Relion 615 series. Transformer Protection and Control RET615 Product Guide
|
|
|
- Lynne Sanders
- 9 years ago
- Views:
Transcription
1 Relion 615 series Transformer Protection and Control Product Guide
2 Contents 1. Description Standard configurations Protection functions Application Supported ABB solutions Control Measurements Disturbance recorder Event log Recorded data Condition monitoring Trip-circuit supervision Self-supervision Fuse failure supervision Access control Inputs and outputs Station communication Technical data Local HMI Mounting methods Relay case and plug-in unit Selection and ordering data Accessories and ordering data Tools Cyber security Terminal diagrams Certificates References Functions, codes and symbols Document revision history Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Copyright 2015 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. 2 ABB
3 Issued: Revision: K 1. Description is a dedicated transformer protection and control relay for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems. is a member of ABB s Relion product family and part of its 615 protection and control product series. The 615 series relays are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC standard for communication and interoperability between substation automation devices. Once the standard configuration relay has been given the application-specific settings, it can directly be put into service. The 615 series relays support a range of communication protocols including IEC with Edition 2 support, process bus according to IEC LE, IEC , Modbus and DNP3. Profibus DPV1 communication protocol is supported by using the protocol converter SPA-ZC Standard configurations is available in eight alternative standard configurations. The standard signal configuration can be altered by means of the signal matrix or the graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions utilizing various logical elements including timers and flip-flops. By combining protection functions with logic function blocks the relay configuration can be adapted to user specific application requirements. The relay is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs. Some of the supported functions in must be added with the Application Configuration tool to be available in the Signal Matrix tool and in the relay. The positive measuring direction of directional protection functions is towards the outgoing feeder. ABB 3
4 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION A PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF 3Ith>T/G/C 49T/G/C 3I> 51P-1 Io 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR Io (HV) 3 6 RTD 2 ma 3I (LV) Io> 51N-1 18 MAP MAP I2> 46 3I>>> 50P/51P 3 Io>> 51N-2 3I> 51P-1 ARC 50L/50NL diolo> 87NL Io 3I>> 51P-2 3dI>T 87T CONDITION MONITORING AND SUPERVISION CBCM CBCM OPTS OPTM 2 TCS TCM CONTROL AND INDICATION 1) Object Ctrl 2) Ind 3) CB 1 - DC 2 3 ES 1 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object COMMUNICATION Protocols: IEC Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP MEASUREMENT - HV side: I, Io - LV side: I - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components Analog interface types 1) Current transformer 7 Voltage transformer - 1) Conventional transformer inputs TPOSM 84M REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-C90DE25B-AEC FC8-F4604ACDB769 V2 EN Figure 1. Functionality overview for standard configuration A 4 ABB
5 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION B PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF Io 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR 6 RTD 2 ma Io (LV) 18 MAP MAP Io> 51N-1 Io>> 51N-2 diolo> 87NL Io 3dI>T 87T CONDITION MONITORING AND SUPERVISION CBCM CBCM OPTS OPTM 2 TCS TCM COMMUNICATION Protocols: IEC Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP 3 3I (LV) I2> 46 3I>>> 50P/51P 3 3I> 51P-1 ARC 50L/50NL 3I>> 51P-2 CONTROL AND INDICATION 1) Object Ctrl 2) Ind 3) CB 1 - DC 2 3 ES 1 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object MEASUREMENT - HV side: I - LV side: I, Io - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components Analog interface types 1) Current transformer 7 Voltage transformer - 1) Conventional transformer inputs TPOSM 84M REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-C948BC5D FC-B8C3F7BA5BAB V2 EN Figure 2. Functionality overview for standard configuration B ABB 5
6 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION C PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR Io 3 Io (HV) 6 RTD 2 ma 3I (LV) Io> 51N-1 diohi> 87NH 18 MAP MAP I2> 46 3I>>> 50P/51P 3 Io>> 51N-2 3dI>T 87T 3I> 51P-1 Io ARC 50L/50NL 3I>> 51P-2 CONDITION MONITORING AND SUPERVISION CBCM CBCM OPTS OPTM 2 TCS TCM CONTROL AND INDICATION 1) Object Ctrl 2) Ind 3) CB DC ES COMMUNICATION Protocols: IEC Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP MEASUREMENT - HV side: I, Io - LV side: I - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object Analog interface types 1) Current transformer 7 Voltage transformer - 1) Conventional transformer inputs TPOSM 84M REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-F8F3319F-B60D-47EF-A BC683D6C V2 EN Figure 3. Functionality overview for standard configuration C 6 ABB
7 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION D PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF Io 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR 6 RTD 2 ma Io (LV) 18 MAP MAP diohi> 87NH Io> 51N-1 3dI>T 87T Io>> 51N-2 CONDITION MONITORING AND SUPERVISION CBCM CBCM OPTS OPTM 2 TCS TCM COMMUNICATION Protocols: IEC Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP Io CONTROL AND INDICATION 1) MEASUREMENT 3 3I (LV) I2> 46 3I>>> 50P/51P 3 3I> 51P-1 ARC 50L/50NL 3I>> 51P-2 Object Ctrl 2) Ind 3) CB 1 - DC 2 3 ES 1 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object - HV side: I - LV side: I, Io - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components Analog interface types 1) Current transformer 7 Voltage transformer - 1) Conventional transformer inputs TPOSM 84M REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-422AE187-3E2A-4A20-BBE2-2B8A840DC1FA V2 EN Figure 4. Functionality overview for standard configuration D ABB 7
8 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control Uo U L1 U L2 U L3 TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION E PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR Io 3 Io (HV) 2xRTD 1xmA Io> 51N-1 18 MAP MAP I2> 46 3 Io>> 51N-2 ARC 50L/50NL diolo> 87NL Io 3dI>T 87T 3I (HV) CONDITION MONITORING AND SUPERVISION 2 FUSEF 60 TCS TCM CBCM CBCM OPTS OPTM CONTROL AND INDICATION 1) COMMUNICATION Protocols: IEC /9-2LE Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP MEASUREMENT 3I (LV) 3I>>> 50P/51P 3I> 51P-1 3I>> 51P-2 Object Ctrl 2) Ind 3) CB DC ES HV side: I, Io, U, Uo, P, Q, E, pf, f - LV side: I - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components U L1 U L2 U L3 2 3U< U> 59 U L1 U L2 U L3 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object Analog interface types 1) Current transformer 7 Voltage transformer 2) 5 1) Conventional transformer inputs Uo 2 Uo> 59G TPOSM 84M 2) One of the five inputs is reserved for future applications REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-DC590CA4-DF86-499D-8B77-3DE0CB2997F0 V2 EN Figure 5. Functionality overview for standard configuration E 8 ABB
9 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control Uo U L1 U L2 U L3 TRANSFORMER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION F PROTECTION LOCAL HMI ALSO AVAILABLE 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF Io 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR 2 RTD 1 ma Io (LV) 18 MAP MAP Io> 51N-1 Io>> 51N-2 diolo> 87NL Io 3dI>T 87T 3I (HV) CONDITION MONITORING AND SUPERVISION 2 FUSEF 60 TCS TCM CBCM CBCM OPTS OPTM COMMUNICATION Protocols: IEC /9-2LE Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP 3 3I (LV) I2> 46 3I>>> 50P/51P 3 3I> 51P-1 ARC 50L/50NL 3I>> 51P-2 CONTROL AND INDICATION 1) Object Ctrl 2) Ind 3) CB DC ES MEASUREMENT - HV side: I, U, Uo, P, Q, E, pf, f - LV side: I, Io - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components U L1 U L2 U L3 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object Analog interface types 1) Current transformer 7 Voltage transformer 2) 5 1) Conventional transformer inputs U L1 U L2 U L3 2 3U< U> 59 2 Uo> 59G TPOSM 84M 2) One of the five inputs is reserved for future applications Uo REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-7F2F76A7-E9D A C V2 EN Figure 6. Functionality overview for standard configuration F ABB 9
10 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control Uo U L1 U L2 U L3 PROTECTION TRANSFORMER PROTECTION AND CONTROL RELAY LOCAL HMI STANDARD CONFIGURATION ALSO AVAILABLE G 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR Io 2xRTD 1xmA Io (HV) Io> 51N-1 diohi> 87NH 18 MAP MAP Io>> 51N-2 3dI>T 87T 3I (HV) CONDITION MONITORING AND SUPERVISION 2 FUSEF 60 TCS TCM CBCM CBCM OPTS OPTM COMMUNICATION Protocols: IEC /9-2LE Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP 3 3I (LV) I2> 46 3I>>> 50P/51P 3 3I> 51P-1 Io ARC 50L/50NL 3I>> 51P-2 U L1 U L2 U L3 CONTROL AND INDICATION 1) Object Ctrl 2) Ind 3) CB 1 - DC 2 3 ES 1 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object MEASUREMENT - HV side: I, Io, U, Uo, P, Q, E, pf, f - LV side: I - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components Analog interface types 1) Current transformer 7 Voltage transformer 5 1) Conventional transformer inputs U L1 U L2 U L3 2 3U< U> 59 2 Uo> 59G TPOSM 84M Uo REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-D133822F-DB95-4CF6-B971-9D67054A5731 V2 EN Figure 7. Functionality overview for standard configuration G 10 ABB
11 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear Configuration System HMI Time Authorization ESC A Clear Transformer Protection and Control Uo U L1 U L2 U L3 PROTECTION TRANSFORMER PROTECTION AND CONTROL RELAY LOCAL HMI STANDARD CONFIGURATION ALSO AVAILABLE H 3I (HV) I2> 46 3I>/Io>BF 51BF/51NBF Io 3Ith>T/G/C 49T/G/C 3I> 51P-1 3I>>> 50P/51P 3I>> 51P-2 I O R L I O R L - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR 2 RTD 1 ma Io (LV) 18 MAP MAP diohi> 87NH Io> 51N-1 3dI>T 87T Io>> 51N-2 3I (HV) CONDITION MONITORING AND SUPERVISION 2 FUSEF 60 TCS TCM CBCM CBCM OPTS OPTM COMMUNICATION Protocols: IEC /9-2LE Modbus IEC DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP Io CONTROL AND INDICATION 1) MEASUREMENT 3 3I (LV) I2> 46 3I>>> 50P/51P 3 3I> 51P-1 ARC 50L/50NL 3I>> 51P-2 U L1 U L2 U L3 Object Ctrl 2) Ind 3) CB 1 - DC 2 3 ES 1 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object - HV side: I, U, Uo, P, Q, E, pf, f - LV side: I, Io - Limit value supervision - Load profile record - RTD/mA measurement, optional - Symmetrical components Analog interface types 1) Current transformer 7 Voltage transformer 5 1) Conventional transformer inputs U L1 U L2 U L3 2 3U< U> 59 2 Uo> 59G TPOSM 84M Uo REMARKS 2 Master trip Lockout relay 94/86 3 Master Trip Lockout relay 94/86 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-8C9FE17B C-BE D23FC744 V2 EN Figure 8. Functionality overview for standard configuration H ABB 11
12 Table 1. Standard configurations Description Transformer differential with low-impedance restricted earth-fault protection on the HV side Transformer differential with low-impedance restricted earth-fault protection on the LV side Transformer differential with high-impedance restricted earth-fault protection on the HV side Transformer differential with high-impedance restricted earth-fault protection on the LV side Transformer differential with voltage protection and measurements, and low-impedance restricted earth-fault protection on the HV side Transformer differential with voltage protection and measurements, and low-impedance restricted earth-fault protection on the LV side Transformer differential with voltage protection and measurements, and high-impedance restricted earth-fault protection on the HV side Transformer differential with voltage protection and measurements, and high-impedance restricted earth-fault protection on the LV side Std. conf. A B C D E F G H 12 ABB
