1 FUSERBLOC Fuse combination switches appli_8_a fuser_548_a cat fuser_59_a cat fuser_52_a cat 2 to 25 A Manual operation Function FUSERBLOC are manually operated multipolar fuse combination switches. They break or switch off on load and provide safety isolation and protection against overcurrent for any low voltage electrical circuit. General characteristics Fully visualised breaking. Double break by phase (top and bottom of fuse). Protection against overcurrent by fuse circuit-breakers (gg, am, UR, BS88) with high breaking capacity ( ka eff.). IP2 protection with terminal shrouds front panel. Compact. TEST position for testing control circuits without power using U type auxiliary contacts. In TEST position, the enclosure door can be opened. Available on request FUSERBLOC with rear top or bottom connections: consult us. Multipolar FUSERBLOC providing various coupling possibilities (for example: FUSERBLOC x 4 A + x 5 A with front or side operation). FUSERBLOC UL and CSA for the North American markets (see page 24). FUSERBLOC with centred operation: consult us. FUSERBLOC for solar applications: consult us. Conformity to standards IEC EN BS EN NBN EN IEC DIN EN NF EN IEC VDE 66- VDE 66-7 IS Standards UL: see FUSERBLOC UL Approvals and certifications () KEMA LOVAG CCC GOST (Russia) CEBEC (Belgium) FI (Finland) CCA UKR (Ukraine) () Product reference on request. fuser_7_a fuser_552_a fuser_597_a Multipolar FUSERBLOC Centred operation FUSERBLOC for solar applications 42 General Catalogue 2-22 SOCOMEC

2 Fuse combination switches FUSERBLOC What you need to know Along with the rating, FUSERBLOC is selected according to the fuse type and functional specifications. SOCOMEC FUSERBLOC can be equipped with NFC, DIN or BS88 fuses. The INSTALFUSE v2 software carries out sizing calculations for low-voltage electrical installations and their fuse protection. Whether it is pole + switched or pole + solid, the FUSERBLOC 2 to 2 A with direct front operation and external operation is the best suited solution in compact design. From 6 to 25 A, the FUSERBLOC unit allows direct and external front or right side operation in 2, or 4 poles. From 2 to 4 A, the FUSERBLOC is available in 2, or 4 poles with direct side operation. FUSERBLOC is available in and 4-pole versions within 2 types of enclosures: - Steel enclosure for front operation from 25 to 8 A, (NFC and DIN) - Polyester enclosure with front and side operation from 5 to 4 A (NFC and DIN). - For BS88 steel enclosed FUSERBLOC please consult us. With external operation, it is possible to operate the device in ways: - Front operation. - Right side operation. - Left side operation. For ratings 2 to 4 A, the flat mounting kit provides a compact solution ideally suited to withdrawable applications. fuser_7_a cat fuser_72_a_2_cat coff_9_a cat fuser_76_a_2_cat coff_295_a cat fuser_75_a cat fuser_74_a cat SOCOMEC General Catalogue

3 FUSERBLOC - References fuser_57_a_2_cat BS 88 - External front and side operation 2 to 6 A Rating (A) Fuse size Frame size Number of poles Reference Switch I- Reference Changeover Switch I--II External front I- TEST External front I- TEST External right side I- Changeover external front I--II Shaft extensions for Terminal shrouds () Additional contact holder for U type AC Integrated solid link A A CD 2 A A 2 A A 6 A A2-A 2 + switched +solid switched + solid P P S type IP () S type 44 2 S type 4 25 () S type S type IP () S type type 48 2 S type IP () S type mm 4 52 Standard (2) A A4 (4) CD 6 A A-A4 (4) A 6 A A4 4 6 A B-B2 4 2 P P P P IP () () IP () IP () mm P (2) () Standard. (2) 4 auxiliary contacts as standard without support (the support is for 4 additional auxiliary contacts. () Top/bottom. (4) For fuse size A4: max diameter mm. General Catalogue 2-22 SOCOMEC

4 Fuse combination switches FUSERBLOC fuser_554_a_2_cat BS 88 - External front and side operation 2 to 25 A Rating (A) Fuse size Frame size Number of poles Reference Switch I- Reference Changeover Switch I--II External front I- TEST External front I- TEST External right side I- Changeover external front I--II Shaft extensions for Terminal shrouds () Additional contact holder for U type AC Integrated solid link CD 2 A A-A4 (5) A 2 P P A B-B A B-B2-B 5 5 A B-B2-B 6 4 A B-B2- B-B4 6 2 P P P P IP () () IP () IP () mm P (4) A C-C2 7 8 A C-C2-C 7 25 A D 8 2 P P S type 4 () S type S type 47 () S type 48 2 mm P P S4 type () () Standard. (2) 4 auxiliary contacts as standard without support (the support is for 4 additional auxiliary contacts. () Top/bottom. (4) 8 AC as standard without support (the support is for 8 additional auxiliary contacts. (5) For fuse size A4: max diameter mm SOCOMEC General Catalogue

5 FUSERBLOC - References (continued) fuser_59_a cat BS 88 - Direct operation 2 to 6 A Rating (A) Fuse size Frame size Number of poles Reference Side direct operation Reference Direct front operation Side direct operation switch Direct front Auxiliary contacts Terminal shrouds () Cage terminals Handle key interlocking accessories (2) 64 2 A A CD 2 A A + switched + solid switched + solid contact NO/NC A type 999 () 2 contacts NO/NC A type () Standard Standard 2 A A 6 A A2-A 2 A A4 (4) 2 P consult us 625 consult us consult us 2 P consult us consult us consult us 2 P consult us 625 consult us consult us contact NO/NC A type () CD 6 A A-A4 (4) A 6 A A4 4 2 P consult us consult us consult us 2 P consult us consult us consult us contacts NO/NC A type () 2 P A B-B2 4 2 P consult us consult us consult us () Max. 2 contacts. (2) Lock not included. () Top/bottom. (4) For fuse size A4: max diameter mm. 46 General Catalogue 2-22 SOCOMEC

6 Fuse combination switches FUSERBLOC fuser_2_a cat BS 88 - Direct operation 2 to 4 A Rating (A) Fuse size Frame size Number of poles Reference Side direct operation Reference Direct front operation Side direct operation switch Direct front Auxiliary contacts Terminal shrouds () Cage terminals Handle key interlocking accessories (2) CD 2 A A-A4 (4) a 2 A B-B A B-B2-B 5 5 A B-B2-B 6 4 A B-B2- B-B4 6 2 P consult us consult us consult us 2 P consult us consult us consult us 2 P consult us consult us consult us 2 P consult us consult us consult us 2 P consult us consult us consult us Consult us contact NO/NC A type () 2 contacts NO/NC A type () 2 P P () Max. 2 contacts. (2) Lock not included. () Top/bottom. (4) For fuse size A4: max diameter mm. fuser_46_a cat Rating (A) Fuse size Frame size 6 A C-C2 7 8 A C-C2-C 7 25 A D 8 Number of poles Reference Side direct operation Reference Direct front operation 2 P P Side direct operation switch Direct front Auxiliary contacts contact NO U type () contact NO U type () Terminal shrouds () 2 P P () Max.number of U type auxiliary contact is 8. (2) Lock not included. () Top/bottom. BS 88 - Direct operation 6 to 25 A Cage terminals Handle key interlocking accessories (2) SOCOMEC General Catalogue

