moulded-case circuit-breakers up to 630 A 1SDC210004D0204
Technical catalogue Tmax Low voltage moulded-case circuit-breakers up to 630 A 1SDC210004D0204 VERVIEW MAIN CHARACTERISTICS THE RANGES ACCESSORIES CHARACTERISTIC CURVES AND TECHNICAL INFORMATION WIRING
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data
Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors Technical Data Table of Contents Introduction... 4 Definitions... 5 Product Range... 8 Product Line Overview...11
Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations
Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has
ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket
Technical Datasheet SNK64D00 Catalogue Page SNK64S00 ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket - Ease your test operations with the built-in test sockets, - Screwdriver
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
ABB Inc. April 19, 2011 Slide 1
ABB Automation & Power World: April 18-21, 2011 Allen Austin - Solar Segment Manager North America, Low Voltage Products WLP-123-1-CEU Solar applications for low voltage products ABB Inc. April 19, 2011
Breakers and Switches. Switches Switch-disconnectors OT, OETL, OTDC and OTM
Breakers and Switches Switches Switch-disconnectors OT, OETL, OTDC and OTM Switch-disconnectors OT 16...2500, OETL 3150, OTDC16...32 and OTM160...2500 Contents 4 Product overview, features 8 Technical
Working with the Trip Characteristic Curves of ABB SACE Low Voltage Circuit-Breakers 1SDC007400G0201
Low Voltage Circuit-Breakers 1SDC74G21 Index 1. Introduction... 2 2. Main Definitions... 3 3. complying with the Standards UL 489 and UL 166 3.1 Generalities on Low Voltage Circuit Breakers... 7 3.2...
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
DC disconnects for solar photovoltaic installations. Connecting the. power of the sun
DC disconnects for solar photovoltaic installations Connecting the power of the sun Solar energy is heating up Interest in renewable energy sources has never been greater, and the fastest growing of these
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
DMX-K-DRV. Integrated Step Motor Driver + (Basic Controller) Manual
DMX-K-DRV Integrated Step Motor Driver + (Basic Controller) Manual DMX-K-DRV Manual page 1 rev 1.33 COPYRIGHT 2007 ARCUS, ALL RIGHTS RESERVED First edition, June 2007 ARCUS TECHNOLOGY copyrights this document.
Renewable energy. Inverters - Socomec G-1. Load break switches (Isolators) - Socomec G-2. Fuses - df G-3. Fuse bases.
G Product page Inverters - Socomec G-1 Load break switches (Isolators) - Socomec G-2 Fuses - df G-3 Fuse bases Surge protection - df G-3 - Wohner G-5 - CPT G-4 - Dehn G-5 Connectors - Wieland G-6 Cable
BB800 Off-Grid Solar System
BB800 Off-Grid Solar System KEY PRODUCT FEATURES Control Box & Charge Controller 1000W of Solar Panels 4x200Ah of SLA Batteries in series 2KW Inverter Output Power Solar Panel & Battery Mounting Our entry
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
more than a breaker it s a breakthrough Compact NSX
Compact NSX, more than a breaker it s a breakthrough Compact NSX 100-630 A Intelligent outlook Today, we are living in an increasingly booming and fast changing world where energy is key. More than ever,
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Type RP73 Series. SMD High Power Precision Resistors. Key Features. Applications. Characteristics - Electrical - RP73 Series - Standard
Key Features n High precision - tolerances down to 0.05% n Low TCR - down to 5ppm/ C n Stable high frequency performance n Operating temperature -55 C to +155 C n Increased power rating - up to 1.0W n
Power Station Photovoltaic Energy
Power Station Photovoltaic Energy A Complete Range of Power Stations for Grid-connected Photovoltaic Plants Photovoltaic Energy 3 Power Station A New Generation of Power Stations 4 After years of success
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager
Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager SACE Emax 2 From Circuit-Breaker to Power Manager Our customers need more efficient solutions, to Increase
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Redundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
Residual current devices
Residual devices Residual devices Description The devices offer a wide range of product for all of your fault protection needs. & C large offering for standard instantaneous and selective C and types.
Bimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
RELAYS Solar Energy Systems
RELAYS Solar Energy Systems FUJITSU COMPONENTS CONTENTS Fujitsu relays for solar applications DC voltage versions - AC voltage versions - Latching versions RELAY PRODUCT LINE UP - SOLAR ENERGY SYSTEMS
Protection and Connection. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole
Protection and Connection EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Contents Introduction 1 Overview 1 and 2-pole 2 Overview 3-pole 3 Overview 4-pole 4 Electronic Fuse Monitoring 5 Busbar Adapters
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL has developed the Molded-Case Circuit Breaker (MCCB) Marking Guide for electrical inspectors, electric utilities, contractors, installers, users, designers, and other interested parties to aid