13 Table 2. Supported functions Function IEC A B C D E F G H Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV PHLPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Three-phase non-directional overcurrent protection, high stage Three-phase non-directional overcurrent protection, instantaneous stage PHHPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV PHHPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV PHIPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV PHIPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Non-directional earth-fault protection, low stage EFLPTOC1 1 HV 1 HV 1) 1 HV 1 HV 1) EFLPTOC2 1 LV 1 LV 2) 1 LV 1 LV 2) Non-directional earth-fault protection, high stage EFHPTOC1 1 HV 1 HV 1) 1 HV 1 HV 1) EFHPTOC2 1 LV 1 LV 2) 1 LV 1 LV 2) Negative-sequence overcurrent protection NSPTOC1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV NSPTOC2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Residual overvoltage protection ROVPTOV 2 HV 2 HV 2 HV 2 HV Three-phase undervoltage protection PHPTUV 2 HV 2 HV 2 HV 2 HV Three-phase overvoltage protection PHPTOV 2 HV 2 HV 2 HV 2 HV Three-phase thermal overload protection, two time constants Stabilized and instantaneous differential protection for two-winding transformers Numerically stabilized low-impedance restricted earth-fault protection High-impedance based restricted earth-fault protection T2PTTR 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV TR2PTDF LREFPNDF 1 HV 1 LV 1 HV 1 LV HREFPDIF 1 HV 1 LV 3) 1 HV 1 LV 3) Circuit breaker failure protection CCBRBRF 1 HV 1) 1 HV 1) 1 HV 1) 1 HV 1) 1 HV 1) 1 HV 1) 1 HV 1) 1 HV 1) Master trip TRPPTRC 2 (3) 4) 2 (3) 4) 2 (3) 4) 2 (3) 4) 2 (3) 4) 2 (3) 4) 2 (3) 4) 2 (3) 4) Arc protection ARCSARC (3) LV 5) (3) LV 5) (3) LV 5) (3) LV 5) (3) LV 5) (3) LV 5) (3) LV 5) (3) LV 5) Multipurpose protection MAPGAPC Control Circuit-breaker control CBXCBR 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV Disconnector control DCXSWI Earthing switch control ESXSWI Disconnector position indication DCSXSWI Earthing switch indication ESSXSWI Tap changer position indication TPOSYLTC Condition monitoring and supervision Circuit-breaker condition monitoring SSCBR 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV Trip circuit supervision TCSSCBR Fuse failure supervision SEQSPVC Runtime counter for machines and devices MDSOPT Measurement Disturbance recorder RDRE Load profile record LDPRLRC Fault record FLTRFRC Three-phase current measurement CMMXU1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV CMMXU2 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV 1 LV Sequence current measurement CSMSQI1 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV 1 HV Residual current measurement RESCMMXU1 1 HV 1 HV 1 HV 1 HV RESCMMXU2 1 LV 1 LV 1 LV 1 LV Three-phase voltage measurement VMMXU 1 HV 1 HV 1 HV 1 HV Residual voltage measurement RESVMMXU 1 HV 1 HV 1 HV 1 HV Sequence voltage measurement VSMSQI 1 HV 1 HV 1 HV 1 HV Three-phase power and energy measurement PEMMXU 1 HV 1 HV 1 HV 1 HV ABB 13
14 Table 2. Supported functions, continued Function IEC A B C D E F G H RTD/mA measurement XRGGIO130 (1) (1) (1) (1) (1) (1) (1) (1) Frequency measurement FMMXU IEC LE sampled value sending 6)7) SMVSENDER (1) (1) (1) (1) IEC LE sampled value receiving SMVRCV (1) (1) (1) (1) (voltage sharing) 6)7) Other Minimum pulse timer (2 pcs) TPGAPC Minimum pulse timer (2 pcs, second resolution) TPSGAPC Minimum pulse timer (2 pcs, minute resolution) TPMGAPC Pulse timer (8 pcs) PTGAPC Time delay off (8 pcs) TOFGAPC Time delay on (8 pcs) TONGAPC Set-reset (8 pcs) SRGAPC Move (8 pcs) MVGAPC Generic control point (16 pcs) SPCGAPC Analog value scaling (4 pcs) SCA4GAPC Integer value move (4 pcs) MVI4GAPC , 2,... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standard configuration. () = optional HV = The function block is to be used on the high-voltage side in the application. LV = The function block is to be used on the low-voltage side in the application. 1) "Io calculated" is always used. 2) IoB calculated is always used. 3) "IoB measured" is always used. 4) Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If additionally the ARC option is selected, ARCSARC is connected in the configuration to the corresponding master trip input. 5) "IoB calculated" and "3IB" are always used. 6) Available only with IEC ) Available only with COM Protection functions The relay features three-phase, multi-slope stabilized (biased) stage transformer differential protection and an instantaneous stage to provide fast and selective protection for phase-tophase short circuit, winding interturn fault and bushing flashover protection. Besides second harmonic restraint, an advanced waveform-based blocking algorithm ensures stability at transformer energization and a fifth harmonic restraint function ensures good protection stability at moderate overexcitation of power transformers. Sensitive restricted earth-fault protection completes the overall differential protection providing detection of even single phase-to-earth faults close to the neutral earthing point of the transformer. Either the conventional high-impedance scheme or a numerical low-impedance scheme can be selected for protection of the transformer windings. When low-impedance restricted earthfault protection is used neither stabilizing resistors nor varistors are needed and as a further benefit the transforming ratio of the neutral earthing CTs can differ from those of the phase current transformers. Due to its unit protection character and absolute selectivity restricted earth fault does not need to be timegraded with other protection schemes, and therefore high speed fault clearance can be achieved. The relay also incorporates a thermal overload protection function, which supervises the thermal stress of the transformer windings to prevent premature aging of the insulation of the windings. Multiple stages of short circuit, phase overcurrent, negative-sequence and earth-fault backup protection are separately available for both sides of the power transformer. Earth-fault protection based on the measured or calculated residual voltage is also available. Depending on the chosen standard configuration the relay also features three-phase overvoltage protection, three-phase undervoltage protection and residual overvoltage protection. Further, the relay also offers circuit breaker failure protection. Enhanced with optional hardware and software, the relay also features three light detection channels for arc fault protection of the circuit breaker, busbar and cable compartment of metalenclosed indoor switchgear. The arc-fault protection sensor interface is available on the optional communication module. Fast tripping increases staff safety and security and limits material damage in an arc fault situation. A binary input and output module can be selected as an option - having three high speed binary outputs (HSO) it further decreases the total operate time with typically ms compared to the normal power outputs. 14 ABB
15 I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L Transformer Protection and Control 4. Application provides main protection for two-winding power transformers and power generator-transformer blocks. The eight standard configurations offer comprehensive protection functions for detection and elimination of operational disturbance conditions and power transformer faults. The standard configurations A, C, E and G are intended for power transformers with earthed HV side neutrals. The A and E configuration features low-impedance REF protection while the C and G configurations offer high-impedance REF protection. The B, D, F and H configurations fit transformers with solidlyearthed LV side neutral or the LV side with a neutral earthing resistor. The B, D, F and H configurations also fit applications including a separate earthing transformer located within the area of protection. The A, B, E, and F configurations also suit applications, where the turns ratio of the CT of the neutral earthing circuit differs from the turns ratio of the line CTs. The C, D, G and H configurations require that the turns ratios of the CTs are equal. Standard configurations E, F, G and H include phase-voltage protection and measurement functions which provide twostage power transformer overvoltage and undervoltage protection and/or supervision. Two optional RTD/mA modules are available. The optional RTD/mA module offered for the standard configurations A-D allows up to eight analog signals to be measured via the six RTD inputs and the two ma inputs using transducers. The RTD and ma inputs can be used for measuring the oil temperature at the bottom and top of the transformer. Furthermore, the RTD/mA inputs can be used for measuring the ambient air temperature. The RTD inputs also offer thermal protection of dry-type power transformers fitted with Pt-100 temperature sensors. Temperature measurement over the RTD/mA inputs extends the function of the three-phase thermal overload protection of the relay. Further, one of the RTD inputs can also be used as a direct resistance measuring input for position information of the on-load tap changer. Alternatively, the tap changer position indication can be obtained via a ma-transducer. The optional RTD/mA module offered for the standard configurations E-H allows up to three analog signals to be measured via the two RTD inputs and the one ma input using transducers. The RTD inputs can be used for measuring the oil temperature and the ambient air temperature. Temperature measurement over the RTD inputs extends the function of the three-phase thermal overload protection of the relay. For onload tap changer, the tap changer position indication can be obtained via a ma transducer. If required, the analog temperature or tap changer position values can be sent to other devices using analog horizontal GOOSE messaging. Analog values can also be received from other devices over the station bus, thus improving the extent of relevant information. 3I (HV) O Std. conf. ANSI 49T 50L/50NL 50P/51P 51P/51N 87NL 87T A IEC Io (HV) 3Ith>T ARC 3I>>> 3I/Io diolo> 3dI>T RTD 3I (LV) GUID-6657E450-7FB D-E896064D04A3 V1 EN Figure 9. Protection of a two-winding power transformer with standard configuration A Figure 9 illustrates the protection of a two-winding power transformer with standard configuration A. The main protection used in this application example is transformer differential protection. Additionally, restricted earth-fault protection with numerical low-impedance principle is applied on the transformer's HV side. ABB 15
16 I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A Clear R L Clear R L Transformer Protection and Control 3I (HV) O Std. conf. D ANSI IEC 49T 3Ith>T RTD 50L/50NL ARC 50P/51P 3I>>> Io (LV) 51P/51N 87NH 3I/Io diohi> 87T 3dI>T 3I (LV) GUID-46A1FCF8-F2EC EA8-636E4AEF84FC V1 EN Figure 10. Protection of a two-winding power transformer with standard configuration D Figure 10 illustrates the protection of a two-winding power transformer with standard configuration D. The main protection used in this application example is transformer differential protection. Additionally, restricted earth-fault protection with high-impedance principle is applied on the transformer's LV side. 3U Uo 3I (HV) O Std. conf. E ANSI IEC RTD Io (HV) 27/59 49T 50L/50NL 50P/51P 51P/51N 59G 87NL 87T 3U</3U> 3Ith>T ARC 3I>>> 3I/Io Uo> diolo> 3dI>T 3I (LV) GUID-3C760FFC-6D6B-4860-A198-4BA4273B32D9 V1 EN Figure 11. Protection of a two-winding power transformer with standard configuration E Figure 11 illustrates the protection of a two-winding power transformer with standard configuration E. The main protection used in this application example is transformer differential protection. Additionally, restricted earth-fault protection with numerical low-impedance principle and voltage based protection are applied on the transformer's HV side. 16 ABB
17 I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L Transformer Protection and Control 3U Uo 3I (HV) O Std. conf. ANSI IEC E RTD Io (HV) 27/59 49T 50L/50NL 50P/51P 51P/51N 87NL 87T 3U</3U> 3Ith>T ARC 3I>>> 3I/Io diolo> 3dI>T 3U 3I (LV) O REU615 Std. conf. B ANSI IEC 27/59 50P/51P 51P/51N 84M 90V 3U</3U> 3I>>> 3I/Io TPOSM COLTC GUID-AB31C909-F38E-4885-AFEE-E2EEE V4 EN Figure 12. Protection of a two-winding power transformer with standard configuration E Figure 12 illustrates the protection of a two-winding power transformer with standard configuration. The main protection used in this application example is transformer differential protection. Restricted earth-fault protection with numerical low-impedance principle is applied on the transformer's HV side. The RTD inputs of are utilized for monitoring the oil temperature and oil level of the transformer. Additionally, REU615 with the standard configuration B is used as automatic voltage regulator for the on-load tap changer of the transformer. ABB 17