7 FUSERBLOC - References (continued) fuser_556_a_2_cat NFC and DIN External front and right side operation 25 to 25 A Rating (A) / Fuse / Frame size No. of poles Switch I--TEST Changeover switch I--II External front TEST external front External right side Changeover external front Shaft for external Auxiliary contacts (2) Terminal shrouds () Integrated solid link 6 2 () A x 8 + switch + solid 6 42 () () S type S type CD 2 A x 8 2 A 4 x switch + solid () switch + solid 6 44 () () IP S type IP S type IP mm 4 52 U type contact A 4 x 5 6 A C 2 2 P () () P () () S type S type Standard A 22 x A 22 x A 2 P () () P P IP IP IP mm 4 2 (2) U type contact P () Available enclosed (see page 494 "Enclosed fuse switches"). (2) Top/bottom. () Maximum 4 contacts. 48 General Catalogue 2-22 SOCOMEC

8 Fuse combination switches FUSERBLOC fuser_548_a cat NFC and DIN External front and right side operation 6 to 25 A Rating (A) / Fuse / Frame size No. of poles Switch I- Changeover switch I--II External front TEST external front External right side Changeover external front Shaft for external Auxiliary contacts Terminal shrouds (2) Integrated solid link 6 A 6 A 4 25 A 5 4 A P P () () P () () P () () Type S2 IP Type S Type S2 IP Type S2 IP mm 4 2 U type contact () U type contact (4) 2 P P A 7 8 A 7 8 A A P 8 26 Type S 8 6 () 8 66 () 2 P P 8 28 Type S P Type S mm P P () Available enclosed (see page 494 "Enclosed fuse switches"). (2) Top/bottom. () Maximum 4 contacts. (4) Maximum 8 contacts. SOCOMEC General Catalogue

9 FUSERBLOC - References (continued) fuser_59_a cat NFC and DIN - Direct operation 25 to 25 A Rating (A) Fuse size Frame size No. of poles Direct side operation Direct front operation Direct Auxiliary contacts Terminal shrouds Cage terminals Lock for fuse protection cover Handle ley interlocking accessories (6) A x 8 CD 2 A x 8 2 A 4 x 5 + switch + solid switch + solid switch + solid ()(2) A type contact NO/NC 999 () A type 2 contacts NO/NC () Standard Standard Standard 5 A 4 x 5 6 A C 2 A 22 x A 22 x A 2 P Consult us 65 5 Consult us Consult us 2 P Consult us 65 6 Consult us Consult us 2 P 65 2 Consult us 65 Consult us 65 6 Consult us 2 P 65 2 Consult us 65 Consult us 65 6 Consult us 2 P Consult us 65 2 Consult us Consult us (5)(2) (5)(2) A type contact NO/NC () A type 2 contacts NO/NC () 2 P 9 26 (4) 9 6 (4) 9 46 (4) () Direct front operation. (2) Standard. () Maximum 2 contacts. (4) Top or bottom. (5) Direct right side operation. (6) Loccking using RONIS ELAP lock (lock not included). 5 General Catalogue 2-22 SOCOMEC

10 Fuse combination switches FUSERBLOC fuser_2_a cat NFC and DIN - Direct operation 6 to 4 A Rating (A) Fuse size Frame size No. of poles Direct side operation Direct front operation Direct Auxiliary contacts Terminal shrouds Cage terminals Lock for fuse protection cover Handle ley interlocking accessories (5) 6 A 6 A 4 25 A 5 4 A P Consult us 65 5 Consult us Consult us (4)() 2 P 9 26 () P Consult us A type 9 6 () Consult us Consult us contact NO/NC 9 46 () (2) P Consult us A type contacts 2 P Consult us (4)() NO/NC () Consult us (2) P Consult us 9 25 () Consult us () Consult us () Standard. (2) Maximum 2 contacts. () Top/bottom. (4) Direct right side operation. (5) Locking using RONIS ELAP lock (lock not included). fuser_46_a cat NFC and DIN - Direct operation 6 to 25 A Rating (A) Fuse size Frame size No. of poles Direct side and front operation Direct front Direct side Auxiliary contacts Terminal shrouds 6 A 7 8 A 7 8 A A P P P P ()(2) ()(2) U type contact NC (4) contact NO (4) 2 P 8 28 () 8 8 () 8 48 () 2 P 8 22 () 8 2 () 8 42 () () Direct front operation. (2) Standard. () Top/bottom. (4) Maximum 8 contacts. SOCOMEC General Catalogue

11 FUSERBLOC - Accessories Direct acces_47_a_2_cat acces_26_a Fig. Fig. 2 For front operation Rating (A) Frame size Figure no. Handle colour Reference Red acces_262_a acces_48_a_2_cat fuser_77_a Fig. Fig. 4 Fig. 5 For right side operation Rating (A) Frame size Figure no. Handle colour Reference / External front operation acces_49_a_2_cat S type acces_64_a_2_cat Padlockable in position Rating (A) Frame size Handle type Handle colour Operation External IP () Defeatable Reference CD 25 6 //2 S I - IP55 Yes 4 2 CD 25 6 //2 S I - Yes 4 2 CD 25 6 //2 S I - Yes 44 2 CD 25 6 //2 S I - - Test Yes 4 25 CD 25 6 //2 S I - - Test Yes S2 I - IP55 Yes S2 I - Yes S2 I - Yes S2 I - - Test IP55 Yes S2 I - - Test Yes S I - Yes S I - Yes S4 I - Yes S4 I - Yes 4 () IP: Degree of protection according to standard IEC acces_5_a_2_cat S type acces_52_a_2_cat S4 type Padlockable in position and I Rating (A) Frame size Handle type Handle colour External IP () Reference CD 25 6 //2 S S () IP: Degree of protection according to standard IEC External right side operation acces_49_a cat S type acces_66_a cat S type Rating (A) Frame size Handle type Handle colour External IP () Reference CD 25 6 //2 S IP CD 25 6 //2 S 47 2 CD 25 6 //2 S S2 IP S S /8 S /8 S 48 () IP: Degree of protection according to standard IEC General Catalogue 2-22 SOCOMEC

