Technical Information POWER PLANT CONTROLLER

Size: px
Start display at page:

Download "Technical Information POWER PLANT CONTROLLER"

Transcription

1 Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for PV power plants with central inverters as well as for PV systems with decentralized string inverters. With the help of simulation tools, valuable predictions on the behavior of the Power Plant Controller and the design of the system are possible even before the commissioning of a PV power plant. A high performance PLC enables fast adaptation of reactive and active power in accordance with the requirements of the electric utility company for the stabilization of the grid. With expandability for new communication protocols, standards for individual connections and a modular design, the Power Plant Controller is well suited to meet the future requirements of PV power plants. PPC-TI-en-12 Version 1.2 ENGLISH

2 1 Power Plant Controller SMA Solar Technology AG 1 Power Plant Controller 1.1 System Overview The Power Plant Controller assumes control of the entire PV power plant. The PV power plant can combine both central inverters and decentralized string inverters, which are monitored and controlled by the Cluster Controller or Inverter Manager. Figure 1: Principle of signal transfer in a PV power plant with Power Plant Controller In the Power Plant Controller, the setpoints for grid management services are received and compared with the values measured at the point of interconnection. Based on this comparison, the Power Plant Controller calculates the required output values which it transmits to the central inverters and the Cluster Controllers or Inverter Managers. Up to 200 central inverters or a maximum of 20 SMA Cluster Controllers and/or Inverter Managers can be connected. In master/slave operation of multiple Power Plant Controllers, uniform control of up to 1,000 central inverters is possible (see Section 3.9, page 9). The Power Plant Controller can receive setpoints in digital or analog form and via Modbus. The digital setpoints are transmitted by the grid operator or by a higher-level SCADA system. The measured values that the Power Plant Controller receives are measured at the point of interconnection, processed by a network analyzer, and transmitted to the Power Plant Controller as analog values or via Modbus protocol. 2 PPC-TI-en-12 Technical Information

3 SMA Solar Technology AG 1 Power Plant Controller Nearly all international directives for grid management services and all the control procedures described in this document are supported. The Power Plant Controller can read out up to three network analyzers connected to the point of interconnection. The network analyzers can be used for redundancy purposes. For each of the measured values P, Q, V and f, a source can be configured for measured value 1 (default) and for measured value 2 (redundant value). If the source for the measured value 1 fails, the second (redundant) measured value will be used instead. Transmission of the output values from the Power Plant Controller to central inverters, SMA Cluster Controllers and Inverter Managers takes place via Modbus protocol. 1.2 Design of the Power Plant Controller Figure 2: Position A B C Exterior and interior view of the Power Plant Controller (example) Designation Touch display* Control unit Connection area *optional 1.3 Dimensions of the Power Plant Controller Width Height Depth Weight 720 mm 1,125 mm 325 mm 60 kg Technical Information PPC-TI-en-12 3

4 2 Mounting Information SMA Solar Technology AG 2 Mounting Information 2.1 Minimum Clearances Observe the following minimum clearances to ensure trouble-free installation. Observe the minimum clearances to ensure easy mounting, opening and closing of the Power Plant Controller. The opening angle of the door is 180. Figure 3: Minimum Clearances 2.2 Requirements for Mounting Requirements for the Mounting Location The Power Plant Controller without display is suitable for outdoor mounting. The Power Plant Controller with display is only suitable for indoor mounting. The mounting location must not be in a living or office area. The mounting location must not block any escape routes. The mounting location must be freely and safely accessible at all times without the necessity for any auxiliary equipment. Non-fulfillment of these criteria may restrict servicing. The mounting location and the mounting foundation must be suitable for the weight and dimensions of the Power Plant Controller. The ambient conditions must be suitable for the operation of the Power Plant Controller. The mounting location should not be exposed to direct solar irradiation. The Power Plant Controller must be mounted on a solid support surface. 4 PPC-TI-en-12 Technical Information

5 SMA Solar Technology AG 2 Mounting Information Permitted Mounting Positions Figure 4: Permitted mounting position 2.3 Requirements for Commissioning the Power Plant Controller Since the Power Plant Controller will take over the control of the entire system according to system-specific specifications, it is necessary for the PV power plant to meet the following requirements at the time of commissioning the Power Plant Controller: All connected inverters have been commissioned and are feeding electric current into the utility grid. A network is installed and all central inverters and the SMA Cluster Controller can be reached via port 80 (HTTP) and port 502 (Modbus TCP/UDP). Local network access to the system network is available. The current feed-in data can be measured at the grid-connection point by up to two network analyzers or with analog signals. It must be possible to measure the values for active and reactive power, frequency and line-to-neutral voltage of the energy fed in. The network analyzers must be accessible via the system network. Commissioning requires sufficient irradiation. The weather forecast should be considered during scheduling. The behavior of the entire PV system is constantly monitored in the course of commissioning. Consequently, it might be necessary to adjust the parameters of the inverters. Prior to commissioning, the requirements for the acceptance tests must be agreed upon with the grid operator and SMA Solar Technology AG. This might result in further requirements for commissioning. The Power Plant Controller can only be reached externally via a VPN connection. SMA must have a VPN connection to the system to be able to intervene promptly whenever service is required. This VPN connection must not necessarily be permanent, but must be possible for service purposes. Technical Information PPC-TI-en-12 5