18 5. Supported ABB solutions ABB s 615 series protection and control relays together with the Substation Automation Unit COM600 constitute a genuine IEC solution for reliable power distribution in utility and industrial power systems. To facilitate and streamline the system engineering, ABB's relays are supplied with connectivity packages. The connectivity packages include a compilation of software and relay-specific information, including single-line diagram templates and a full relay data model. The data model also includes event and parameter lists. With the connectivity packages, the relays can be readily configured using PCM600 and integrated with the Substation Automation Unit COM600 or the network control and management system MicroSCADA Pro. The 615 series relays offer native support for IEC Edition 2 also including binary and analog horizontal GOOSE messaging. In addition, process bus with the sending of sampled values of analog currents and voltages and the receiving of sampled values of voltages is supported. Compared to traditional hard-wired, inter-device signaling, peer-to-peer communication over a switched Ethernet LAN offers an advanced and versatile platform for power system protection. Among the distinctive features of the protection system approach, enabled by the full implementation of the IEC substation automation standard, are fast communication capability, continuous supervision of the integrity of the protection and communication system, and an inherent flexibility regarding reconfiguration and upgrades. This protection relay series is able to optimally utilize interoperability provided by the IEC Edition 2 features. At substation level, COM600 uses the data content of the baylevel devices to enhance substation level functionality. COM600 features a Web browser-based HMI, which provides a customizable graphical display for visualizing single-line mimic diagrams for switchgear bay solutions. The SLD feature is especially useful when 615 series relays without the optional single-line diagram feature are used. The Web HMI of COM600 also provides an overview of the whole substation, including relay-specific single-line diagrams, which makes information easily accessible. Substation devices and processes can also be remotely accessed through the Web HMI, which improves personnel safety. In addition, COM600 can be used as a local data warehouse for the substation's technical documentation and for the network data collected by the devices. The collected network data facilitates extensive reporting and analyzing of network fault situations, by using the data historian and event handling features of COM600. The history data can be used for accurate monitoring of process and equipment performance, using calculations based on both real-time and history values. A better understanding of the process dynamics is achieved by combining time-based process measurements with production and maintenance events. COM600 can also function as a gateway and provide seamless connectivity between the substation devices and network-level control and management systems, such as MicroSCADA Pro and System 800xA. GOOSE Analyzer interface in COM600 enables the following and analyzing the horizontal IEC application during commissioning and operation at station level. It logs all GOOSE events during substation operation to enable improved system supervision. Table 3. Supported ABB solutions Product Substation Automation Unit COM600 Version 4.0 SP1 or later 4.1 or later (Edition 2) MicroSCADA Pro SYS FP2 or later 9.4 or later (Edition 2) System 800xA 5.1 or later 18 ABB
19 ABB MicroSCADA Pro/ System 800xA Utility: IEC Industry: OPC COM600 Web HMI COM600 Web HMI Ethernet switch PCM600 Ethernet switch PCM600 Analog and binary horizontal GOOSE communication IEC Analog and binary horizontal GOOSE communication IEC GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V2 EN Figure 13. ABB power system example using Relion relays, Substation Automation Unit COM600 and MicroSCADA Pro/System 800xA 6. Control integrates functionality for the control of a circuit breaker via the front panel HMI or by means of remote controls. In addition to the circuit-breaker control the relay features two control blocks which are intended for motor-operated control of disconnectors or circuit breaker truck and for their position indications. Further, the relay offers one control block which is intended for motor-operated control of one earthing switch control and its position indication. Two physical binary inputs and two physical binary outputs are needed in the relay for each controllable primary device taken into use. Depending on the chosen standard configuration of the relay the number of unused binary inputs and binary outputs varies. Further, some standard configurations also offer optional hardware modules that increase the number of available binary inputs and outputs. If the amount of available binary inputs or outputs of the chosen standard configuration is not sufficient, the standard configuration can be modified to release some binary inputs or outputs which have originally been configured for other purposes, when applicable, or an external input or output module, for example, RIO600 can be integrated to the relay. The binary inputs and outputs of the external I/O module can be used for the less time critical binary signals of the application. The integration enables releasing of some initially reserved binary inputs and outputs of the relay in the standard configuration. The suitability of the binary outputs of the relay which have been selected for controlling of primary devices should be carefully verified, for example the make and carry as well as the breaking capacity. In case the requirements for the control-circuit of the primary device are not met, the use of external auxiliary relays should to be considered. The optional large graphical LCD of the relay's HMI includes a single-line diagram (SLD) with position indication for the relevant primary devices. Interlocking schemes required by the application are configured using the signal matrix or the application configuration functionality of PCM600. ABB 19
20 7. Measurements The relay continuously measures the high voltage (HV) side and the low voltage (LV) side phase currents and the neutral current of the protected transformer. In addition, the relay calculates the symmetrical components of the currents and voltages, maximum current demand value over a user-selectable pre-set time frame, the active and reactive power, the power factor, and the active and reactive energy values. Calculated values are also obtained from the protection and condition monitoring functions of the relay. Depending on the standard configuration, the relay also measures the phase voltages, the residual voltage and the voltage sequence components. For standard configuration A, B, C and D RTD/mA inputs are offered as an option. By means of the optional RTD/mA module the relay can measure up to eight analog signals such as temperature, pressure and tap changer position values via the six RTD inputs or the two ma inputs using transducers. For standard configuration E, F, G and H RTD/mA inputs are offered as an option. By means of these inputs the relay can measure up to three analog signals such as temperature, pressure and tap changer position values via the two RTD inputs or the one ma inputs using transducers. The values measured can be accessed locally via the user interface on the relay's front panel or remotely via the communication interface of the relay. The values can also be accessed locally or remotely using the Web browser-based user interface. The relay is provided with a load profile recorder. The load profile feature stores the historical load data captured at a periodical time interval (demand interval). The records are in COMTRADE format. 8. Disturbance recorder The relay is provided with a disturbance recorder with up to 12 analog and 64 binary signal channels. The analog channels can be set to record either the waveform or the trend of the currents and voltages measured. The analog channels can be set to trigger the recording function when the measured value falls below, or exceeds, the set values. The binary signal channels can be set to start a recording either on the rising or the falling edge of the binary signal or on both. By default, the binary channels are set to record external or internal relay signals, for example, the start or trip signals of the relay stages, or external blocking or control signals. Binary relay signals, such as protection start and trip signals, or an external relay control signal via a binary input, can be set to trigger the recording. Recorded information is stored in a non-volatile memory and can be uploaded for subsequent fault analysis. 9. Event log To collect sequence-of-events information, the relay has a nonvolatile memory with a capacity of storing 1024 events with associated time stamps. The non-volatile memory retains its data also in case the relay temporarily loses its auxiliary supply. The event log facilitates detailed pre- and post-fault analyses of feeder faults and disturbances. The increased capacity to process and store data and events in the relay offers prerequisites to support the growing information demand of future network configurations. The sequence-of-events information can be accessed either locally via the user interface on the relay's front panel, or remotely via the communication interface of the relay. The information can also be accessed using the Web browserbased user interface, either locally or remotely. 10. Recorded data The relay has the capacity to store the records of the 128 latest fault events. The records enable the user to analyze the power system events. Each record includes current, voltage and angle values, time stamp and so on. The fault recording can be triggered by the start signal or the trip signal of a protection block, or by both. The available measurement modes include DFT, RMS and peak-to-peak. Fault records store relay measurement values at the moment when any protection function starts. In addition, the maximum demand current with time stamp is separately recorded. The records are stored in the non-volatile memory. 11. Condition monitoring The condition monitoring functions of the relay constantly monitor the performance and the condition of the circuit breaker. The monitoring comprises the spring charging time, SF6 gas pressure, the travel time and the inactivity time of the circuit breaker. The monitoring functions provide operational circuit breaker history data, which can be used for scheduling preventive circuit breaker maintenance. In addition, the relay includes a runtime counter for monitoring of how many hours a protected device has been in operation thus enabling scheduling of time-based preventive maintenance of the device. 12. Trip-circuit supervision The trip-circuit supervision continuously monitors the availability and operability of the trip circuit. It provides opencircuit monitoring both when the circuit breaker is in its closed and in its open position. It also detects loss of circuit-breaker control voltage. 20 ABB