12 Fuse combination switches FUSERBLOC External front with metal tab Rating (A) Frame size Handle type Handle colour External IP () Defeatable Reference CD 25 6 //2 S Yes 4D 29 CD 25 6 //2 S Yes 4E 29 acces_26_a cat acces_25_a S type 4 6 S2 Yes 42D S2 Yes 42E S Yes 4D S Yes 4E S4 Yes D S4 Yes E 9 () IP: Degree of protection according to standard IEC S type adapter Use Enables S type s to be fitted in place of existing older style SOCOMEC s. Adapter can also be utilised as a spacer to increase the distance between the panel door and the lever. Dimensions Adds 2 mm to the depth. acces_87_a cat To be ordered Handle colour in multiples of External IP () Reference 49 () IP: Degree of protection according to standard IEC Alternative S-type cover colours acces a cat Use For single lever s type S, S2, S and double arms lever, type S4. Other colours: consult us. Handle colour To be ordered in multiples of Handle Reference Light grey 5 Type S, S2, S 4 Dark grey 5 Type S, S2, S 4 Light grey 5 S4 type 4 Dark grey 5 S4 type 4 4 Flat mounting kit Use The flat mounting kit provides a compact solution ideally suited to withdrawable applications. fuser_55_a cat Rating (A) Frame size Type Reference CD 2 CD 2 Kit + Shaft 2 mm Kit + Shaft 2 mm Handle for flat mounting kit fuser_56_a cat. Padlockable in position Rating (A) Frame size Handle type Handle colour External IP () Reference CD 2 6 //2 S IP (2) CD 2 6 //2 S 44 2 (2) 4 6 S2 IP (2) 4 6 S (2) () IP: Degree of protection according to standard IEC (2) Defeatable in position I. SOCOMEC General Catalogue

13 FUSERBLOC - Accessories (continued) Front operation shaft support accessory Use This support maintains shaft position for extension shafts greater than 2 mm in length. fuser_6_a_2_cat Rating (A) Frame size Reference Shaft guide for external operation Use To guide the shaft extension into the external. This accessory enables to engage extension shaft with a misalignment of up to 5 mm. Required for a shaft length over 2 mm. acces_26_a_2_cat Description Reference Shaft guide 429 acces_45_b cat Shaft for external front acces_4_b cat Use Standard lengths: Other lengths: consult us. - 2 mm - 2 mm - 4 mm - 5 mm. Rating (A) Frame size Shaft length (mm) Reference CD 2 CD CD 2 CD CD 2 CD () acces_22_a cat X (2) / / () () Use the accessory "guide cone for external control". (2) Use the accessory "shaft extension support for external front control". Dimension X (mm) for FUSERBLOC BS88 Rating (A) CD 2 CD CD6 CD Shaft extension length Fuse size A A A2-A/A4 A-A4 B-B2 B-B2-B C-C2-C D (mm) Frame size 2//4 A 4/5 5/ Dimension X (mm) for FUSERBLOC NFC and DIN Rating (A) CD 25 CD Shaft extension length Fuse size x8/4x5 4x5 C 22x58/ /2 4 (mm) Frame size 2 4 5/ Shaft for external side Use Standard lengths, 2 mm. acces_2_a cat Y Rating (A) Frame size Handle type Dimension Y (mm) Shaft length (mm) Reference CD 2 CD 2 S S /8 S General Catalogue 2-22 SOCOMEC

14 Fuse combination switches FUSERBLOC acces a cat Integrated solid link acces a cat Use Fixing the solid onto the mechanism produces a device with a solid of the same size as a standard three-pole device (+ 6 mm). BS88 for external front operation Rating (A) Switch body size Bar rating (A) Reference CD 6 CD 2 a NFC and DIN for external front operation Rating (A) Switch body size Bar rating (A) Reference acces_99_a_2_cat Solid module BS88 for external front operation Rating (A) Switch body size Imax (A) Distance (mm) Reference CD 6 CD 2 a NFC and DIN for external front operation Rating (A) Frame size Imax(A) Distance (mm) Reference 5 / / / / / / fusib_2_a_2_cat Solid links fusib_24_a_2_cat BS88 switches Rating (A) Frame size Fuse size Imax (A) Reference 2 A A2-A A CD 6 a A-A A B-B CD 2 a A-A B-B B-B2-B B-B2-B B-B2-B-B C-C D NFC and DIN switches Rating (A) Frame size Fuse size Imax (A) Reference 5 / 4 x /2 C / 22 x / / / / SOCOMEC General Catalogue

15 FUSERBLOC - Accessories (continued) U type auxiliary contacts Use Compact universal type auxiliaries can be configured to be operated on both, standard and TEST position switches from CD 2 to 25 A. Each slot can accommodate up to 2 interlocked ACs. Connection to the control circuit By terminals with max. section 2 x 2.5 mm². For FUSERBLOC CD 2 to 4 A. Pre-break and signalling of positions, I and Test. For FUSERBLOC 6 A: Pre-break and position and I signalling. acces_56_a cat References NO auxiliary contacts Rating (A) Frame size Contact(s) Reference CD acces_4_a x_cat A B NC auxiliary contacts Rating (A) Frame size Contact(s) Reference CD Contact holder for auxiliary contacts Rating (A) Frame size Contact(s) Reference (2) CD (2 x 2 max) included /6 8 (4 x 2 max) included /8 8 (4 x 2 max) included (2) Cannot be mounted in direct operation. Contact holder for additional auxiliary contacts Rating (A) Frame size Contact(s) Reference CD 2 CD 2 4 (2 x 2 max) (2 x 2 max) Characteristics Operating currentie (A) 25 VAC 4 VAC 24 VDC 48 VDC Rating (A) AC-5 AC-5 DC- DC- CD A type auxiliary contacts Use Pre-break and position and I signalling by or 2 NO /NC auxiliary contacts. For low level use, specific auxiliary contacts: consult us. References Connection to the control circuit By 6.5 mm fast-on terminal. Electrical characteristics operations. acces_46_a cat NO / NC auxiliary contacts Rating (A) Frame size Contact(s) Reference CD 2 CD CD 2 CD () (2) 2 4 () (2) () Side direct operation switch only. (2) A type auxiliary contacts cannot be mounted conjunction with integrated solid. acces_47_a_2_cat Characteristics Operating currentie (A) Current 25 VAC 4 VAC 24 VDC 48 VDC Rating (A) nominal (A) AC- AC- DC- DC- CD General Catalogue 2-22 SOCOMEC

16 Fuse combination switches FUSERBLOC S and ST type auxiliary contacts Use For FUSERBLOCs 2 to 25 A, position and I signalling by to 4 NO + NC auxiliary contacts. Electrical principle The NO + NC S type auxiliary contacts can be configured as 2 NC or 2 NO. Connection By terminals with max. section mm 2. Mechanical characteristics operations. acces_5_a_2_cat References S type auxiliary contacts I- for external front and right-side operation (Standard operation) Rating (A) Frame size Contact type Reference NC+NO ST type auxiliary contacts I--TEST for external front and right-side operation (TEST operation) Contact Rating (A) Frame size type Description Reference NC+NO TEST + ON O TEST + ON acces_8_a cat Drive shaft kit for auxiliary contact operation. Type of AC Operation type Reference S type Standard 999 ST type TEST 999 Characteristics Current Operating current Ie (A) 25 VAC 4 VAC Rating (A) nominal (A) AC- AC Fuse cover interlocking Use On NFC and DIN, side direct operation, locking of the opening of the fuse protection cover when FUSERBLOC is engaged (position I). Rating (A) Frame size Fuse size No. of poles Reference CD 25 5 x 8 / 4 x 5 2 / / 4 included 6 2 C 2 / / x 58 2 / / / / P P P SOCOMEC General Catalogue