6 3 Functional Description of the Power Plant Controller SMA Solar Technology AG 3 Functional Description of the Power Plant Controller 3.1 New Functions as of Software Version R. (Release 3) Feed-in limitation (see Section 3.4, page 7) Direct marketing interface(see Section 3.4, page 7) Individual reactive power supply by the inverters(see Section 3.5, page 7) Activation of the functions "Q at Night" and "Q on Demand" in the inverters (see Section 3.5, page 7) Disconnection of the inverters(see Section 3.11, page 9) 3.2 Control Procedure The Power Plant Controller operates with two independent controllers: one active power controller and one reactive power controller. Each controller can be operated in different modes. All relevant parameters and procedures are configured during commissioning. Mode Control mode Control mode Manual operation Description The Power Plant Controller transmits the setpoints of the grid operator to the connected devices. The Power Plant Controller calculates an output value using the current actual value and the specified setpoint. The actual value is measured in the network analyzer at the point of interconnection. A deadband can be set up for control within which deviations are ignored and control is not activated. The Power Plant Controller transmits the manually configured setpoint to the connected devices. The manual setpoint can either be specified via the Modbus protocol or configured via the user interface during commissioning. It is ensured that all transmitted output values are within the permitted control range for all modes. The changeover from control or manual mode to control mode is bumpless. This prevents sudden power changes during switchover. 3.3 Control Principle The actual values of the PV power plant measured at the point of interconnection and the current setpoints are transmitted to the Power Plant Controller. The setpoints can either be specified manually or by the grid operator. The PID controller in the Power Plant Controller compares the incoming actual values with the setpoints and calculates an output value according to the specifications. The Power Plant Controller transmits this output value to the connected devices. The inverters adjust the power fed in based on the new setpoints and feed this in at the grid-connection point. There, this power is measured again and transmitted as an actual value to the Power Plant Controller. The new actual values are compared with the setpoints in the PID controller and new output values are calculated that help the inverters achieve the specified setpoints even more closely. This constant control procedure ensures that changes in the power fed in are monitored and that modified setpoints are taken into account within a very short period of time. The interval that the Power Plant Controller uses to send the output values to the connected devices must be configured individually for the specific system. A minimum interval of 100 ms is possible for central inverters and a minimum interval of one second for Cluster Controllers. Actual achievable values depend on many factors and must be specified for each system individually. 6 PPC-TI-en-12 Technical Information

7 SMA Solar Technology AG 3 Functional Description of the Power Plant Controller 3.4 Active Power Control There are two procedures available for active power control. Procedure Direct setpoint specification Setpoint in accordance with P(f) characteristic curve Description Limitation of the active power setpoint to a setpoint entered on the user interface or to an externally specified setpoint. The permissible range for this setpoint can be parameterized via the user interface. Frequency-dependent specification of the active power setpoint. The setpoint is calculated from a characteristic curve. Characteristic curves are available for the requirements in Germany, France, and South Africa. Both procedures can operate in parallel with active power control. This ensures that the lower setpoint is transmitted to the connected devices. If both procedures for active power control are deactivated, the maximum active power setpoint is always active. Direct Marketing Interface In addition to the grid operator interface, a direct marketing interface is implemented in the Power Plant Controller. Alongside the grid operator, the direct marketer can specify direct setpoints for the active power using the Modbus interface. If different default values are specified, the smaller value has priority. Feed-In Limitation In some regions, the grid operator requires that the PV energy generated is used exclusively or mostly for self-consumption. If no active power is allowed to be fed in (zero export), the Power Plant Controller adjusts to a setpoint of 0 W at the feed-in point. To avoid short-term grid feed-in after internal loads have been disconnected, a safety margin can be configured as an offset to the permitted feed-in amount. 3.5 Reactive Power Control One procedure is active for reactive power control. Procedure Direct setpoint specification Setpoint specification according to Q(V) characteristic curve Direct power factor specification Setpoint specification in accordance with cos φ(p) characteristic curve Voltage - reactive power droop Direct voltage control Hybrid control Description Specification of a fixed setpoint for reactive power. The permissible range for this setpoint can be parameterized on the user interface and must not exceed ± 50% of the nominal power of the PV power plant. Voltage-dependent specification of the reactive power setpoint. The setpoint is calculated from a characteristic curve. The measured voltage values are smoothed before further processing. Specification of a fixed power factor to a fixed value within the range. Power factor specification dependent on active power Voltage-dependent calculation of the reactive power setpoint. The output value is calculated from the actual voltage value and the specified voltage setpoint using the gradient of the characteristic curve. Control takes place as a direct function of the voltage. A hybrid value is calculated both from the setpoints and from the actual values for voltage and reactive power. The Power Plant Controller calculates the reactive power output values from the hybrid setpoints and actual values. Technical Information PPC-TI-en-12 7

8 3 Functional Description of the Power Plant Controller SMA Solar Technology AG "Q at Night" and "Q on Demand" Function of the Inverters With the inverter order option "Q at Night" or "Q on Demand", the inverter can supply reactive power in order to stabilize the utility grid during non-feed-in operation, e.g. at night (for further information on the "Q at Night" function, see the inverter manual). By activating the function "Q at Night", the Power Plant Controller can send the reactive power setpoints to the inverter even in non-feed-in mode. This function needs to be activated in the inverter and in the Power Plant Controller under PPC > Grid system services > Device table inverters for each individual inverter. Individual Reactive Power Supply (2 Options) There are two options for distributing reactive power to individual inverters: via the reactive power limitation for individual inverters via activation of the individual reactive power supply It is not possible to use both options simultaneously. Option 1: Individual reactive power limitation For this function, the nominal reactive power as well as two possible thresholds are parameterized for each inverter. If the lower reactive power threshold is reached during operation, the given inverter will not receive any higher output values for the time being. The effectiveness of this threshold is, however, canceled if the inverter would be able mathematically to supply reactive powers above the second threshold. Using this function, a PV system can, by taking the system topology into account, maintain the power factor required by the grid operator without having to carry out dynamic reduction of the active power. The function is deactivated if both thresholds are set to the same value (default setting). Option 2: Individual reactive power supply Alternatively, it is possible to activate the function "Individual reactive power supply". Using this function, inverters with low instantaneous power make a large contribution to reactive power, and vice versa. 3.6 Apparent Power Limitation The output values of active and reactive power control are limited to the maximum apparent power. Here, you have the option of configuring priority for active or reactive power. 3.7 Limitation of the Setpoint Modification Gradient In order to prevent large gradients when modifying the setpoints for active power and reactive power, the gradient for the modifications can be limited by two parameters each: one parameter for increasing the setpoints and one parameter for decreasing the setpoints. This parameter is independent of the procedure for the smooth transition of the operating modes (see Section 3.2 "Control Procedure", page 6). 3.8 Power Limitation with Strongly Increasing Irradiation Values In order to prevent a rapid rise in the feed-in power when there is a sudden increase in the irradiation, the power modification can be limited using the function "Limitation of the active power gradient". This function simultaneously activates the function for limiting the gradient of setpoint modification. 8 PPC-TI-en-12 Technical Information