21 13. Self-supervision The relay s built-in self-supervision system continuously monitors the state of the relay hardware and the operation of the relay software. Any fault or malfunction detected is used for alerting the operator. A permanent relay fault blocks the protection functions to prevent incorrect operation. 14. Fuse failure supervision Depending on the chosen standard configuration, the relay includes fuse failure supervision functionality. The fuse failure supervision detects failures between the voltage measurement circuit and the relay. The failures are detected either by the negative sequence-based algorithm or by the delta voltage and delta current algorithm. Upon the detection of a failure, the fuse failure supervision function activates an alarm and blocks voltage-dependent protection functions from unintended operation. 15. Access control To protect the relay from unauthorized access and to maintain information integrity, the relay is provided with a four-level, rolebased authentication system with administrator-programmable individual passwords for the viewer, operator, engineer and administrator level. The access control applies to the frontpanel user interface, the Web browser-based user interface and PCM Inputs and outputs The relay is equipped with six phase-current inputs and one neutral-current input or six phase-current inputs, one neutralcurrent input, three phase-voltage inputs and one residual voltage input. The rated level of the current inputs is 1/5 A and selectable in the relay software. The three phase-voltage inputs and the residual-voltage input covers the rated voltages V. Both phase-to-phase voltages and phase-to-earth voltages can be connected. In addition, the binary input thresholds V DC are selected by adjusting the relay s parameter settings. All binary inputs and outputs contacts are freely configurable with the signal matrix or application configuration functionality of PCM600. As an option for standard configurations A, B, C and D, the relay offers six RTD inputs and two ma inputs. By means of the optional RTD/mA module the relay can measure up to eight analog signals such as temperature, pressure and tap changer position values via the six RTD inputs or the two ma inputs using transducers. The values can, apart from measuring and monitoring purposes, be used for tripping and alarm purposes using the offered optional multipurpose protection functions. As an option for standard configurations E, F, G and H, the relay offers two RTD inputs and one ma input. As an option a binary input and output module can be selected, having three high speed binary outputs (HSO), decreasing further the total operate time with typically ms compared to the normal power outputs. Please refer to the Input/output overview table and the terminal diagrams for more detailed information about the inputs and outputs. Table 4. Input/output overview Std. conf. Order code digit Analog channels Binary channels CT VT BI BO RTD ma BB PO + 9 SO - - A B C D E F G H BA BG BC BE FF PO + 5 SO + 3 HSO - - BA PO + 6 SO 6 2 FD PO + 2 SO + 3 HSO 6 2 AD PO + 6 SO - - FE PO + 2 SO + 3 HSO - - BA PO + 6 SO 2 1 FD PO + 2 SO + 3 HSO 2 1 ABB 21
22 17. Station communication The relay supports a range of communication protocols including IEC Edition 2, IEC LE, IEC , Modbus and DNP3. Profibus DPV1 communication protocol is supported with using the protocol converter SPA-ZC 302. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the relays, is only enabled by the IEC communication protocol. The IEC protocol is a core part of the relay as the protection and control application is fully based on standard modelling. The relay supports Edition 2 and Edition 1 versions of the standard. With Edition 2 support, the relay has the latest functionality modelling for substation applications and the best interoperability for modern substations. It incorporates also the full support of standard device mode functionality supporting different test applications. Control applications can utilize the new safe and advanced station control authority feature. The IEC communication implementation supports monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC protocol. Disturbance recordings are available to any Ethernet-based application in the standard COMTRADE file format. The relay supports simultaneous event reporting to five different clients on the station bus. The relay can exchange data with other devices using the IEC protocol. The relay can send binary and analog signals to other devices using the IEC GOOSE (Generic Object Oriented Substation Event) profile. Binary GOOSE messaging can, for example, be employed for protection and interlocking-based protection schemes. The relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC standard (<10 ms data exchange between the devices). The relay also supports the sending and receiving of analog values using GOOSE messaging. Analog GOOSE messaging enables easy transfer of analog measurement values over the station bus, thus facilitating for example the sending of measurement values between the relays when controlling parallel running transformers. The relay also supports IEC process bus by sending sampled values of analog currents and voltages and by receiving sampled values of voltages. With this functionality the galvanic interpanel wiring can be replaced with Ethernet communication. The measured values are transferred as sampled values using IEC LE protocol. The intended application for sampled values shares the voltages to other 615 series relays, having voltage based functions and 9-2 support. 615 relays with process bus based applications use IEEE 1588 for high accuracy time synchronization. For redundant Ethernet communication, the relay offers either two optical or two galvanic Ethernet network interfaces. A third port with galvanic Ethernet network interface is also available. The third Ethernet interface provides connectivity for any other Ethernet device to an IEC station bus inside a switchgear bay, for example connection of a Remote I/O. Ethernet network redundancy can be achieved using the high-availability seamless redundancy (HSR) protocol or the parallel redundancy protocol (PRP) or a with self-healing ring using RSTP in managed switches. Ethernet redundancy can be applied to Ethernet-based IEC 61850, Modbus and DNP3 protocols. The IEC standard specifies network redundancy which improves the system availability for the substation communication. The network redundancy is based on two complementary protocols defined in the IEC standard: PRP and HSR protocols. Both the protocols are able to overcome a failure of a link or switch with a zero switch-over time. In both the protocols, each network node has two identical Ethernet ports dedicated for one network connection. The protocols rely on the duplication of all transmitted information and provide a zero switch-over time if the links or switches fail, thus fulfilling all the stringent real-time requirements of substation automation. In PRP, each network node is attached to two independent networks operated in parallel. The networks are completely separated to ensure failure independence and can have different topologies. The networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid failures. 22 ABB
23 COM600 SCADA Ethernet switch IEC PRP Ethernet switch REF615 REF620 RET620 REM620 REF615 GUID-334D26B1-C3BD-47B6-BD9D A5E9D V1 EN Figure 14. Parallel redundancy protocol (PRP) solution HSR applies the PRP principle of parallel operation to a single ring. For each message sent, the node sends two frames, one through each port. Both the frames circulate in opposite directions over the ring. Every node forwards the frames it receives from one port to another to reach the next node. When the originating sender node receives the frame it sent, the sender node discards the frame to avoid loops. The HSR ring with 615 series relays supports the connection of up to 30 relays. If more than 30 relays are to be connected, it is recommended to split the network into several rings to guarantee the performance for real-time applications. ABB 23
24 COM600 SCADA Devices not supporting HSR Ethernet switch Redundancy Box Redundancy Box Redundancy Box IEC HSR REF615 REF620 RET620 REM620 REF615 GUID D-7FC8-49F3-A4FE-FB4ABB V1 EN Figure 15. High availability seamless redundancy (HSR) solution The choice between the HSR and PRP redundancy protocols depends on the required functionality, cost and complexity. The self-healing Ethernet ring solution enables a cost-efficient communication ring controlled by a managed switch with standard Rapid Spanning Tree Protocol (RSTP) support. The managed switch controls the consistency of the loop, routes the data and corrects the data flow in case of a communication switch-over. The relays in the ring topology act as unmanaged switches forwarding unrelated data traffic. The Ethernet ring solution supports the connection of up to series relays. If more than 30 relays are to be connected, it is recommended to split the network into several rings. The self-healing Ethernet ring solution avoids single point of failure concerns and improves the reliability of the communication. 24 ABB
25 Client A Client B Network A Network B Managed Ethernet switch with RSTP support Managed Ethernet switch with RSTP support GUID-AB81C355-EF5D AE0-01DC076E519C V4 EN Figure 16. Self-healing Ethernet ring solution All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The relay can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber optic LC connector (100Base-FX). If connection to serial bus is required, the 9-pin RS-485 screw-terminal can be used. An optional serial interface is available for RS-232 communication. Modbus implementation supports RTU, ASCII and TCP modes. Besides standard Modbus functionality, the relay supports retrieval of time-stamped events, changing the active setting group and uploading of the latest fault records. If a Modbus TCP connection is used, five clients can be connected to the relay simultaneously. Further, Modbus serial and Modbus TCP can be used in parallel, and if required both IEC and Modbus protocols can be run simultaneously. The IEC implementation supports two parallel serial bus connections to two different masters. Besides basic standard functionality, the relay supports changing of the active setting group and uploading of disturbance recordings in IEC format. Further, IEC can be used at the same time with the IEC protocol. DNP3 supports both serial and TCP modes for connection up to five masters. Changing of the active setting and reading fault records are supported. DNP serial and DNP TCP can be used in parallel. If required, both IEC and DNP protocols can be run simultaneously. 615 series supports Profibus DPV1 with support of SPA-ZC 302 Profibus adapter. If Profibus is required the relay must be ordered with Modbus serial options. Modbus implementation includes SPA-protocol emulation functionality. This functionality enables connection to SPA-ZC 302. When the relay uses the RS-485 bus for the serial communication, both two- and four wire connections are supported. Termination and pull-up/down resistors can be configured with jumpers on the communication card so external resistors are not needed. The relay supports the following time synchronization methods with a time-stamping resolution of 1 ms. Ethernet-based SNTP (Simple Network Time Protocol) With special time synchronization wiring IRIG-B (Inter-Range Instrumentation Group - Time Code Format B) ABB 25
26 The relay supports the following high accuracy time synchronization method with a time-stamping resolution of 4 µs required especially in process bus applications. PTP (IEEE 1588) v2 with Power Profile The IEEE 1588 support is included in all variants having a redundant Ethernet communication module. IEEE 1588 v2 features Ordinary Clock with Best Master Clock algorithm One-step Transparent Clock for Ethernet ring topology 1588 v2 Power Profile Receive (slave): 1-step/2-step Transmit (master): 1-step Layer 2 mapping Peer to peer delay calculation Multicast operation Required accuracy of grandmaster clock is +/-1 µs. The relay can work as a master clock per BMC algorithm if the external grandmaster clock is not available for short term. The IEEE 1588 support is included in all variants having a redundant Ethernet communication module. In addition, the relay supports time synchronization via Modbus, DNP3 and IEC serial communication protocols. Table 5. Supported station communication interfaces and protocols Interfaces/Protocols Ethernet Serial 100BASE-TX RJ BASE-FX LC RS-232/RS-485 Fiber optic ST IEC IEC LE - - MODBUS RTU/ASCII - - MODBUS TCP/IP - - DNP3 (serial) - - DNP3 TCP/IP - - IEC = Supported 26 ABB