17 FUSERBLOC - Accessories (continued) Terminal shrouds fuser_4_a cat Use Top or bottom IP 2 protection (at front) against direct contact with terminals or connection parts. 2 sets required to fully shroud both incoming and outgoing terminals. Rating (A) Frame size Position No. of poles Reference CD top / bottom 2 / / integrated CD 2 /4 top / bottom 2 P 9 26 CD 2 /4 top / bottom 9 6 CD 2 /4 top / bottom /6 top / bottom 2 P /6 top / bottom /6 top / bottom top / bottom 2 P top / bottom top / bottom top / bottom 2 P top / bottom top / bottom 8 42 NFC and DIN fuse blowm indication fuser_2_a cat fuser a cat Use For fuse cartridge with striker (size 4 x 5 22 x 58; ; ; 2; and 4). Electrical principle A NO/ NC auxiliary contact detects that the fuse has blown. Connection to the control circuit By 6.5 mm fast-on terminal. Mechanical characteristics operations. References NO/ NC type auxiliary contacts for 2 pole Rating (A) Frame size Fuse Contact(s) Reference 5 4 x 5 st x 58 st st /6-2 st st st NO/ NC type auxiliary contacts for pole Rating (A) Frame size Fuse Contact(s) Reference CD 2 4 x 5 st x 5 st x 58 st st /6-2 st st st nd NO/ NC type auxiliary contacts for 4 pole or pole + Rating (A) Frame size Fuse Contact(s) Reference 5 4 x 5 st x 58 st st /6-2 st st st nd Characteristics Operating currentie (A) Current 25 VAC 4 VAC 24 VDC 48 VDC Rating (A) nominal (A) AC- AC- DC- DC- CD General Catalogue 2-22 SOCOMEC

18 Fuse combination switches FUSERBLOC Cage terminals Use Connection of bare copper cables onto the terminals (without lugs). References acces_9_a x_cat acces_5_a cat øx Z A X acces_92_a x_cat C A R Rating max (A) Frame size No. of poles Reference CD / / integrated 6 / / Connections Section flexible cable (mm 2 ) Section rigid cable (mm 2 ) Width flexible bar (mm) Rating (A) Stripped over (mm) Dimensions Rating (A) A A C R ØX X Z M M M2 5 Handle key interlocking accessories Label holder Use Recognisable self-adhesive label allowing identification of the devices. To be ordered Dimensions W x H (mm) in multiples of Reference 8 x acces a cat acces_42_a x_cat Fig. Use Locking in position of the direct, front or right side operation: using padlock (not supplied) in direct operation: - integrated into the of 2 to 4 A, - integrated into the frame of 6 to 25 A. using key interlocking (not supplied) in external operation (see below). Locking using RONIS EL AP lock (not supplied) Rating (A) Frame size Operation Figure n Reference CD external front /2 direct direct direct Locking using CASTELL K lock (not supplied) Rating (A) Frame size Operation Figure n Reference CD external front acces_58_a x_cat Fig. 2 acces_57_a x_cat Fig. Locking using CASTELL FS lock (not supplied) Rating (A) Frame size Operation Figure n Reference CD external front Locking using XOP (not included) Rating (A) Frame size Operation Reference CD external front SOCOMEC General Catalogue

19 FUSERBLOC - Characteristics according to IEC to A Thermal current Ith (4 C) 2 A 25 A CD 2 A CD 2 A 2 A 5 A 6 A A BS88/DIN fuse size A/- -/ x 8 -/ x 8 A/4 x 5 A/- -/4 x 5 A2-A/C A4*/22 x 58 Frame size for direct operation 2 Switch body size for front and side operation 2 Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kv) Rated operational currents Ie (A) Rated voltage Load duty category A/B () A/B () A/B () A/B () A/B () A/B () A/B () A/B () 4 VAC AC-22 A / AC-22 B 2/2 25/25 2/2 2/2 2/2 5/5 6/6 / 4 VAC AC-2 A / AC-2 B 2/2 25/25 2/2 2/2 2/2 5/5 6/6 / 69 VAC AC-22 A / AC-22 B 2/2 25/25 2/2 2/2 2/2 5/5 6/6 (4) / (4) 69 VAC AC-2 A / AC-2 B 2/2 25/25 2/2 2/2 2/2 5/5 6/6 (4) / (4) 22 VDC DC-2 A / DC-2 B -/2 2/2 5/5 6/6 / 22 VDC DC-2 A / DC-2 B -/25 (2) 2/2 4/4 4/4 / VDC DC-2 A / DC-2 B 2 () /2 () 5 () /5 () 6 () /6 () () / () VDC DC-2 A / DC-2 B 2 () /2 () 4 () /4 () 4 () /4 () () / () Operational power in AC-2 (kw) At 4 VAC without pre-break in AC ()(5) 9/9 / 5/5 5/5 5/5 25/25 / 5/5 At 69 VAC without pre-break in AC ()(5) 5/5 22/22 25/25 25/25 25/25 45/45 55/55 9/9 Reactive power (kvar) At 4 VAC (5) Fuse protected short-circuit withstand BS88/DIN (ka rms prospective) Prospective short-circuit (ka rms) (6) 8/- -/ -/ 8/ 8/ -/ 8/ 8/ Associated fuse rating (A) (6) 2/- -/25 -/2 2/2 2/2 -/5 6/6 / Short-circuit capacity Rated peak withstand current (ka peak) (6) Fuse selection (maximum fuse size) (7) SOCOMEC BS88 6A A 2 6A 2 6A 6 6A4 SOCOMEC BS88 6AM AM 6 6AM 2 6AM 8 6A4M 25 SOCOMEC DIN SOCOMEC DIN BUSSMANN NITD 2 NITD 2 NITD 2 BAO 6 CEO BUSSMANN NITD 2M2 NITD 2M6 NITD 2M6 BAO 6M8 CEO M25 LAWSON NIT 2 NIT 2 NIT 2 TIS 6 TCP LAWSON NIT 2M2 NIT 2M2 TIS 6M8 CTFP M25 GE NIT 2 NET 2 NET 2 TIS 6 TCP GE NIT 2M2 NET 2M6 NET 2M6 TIS 6M8 OCP M25 Connection Minimum Cu cable section (mm 2 ) Maximum Cu cable section (mm 2 ) Maximum busbar width (mm) 2 Min. / Max. tightening torque min (Nm) 2/- 2/- 2/ 2 2.5/ 2.5/ 2.5/ 8./ Mechanical characteristics Durability (number of operating cycles) Weight of switch (kg) Weight of switch (kg) Weight of P extra (kg) Frame pitch (mm) () Category with index A = frequent operation - Category with index B = infrequent operation. (2) With terminal shrouds or terminal screen. () 4-pole device with 2 pole in series by polarity. (4) Poles cannot be juxtaposed. (5) The power value is given for information only, the current values vary from one manufacturer to another. (6) For a rated operational voltage Ue = 4 VAC. (7) Fuse 8 A, 69 Vac does not exist, tests conducted with bars. * For fuse size A4: max diameter mm. ** Please ensure that fuse let through current does not exceed short-circuit capacity of the switch (ka peak). 6 General Catalogue 2-22 SOCOMEC