9 SMA Solar Technology AG 3 Functional Description of the Power Plant Controller 3.9 Master/Slave Operation of the Power Plant Controllers Using Power Plant Controllers, you can monitor a PV power plant with up to 1,000 central inverters. The master/slave concept of the Power Plant Controllers enables all 1,000 inverters to be controlled uniformly and simultaneously. The Power Plant Controller master transmits the output values for the active and reactive power control to the Power Plant Controller slaves. A Power Plant Controller master can control up to ten Power Plant Controller slaves. There are three modes of slave operation: Slave mode Description 1 The active power setpoints are processed by the controller of the master and transmitted as output values to the slave. The slave does not control but transmits the output values to the inverters. or Cascade control: The active power output values of the master are processed by the slave controller as setpoints and sent to the inverters. For this type of slave operation, the slave must receive the actual values from an additional network analyzer. This network analyzer must record the values of the part of the PV power plant that is to be controlled. For cascade control, therefore, an additional network analyzer is required for each slave. The reactive power setpoints are processed by the slave's own controller. 2 The reactive power setpoints are processed by the controller of the master and transmitted as output values to the slave. The slave does not control but transmits the output values to the inverters. The active power setpoints are processed by the slave's own controller. 3 The active and reactive power setpoints are processed by the controller of the master and transmitted as output values to the slave. The slave does not control but transmits the output values to the inverters Temperature and Irradiation Sensors From release 2.0, you can connect the following sensors to the Power Plant Controller and monitor the measured values of the sensors: Two irradiation sensors Sensor for the ambient temperature Sensor for the temperature of the PV modules It is possible to receive the measured values via the analog inputs or the Modbus server Disconnection of the Inverters Fast disconnection of the inverters can be triggered e.g. by the grid operator using a Modbus command. In addition, the active and reactive power setpoint can be set to zero via a digital input. Technical Information PPC-TI-en-12 9

10 4 Interface Description SMA Solar Technology AG 4 Interface Description 4.1 Network Inputs The Power Plant Controller uses the Modbus protocol for data transmission. The following data can be transmitted by Modbus protocol: Specifications of the grid operator to the Power Plant Controller Transfer of the output values from the Power Plant Controller to central inverters and SMA Cluster Controllers Transfer of internal device data from central inverters and SMA Cluster Controllers to the Power Plant Controller Figure 5: Principle of the communication network of the PV system with Power Plant Controller (example) The Power Plant Controller supports the transfer protocols TCP and UDP. The Power Plant Controller makes two LAN ports available for data transmission by Modbus protocol. The following are examples for the possible assignment of the network inputs: Input LAN1 LAN3 Incoming signals Signals from the transducer, from the central inverters, and the SMA Cluster Controllers Specifications of the grid operator For some supported network analyzers it is necessary to put the network analyzer in the network where no inverters are connected. This can be attributed to the communication behavior of the devices. 10 PPC-TI-en-12 Technical Information

11 SMA Solar Technology AG 4 Interface Description 4.2 Digital and Analog Inputs Depending on the order, the Power Plant Controller is equipped with two options for transmitting the analog and digital signals. It is also possible to connect the I/O components to the Power Plant Controller via the network. This can be coordinated with SMA Solar Technology depending on the project. Standard Inputs and Outputs Digital or analog measured data can be transmitted from the network analyzer to the Power Plant Controller via the corresponding inputs. If a feedback signal is requested, it can be transmitted via the associated digital or analog outputs. Input Description 4 analog inputs for current or 4 analog inputs for voltage ±0 ma to 20 ma, 12 bit resolution or 10 V to +10 V, 12 bit resolution 3 analog outputs ±0 ma to 20 ma, 12 bit resolution 6 digital inputs 15 V DC to 30 V DC, typical current consumption: 5 ma 4 digital outputs Power rating: 48 V DC, 30 W Optional Inputs and Outputs If the inputs and outputs available by default are not sufficient for the requirements of the project, additional inputs and outputs are available via a bus coupler. As an option, the following inputs and outputs can be used: Input Description 8 analog inputs for current or 4 analog inputs for voltage ±0 ma to 20 ma, 12 bit resolution or 10 V to +10 V, 12 bit resolution 4 analog outputs Power rating: 250 V AC or 30 V DC, 5 A 12 digital inputs 15 V DC to 30 V DC, typical current consumption: 5 ma 12 digital outputs Power rating: 48 V DC, 30 W 4.3 Interfaces User Interface The Power Plant Controller can be configured, parameterized and operated with a PC via the network and user interface. For this, the Chrome or Firefox web browser must be installed on the PC. Touch Display The Power Plant Controller can be equipped with an optional touch display. With the touch display, the Power Plant Controller can be configured, parameterized and operated directly on the device. The operating states of the Power Plant Controller can be visualized. Technical Information PPC-TI-en-12 11