27 18. Technical data Table 6. Dimensions Description Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm ( mm) Weight Complete protection relay 4.1 kg Plug-in unit only 2.1 kg Table 7. Power supply Description Type 1 Type 2 Nominal auxiliary voltage U n 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC 48, 60, 110, 125, 220, 250 V DC Maximum interruption time in the auxiliary DC voltage without resetting the relay 50 ms at U n Auxiliary voltage variation % of U n ( V AC) % of U n ( V DC) % of U n ( V DC) Start-up threshold 19.2 V DC (24 V DC 80%) Burden of auxiliary voltage supply under quiescent (P q )/operating condition Ripple in the DC auxiliary voltage Fuse type DC <12.0 W (nominal)/<18.0 W (max) AC <16.0 W (nominal)/<21.0 W (max) Max 15% of the DC value (at frequency of 100 Hz) T4A/250 V DC <12.0 W (nominal)/<18.0 W (max) Table 8. Energizing inputs Description Rated frequency 50/60 Hz ± 5 Hz Current inputs Rated current, I n 1/5 A 1) Thermal withstand capability: Continuously For 1 s 20 A 500 A Dynamic current withstand: Half-wave value Input impedance 1250 A <20 mω Voltage inputs Rated voltage V AC Voltage withstand: Continuous For 10 s Burden at rated voltage 240 V AC 360 V AC <0.05 VA 1) Residual current and/or phase current ABB 27
28 Table 9. Binary inputs Description Operating range Rated voltage Current drain Power consumption Threshold voltage Reaction time ±20% of the rated voltage V DC ma mw V DC <3 ms Table 10. RTD/mA measurement (XRGGIO130) Description RTD inputs Supported RTD sensors 100 Ω platinum 250 Ω platinum 100 Ω nickel 120 Ω nickel 250 Ω nickel 10 Ω copper TCR (DIN 43760) TCR TCR (DIN 43760) TCR TCR TCR Supported resistance range Maximum lead resistance (threewire measurement) Isolation Response time RTD/resistance sensing current kω 25 Ω per lead 2 kv (inputs to protective earth) <4 s Maximum 0.33 ma rms Operation accuracy Resistance Temperature ma inputs Supported current range 0 20 ma Current input impedance 44 Ω ± 0.1% ± 2.0% or ±1 Ω ±1 C 10 Ω copper: ±2 C Operation accuracy ±0.5% or ±0.01 ma Table 11. Signal output X100: SO1 Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R<40 ms Minimum contact load 250 V AC/DC 5 A 15 A 30 A 1 A/0.25 A/0.15 A 100 ma at 24 V AC/DC 28 ABB
29 Table 12. Signal outputs and IRF output Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry 0.5 s Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC Minimum contact load 250 V AC/DC 5 A 10 A 15 A 1 A/0.25 A/0.15 A 10 ma at 5 V AC/DC Table 13. Double-pole power output relays with TCS function Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC (two contacts connected in series) Minimum contact load 250 V AC/DC 8 A 15 A 30 A 5 A/3 A/1 A 100 ma at 24 V AC/DC Trip-circuit supervision (TCS): Control voltage range Current drain through the supervision circuit V AC/DC ~1.5 ma Minimum voltage over the TCS contact 20 V AC/DC ( V) Table 14. Single-pole power output relays Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC Minimum contact load 250 V AC/DC 8A 15 A 30 A 5 A/3 A/1 A 100 ma at 24 V AC/DC ABB 29
30 Table 15. High-speed output HSO with BIO0007 Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V DC Operate time Reset 250 V AC/DC 6 A 15 A 30 A 5 A/3 A/1 A <1 ms <20 ms, resistive load Table 16. Front port Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s Table 17. Station communication link, fiber optic Connector Fiber type 1) Wave length Typical max. length 2) Permitted path attenuation 3) LC ST MM 62.5/125 or 50/125 μm glass fiber core MM 62.5/125 or 50/125 μm glass fiber core 1300 nm 2 km <8 db nm 1 km <11 db 1) (MM) multi-mode fiber, (SM) single-mode fiber 2) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path. 3) Maximum allowed attenuation caused by connectors and cable together Table 18. IRIG-B Description IRIG time code format B004, B005 1) Isolation Modulation Logic level Current consumption Power consumption 500V 1 min Unmodulated 5 V TTL <4 ma <20 mw 1) According to the IRIG standard Table 19. Lens sensor and optical fiber for arc protection Description Fiber optic cable including lens Normal service temperature range of the lens Maximum service temperature range of the lens, max 1 h Minimum permissible bending radius of the connection fiber 1.5 m, 3.0 m or 5.0 m C +140 C 100 mm 30 ABB
31 Table 20. Degree of protection of flush-mounted protection relay Description Front side IP 54 Rear side, connection terminals IP 20 Table 21. Environmental conditions Description Operating temperature range ºC (continuous) Short-time service temperature range ºC (<16h) 1)2) Relative humidity Atmospheric pressure Altitude Transport and storage temperature range <93%, non-condensing kpa Up to 2000 m ºC 1) Degradation in MTBF and HMI performance outside the temperature range of ºC 2) For relays with an LC communication interface the maximum operating temperature is +70 ºC ABB 31
32 Table 22. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 khz burst disturbance test IEC IEC , class III IEEE C Common mode 2.5 kv Differential mode 2.5 kv 3 MHz, 10 MHz and 30 MHz burst disturbance test IEC IEC , class III Common mode 2.5 kv Electrostatic discharge test IEC IEC IEEE C Contact discharge 8 kv Air discharge 15 kv Radio frequency interference test 10 V (rms) f = 150 khz...80 MHz 10 V/m (rms) f = MHz 10 V/m f = 900 MHz 20 V/m (rms) f = MHz IEC IEC , class III IEC IEC , class III ENV IEC , class III IEEE C Fast transient disturbance test IEC IEC IEEE C All ports 4 kv Surge immunity test IEC IEC Communication 1 kv, line-to-earth Other ports 4 kv, line-to-earth 2 kv, line-to-line Power frequency (50 Hz) magnetic field immunity test IEC Continuous s Pulse magnetic field immunity test 300 A/m 1000 A/m 1000 A/m 6.4/16 µs IEC Damped oscillatory magnetic field immunity test IEC s 100 A/m 1 MHz 400 transients/s Voltage dips and short interruptions 30%/10 ms 60%/100 ms 60%/1000 ms >95%/5000 ms IEC ABB
33 Table 22. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC IEC , class A Common mode 300 V rms Differential mode 150 V rms Conducted common mode disturbances 15 Hz khz Test level 3 (10/1/10 V rms) IEC Emission tests EN 55011, class A IEC CISPR 11 CISPR 12 Conducted MHz <79 db (µv) quasi peak <66 db (µv) average MHz <73 db (µv) quasi peak <60 db (µv) average Radiated MHz <40 db (µv/m) quasi peak, measured at 10 m distance MHz <47 db (µv/m) quasi peak, measured at 10 m distance 1 3 GHz < 76 db (µv/m) peak < 56 db (µv/m) average, measured at 3 m distance 3 6 GHz < 80 db (µv/m) peak < 60 db (µv/m) average, measured at 3 m distance Table 23. Insulation tests Description Type test value Reference Dielectric tests Impulse voltage test 2 kv, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication 5 kv, 1.2/50 μs, 0.5 J 1 kv, 1.2/50 μs, 0.5 J, communication IEC IEC Insulation resistance measurements >100 MΩ, 500 V DC IEC Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC Table 24. Mechanical tests Description Reference Requirement Vibration tests (sinusoidal) Shock and bump test IEC (test Fc) IEC IEC (test Ea shock) IEC (test Eb bump) IEC Class 2 Class 2 Seismic test IEC Class 2 ABB 33
34 Table 25. Environmental tests Description Type test value Reference Dry heat test 96 h at +55ºC IEC h at +85ºC 1) Dry cold test Damp heat test 96 h at -25ºC 16 h at -40ºC 6 cycles (12 h + 12 h) at +25 C +55 C, humidity >93% IEC IEC Change of temperature test 5 cycles (3 h + 3 h) at -25 C C IEC Storage test 96 h at -40ºC 96 h at +85ºC IEC IEC ) For relays with an LC communication interface the maximum operating temperature is +70 o C Table 26. Product safety Description LV directive Reference 2006/95/EC Standard EN (2013) EN (2009) Table 27. EMC compliance Description EMC directive Reference 2004/108/EC Standard EN (2013) Table 28. RoHS compliance Description Complies with RoHS directive 2002/95/EC 34 ABB
35 Protection functions Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz PHLPTOC PHHPTOC and PHIPTOC ±1.5% of the set value or ±0.002 I n ±1.5% of set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Start time 1)2) Minimum Typical Maximum PHIPTOC: I Fault = 2 set Start value 16 ms 19 ms 23 ms I Fault = 10 set Start value 11 ms 12 ms 14 ms PHHPTOC and PHLPTOC: I Fault = 2 x set Start value 23 ms 26 ms 29 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <30 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics RMS: No suppression DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression P-to-P+backup: No suppression 1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Includes the delay of the heavy-duty output contact ABB 35
36 Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function (Range) Step Start PHLPTOC I n 0.01 PHHPTOC I n 0.01 PHIPTOC I n 0.01 Time multiplier PHLPTOC PHHPTOC Operate delay time PHLPTOC ms 10 PHHPTOC ms 10 PHIPTOC ms 10 Operating curve type 1) PHLPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 PHHPTOC PHIPTOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time 1) For further reference, see Operation characteristics table Table 31. Non-directional earth-fault protection (EFxPTOC) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz EFLPTOC EFHPTOC and EFIPTOC ±1.5% of the set value or ±0.002 I n ±1.5% of set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Start time 1)2) Minimum Typical Maximum EFIPTOC: I Fault = 2 set Start value I Fault = 10 set Start value 16 ms 11 ms 19 ms 12 ms 23 ms 14 ms EFHPTOC and EFLPTOC: I Fault = 2 set Start value 23 ms 26 ms 29 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <30 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics RMS: No suppression DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression 1) Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of ABB
37 Table 32. Non-directional earth-fault protection (EFxPTOC) main settings Parameter Function (Range) Step Start value EFLPTOC I n EFHPTOC I n 0.01 EFIPTOC I n 0.01 Time multiplier EFLPTOC EFHPTOC Operate delay time EFLPTOC ms 10 EFHPTOC ms 10 EFIPTOC ms 10 Operating curve type 1) EFLPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 EFHPTOC EFIPTOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time 1) For further reference, see Operation characteristics table Table 33. Negative-sequence overcurrent protection (NSPTOC) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±1.5% of the set value or ±0.002 I n Start time 1)2) Minimum Typical Maximum I Fault = 2 set Start value I Fault = 10 set Start value 23 ms 15 ms 26 ms 18 ms 28 ms 20ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of Table 34. Negative-sequence overcurrent protection (NSPTOC) main settings Parameter Function (Range) Step Start value NSPTOC I n 0.01 Time multiplier NSPTOC Operate delay time NSPTOC ms 10 Operating curve type 1) NSPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 1) For further reference, see Operation characteristics table ABB 37
38 Table 35. Residual overvoltage protection (ROVPTOV) Characteristic Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 2 set Start value 48 ms 51 ms 54 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode Suppression of harmonics <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Residual voltage before fault = 0.0 U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact Table 36. Residual overvoltage protection (ROVPTOV) main settings Parameter Function (Range) Step Start value ROVPTOV U n Operate delay time ROVPTOV ms 1 Table 37. Three-phase undervoltage protection (PHPTUV) Characteristic Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 0.9 set Start value 62 ms 66 ms 70 ms Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Typically 40 ms Depends on the set Relative hysteresis <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Start value = 1.0 U n, Voltage before fault = 1.1 U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Minimum Start value = 0.50, Start value multiples in range of ABB