20 Fuse combination switches FUSERBLOC 25 to 2 A Thermal current Ith (4 C) 25 A 25 A 6 A CD 6 A 6 A 6 A CD 2 A 2 A NFC/DIN fuse size -/22 x 58 -/ -/ A-A4*/- A4/ B-B2/- A-A4*/- B-B2/- Frame size for direct operation Switch body size for front and side operation a 4 4 a 5 Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kv) Rated operational currents Ie (A) Rated voltage Load duty category A/B () A/B () A/B () A/B () A/B () A/B () A/B () A/B () 4 VAC AC-22 A / AC-22 B 25/25 25/25 6/6 6/6 6/6 6/6 2/2 2/2 4 VAC AC-2 A / AC-2 B 25/25 25/25 6/6 6/6 6/6 6/6 2/2 2/2 69 VAC AC-22 A / AC-22 B 25 (2) /25 (2) 25 (2) /25 (2) 6 (2) /6 (2) 6 (2 /6 (2) 6 (2) /6 (2) 6 (2) /6 (2) 6 (2) /6 (2) 2 (2) /2 (2) 69 VAC AC-2 A / AC-2 B (2) / (2) (2) / (2) 25 (2) /25 (2) 25 (2) /25 (2) 25 (2) /25 (2) 25 (2) /25 (2) 25 (2) /25 (2) 2 (2) /6 (2) 22 VDC DC-2 A / DC-2 B 25/25 25/25 6/6 6/6 6/6 6/6 6/6 2/2 22 VDC DC-2 A / DC-2 B / / 25/25 25/25 25/25 25/25 25/25 2/2 VDC DC-22 A / DC-22 B 25 () /25 () 25 () /25 () 6 () /6 () 6 () /6 () 6 () /6 () 6 () /6 () 6 () /6 () 2 () /2 () VDC DC-2 A / DC-2 B () / () () / () 25 () /25 () 6 () /6 () 25 () /25 () 25 () /25 () 25 () /25 () 2 () /2 () Operational power in AC-2 (kw) At 4 VAC without pre-break in AC ()(5) 6/6 6/6 8/8 8/8 8/8 8/8 8/8 / At 69 VAC without pre-break in AC ()(5) 9/9 9/9 / / / / / 5/85 Reactive power (kvar) At 4 VAC (5) Fuse protected short-circuit withstand (ka rms prospective) Prospective short-circuit (ka rms) (6) -/ -/ -/ (5) 5/- 8/ 8/ 5/- 8/- Associated fuse rating (A) (6) -/25 -/25 -/25 (6) 6/- 6/6 6/6 2/- 2/- Short-circuit capacity Rated peak withstand current (ka peak) (6) Fuse selection (maximum fuse size) (7) SOCOMEC BS88 6A4 6 6B2 6 6B2 2 6B2 2 SOCOMEC BS88 6A4 6 6A4M 6 6BM 2 6B2M 5 6B2M 5 SOCOMEC DIN SOCOMEC DIN BUSSMANN DEO 6 DEO 6 DD 6 DD 2 DD 2 BUSSMANN CEO M6 DEO M2 CD M2 DD 2M5 DD 2M5 LAWSON CTFP 6 TFP 6 TF 6 TF 2 TF 2 LAWSON CTCP M6 TCP M2 TCP M2 TC 2M5 TC 2M5 GE TCP TFP 6 TF 6 TF 2 TF 2 GE OCP M6 TCP M2 TC M2 TF 2M5 TF 2M5 Connection Minimum Cu cable section (mm 2 ) Maximum Cu cable section (mm 2 ) Maximum busbar width (mm) Tightening torque min (Nm) 8./ 8./ 8./ 8./ 8./ 8./ 2/26 2/26 Mechanical characteristics Durability (number of operating cycles) Weight of switch (kg) Weight of switch (kg) Weight of P extra (kg) Frame pitch (mm) () Category with index A = frequent operation - Category with index B = infrequent operation. (2) With terminal shrouds or terminal screen. () 4-pole device with 2 pole in series by polarity. (4) Poles cannot be juxtaposed. (5) The power value is given for information only, the current values vary from one manufacturer to another. (6) For a rated operational voltage Ue = 4 VAC. (7) Fuse 8 A, 69 Vac does not exist, tests conducted with bars. * For fuse size A4: max diameter mm. ** Please ensure that fuse let through current does not exceed short-circuit capacity of the switch (ka peak). SOCOMEC General Catalogue

21 FUSERBLOC - Characteristics according to IEC (continued) 25 to 25 A Thermal current Ith (4 C) 25 A 5 A 4 A 6 A 8 A 8 A 25 A NFC/DIN fuse size B-B2-B/ B-B2-B/- B-B2-B-B4/2 C-C2/ C-C2-C/ -/4 D/4 Frame size for direct operation Switch body size for front and side operation Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kv) Rated operational currents Ie (A) Rated voltage Load duty category A/B () A/B () A/B () A/B () A/B () A/B () A/B () 4 VAC AC-22 A / AC-22 B 25/25 5/5 4/4 6/6 8/8 8/8 25/25 4 VAC AC-2 A / AC-2 B 25/25 5/5 4/4 6/6 8/8 8/8 /25 69 VAC AC-22 A / AC-22 B 25 (2) /25 (2) 5 (2) /5 (2) 5/4 5/6 8/8 8/8 (7) 8/25 69 VAC AC-2 A / AC-2 B 25 (2) /25 (2) 25 (2) /5 (2) 25/5 5/4 6/6 8/8 (7) 8/6 22 VDC DC-2 A / DC-2 B 25/25 25/25 5/5 5/6 8/8 8/8 25/25 22 VDC DC-2 A / DC-2 B 2/2 2/2 2/5 4/6 8/8 8/8 25/25 VDC DC-22 A / DC-22 B 25 () / 25 () 25 () / 25 () 5 (4) /5 (4) 5/6 (4) 8 () / 8 () 8/8 () / () VDC DC-2 A / DC-2 B 2 () / 2 () 2 () / 2 () 25 (4) / 5 (4) 4 (4) /6 (4) 8 () / 8 () 8 / 8 () () / () Operational power in AC-2 (kw) At 4 VAC without pre-break in AC ()(5) 2/2 6/6 22/22 55/55 45/45 45/45 56/56 At 69 VAC without pre-break in AC ()(5) 22/22 22/295 22/ /4 4/4 4/4 4/475 Reactive power (kvar) At 4 VAC (5) Fuse protected short-circuit withstand (ka rms prospective) Prospective short-circuit (ka rms) (6) 8/ 8/- 8/5 8/ 8/ -/ -/ Associated fuse rating (A) (6) 25/25 5/- 4/4 6/6 8/8 -/8 -/25 Short-circuit capacity Rated peak withstand current (ka peak) (6) Fuse selection (maximum fuse size) (7) SOCOMEC BS88 6B2 25 6B 5 6B4 4 6C2 6 6C 8 SOCOMEC BS88 6B2M 5 6BM 4 6B4M 5 SOCOMEC DIN SOCOMEC DIN BUSSMANN ED 25 ED 5 ED 4 FF 6 GF 8 BUSSMANN DD 2M5 ED 5M4 ED 4M5 LAWSON TKF 25 TKF 5 TMF 4 TTM 6 TLM 8 LAWSON TF 2M5 TKF 5M4 TMF 4M5 GE TKF 25 TKF 5 TMF 4 TTM 6 TLM 8 GE TF 2M5 TKF 5M55 TMF 4M45 Connection Minimum Cu cable section (mm 2 ) x 5 2 x 85 Maximum Cu cable section (mm 2 ) x 2 x 4 x 85 4 x 85 Maximum busbar width (mm) Tightening torque min (Nm) 2/26 2/26 2/26 4/45 4/45 4/45 4/45 Mechanical characteristics Durability (number of operating cycles) Weight of switch (kg) Weight of switch (kg) Weight of P extra (kg)... Frame pitch (mm) () Category with index A = frequent operation - Category with index B = infrequent operation. (2) With terminal shrouds or terminal screen. () 4-pole device with 2 pole in series by polarity. (4) Poles cannot be juxtaposed. (5) The power value is given for information only, the current values vary from one manufacturer to another. (6) For a rated operational voltage Ue = 4 VAC. (7) Fuse 8 A, 69 Vac does not exist, tests conducted with bars. ** Please ensure that fuse let through current does not exceed short-circuit capacity of the switch (ka peak). 62 General Catalogue 2-22 SOCOMEC