12 5 Option Code SMA Solar Technology AG 5 Option Code Code option Option Option Explanation code 1 - Enclosure 1 Enclosure Enclosure option 2 - Display 0 without display No integrated display 1 With display Switch cabinet equipped with 10.4" TFT touch display (only suitable for indoors) 3 - Voltage supply 0 AC power supply unit, redundant (100 V AC to 240 V AC ) 1 DC power supply unit, redundant (30 V DC to 60 V DC ) For operation on AC supply (100 V AC to 240 V AC ) For operation on DC supply (30 V DC to 60 V DC ) 4 - PLC 0 1 control CPU 1 control CPU 5 - Digital outputs 0 4 DO 4 digital outputs on the control CPU, power rating: 48 V DC /30 W 1 8 DO 4 digital outputs on the control CPU, power rating: 48 V DC /30 W + 4 digital outputs, power rating: 250 V AC / or 30 V DC, 5 A 2 12 DO 4 digital outputs on the control CPU, power rating: 48 V DC /30 W + 8 digital outputs, power rating: 250 V AC / or 30 V DC, 5 A 3 16 DO 4 digital outputs on the control CPU, power rating: 48 V DC /30 W + 12 digital outputs, power rating: 250 V AC / or 30 V DC, 5 A 6 - Digital inputs 0 6 DI 6 digital inputs, signal voltage "1": 15 V DC to 30 V DC, typ. 5 ma current consumption 1 10 DI 10 digital inputs, signal voltage "1": 15 V DC to 30 V DC, typ. 5 ma current consumption 2 14 DI 14 digital inputs, signal voltage "1": 15 V DC to 30 V DC, typ. 5 ma current consumption 3 18 DI 18 digital inputs, signal voltage "1": 15 V DC to 30 V DC, typ. 5 ma current consumption 7 - Analog outputs (4 ma to 20 ma) 0 3 AO 3 analog outputs, 4 ma to 20 ma, 12 bit resolution 1 5 AO 5 analog outputs, 4 ma to 20 ma, 12 bit resolution 2 7 AO 7 analog outputs, 4 ma to 20 ma, 12 bit resolution 12 PPC-TI-en-12 Technical Information

13 SMA Solar Technology AG 5 Option Code Code option Option code 8 - Analog inputs 0 4 AI current/voltage 4 analog inputs, 0 V to 10 V or 4 ma to 20 ma, 12 bit resolution 1 4 AI current/voltage + 4 AI current 2 4 AI current/voltage + 4 AI voltage 3 4 AI current/voltage + 8 AI current 4 analog inputs, 0 V to 10 V or 4 ma to 20 ma, 12 bit resolution + 4 analog inputs, 4 ma to 20 ma, 12 bit resolution 4 analog inputs, 0 V to 10 V or 4 ma to 20 ma, 12 bit resolution + 4 analog inputs, 10 V to 10 V, 12 bit resolution 4 analog inputs, 0 V to 10 V or 4 ma to 20 ma, 12 bit resolution + 8 analog inputs, 4 ma to 20 ma, 12 bit resolution 9 - Communication 0 None No serial interfaces interface 10 - Network slot 1 0 None No additional network switch, but with unmanaged 2-port Fast Ethernet network switch (RJ45, 100 Mbit/s) on the control CPU 1 Network switch 8 TX Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports (100 Mbit/s) 2 Network switch 2 FX-M (SC) 8 TX 3 Network switch 2 FX-S (SC) 8 TX B C Option Network switch 2 FX-M (SC) 8 TX MNG Network switch 2 FX-S (SC) 8 TX MNG Explanation Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports and 2 optical fiber ports for multi-mode optical fiber (100 Mbit/s) Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports and 2 optical fiber ports for single-mode optical fiber (100 Mbit/s) Managed Fast Ethernet network switch for industrial networks with 6 RJ45 copper ports and 2 optical fiber ports for multi-mode optical fiber (100 Mbit/s) Managed Fast Ethernet network switch for industrial networks with 6 RJ45 copper ports and 2 optical fiber ports for single-mode optical fiber (100 Mbit/s) Technical Information PPC-TI-en-12 13

14 5 Option Code SMA Solar Technology AG Code option 11 - Network slot 2 0 None No additional network switch, but with unmanaged 2-port Fast Ethernet network switch (RJ45, 100 Mbit/s) on the control CPU 1 Network switch 8 TX Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports (100 Mbit/s) 2 Network switch 2 FX-M (SC) 8 TX 3 Network switch 2 FX-S (SC) 8 TX B C Network switch 2 FX-M (SC) 8 TX MNG Network switch 2 FX-S (SC) 8 TX MNG 12 - Patch panel 0 None No patch panel 13 - Ethernet overvoltage protection Option code Option 1 Patch panel 6 optical fibers (SC/SC) Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports and 2 optical fiber ports for multi-mode optical fiber (100 Mbit/s) Unmanaged Fast Ethernet network switch for industrial networks with 8 copper ports and 2 optical fiber ports for single-mode optical fiber (100 Mbit/s) Managed Fast Ethernet network switch for industrial networks with 6 RJ45 copper ports and 2 optical fiber ports for multi-mode optical fiber (100 Mbit/s) Managed Fast Ethernet network switch for industrial networks with 6 RJ45 copper ports and 2 optical fiber ports for single-mode optical fiber (100 Mbit/s) Modular, flexible patch panel, terminals for 6 x SC adapter duplex 2 Patch panel 4 ETH Modular, flexible patch panel, terminals for 4 x RJ45 keystone pin connectors, shielded 3 Patch panel 8 ETH Modular, flexible patch panel, terminals for 8 x RJ45 keystone pin connectors, shielded 4 Patch panel 6 optical fibers (SC/SC)/ 4 ETH Explanation Modular, flexible patch panel, terminals for 6 x SC adapter duplex, 4 x RJ45 keystone pin connectors, shielded 0 None No surge arrester for Ethernet x universal arrester for industrial Ethernet in accordance with class E up to 250 MHz x universal arrester for industrial Ethernet in accordance with class E up to 250 MHz x universal arrester for industrial Ethernet in accordance with class E up to 250 MHz 14 PPC-TI-en-12 Technical Information