39 Table 38. Three-phase undervoltage protection (PHPTUV) main settings Parameter Function (Range) Step Start value PHPTUV U n 0.01 Time multiplier PHPTUV Operate delay time PHPTUV ms 10 Operating curve type 1) PHPTUV Definite or inverse time Curve type: 5, 15, 21, 22, 23 1) For further reference, see Operation characteristics table Table 39. Three-phase overvoltage protection (PHPTOV) Characteristic Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 1.1 set Start value 23 ms 27 ms 31 ms Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Typically 40 ms Depends of the set Relative hysteresis <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Start value = 1.0 U n, Voltage before fault = 0.9 U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 1.20 U n, Start value multiples in range of Table 40. Three-phase overvoltage protection (PHPTOV) main settings Parameter Function (Range) Step Start value PHPTOV U n 0.01 Time multiplier PHPTOV Operate delay time PHPTOV ms 10 Operating curve type 1) PHPTOV Definite or inverse time Curve type: 5, 15, 17, 18, 19, 20 1) For further reference, see Operation characteristics table Table 41. Three-phase thermal overload protection, two time constants (T2PTTR) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 x I n (at currents in the range of x I n ) Operate time accuracy 1) ±2.0% of the theoretical value or ±0.50 s 1) Overload current > 1.2 x Operate level temperature ABB 39
40 Table 42. Three-phase thermal overload protection, two time constants (T2PTTR) main settings Parameter Function (Range) Step Temperature rise T2PTTR C 0.1 Max temperature T2PTTR C 0.1 Operate temperature T2PTTR % 0.1 Weighting factor p T2PTTR Short time constant T2PTTR s 1 Current reference T2PTTR I n 0.01 Operation T2PTTR Off On - Table 43. Transformer differential protection of two-winding transformers (TR2PTDF) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±3.0% of the set value or ±0.002 I n Start time 1)2) Minimum Typical Maximum Low stage High stage 36 ms 21 ms 41 ms 22 ms 46 ms 24 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements 2) Includes the delay of the output contact. When differential current = 2 set operate value and f n = 50 Hz. 40 ABB
41 Table 44. Stabilized differential protection for two-winding transformers (TR2PTDF) main settings Parameter Function (Range) Step Restraint mode TR2PTDF 2.h & 5.h & wav Waveform 2.h & waveform 5.h & waveform - High operate value TR2PTDF % 10 Low operate value TR2PTDF % 1 Slope section 2 TR2PTDF % 1 End section 2 TR2PTDF % 1 Start value 2.H TR2PTDF % 1 Start value 5.H TR2PTDF % 1 Operation TR2PTDF Off On Winding 1 type TR2PTDF Y YN D Z ZN Winding 2 type TR2PTDF Y YN D Z ZN Zro A elimination TR2PTDF Not eliminated Winding 1 Winding 2 Winding 1 and Table 45. Numerical stabilized low impedance restricted earth-fault protection (LREFPNDF) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±2.5% of the set value or ±0.002 x I n Start time 1)2) Minimum Typical Maximum I Fault = 2.0 set Operate value 37 ms 41 ms 45 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode Suppression of harmonics <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact ABB 41
42 Table 46. Stabilized restricted earth-fault protection (LREFPNDF) main settings Parameter Function (Range) Step Operate value LREFPNDF % 1 Restraint mode LREFPNDF None 2nd harmonic - Start value 2.H LREFPNDF % 1 Minimum operate time LREFPNDF ms 1 Operation LREFPNDF Off On - Table 47. High-impedance based restricted earth-fault protection (HREFPDIF) Characteristic Operation accuracy At the frequency f = f n Start time 1)2) Reset time I Fault = 2.0 set Operate value I Fault = 10.0 set Operate value ±1.5% of the set value or ±0.002 I n Typically 22 ms (±5 ms) Typically 15 ms (±5 ms) <60 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <60 ms ±1.0% of the set value or ±20 ms 1) Current before fault = 0.0 I n, f n = 50 Hz 2) Includes the delay of the signal output contact Table 48. High-impedance based restricted earth-fault protection (HREFPDIF) main settings Parameter Function (Range) Step Operate value HREFPDIF % 0.1 Minimum operate time HREFPDIF ms 1 Operation HREFPDIF Off On - Table 49. Circuit breaker failure protection (CCBRBRF) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±1.5% of the set value or ±0.002 I n Operate time accuracy Reset time 1) Retardation time ±1.0% of the set value or ±20 ms Typically 40 ms <20 ms 1) Trip pulse time defines the minimum pulse length 42 ABB
43 Table 50. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function (Range) Step Current value (Operating phase current) Current value Res (Operating residual current) CCBRBRF I n 0.05 CCBRBRF I n 0.05 CB failure mode (Operating mode of function) CCBRBRF 1 = Current 2 = Breaker status 3 = Both - CB fail trip mode CCBRBRF 1 = Off 2 = Without check 3 = Current check - Retrip time CCBRBRF ms 10 CB failure delay CCBRBRF ms 10 CB fault delay CCBRBRF ms 10 Table 51. Arc protection (ARCSARC) Characteristic Operation accuracy ±3% of the set value or ±0.01 I n Operate time Minimum Typical Maximum Operation mode = "Light 9 ms 3) 12 ms 3) 15 ms 3) +current" 1)2) 4 ms 4) 6 ms 4) 9 ms 4) Operation mode = "Light only" 2) 9 ms 3) 4 ms 4) 6 ms 4) 7 ms 4) 10 ms 3) 12 ms 3) Reset time Typically 40 ms Reset ratio Typically ) Phase start value = 1.0 I n, current before fault = 2.0 set Phase start value, f n = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements 2) Includes the delay of the heavy-duty output contact 3) Normal power output 4) High-speed output Table 52. Arc protection (ARCSARC) main settings Parameter Function (Range) Step Phase start value (Operating phase current) Ground start value (Operating residual current) ARCSARC x I n 0.01 ARCSARC x I n 0.01 Operation mode ARCSARC 1=Light+current 2=Light only 3=BI controlled Table 53. Multipurpose protection (MAPGAPC) Characteristic Operation accuracy ±1.0% of the set value or ±20 ms ABB 43
44 Table 54. Multipurpose protection (MAPGAPC) main settings Parameter Function (Range) Step Start value MAPGAPC Operate delay time MAPGAPC ms 100 Operation mode MAPGAPC Over Under - Table 55. Operation characteristics Parameter Operating curve type Operating curve type (voltage protection) (Range) 1 = ANSI Ext. inv. 2 = ANSI Very. inv. 3 = ANSI Norm. inv. 4 = ANSI Mod inv. 5 = ANSI Def. Time 6 = L.T.E. inv. 7 = L.T.V. inv. 8 = L.T. inv. 9 = IEC Norm. inv. 10 = IEC Very inv. 11 = IEC inv. 12 = IEC Ext. inv. 13 = IEC S.T. inv. 14 = IEC L.T. inv 15 = IEC Def. Time 17 = Programmable 18 = RI type 19 = RD type 5 = ANSI Def. Time 15 = IEC Def. Time 17 = Inv. Curve A 18 = Inv. Curve B 19 = Inv. Curve C 20 = Programmable 21 = Inv. Curve A 22 = Inv. Curve B 23 = Programmable 44 ABB
45 Control functions Table 56. Tap position indication (TPOSYLTC) Descrpition Response time for binary inputs Typical 100 ms ABB 45
46 Condition and supervision functions Table 57. Circuit-breaker condition monitoring (SSCBR) Characteristic Current measuring accuracy Operate time accuracy Travelling time measurement ±1.5% or ±0.002 x I n (at currents in the range of x I n ) ±5.0% (at currents in the range of x I n ) ±1.0% of the set value or ±20 ms +10 ms / -0 ms Table 58. Fuse failure supervision (SEQSPVC) Characteristic Operate time 1) NPS function U Fault = 1.1 set Neg Seq voltage Lev U Fault = 5.0 set Neg Seq voltage Lev <33 ms <18 ms Delta function ΔU = 1.1 set Voltage change rate <30 ms ΔU = 2.0 set Voltage change rate <24 ms 1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements Table 59. Runtime counter for machines and devices (MDSOPT) Description Motor runtime measurement accuracy 1) ±0.5% 1) Of the reading, for a stand-alone relay, without time synchronization. 46 ABB
47 Measurement functions Table 60. Three-phase current measurement (CMMXU) Characteristic Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±0.5% or ±0.002 I n (at currents in the range of I n ) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression Table 61. Sequence current measurement (CSMSQI) Characteristic Operation accuracy Depending on the frequency of the measured current: f/f n = ±2 Hz ±1.0% or ±0.002 I n at currents in the range of I n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 62. Residual current measurement (RESCMMXU) Characteristic Operation accuracy Depending on the frequency of the current measured: f/f n = ±2 Hz ±0.5% or ±0.002 I n at currents in the range of I n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression Table 63. Three-phase voltage measurement (VMMXU) Characteristic Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz At voltages in range U n ±0.5% or ±0.002 U n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression Table 64. Residual voltage measurement (RESVMMXU) Characteristic Operation accuracy Depending on the frequency of the measured current: f/f n = ±2 Hz ±0.5% or ±0.002 U n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression ABB 47
48 Table 65. Sequence voltage measurement (VSMSQI) Characteristic Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz At voltages in range U n ±1.0% or ±0.002 U n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 66. Three-phase power and energy measurement (PEMMXU) Characteristic Operation accuracy At all three currents in range I n At all three voltages in range U n At the frequency f n ±1 Hz ±1.5% for apparent power S ±1.5% for active power P and active energy 1) ±1.5% for reactive power Q and reactive energy 2) ±0.015 for power factor Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) PF >0.5 which equals cosφ >0.5 2) PF <0.86 which equals sinφ >0.5 Table 67. RTD/mA measurement (XRGGIO130) Description RTD inputs Supported RTD sensors 100 Ω platinum 250 Ω platinum 100 Ω nickel 120 Ω nickel 250 Ω nickel 10 Ω copper TCR (DIN 43760) TCR TCR (DIN 43760) TCR TCR TCR Supported resistance range Maximum lead resistance (threewire measurement) Isolation Response time RTD/resistance sensing current kω 25 Ω per lead 2 kv (inputs to protective earth) <4 s Maximum 0.33 ma rms Operation accuracy Resistance Temperature ma inputs Supported current range 0 20 ma Current input impedance 44 Ω ± 0.1% ± 2.0% or ±1 Ω ±1 C 10 Ω copper: ±2 C Operation accuracy ±0.5% or ±0.01 ma 48 ABB
49 Other functions Table 68. Pulse timer function block (PTGAPC) Characteristic Operate time accuracy ±1.0% of the set value or ±20 ms Table 69. Time delay off (8 pcs) (TOFPAGC) Characteristic Operate time accuracy ±1.0% of the set value or ±20 ms Table 70. Time delay on (8 pcs) (TONGAPC) Characteristic Operate time accuracy ±1.0% of the set value or ±20 ms ABB 49
50 19. Local HMI The relay is available with two optional displays, a large one and a small one. The large display is suited for relay installations where the front panel user interface is frequently used and a single line diagram is required. The small display is suited for remotely controlled substations where the relay is only occasionally accessed locally via the front panel user interface. Both LCD displays offer front-panel user interface functionality with menu navigation and menu views. However, the large display offers increased front-panel usability with less menu scrolling and improved information overview. In addition, the large display includes a user-configurable single line diagram (SLD) with position indication for the associated primary equipment. Depending on the chosen standard configuration, the relay displays the related measuring values, apart from the default single line diagram. The SLD view can also be accessed using the Web browser-based user interface. The default SLD can be modified according to user requirements by using the Graphical Display Editor in PCM600. The user can create up to 10 SLD pages. The local HMI includes a push button (L/R) for local/remote operation of the relay. When the relay is in the local mode, it can be operated only by using the local front panel user interface. When the relay is in the remote mode, it can execute commands sent from a remote location. The relay supports the remote selection of local/remote mode via a binary input. This feature facilitates, for example, the use of an external switch at the substation to ensure that all relays are in the local mode during maintenance work and that the circuit breakers cannot be operated remotely from the network control center. IECA V3 EN IECA V3 EN Figure 17. Small display Figure 18. Large display Table 71. Small display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) 5 20 Large, variable width (13x14 pixels) 3 8 or more 1) Depending on the selected language Table 72. Large display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 7 8 or more 1) Depending on the selected language 50 ABB