22 Fuse combination switches FUSERBLOC FUSERBLOC - Dimensions External operation BS88 - FUSERBLOC CD 2 to CD 2 A in size A External front operation 2 min vfuser_292_d x_cat 4. With U type AC: mm With 2 U type AC: 55 mm External side operation min min. fuser_295_c x_cat External front operation fuse combination changeover 5 min fuser b x_cat With U type AC: mm With 2 U type AC: 55 mm. SOCOMEC General Catalogue

23 FUSERBLOC - Dimensions (continued) External operation NFC and DIN - FUSERBLOC 25 to 2 A in size x 8 External front operation External side operation 2 min mini mini fuser_29_d x_cat 7 fuser_294_c x_cat NFC and DIN - FUSERBLOC 2 A in size 4 x 5 External front operation 2 min With U type AC: mm. With 2 U type AC: 55 mm External side operation min min. 45 fuser_292_d x_cat fuser_295_c x_cat With U type AC: mm. With 2 U type AC: 55 mm. NFC and DIN - FUSERBLOC 25 to 2 A in size x 8 and 4 x 5 External front operation fuse combination changeover 5 min fuser b x_cat With U type AC: mm. With 2 U type AC: 55 mm. 64 General Catalogue 2-22 SOCOMEC

24 Fuse combination switches FUSERBLOC External front or right side operation BS88 - FUSERBLOC 2 A in fuse size A NFC and DIN - FUSERBLOC 5 A in fuse size 4 x 5 *fix min 5 max Y Ø6.2 2 (P) 48 (4P) min + N x 2.5* max 45 + N x 2.5* 2.5* W fix Z fix 6 *fix fuser_624_b X * to use if pre-break auxiliary contact number > 4 W : 84.5 for BS88 ; 87 for NFC and DIN X : 5 only for DIN Y : 85 only for DIN Z : 26 only for DIN. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). or 2 pre-break auxiliary contact (fuse blown indication) 4. to 4 pre-break auxiliary contact for signalisation 5. Additional contact holder for U type AC Dimensions for external s BS88 - FUSERBLOC 2 to 6 A NFC and DIN - FUSERBLOC 25 to 6 A Handle type Front operation Direction of operation Door drilling Side operation Direction of operation Door drilling fuser_72_a gb_cat S type Box size Ø.7 Ø TEST 65 9 I Ø.46 Ø 7 4 Ø.27 4 Ø I 4 Ø.27 4 Ø Ø.46 Ø SOCOMEC General Catalogue

25 FUSERBLOC - Dimensions (continued) External front or right side operation BS88 - FUSERBLOC 6 A in fuse size A2 - A NFC and DIN - FUSERBLOC 6 A in fuse size C *fix min 5 max Ø min W max X (P) 68 (4P) fix fix 6 *fix fuser_625_b Y * to use if pre-break auxiliary contact number > 4 W : 24 + N x 2.5 for BS88 ; 9 for NFC and DIN X : 45 + N x 2.5 for BS88 ; 45 for NFC and DIN Y : 59 only for DIN Z : 45 only for DIN. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 4 pre-break auxiliary contact for signalisation 4. Additional contact holder for U type AC 66 General Catalogue 2-22 SOCOMEC

26 Fuse combination switches FUSERBLOC BS88 - FUSERBLOC A in fuse size A4 - max Ø mm NFC and DIN - FUSERBLOC to 25 A in fuse size 22 x 58 FUSERBLOC 25 to 6 A in fuse size * fix min 5 max (P) 84 (4P) Ø8.7 min 9 max fix fix fix 52.5* fuser_626_a Ø8.5 5 X * to use if pre-break auxiliary contact number > 4 X : 79 for BS88 / NFC and DIN to 25 A 89 for NFC and DIN 25 to 6 A. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 4 pre-break auxiliary contact for signalisation 4. or 2 pre-break auxiliary contact (fuse blown indication) 5. Terminal shrouds 6. Additional contact holder for U type AC SOCOMEC General Catalogue

27 FUSERBLOC - Dimensions (continued) External front or right side operation BS88 - FUSERBLOC CD 6 to CD 2 A in fuse size A-A4 (A4 max Ø mm) *fix. 5.5 B min 5 max (P) 84 (4P) Ø8.7 min 45 max fix fix fix. 52.5* Ø fuser_627_b * to use if pre-break auxiliary contact number > 4. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 4 pre-break auxiliary contact for signalisation 4. Terminal shrouds 5. Additional contact holder for U type AC 68 General Catalogue 2-22 SOCOMEC

28 Fuse combination switches FUSERBLOC BS88 - FUSERBLOC 6 A in fuse size A4 & B-B2 NFC and DIN - FUSERBLOC 6 A in fuse size *fix min 5 max Ø8.7 min 45 max fix (P) 24 (4P) fix fix 52.5* Ø fuser_628_b * to use if pre-break auxiliary contact number > 4. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 4 pre-break auxiliary contact for signalisation 4. or 2 pre-break auxiliary contact (fuse blown indication) 5. Terminal shrouds 6. Additional contact holder for U type AC SOCOMEC General Catalogue

29 FUSERBLOC - Dimensions (continued) External front or right side operation BS88 - FUSERBLOC 2 A in fuse size B-B2 FUSERBLOC 25 A in fuse size B-B2-B NFC and DIN - FUSERBLOC 25 A in fuse size *fix min 5 max fix *fix Ø 24 (P) 294 (4P) min 54 max fix 6 P 86 4P Ø fuser_629_b 25 * to use if pre-break auxiliary contact number > 4. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 8 pre-break auxiliary contact for signalisation 4. or 2 pre-break auxiliary contact (fuse blown indication) 5. Terminal shrouds 6. Additional contact holder for U type AC 7 General Catalogue 2-22 SOCOMEC