Technical Information SUNNY CENTRAL COMMUNICATION CONTROLLER

Technical Information SUNNY CENTRAL COMMUNICATION CONTROLLER Technical Information SUNNY CENTRAL COMMUNICATION CONTROLLER Content The Sunny Central Communication Controller is an integral part of the central inverter which is responsible for establishing the connection

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

WEB log. Device connection plans

WEB log. Device connection plans WEB log LIGHT+ 20 BASIC 100 PRO unlimited Device connection plans Version 20151210* Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited,

More information

Operating Manual POWER PLANT CONTROLLER

Operating Manual POWER PLANT CONTROLLER Operating Manual POWER PLANT CONTROLLER PPC-BE-P7-en-13 98-113900.02 Version 1.3 ENGLISH Legal Provisions SMA Solar Technology AG Legal Provisions The information contained in this document is the property

More information

TX2123 RS485 TO ETHERNET ADAPTOR

TX2123 RS485 TO ETHERNET ADAPTOR TX2123 RS485 TO ETHERNET ADAPTOR Converts Datacomms between fibre optic Modbus TCP over Ethernet and hard-wired copper Modbus RTU over RS485 Fibre Optic MODBUS TCP/ IP Ethernet Copper MODBUS RTU RS485

More information

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management Energy Depot GmbH Delivering Solutions for Energy Management PRODUCT AND APPLICATION GUIDE Total Monitoring Solution for PV SOLAR LOGGER & ANALYSIS DC STRING MONITORING Residential Comprehensive Solar

More information

SCADA and Monitoring for Solar Energy Plant

SCADA and Monitoring for Solar Energy Plant SCADA and Monitoring for Solar Energy Plant Segment: Industry Country: Thailand Author: Ranon Satitpanyapan Products: NI LabVIEW with LabVIEW Real-Time Module crio Real-Time controller 8 slot with 16 current

More information

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards. 56 / Accessories for inverters Accessories for inverters / Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards. FRONIUS STRING

More information

NetScanner System. Toronto: 416 754 7008, Montreal: 514 695 5147, Toll Free:1888 754 7008, Email: sales@a-tech.ca; www.a-tech.ca

NetScanner System. Toronto: 416 754 7008, Montreal: 514 695 5147, Toll Free:1888 754 7008, Email: sales@a-tech.ca; www.a-tech.ca Networking Solutions NetScanner System 9IFC/90DB/90DC FEATURES Ethernet Interface for NetScanner System Modules Provides Power and Hardware Trigger Interface 10/100 Base-T Auto-Negotiating Universal AC

More information

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved.

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved. SIMATIC S7-1200 It s the Interplay that makes the difference SIMATIC S7-1200 Controller SIMATIC S7-1200 CPUs CPU 1211C 3 configurations per CPU Dimensions W x H x D (mm) CPU 1212C CPU 1214C DC/DC/DC, AC/DC/RLY,

More information

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

WEB log. Device connection plans

WEB log. Device connection plans WEB log LIGHT+ 20 BASIC 100 PRO unlimited Device connection plans Version 20160425* Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited,

More information

High Power Programmable DC Power Supplies PVS Series

High Power Programmable DC Power Supplies PVS Series Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient

More information

PV And Storage: Solutions with Potential

PV And Storage: Solutions with Potential EN PV And Storage: Solutions with Potential Energy on demand with the Sunny Central Storage Large-scale storages... support the growth of renewable energies complete diesel and solar diesel hybrid systems

More information

NEW. EVEN MORE data acquisition and test stand automation

NEW. EVEN MORE data acquisition and test stand automation NEW EVEN MORE data acquisition and test stand automation the new class of data The plug&play complete package User benefits Expert Series is the latest generation of data acquisition Complete hardware

More information

Fronius CL. PV central inverter with Fronius MIX concept

Fronius CL. PV central inverter with Fronius MIX concept Fronius CL PV central inverter with Fronius MIX concept Modular system. Maximum yield. The Fronius CL combines high-yield power electronics with the unique, modular system design of up to 15 identical

More information

Vibration analysis and monitoring Compact. Powerful. Modern technology.

Vibration analysis and monitoring Compact. Powerful. Modern technology. Vibration analysis and monitoring Compact. Powerful. Modern technology. Maximum performance Vibration measurement with state of the art processor technology Expert Vibro is Delphin Technology's new device

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Series: IDAM Servo Drive E Digital Motor Drive - DMD-078.12

Series: IDAM Servo Drive E Digital Motor Drive - DMD-078.12 Series: IDAM Servo Drive E Digital Motor Drive - DMD-078.12 inside Integrated amplifiers for 8 single-phase motors, 4 two-phases motors or 4 three-phases motors or combinations of them in one device Position

More information

Installation Manual SMA CLUSTER CONTROLLER

Installation Manual SMA CLUSTER CONTROLLER Installation Manual SMA CLUSTER CONTROLLER ClusterController-IA-en-15 Version 1.5 ENGLISH Legal Provisions SMA Solar Technology AG Legal Provisions The information contained in these documents is property

More information

HARTING mcon 1000 Introduction and features

HARTING mcon 1000 Introduction and features Introduction and features HARTING mcon 1000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features Supporting Ethernet (10 Mbit/s), Fast Ethernet (100 Mbit/s)

More information

Security & Surveillance Cabling Systems

Security & Surveillance Cabling Systems Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.