51 20. Mounting methods By means of appropriate mounting accessories the standard relay case for the 615 series relay can be flush mounted, semiflush mounted or wall mounted. The flush mounted and wall mounted relay cases can also be mounted in a tilted position (25 ) using special accessories. Further, the relays can be mounted in any standard 19 instrument cabinet by means of 19 mounting panels available with cut-outs for one or two relays.alternatively, the relay can be mounted in 19 instrument cabinets by means of 4U Combiflex equipment frames. For the routine testing purposes, the relay cases can be equipped with test switches, type RTXP 18, which can be mounted side by side with the relay cases. Mounting methods: Flush mounting Semi-flush mounting Semi-flush mounting in a 25 tilt Rack mounting Wall mounting Mounting to a 19" equipment frame Mounting with a RTXP 18 test switch to a 19" rack Panel cut-out for flush mounting: Height: ±1 mm Width: ±1 mm IECA V4 EN IECA V4 EN IECA V4 EN Figure 19. Flush mounting Figure 20. Semi-flush mounting Figure 21. Semi-flush with a 25º tilt 21. Relay case and plug-in unit For safety reasons, the relay cases for current measuring relays are provided with automatically operating contacts for shortcircuiting the CT secondary circuits when a relay unit is withdrawn from its case. The relay case is further provided with a mechanical coding system preventing current measuring relay units from being inserted into a relay case for a voltage measuring relay unit and vice versa, that is, the relay cases are assigned to a certain type of plug-in unit. 22. Selection and ordering data Use the ABB Library to access the selection and ordering information and to generate the order number. ABB 51
52 23. Accessories and ordering data Table 73. Cables Item Cable for optical sensors for arc protection 1.5 m Cable for optical sensors for arc protection 3.0 m Cable for optical sensors for arc protection 5.0 m Order number 1MRS MRS MRS Table 74. Mounting accessories Item Semi-flush mounting kit Wall mounting kit Inclined semi-flush mounting kit Order number 1MRS MRS MRS rack mounting kit with cut-out for one relay 1MRS rack mounting kit with cut-out for two relays 1MRS Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19 variant C) Mounting bracket for one relay in 4U Combiflex (RHGT 19 variant C) 2RCA022642P0001 2RCA022643P rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the delivery) 2RCA021952A rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the delivery) 2RCA022561A0003 Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the installation plate) Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of the installation plate) Replacement kit for two Strömberg SP_J3 series relays 2RCA027871A0001 2RCA027874A0001 2RCA027880A rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001 Replacement kit for a Strömberg SP_J6 series relay Replacement kit for three BBC S_ series relays Replacement kit for a SPA 300 series relay 2RCA027881A0001 2RCA027882A0001 2RCA027885A ABB
53 24. Tools The protection relay is delivered as a pre-configured unit. The default parameter setting values can be changed from the frontpanel user interface, the Web browser-based user interface (Web HMI) or the PCM600 tool in combination with the relayspecific connectivity package. The Protection and Control IED Manager PCM600 offers extensive relay configuration functions such as relay signal configuration, application configuration, graphical display configuration including single line diagram configuration, and IEC communication configuration including horizontal GOOSE communication. When the Web browser-based user interface is used, the protection relay can be accessed either locally or remotely using a Web browser (Internet Explorer). For security reasons, the Web browser-based user interface is disabled by default but it can be enabled via the front-panel user interface. The Web HMI functionality can be limited to read-only access. The relay connectivity package is a collection of software and specific relay information, which enable system products and tools to connect and interact with the protection relay. The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and setup times. Further, the connectivity packages for protection relays of this product series include a flexible update tool for adding one additional local HMI language to the protection relay. The update tool is activated using PCM600, and it enables multiple updates of the additional HMI language, thus offering flexible means for possible future language updates. Table 75. Tools Configuration and setting tools PCM600 Version 2.6 (Rollup ) or later Web browser-based user interface IE 8.0, IE 9.0, IE 10.0 or IE 11.0 Connectivity Package 5.1 or later ABB 53
54 Table 76. Supported functions Function Web HMI PCM600 Relay parameter setting Saving of relay parameter settings in the relay Signal monitoring Disturbance recorder handling Alarm LED viewing Access control management Relay signal configuration (Signal Matrix) - Modbus communication configuration (communication management) - DNP3 communication configuration (communication management) - IEC communication configuration (communication management) - Saving of relay parameter settings in the tool - Disturbance record analysis - XRIO parameter export/import - Graphical display configuration - Application configuration - IEC communication configuration, GOOSE (communication configuration) - Phasor diagram viewing - Event viewing Saving of event data on the user's PC Online monitoring - = Supported 25. Cyber security The relay supports role based user authentication and authorization. It can store 2048 audit trail events to a nonvolatile memory. The non-volatile memory is based on a memory type which does not need battery backup or regular component exchange to maintain the memory storage. FTP and Web HMI use TLS encryption with a minimum of 128 bit key length protecting the data in transit. In this case the used communication protocols are FTPS and HTTPS. All rear communication ports and optional protocol services can be deactivated according to the desired system setup. 54 ABB
55 26. Terminal diagrams GUID-3CB989EB-6ECA-471F-8692-DB15C1DE5EFB V2 EN Figure 22. Terminal diagram of standard configurations A-D ABB 55
56 GUID-3655E0AF-034F-4D63-B098-5B5321A13662 V1 EN Figure 23. Terminal diagram of standard configurations E-H 56 ABB
57 27. Certificates DNV GL has issued an IEC Edition 2 Certificate Level A1 for Relion 615 series. Certificate number: I-OPE/INC DNV GL has issued an IEC Edition 1 Certificate Level A1 for Relion 615 series. Certificate number: OPE/INC References The portal provides information on the entire range of distribution automation products and services. You will find the latest relevant information on the protection and control relay on the product page. Scroll down the page to find and download the related documentation. Additional certificates can be found on the product page. ABB 57
58 29. Functions, codes and symbols Table 77. Functions included in the relay Function IEC IEC IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage Three-phase non-directional overcurrent protection, high stage Three-phase non-directional overcurrent protection, instantaneous stage PHLPTOC1 3I> (1) 51P-1 (1) PHLPTOC2 3I> (2) 51P-1 (2) PHHPTOC1 3I>> (1) 51P-2 (1) PHHPTOC2 3I>> (2) 51P-2 (2) PHIPTOC1 3I>>> (1) 50P/51P (1) PHIPTOC2 3I>>> (2) 50P/51P (2) Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1) EFLPTOC2 Io> (2) 51N-1 (2) Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1) EFHPTOC2 Io>> (2) 51N-2 (2) Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46 (1) NSPTOC2 I2> (2) 46 (2) Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1) ROVPTOV2 Uo> (2) 59G (2) Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1) PHPTUV2 3U< (2) 27 (2) Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1) PHPTOV2 3U> (2) 59 (2) Three-phase thermal overload protection, two time constants Stabilized and instantaneous differential protection for two-winding transformers Numerically stabilized low-impedance restricted earthfault protection T2PTTR1 3Ith>T/G/C (1) 49T/G/C (1) TR2PTDF1 3dI>T (1) 87T (1) LREFPNDF1 diolo> (1) 87NL (1) High-impedance based restricted earth-fault protection HREFPDIF1 diohi> (1) 87NH (1) Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1) Master trip TRPPTRC1 Master Trip (1) 94/86 (1) TRPPTRC2 Master Trip (2) 94/86 (2) TRPPTRC3 Master Trip (3) 94/86 (3) TRPPTRC4 Master Trip (4) 94/86 (4) TRPPTRC5 Master Trip (5) 94/86 (5) Arc protection ARCSARC1 ARC (1) 50L/50NL (1) ARCSARC2 ARC (2) 50L/50NL (2) ARCSARC3 ARC (3) 50L/50NL (3) 58 ABB
59 Table 77. Functions included in the relay, continued Function IEC IEC IEC-ANSI Multipurpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4) MAP (4) MAPGAPC5 MAP (5) MAP (5) MAPGAPC6 MAP (6) MAP (6) MAPGAPC7 MAP (7) MAP (7) MAPGAPC8 MAP (8) MAP (8) MAPGAPC9 MAP (9) MAP (9) MAPGAPC10 MAP (10) MAP (10) MAPGAPC11 MAP (11) MAP (11) MAPGAPC12 MAP (12) MAP (12) MAPGAPC13 MAP (13) MAP (13) MAPGAPC14 MAP (14) MAP (14) MAPGAPC15 MAP (15) MAP (15) MAPGAPC16 MAP (16) MAP (16) MAPGAPC17 MAP (17) MAP (17) MAPGAPC18 MAP (18) MAP (18) Control Circuit-breaker control CBXCBR1 I <-> O CB (1) I <-> O CB (1) Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1) DCXSWI2 I <-> O DCC (2) I <-> O DCC (2) Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1) Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1) DCSXSWI2 I <-> O DC (2) I <-> O DC (2) DCSXSWI3 I <-> O DC (3) I <-> O DC (3) Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1) ESSXSWI2 I <-> O ES (2) I <-> O ES (2) Tap changer position indication TPOSYLTC1 TPOSM (1) 84M (1) Condition monitoring and supervision Circuit-breaker condition monitoring SSCBR1 CBCM (1) CBCM (1) Trip circuit supervision TCSSCBR1 TCS (1) TCM (1) TCSSCBR2 TCS (2) TCM (2) Fuse failure supervision SEQSPVC1 FUSEF (1) 60 (1) Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1) Measurement Disturbance recorder RDRE1 DR (1) DFR (1) Load profile record LDPRLRC1 LOADPROF (1) LOADPROF (1) ABB 59
60 Table 77. Functions included in the relay, continued Function IEC IEC IEC-ANSI Fault record FLTRFRC1 FAULTREC (1) FAULTREC (1) Three-phase current measurement CMMXU1 3I (1) 3I (1) CMMXU2 3I (2) 3I (2) Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1) Residual current measurement RESCMMXU1 Io (1) In (1) RESCMMXU2 Io (2) In (2) Three-phase voltage measurement VMMXU1 3U (1) 3V (1) Residual voltage measurement RESVMMXU1 Uo (1) Vn (1) Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1) Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1) RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1) Frequency measurement FMMXU1 f (1) f (1) IEC LE sampled value sending SMVSENDER SMVSENDER SMVSENDER IEC LE sampled value receiving (voltage sharing) SMVRCV SMVRCV SMVRCV Other Minimum pulse timer (2 pcs) TPGAPC1 TP (1) TP (1) TPGAPC2 TP (2) TP (2) TPGAPC3 TP (3) TP (3) TPGAPC4 TP (4) TP (4) Minimum pulse timer (2 pcs, second resolution) TPSGAPC1 TPS (1) TPS (1) Minimum pulse timer (2 pcs, minute resolution) TPMGAPC1 TPM (1) TPM (1) Pulse timer (8 pcs) PTGAPC1 PT (1) PT (1) PTGAPC2 PT (2) PT (2) Time delay off (8 pcs) TOFGAPC1 TOF (1) TOF (1) TOFGAPC2 TOF (2) TOF (2) TOFGAPC3 TOF (3) TOF (3) TOFGAPC4 TOF (4) TOF (4) Time delay on (8 pcs) TONGAPC1 TON (1) TON (1) TONGAPC2 TON (2) TON (2) TONGAPC3 TON (3) TON (3) TONGAPC4 TON (4) TON (4) Set-reset (8 pcs) SRGAPC1 SR (1) SR (1) SRGAPC2 SR (2) SR (2) SRGAPC3 SR (3) SR (3) SRGAPC4 SR (4) SR (4) Move (8 pcs) MVGAPC1 MV (1) MV (1) MVGAPC2 MV (2) MV (2) 60 ABB
61 Table 77. Functions included in the relay, continued Function IEC IEC IEC-ANSI Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1) SPCGAPC2 SPC (2) SPC (2) Analog value scaling SCA4GAPC1 SCA4 (1) SCA4 (1) SCA4GAPC2 SCA4 (2) SCA4 (2) SCA4GAPC3 SCA4 (3) SCA4 (3) SCA4GAPC4 SCA4 (4) SCA4 (4) Integer value move MVI4GAPC1 MVI4 (1) MVI4 (1) 30. Document revision history Document revision/date Product version History A/ First release B/ Content updated C/ Content updated to correspond to the product version D/ Terminology updated E/ Content updated F/ Content updated to correspond to the product version G/ FP1 Content updated to correspond to the product version H/ Content updated to correspond to the product version K/ FP1 Content updated to correspond to the product version ABB 61
62 62
63
64 Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI VAASA, Finland Phone Fax ABB India Limited, Distribution Automation Maneja Works Vadodara , India Phone Fax Copyright 2015 ABB. All rights reserved.