30 Fuse combination switches FUSERBLOC BS88 - FUSERBLOC 5 A in fuse size B-B2-B FUSERBLOC 4 A in fuse size B-B2-B-B4 NFC and DIN - FUSERBLOC 4 A in fuse size 2 *fix min 5 max (P) 8 (4P) Ø 4.5 min 57 max fix fix *fix * to use if pre-break auxiliary contact number > 4. S type auxiliary contact NO + NC to use if block number > 4 2. Rear connection (option). to 8 pre-break auxiliary contact for signalisation4. or 2 pre-break auxiliary contact (fuse blown indication) 5. Terminal shrouds 6. Additional contact holder for U type AC Ø 75 fuser_6_b Dimensions for external s BS88 / NFC and DIN - FUSERBLOC to 4 A Handle type Front operation Direction of operation Door drilling Side operation Direction of operation Door drilling fuser_7_a gb_cat Box size -6 Ø.7 Ø TEST 65 9 I Ø.46 Ø Ø.27 4 Ø I 4 Ø.27 4 Ø Ø.46 Ø SOCOMEC General Catalogue

31 FUSERBLOC - Dimensions (continued) BS88 - External front operation fuse combination changeover FUSERBLOC 2 to 4 A A Ø78 B Ø78 I Ø7 F A E min. J J H 4 DA 2 BA N 8.2 AA AC 7 II C ØD fuser_64_d x_cat DB 2 Y Z W U T T T T A. S : 2 and 6 A B. S2 : to 4 A C. Door drilling. Fuse blown indicaion not available for BS88 2. Terminal shrouds Rating (A) Frame size Dimensions A A E min p. 4p. E max Terminal shrouds AC Switch body F F H p. 4p. J p. J 4p. J p. J 4p. Switch mounting Connection DA DB N T U W Y Z AA BA Fuse size 2 A () 46 () A2-A A (2) CD 6 A-A4 a A B-B CD 2 A-A4 a B-B B-B2-B B-B2-B B-B2-B-B () AC: mm / 2 AC: + 47 mm. (2) 2 mm with 2 AC. 72 General Catalogue 2-22 SOCOMEC

32 Fuse combination switches FUSERBLOC NFC and DIN - External front operation fuse combination changeover FUSERBLOC 5 to 4 A A Ø78 B Ø78 25 I 4 4Ø7 F A E min. J J H 4 DA 2 BA N 8.2 AA AC 7 II C ØD fuser_64_d x_cat DB 2 Y Z W U T T T T A. S : 5 and 6 A B. S2 : to 4 A C. Door drilling. Fuse blown indicaion not available for BS88 2. Terminal shrouds Rating (A) Fuse size Frame size Overall dimensions A A E p 4p min E max Terminal shrouds Switch body AC F F H p. 4p. J p J 4p J p J 4p Switch mounting Connection DA DB N T U W Y Z AA BA 5 4 x () 46 () () C (2) x (2) x (2) () AC: +2.5 / 2 AC: +47 (2) 2 with 2 AC SOCOMEC General Catalogue

33 FUSERBLOC - Dimensions (continued) BS88 - Direct operation FUSERBLOC CD 2 to CD 2 A in frame size / fuse size A fuser_48_c x_cat FUSERBLOC 2 to 4 A 2 H S AD R T J 7 BA N AA AC Y DA Z W fuser_64_b x_cat DB C U AB T A. Protection screen lockable in position I 2. or 2 fuse blown indication.. or 2 A type ACs Rating (A) Frame size Dimensions Terminal shrouds Switch body Switch mounting Connection A p. A 4p. C AB p AB 4p AC AD H J DA DB N R S T U W Y Z AA BA Fuse size 2 A A2-A A CD 6 A-A4 a A B-B CD 2 A-A4 a B-B B-B2-B B-B2-B B-B2-B-B General Catalogue 2-22 SOCOMEC

34 Fuse combination switches FUSERBLOC NFC and DIN - Direct operation FUSERBLOC 25 to 2 A in frame size / fuse size x 8 FUSERBLOC 2 A in frame size / fuse size 4 x fuser_8_c x_cat FUSERBLOC 5 to 4 A 2 H S AD R T J 7 BA N AA AC fuser_48_c x_cat Y DA Z W fuser_64_b x_cat DB C U AB T A. Protection screen lockable in position I 2. or 2 fuse blown indication.. or 2 A type ACs Rating (A) Fuse size Frame size Overall dimensions Terminal shrouds Switch body Switch mounting Connection A p. A 4p. C AB p. AB 4p. AC AD H J DA DB N R S T U W Y Z AA BA 5 4 x C x x SOCOMEC General Catalogue

35 FUSERBLOC - Dimensions (continued) Direct and external front or right side operation BS88 - FUSERBLOC 6 A in fuse size C-C2 FUSERBLOC 8 A in fuse size C-C2-C NFC and DIN - FUSERBLOC 6 to 8 A in fuse size min min (P) 458 (4P) 2 46 Fix 284 (P) Fix 78 (4P) 65 4 min fix 25 Ø fuser_6_b Direct operation 2. S type auxiliary contact NO + NC. Rear connection (option) 4. to 8 pre-break auxiliary contact for signalisation 5. Terminal shrouds Dimensions for external s FUSERBLOC 6 to 8 A Handle type S type Box size 7 Ø.7 Ø78 fuser_74_a gb_cat 6 2 Direction of operation Front operation 9 I Ø.46 Ø 7 Door drilling Ø.27 4 Ø Side operation Direction of operation Door drilling 9 I 4 Ø.27 4 Ø Ø.46 Ø General Catalogue 2-22 SOCOMEC

36 Fuse combination switches FUSERBLOC BS88 - FUSERBLOC 25 A in fuse size D NFC and DIN - FUSERBLOC 8 to 25 A in fuse size 4. Direct operation 2. S type auxiliary contact NO + NC. Rear connection (option) 4. to 8 pre-break auxiliary contact for signalisation 5. Terminal shrouds min (P) 562 (4P) min 5 min fix 62 (P) fix 482 (4P) fix fuser_62_b FUSERBLOC 8 to 25 A Handle type Front operation Direction of operation Side operation Direction of operation Door drilling S type Box size 8 Ø78 I Ø 7 Ø 7 S4 type Ø I fuser_75_a gb_cat 6 SOCOMEC General Catalogue

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

GE Power Controls. MiniFORM Switchboards

GE Power Controls. MiniFORM Switchboards GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Catalogue May 2015. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole

Catalogue May 2015. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Catalogue May 2015 EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Contents Introduction 1 Overview 1-pole 2 Overview 2-pole 3 Overview 3-pole 4 Overview 4-pole 5 Electronic Fuse Monitoring 6 Busbar

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Rotary Disconnect Switch Specifications

Rotary Disconnect Switch Specifications Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Safety detection solutions

Safety detection solutions Presentation, actuator operated etal, types CS A, CS B, CS C and CS E Plastic, double insulated, turret head, types CS P or CS PA or CS TA and CS TE etal, types CS A, CS B, CS C, CS E with or without locking

More information

Renewable energy. Inverters - Socomec G-1. Load break switches (Isolators) - Socomec G-2. Fuses - df G-3. Fuse bases.