More information

HARTING econ 3000 Introduction and features

HARTING econ 3000 Introduction and features HARTING Introduction and features HARTING es, unmanaged, for installation in control cabinets General Description Features The Fast es of the product family HARTING are suitable for industrial applications

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

ABB RTU560A Series CMU & Modules

ABB RTU560A Series CMU & Modules ABB RTU560A Series CMU & Modules 1KGT 150 648 V1.02 March 4, 2012 Slide 1 Contents RTU560A rack solutions March 4, 2012 Slide 2 560CSR01 Available for wall mounting and swing frame Supports redundant power

More information

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter ICS-2 S15 Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter Cost Effective Solution for RS-232 / RS-422 / RS-485 to Industrial Ethernet Application PLANET ICS-210x series Smart Media Converter

More information

/ The personal storage solution for 24H Sun. / Dynamic Peak Manager. / Smart Grid Ready THREE-PHASE

/ The personal storage solution for 24H Sun. / Dynamic Peak Manager. / Smart Grid Ready THREE-PHASE Perfect Welding Solar Energy Perfect Charging FRONIUS ENERGY PACKAGE The personal storage solution for 24H Sun. PC board replacement process SnapINverter technology Integrated data communication Dynamic

More information

User manual Compact Web PLC WP240 series IEC-line

User manual Compact Web PLC WP240 series IEC-line User manual Compact Web PLC WP240 series IEC-line update: 09-01-2014 IEC-line by OVERDIGIT overdigit.com 1. General description The WP240 device is a PLC, programmable in IEC61131-3 language using CoDeSys

More information

Modbus Server SAMSUNG Air Conditioners

Modbus Server SAMSUNG Air Conditioners IntesisBox Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung Air Conditioning Systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel ) Master TCP Master

More information

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................

More information

sat-nms SMU Signal Management Unit

sat-nms SMU Signal Management Unit sat-nms SMU Signal Management Unit Application Note 2014, SatService GmbH www.satnms.com SMU-APP-1408-1 1/37 1 System Description and Configuration of sat-nms SMU The sat-nms SMU is the unit you were always

More information

ABB central inverters PVS800 100 to 1000 kw

ABB central inverters PVS800 100 to 1000 kw Solar inverters ABB central inverters PVS800 100 to 1000 kw ABB central inverters raise reliability, efficiency and ease of installation to new levels. The inverters are aimed at system integrators and

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Applications. diris_826_a_1_gb_cat

Applications. diris_826_a_1_gb_cat Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered

More information

Swiss Time Systems. The new multipurpose time server for the LAN and NTP-based Distributed Time System. by MOBATIME DTS 4138.

Swiss Time Systems. The new multipurpose time server for the LAN and NTP-based Distributed Time System. by MOBATIME DTS 4138. Proud Partners with MOBATime GPS or DCF 77 MOBA-NMS (Network Management Sy The new multipurpose time server for the LAN and NTP-based Distributed Time System by MOBATIME DTS 4138.timeserver The DTS 4138.timeserver

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

SNMP Web Management. User s Manual For SNMP Web Card/Box

SNMP Web Management. User s Manual For SNMP Web Card/Box SNMP Web Management User s Manual For SNMP Web Card/Box Management Software for Off-Grid Inverter Version: 1.2 Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2 Features... 1 1.3 Overlook...

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

COFDM Transmission systems

COFDM Transmission systems COFDM Transmission systems www.vtq.de COFDM Radio Communication Appliance O.R.C.A - Trade Show Highlights Probably the fastest¹ COFDM video transmitter world s The brand new generation of O.R.C.A transmitters

More information

CANtrol EC Modular Control System Powerful and versatile

CANtrol EC Modular Control System Powerful and versatile Controls CANtrol EC Modular Control System Powerful and versatile CANtrol EC The modular control system Components of CANtrol EC 1 EC1000 Ethernet Controller 2 E-I/O EtherCAT I/O family communicating controlling

More information

SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes:

SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes: SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL 1.01 Summary A. Section Includes: 1. The ISS shall furnish all labor, materials, equipment, services and incidentals

More information

Light scene push button 8gang comfort flush-mounted 751688xx

Light scene push button 8gang comfort flush-mounted 751688xx 751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

NETWORK ENABLED EQUIPMENT MONITOR

NETWORK ENABLED EQUIPMENT MONITOR NETWORK ENABLED EQUIPMENT MONITOR Remotely Monitor Sensors over the Internet Connect Sensors to the Web to Remotely Monitor Equipment, Processes or Other Applications A Complete, Easy to Deploy, Stand-Alone

More information

Foxboro Evo Process Automation System

Foxboro Evo Process Automation System Foxboro Evo Process Automation System Product Specifications PSS 31H-2Z32 FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single The FBM232 Field Device System Integrator (FDSI) module

More information

KACO-monitoring. onlinecomponents.com. Integrated monitoring available. Monitor up to 32 inverters per prolog. Reliable and accurate data

KACO-monitoring. onlinecomponents.com. Integrated monitoring available. Monitor up to 32 inverters per prolog. Reliable and accurate data KACO-monitoring watchdog insight prolog Integrated monitoring available Monitor up to 32 inverters per prolog Reliable and accurate data Email alarms to maximize uptime Historical, current and production

More information

FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID

FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID As the number of decentralized energy generators grows, also the need for an intelligent power grid rises. In the Smart Grid of the

More information

PROFINET the Industrial Ethernet standard. Siemens AG 2013. Alle Rechte vorbehalten.