Relion 615 series. Transformer Protection and Control RET615 Product Guide
Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...14 4. Application...14 5. Supported ABB solutions...18
Line differential protection and control RED615 Compact and versatile solution for utility and industrial power distribution systems
Relion 65 series Line differential protection and control RED65 Compact and versatile solution for utility and industrial power distribution systems Ideal selectivity for twoend line differential protection
Relion 615 series. Voltage Protection and Control REU615 Product Guide
Relion 615 series Voltage Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...7 4. Application...7 5. Supported ABB solutions...9 6.
Relion 615 series. Motor Protection and Control REM615 Application Manual
Relion 615 series Motor Protection and Control REM615 Document ID: 1YHT530017D05 Issued: 2014-05-14 Revision: B Product version: 4.1 Copyright 2014 ABB. All rights reserved Copyright This document and
Relion 615 series. Line Differential Protection and Control RED615 Product Guide
Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...11 4. Application...11 5. Supported ABB solutions...14
Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification
Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version
Relion product family. Grid Automation Recloser Protection and Control RER615 Product Guide
Relion product family Grid Automation Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...8 4. Application...8 5. Supported ABB solutions...10 6. Control...10
Relion 611 series. Feeder Protection and Control REF611 Application Manual
Relion 611 series Feeder Protection and Control REF611 Document ID: 1MRS757456 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document and parts
Relion 620 series. Feeder Protection and Control REF620 Product Guide
Relion 620 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Default configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...15
Numerical transformer protection in medium voltage networks Transformer Protection and Control RET620
Guideform Specification 1MRS758531 A Numerical transformer protection in medium voltage networks Transformer Protection and Control RET620 The configurable transformer management relay is intended for
Relion 630 series. Motor Protection and Control REM630 Product Guide
Relion 630 series Motor Protection and Control Product Guide Contents 1. Description... 3 2. Application... 3 3. Preconfigurations... 7 4. Protection functions...12 5. Control... 12 6. Measurement... 12
Relion 611 series. Feeder Protection and Control REF611 Product Guide
Relion 611 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...7 5. Supported ABB solutions...9 6.
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Relion product family. Grid Automation Remote Monitoring and Control REC615 Product Guide
Relion product family Grid Automation Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...12 6. Control...13
Substation Automation Products Relion 670/650 series IEC and ANSI Hardware
Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common
Station Automation Series COM600 Protection and control from ABB Future-proof Concept: Extensive Substation System Integration and Interoperability The Station Automation Series COM600 is a dedicated system
IEC 61850 in ZX Gas-insulated medium voltage switchgear
IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Just as the supply of electrical power is becoming more and more important in a networked world, demands for the integration of electrical
Disturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide
Relion 605 series Feeder protection and control / Feeder protection Product Guide Product version: 2.2FP1 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...
Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual
Relion 611 series Feeder Protection and Control REF611 Modbus Document ID: 1MRS757463 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Relion 605 series. Self-powered feeder protection REJ603 Product Guide
Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...
Managing Relion IEDs Protection and control IED manager PCM600
Managing Relion IEDs Protection and control IED manager PCM600 Efficient management of Relion protection and control IEDs The protection and control IED manager PCM600 tool provides versatile functionalities
Power network telecommunication
www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,
ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
Relion 620 series. Motor protection and control REM620 ANSI Product guide
Relion 620 series Motor protection and control REM620 ANSI Product guide Table of contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions... 8 4. Application... 8 5. Supported
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
How To Replace Ancienti'S Ref615R
Relion 615 series Feeder protection and control REF615R Product guide Table of contents 1. Description...3 2. Standard configurations...4 3. Protection functions...6 4. Application...7 5. Supported ABB
Secure your electrical network. PACiS The Safety Solution for Healthcare Institutions
Secure your electrical network The Safety Solution for Healthcare Institutions Fast Secure : the solution for fault isolation and electrical network restoration in less than 500 ms 03 A Real Time System
Relion Protection and Control. 611 series Technical Manual
Relion Protection and Control 611 series Document ID: 1MRS757454 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document and parts thereof must
E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays E-Series protective relay family Reliable protection for every application Eaton s E-Series relay
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850
Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing
Feeder Protection Relay. Technical Reference Manual - ANSI Version
1MRS755535 Issued: 30.01.2005 Version: E/18.11.2011 Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4. Product documentation...
How To Protect Your Power Supply From Dangerous Currents And Voltages
ids ACOS 300 Protection equipment for medium and highvoltage grids ACOS 300 Protection Devices Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
IEC 61850: Communication Networks and Systems in Substations
IEC 61850: Communication Networks and Systems in Substations Sistemi e strumenti per l'automazione, A. Flammini, AA2011-2012 Background I: Power Grid Sistemi e strumenti per l'automazione A. Flammini,
Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE
Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Relion 670 series. Busbar protection REB670 2.0 Product guide
Relion 670 series Busbar protection REB670 2.0 Product guide Contents 1. Application... 3 2. Available functions...11 3. Differential protection...19 4. Zone selection...20 5. Current protection... 22
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
30 ms High Speed Transfer System (HSTS) Product Description
30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
TDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Protection and Substation Automation. Training Programmes
Protection and Substation Automation Training Programmes Protection and Substation Automation Training Programme Overview The objective of the Training Program is to provide education and training to make
Grid Automation Products. MicroSCADA Pro for substation automation
Grid Automation Products for substation automation Perfect control anywhere, anytime is an investment for today and tomorrow. Start, for instance, with monitoring or gateway functionality and integrate
EnerVista Viewpoint Monitoring
EnerVista Viewpoint Monitoring Easy to Use Monitoring and Data Recording EnerVista Viewpoint Monitoring is an easy to setup, powerful and simple to use data monitoring and recording software application
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
Applications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
Technical Information POWER PLANT CONTROLLER
Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
GE Protection and Control Business Department. Page 1 Date 5/11/99
GE Protection and Control Business Department Page 1 GE Protection and Control Business Department Proven Overcurrent Protection with Power Management Communication The The Advantages of Microprocessor
Technical Specification Of Substation Protection & Control System with IEC 61850 BHEL s Perspective
Technical Specification Of Substation Protection & Control System with IEC 61850 BHEL s Perspective India Core Events 2008 September 24 th 2008 1 Background Stability & Reliability Data Storage Communication
Capacitor Protection Relay SPAJ 160 C. Product Guide
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
ABB RTU560A Series CMU & Modules
ABB RTU560A Series CMU & Modules 1KGT 150 648 V1.02 March 4, 2012 Slide 1 Contents RTU560A rack solutions March 4, 2012 Slide 2 560CSR01 Available for wall mounting and swing frame Supports redundant power
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General A. Electrical usage on the Brown campus is presently monitored by a Siemens-brand, web-based central metering system, which includes
Measuring and monitoring units VAMP 96 VAMP 260 WIMO 6CP10
Measuring and monitoring units VAMP 96 Measuring and monitoring units Main characteristics Intelligent measuring and monitoring units The VAMP and WIMO meters come with an extensive selection of pre-configured
Low Voltage Products
Low Voltage Products ABB Power Quality Filters: The most efficient solution for active filtering of harmonics, smooth reactive power compensation and load balancing. Enabling trouble-free and efficient
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Grid Automation Products. SAM600 Process Bus I/O System Cyber Security Deployment Guideline
Grid Automation Products SAM600 Process Bus I/O System Cyber Security Deployment Guideline Document ID: 1MRK 511 430-UEN Issued: April 2016 Revision: - Product version: 1.1 Copyright 2016 ABB. All rights
Communicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
EnerVista Viewpoint Monitoring
EnerVista Viewpoint Monitoring Easy to Use Monitoring and Data Recording EnerVista Viewpoint Monitoring is an easy to setup, powerful and simple to use data monitoring and recording software application
Cahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
Emirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland [email protected] ESB International, Ireland [email protected]
A project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template
Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister [email protected] Date
ISBN 978-967-5770-63-0
Assessment of Arc Flash Detection System in Distribution Network Imran bin Hussin College of Engineering, Universiti Tenaga Nasional, Malaysia. Email: [email protected] Dr Au Mau Teng College of
Internet-Accessible Power Monitoring & Control Systems
Internet-Accessible Power Monitoring & Control Systems By GE Specification Engineers Keith B. Brock, P.E. Robert P. Hansen, PhD, P.E. Introduction Accessing electrical system information from any location
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
G650. Protection, control and monitoring for generator interconnection. Digital Energy Multilin. Communications
G650 & ontrol System Protection, control and monitoring for generator interconnection Key Benefits omplete distributed generator interconnection protection with two protection options, Basic Protection
GROUP OF SPANISH ELECTRICITY COMPANIES FOR STUDIES ON IEC 61850
GROUP OF SPANISH ELECTRICITY COMPANIES FOR STUDIES ON IEC 61850 MINIMUM COMMON SPECIFICATION FOR SUBSTATION PROTECTION AND CONTROL EQUIPMENT IN ACCORDANCE WITH THE IEC 61850 STANDARD EDITION MODIFICATION
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand
Electric utilities may vary in their application of end-to-end testing
An Application Case of End-to-End Relay Testing of Communication-Based Protection Schemes Using GPS-Synchronized Secondary Injection Feature by J. Ariza, Megger USA G. Ibarra, CFE, Mexico Electric utilities
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
Logic, IEC61850 System Configuration and Real-Time Monitoring. Security Auditing, Device and Asset Health Reporting and Fault Data Retrieval
The EnerVista suite is designed to simplify every aspect of your workflow processes Device Setup & Document Management Toolset The EnerVista launchpad software is a powerful toolset used for the complete
Process Alarm Solutions
Process Alarm Solutions Reliable Supervision and Control www.selco.com SELCO flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring of electrical
Medium voltage arc flash eliminator units VAM 3ED,
Medium voltage arc flash eliminator units VAM 3ED,, Medium voltage arc flash eliminator units Medium voltage arc flash eliminator units The new innovative arc eliminator VAM 3ED is an extremely fast acting