Renewable energy. Inverters - Socomec G-1. Load break switches (Isolators) - Socomec G-2. Fuses - df G-3. Fuse bases. G Product page Inverters - Socomec G-1 Load break switches (Isolators) - Socomec G-2 Fuses - df G-3 Fuse bases Surge protection - df G-3 - Wohner G-5 - CPT G-4 - Dehn G-5 Connectors - Wieland G-6 Cable

More information

Manual Motor Starter MS 116 up to 16 A Technical Data

Manual Motor Starter MS 116 up to 16 A Technical Data Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Protection and Connection. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole

Protection and Connection. EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Protection and Connection EasyLine XLP Fuse Switch Disconnector 1-2-3-4 pole Contents Introduction 1 Overview 1 and 2-pole 2 Overview 3-pole 3 Overview 4-pole 4 Electronic Fuse Monitoring 5 Busbar Adapters

More information

Plug and Socket Devices CES 63 A Series 8579

Plug and Socket Devices CES 63 A Series 8579 www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

Breakers and Switches. Switches Switch-disconnectors OT, OETL, OTDC and OTM

Breakers and Switches. Switches Switch-disconnectors OT, OETL, OTDC and OTM Breakers and Switches Switches Switch-disconnectors OT, OETL, OTDC and OTM Switch-disconnectors OT 16...2500, OETL 3150, OTDC16...32 and OTM160...2500 Contents 4 Product overview, features 8 Technical

More information

08. SEK IDC CONNECTORS

08. SEK IDC CONNECTORS . IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these

More information

3K Load-Break Switches The Program for Safety and Performance. sentric

3K Load-Break Switches The Program for Safety and Performance. sentric 3K Load-Break Switches The Program for Safety and Performance sentric Whether for reliable switching and isolation under load, or for protection against overload or short-circuits our 3K range of load-break

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Technical catalogue. Modular DIN rail components Installation contactors

Technical catalogue. Modular DIN rail components Installation contactors Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a

More information

Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable. Technical Data:

Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable. Technical Data: Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable Catalogue Symbol: Class of Operation: Fuse Size: NIT (amp rating) NET (amp rating) TIA (amp rating) TIS

More information

System pro M compact Miniature Circuit Breaker S 200/S 200 M

System pro M compact Miniature Circuit Breaker S 200/S 200 M Data Sheet System pro M compact Miniature Circuit Breaker S 200/S 200 M 2CDC021023S0012 2CDC021038S0012 The miniature circuit breakers of the System pro M compact series S 200 and S 200 M provide state-of-the-art

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information

D-Line Contactors, Overload Relays and Accessories

D-Line Contactors, Overload Relays and Accessories D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

Plug and Socket Devices SolConeX 16 A Series 8570

Plug and Socket Devices SolConeX 16 A Series 8570 www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control and signalling purposes > arge switching handle

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02. Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11

More information

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits Fuses for Semiconductor Protection - Cylindrical Fuses SIBA cylindrical Ultra-Rapid fuses are available in six different sizes They can be ordered with an integral striker for blown fuse indication or

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Panel Meters and Controllers Modular Panel Meter Type EDM 35 Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Pendant control stations 6

Pendant control stations 6 Characteristics 6 Environment Conformity to standards EN/IEC 6097-5-1 EN/IEC 600-, UL 508, CSA C- n EN/IEC 6097-5-5 and EN/ISO 850 for versions with trigger action Emergency stop Product certifications

More information

Catalog. Modular DIN rail components Installation contactors

Catalog. Modular DIN rail components Installation contactors Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry.

HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry. y HS5D First in the Industry Miniature Interlock Switches First in the Industry Head Removal Detection Function for Safer Performance (*based on IDEC research, July 09) New Generation Miniature Interlock

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide - long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and

More information

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00 Soft Starter Three Phase General Purpose Soft Starters Type RSGD Soft starting and soft-stopping of 3-phase squirrel cage motors 45mm wide IP20 housing Operational Voltage: RSGD40 (220-400V), RSGD60 (220-600V)

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

BETA Protecting SITOR Semiconductor Fuses

BETA Protecting SITOR Semiconductor Fuses BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Givare NC-SRS 280 och 880

Givare NC-SRS 280 och 880 Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Distribution Boards & Consumer Units

Distribution Boards & Consumer Units Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories

More information

3RV Motor Starter Protectors up to 100 A

3RV Motor Starter Protectors up to 100 A General data Overview S0 motor 3RV1 motor are compact, current limiting motor which are optimized for load feeders. The motor are used for switching and protecting three-phase induction motors of up to

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

Technical catalog - Edition 2015. SACE Tmax PV Adaptability, versatility and complete freedom continue

Technical catalog - Edition 2015. SACE Tmax PV Adaptability, versatility and complete freedom continue Technical catalog - Edition 205 SCE Tmax PV daptability, versatility and complete freedom continue SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors The Tmax PV line

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Breaking and protection devices

Breaking and protection devices Breaking and protection devices 05 POWER GUIDE 2009 / BOOK 05 INTRO The purpose of selecting a protection device is to perform two essential functions: to protect people and to protect trunking, while

More information

Photovoltaic System Overcurrent Protection

Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Introduction Solar Photovoltaic (PV) systems have, over the last fifty years, evolved into a mature, sustainable and

More information

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Control Devices Catalogue. Control Devices. Preferred and Standard Products Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface

More information

Applications. diris_826_a_1_gb_cat

Applications. diris_826_a_1_gb_cat Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered

More information

Common Features of Electromechanical Switches

Common Features of Electromechanical Switches Common Features of Electromechanical Switches Switching systems Switching elements lie at the heart of all electromechanical switching devices and must correspond to the respective application. Essentially

More information

Technical catalog. FORMULA UL New low voltage molded case circuit breakers up to 250A. Power and productivity for a better world TM

Technical catalog. FORMULA UL New low voltage molded case circuit breakers up to 250A. Power and productivity for a better world TM Technical catalog FORMULA UL New low voltage molded case circuit breakers up to 2A Power and productivity for a better world TM Index Main characteristics 1 Circuit breakers for power distribution 2 Accessories

More information

Safety dialogue solutions

Safety dialogue solutions General Presentation Emergency stop trip wire switches Emergency stop trip wire switches are designed to: b avert hazards (dangerous phenomena) at the earliest possible moment, or to reduce risks which

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 40, RS 48

Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 40, RS 48 Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 0, RS 8 Zero switching AC Solid State Relay Direct copper bonding (DCB) technology in 25A and 0A types LED indication Clip-on IP 20 protection

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

7000 Series Buccaneer

7000 Series Buccaneer The all plastic and metal construction of the - circular that combine the ease of use of a quick coupling mechanism with proven environmental sealing for signal and mains power. Designed and independently

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Preventa Machine Safety Products

Preventa Machine Safety Products Preventa Machine Safety Products Catalog 2009 200 Supplement Safety Relay Modules 2 Contents Preventa safety relay modules Selection guide 2 Electrical Ratings 6 Types XPSAC and XPSAXE For Emergency stop

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information