PROFINET the Industrial Ethernet standard. Siemens AG 2013. Alle Rechte vorbehalten. the Industrial Ethernet standard is 100% Ethernet is Ethernet Ethernet is the established standard in the IT world for fast exchange of data (IEEE 802.3) is always full duplex simultaneous communication

More information

Installation Guide Solar Connect-11

Installation Guide Solar Connect-11 Installation Guide Solar Connect-11 Version 1.1 Contents Important Product Information 3 System Registration Form 4 Solar Connect-11 Overview 5 Internet & Power Connections 6 Single Phase CT Connections

More information

EFC 3600. Frequency converters

EFC 3600. Frequency converters 2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation

More information

DCM. Product Brochure. Diagnostic Communication Master

DCM. Product Brochure. Diagnostic Communication Master DCM Product Brochure Diagnostic Communication Master DCM The DCM Diagnostic Communication Master is the best solution for the control of actuators from a remote control room through a two-wire transmission-mode

More information

Contents Chapter 1: Introduction... 3 Chapter 2: Ethernet (LAN)... 5 Chapter 3: ZigBee Wireless Connection Options... 7

Contents Chapter 1: Introduction... 3 Chapter 2: Ethernet (LAN)... 5 Chapter 3: ZigBee Wireless Connection Options... 7 Contents Chapter 1: Introduction... 3 Communication Types and Functionality... 3 Communication Connectors... 3 Communication Lightning Protection... 4 Chapter 2: Ethernet (LAN)... 5 Single/Multiple Devices,

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves

More information

emobility WAGO Leading the Charge

emobility WAGO Leading the Charge emobility WAGO Leading the Charge Six Steps to a Full Battery WAGO supports every aspect of charging from: TO-PASS GPRS Modem, VPN Router, 761-520 Identification / Registration /Authorization RFID SMS

More information

Fieldbus slave modules with I/Os, DIO

Fieldbus slave modules with I/Os, DIO 140 Fieldbus slave modules with I/Os, DIO 1534CF00 1534CH00 1534PF00 1534PH00 1536CH00 1536CL10 1536PH00 1536PL00 Order number 1534CF00 1534CH00 1534PF00 1534PH00 Figure Type SM 153, CANopen slave, DIO

More information

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

SolarMax P series The power package for residential solar plants

SolarMax P series The power package for residential solar plants SolarMax P series The power package for residential solar plants The future-proof solution The requirements for residential photovoltaic plants have increased continuously in the past years. Due to our

More information

SRS2025. Home & small Business. Energy Storage Solution

SRS2025. Home & small Business. Energy Storage Solution SRS2025 Home & small Business Energy Storage Solution Leclanché Lithium-ion complete system The ideal energy storage system for Home & Small Business Lithium-ion battery storage systems Home & Small Business

More information

FlexDSL MiniFlex. SHDSL.bis Up to 30Mbps Ddd. Ethernet. Features. Possible Applications

FlexDSL MiniFlex. SHDSL.bis Up to 30Mbps Ddd. Ethernet. Features. Possible Applications SHDSL.bis Up to 30Mbps Ddd Ethernet FlexDSL MiniFlex Features Up to 15Mbps Data Transmission per Copper Pair SHDSL and SHDSL.bis, TC-PAM16/32 Additional TC-PAM4/8/64/128 Available 1 or 2 Copper Pairs Support

More information

Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light

Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light In this issue, we would like to present the EnOcean radio sensor module STM 110 in more detail. The module

More information

Single channel data transceiver module WIZ2-434

Single channel data transceiver module WIZ2-434 Single channel data transceiver module WIZ2-434 Available models: WIZ2-434-RS: data input by RS232 (±12V) logic, 9-15V supply WIZ2-434-RSB: same as above, but in a plastic shell. The WIZ2-434-x modules

More information

Unidirectional Transmitter/ Receiver Units Introduction

Unidirectional Transmitter/ Receiver Units Introduction Unidirectional Transmitter/ Receiver Units Introduction Wireless Input/Output (I/O) connects directly to analog, discrete and pulse transducer signals. The signals are transmitted by radio and either re-created

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

TK800-Series Industrial GPRS / UMTS / LTE Router

TK800-Series Industrial GPRS / UMTS / LTE Router The new generation LTE with 100 Mbps LTE standard for high transmission rates and good network coverage in sparsely populated areas Dynamic Multipoint VPN GRE, L2TP, IPSec, DMVPN, OpenVPN Simple and fast

More information

PE310G4BPi40-T Quad port Copper 10 Gigabit Ethernet PCI Express Bypass Server Intel based

PE310G4BPi40-T Quad port Copper 10 Gigabit Ethernet PCI Express Bypass Server Intel based PE310G4BPi40-T Quad port Copper 10 Gigabit Ethernet PCI Express Bypass Server Intel based Description Silicom s quad port Copper 10 Gigabit Ethernet Bypass server adapter is a PCI-Express X8 network interface

More information

Kokii BatteryDAQ. BMS Software Manual. Battery Analyzer Battery DAS

Kokii BatteryDAQ. BMS Software Manual. Battery Analyzer Battery DAS Kokii BatteryDAQ BMS Battery Analyzer Battery DAS Updated: October 2008 Caution: High Voltage Exists on Battery Power and Sampling Connectors! Please refer to device installation and operation manual for

More information

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and

More information

SolarEdge Export Limitation Guide

SolarEdge Export Limitation Guide SolarEdge Export Limitation Guide Europe and APAC Version 2.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in

More information

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with

More information

Ha-VIS FTS 3000 Introduction and features

Ha-VIS FTS 3000 Introduction and features Ha-VIS Introduction and features Ethernet Switch Ha-VIS FTS 3100s-A 10-port Ethernet Switch with Fast Track Technology configurable via USB General Description Features The Fast Ethernet Switches of the

More information

Product Data. Thermal Comfort Data Logger Type 1221. Including Application Software Type 7301

Product Data. Thermal Comfort Data Logger Type 1221. Including Application Software Type 7301 Product Data Thermal Comfort Data Logger Type 1221 Including Application Software Type 7301 USES: For measuring all physical parameters necessary to evaluate heat stress and thermal comfort For evaluating

More information

SUNNY TRIPOWER 5000TL 12000TL

SUNNY TRIPOWER 5000TL 12000TL SUNNY TRIPOWER 5000TL 12000TL STP 5000TL-20 / STP 6000TL-20 / STP 7000TL-20 / STP 8000TL-20 / STP 9000TL-20 / STP 10000TL-20 / STP 12000TL-20 NEW available as 10 kva and 12 kva versions Economical Flexible

More information

IntesisBox KNX Modbus TCP master

IntesisBox KNX Modbus TCP master IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration

More information

Programmable set for Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-8

Programmable set for Ethernet Modbus/TCP in IP20 TI-BL20-PG-EN-8 CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps LEDs for display of supply voltage, group and bus errors as well as status and diagnostics Connection

More information

Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 6-gang (3+3)

Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 6-gang (3+3) KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang

More information

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters Content During grid failures as for example voltage dips, all PV inverters may generate currents that

More information

ugrid Testbed. Rein in microgrid complexity. With ease.

ugrid Testbed. Rein in microgrid complexity. With ease. ugrid Testbed. Rein in microgrid complexity. With ease. Outsmart the microgrid. ugrid Testbed Ultimate test solution for microgrid control system verification What is a microgrid? Microgrid is a collection

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs and 8 digital PNP outputs 2 A TBEN-L1-8DIP-8DOP

Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs and 8 digital PNP outputs 2 A TBEN-L1-8DIP-8DOP EtherNet/IP, Modbus TCP, or PROFINET slave Integrated Ethernet switch Supports 10 Mbps/100 Mbps 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection 7/8" males, 5-pin, for power supply Separated power

More information

KNX Panasonic Air Conditioners

KNX Panasonic Air Conditioners IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line

More information

OPTICAL FIBER repeaters/ isolators

OPTICAL FIBER repeaters/ isolators OPTICAL FIBER repeaters/ isolators FUNCTINALITY AND RELIABILITY' Optical Fiber converters give the possibilità to extend on Optical Fiber (also at the same time) every type of network/bus (LAN/Ethernet,

More information

/ The allrounder with maximum yield. / WLAN interface / Smart Grid Ready

/ The allrounder with maximum yield. / WLAN interface / Smart Grid Ready / Battery Charging Systems / Welding Technology / Solar Electronics FRONIUS IG PLUS / The allrounder with maximum yield. / Fronius MIX technology / HF transformer switchover / PC board replacement process

More information

Counter for Energy. We make energy measurable and secure your future. www.g-mw.de

Counter for Energy. We make energy measurable and secure your future. www.g-mw.de Counter for Energy We make energy measurable and secure your future www.g-mw.de 10 reasons for GMW Customer oriented solutions Individual consultancy Satisfied customers in all continents Large range of

More information

Introduction Media converters

Introduction Media converters Optical media converter Introduction s The use of fiber optics is advisable when reliability demands are high or there are long distances to cover. One simple and inexpensive solution is the Weidmuller

More information

Yield Reduction due to Shading:

Yield Reduction due to Shading: 1x4 1x16 10 x CBC Energy A/S x Danfoss Solar Inverters CBC-40W Poly 40 W TLX 1,5k 5 ; 1x11 3x4 0 1,5kW 1536 x CBC Energy A/S 1 x Power-One CBC-40W Poly 40 W TRIO-7,6-TL-OUTD 30 ; 4x14 0 7,6kW Location:

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

Table of Contents. Creating a VC1000 Network... 3

Table of Contents. Creating a VC1000 Network... 3 2 Table of Contents Creating a VC1000 Network... 3 Topology... 3 Unit ddressing... 4 Terminating Resistors... 5 Shielding... 5 Interconnecting the common... 6 ias Resistors... 6 VC1000 Hardware Configuration...

More information

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx 756627xx, 756637xx, 756657xx Documentation Product name: Push button 2-, 3-, 5- gang RTR + display Design: UP (flush-mounting type) ETS search path: Push button / Push button xgang / Push button xgang

More information

NXL Series Inverters. HVAC Inverters made simple

NXL Series Inverters. HVAC Inverters made simple NXL Series Inverters HVAC Inverters made simple Honeywell s Voice Of the Customer process unveils a range of requirements expressed by specifiers and installers, that are ideally covered by the NXL inverter

More information

IntesisBox Modbus Server - Mitsubishi Electric G50

IntesisBox Modbus Server - Mitsubishi Electric G50 IntesisBox Server - Mitsubishi Electric G50 Gateway for monitor and control Mitsubishi Electric City Multi Air Conditioning systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel )

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

DCS Data and communication server

DCS Data and communication server 8 58 PLD.TOWER PLD.RACK VISONIK DCS Data and communication server PLD.TOWER PLD.RACK Data and communication servers (DCS) are used as management stations in building automation and control (BAC). With

More information

EtherDevice Switch EDS-726 Series

EtherDevice Switch EDS-726 Series Managed Redundant EtherDevice TM Switch Solutions EtherDevice Switch EDS-726 Series 26-Port Gigabit Ethernet Switch Modular, Managed, Redundant Features Industrial Networking Capability Redundant Gigabit

More information

Designed for the needs of automation, telecommunications, remote supervision, and monitoring

Designed for the needs of automation, telecommunications, remote supervision, and monitoring - Programmable automation controller (PAC) MADE IN EU is a series of industrial computers which you can easily adapt to your needs by choosing from the available options. Energy-efficient ARM11 700 MHz

More information