Relion product family. Grid Automation Recloser Protection and Control RER615 Product Guide

Size: px
Start display at page:

Download "Relion product family. Grid Automation Recloser Protection and Control RER615 Product Guide"

Transcription

1 Relion product family Grid Automation Product Guide

2 Contents 1. Description Standard configurations Protection functions Application Supported ABB solutions Control Measurement Fault location Disturbance recorder Event log Fault recorder Condition monitoring Trip-circuit supervision Self-supervision Fuse failure supervision Autoreclosing Hot line tag Access control Inputs and outputs Station communication Technical data Local HMI Mounting methods Relay case and plug-in unit Selection and ordering data Accessories and ordering data Tools Connection diagrams References Functions, codes and symbols Document revision history...54 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Copyright 2015 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. 2 ABB

3 Issued: Revision: C 1. Description RER615 is a recloser controller designed for remote control and monitoring, protection, fault indication, power quality analysis and automation in medium-voltage secondary distribution systems, including radial, looped and meshed distribution networks, with or without distributed power generation. RER615 is a member of the Relion product family. The relay has inherited features from the 615 series relays that are characterized by their compactness as well as environmentally friendly (RoHS compliance) and withdrawableunit design. Re-engineered from the ground up, the relays have been designed to unleash the full potential of the IEC standard for communication and interoperability between substation automation devices. With RER615, grid reliability can be enhanced, ranging from basic, non-directional overload protection to extended protection functionality with power quality analyses. RER615 meets today s requirements for smart grids and supports the protection of overhead lines in isolated neutral, resistanceearthed, compensated and solidly earthed networks. RER615 is freely programmable with horizontal GOOSE communication, thus enabling sophisticated interlocking functions. RER615 includes sophisticated protection functionality to detect, isolate and restore power in all types of networks but especially in compensated networks (including recloser tripping curves). As part of an ABB smart grid solution, the relay provides superior fault location, isolation and restoration (FLIR) to lower the frequency and shorten the duration of faults. The adaptable standard configurations allow the relay to be taken into use right after the application-specific parameters have been set, thus enabling rapid commissioning. RER615 supports the same configuration tools as the other relays in the Relion product family. The freely programmable relay contains six easily manageable setting groups. Via the relay's front panel HMI or a remote control system, one recloser can be controlled. The relay's large, easy-toread LCD screen with single-line diagram offers local control and parametrization possibilities with dedicated push buttons for safe operation. Easy Web-based parametrization tool is also available with download possibility. To protect the relay from unauthorized access and to maintain the integrity of information, the relay is provided with a four-level, role-based user authentication system, with individual passwords for the viewer, operator, engineer and administrator levels. The access control system applies to the front panel HMI, embedded Web browser-based HMI and Protection and Control IED Manager PCM600. In addition, the relay also includes cyber security features such as audit trail. RER615 supports a variety of communication protocols for remote communication, such as IEC /104, DNP3 level 2 and Modbus, simultaneously also supporting IEC with GOOSE messaging for high-speed protection, fault isolation and restoration. 2. Standard configurations RER615 is available in two standard configurations. An example configuration suitable for recloser applications is delivered with each standard configuration. This minimizes the required amount of engineering, allowing fast commissioning by just parametrizing the protection functions. For applications where the example configuration is not suitable, the standard signal configuration can be easily altered using the application configuration or signal matrix functionality of the Protection and Control IED Manager PCM600. The application configuration functionality of PCM600 also supports the creation of multilayer logic functions using various logical elements. By combining protection functions with logic function blocks, the relay configuration can be adapted to user-specific application requirements. Standard configuration A supports traditional current and voltage transformers. The residual current for the earth-fault protection is derived from the phase currents in a Holmgren connection. Alternatively, the core balance current transformers can be used for measuring the residual current, especially when sensitive earth-fault protection is required. Standard configuration D supports a combination of traditional current and voltage transformers or alternatively voltage sensors. The residual current for the earth-fault protection is derived from the phase currents in a Holmgren connection. Alternatively, the core balance current transformers can be used for measuring the residual current, especially when sensitive earth-fault protection is required. The sensor inputs are highly flexible and are type-tested to support both ABB's capacitive and resistive voltage sensors. ABB 3

4 Close Open U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC IA=0A IB=0A IC=0A IG=0. 0A VAB=0.00kV VBC=0. 00kV VCA=0. 00kV 3P=0kW 3Q=0kVAr ESC REF615 A Clear Clear Menu Help Configuration System HMI Time Authorization ESC A Clear Grid Automation Source RER615 Version 1.1 RECLOSER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION A PROTECTION LOCAL HMI ALSO AVAILABLE 3I 2 2 Master Trip Lockout relay 94/86 I2> 46 I2/I1> 46PD 3I>/Io>BF 51BF/51NBF 3Ith>F 49F 3I> 51P-1 OR 3I>>> 50P/51P 2 3I> 67-1 IEC I O ANSI R L I O R L - Disturbance recorder - Event log - Fault recorder - Relay self-supervision - Load profile - Local/Remote push-button on LHMI - Recorded data - User management - Web HMI AND OR Io 3I>> 51P-2 Io>>> 50N/51N 3I>> 67-2 Io>> Io>> 51N-2 67N-2 OR 3 Yo> 21YN OR OR 3I2f> 68 2 Io> Io> 51N-1 67N-1 OR 3 Po> 32N OR Io> IEF 67NIEF Io>HA 51NHA 3I U L1 U L2 U L3 CONDITION MONITORING AND SUPERVISION FUSEF 60 R L CBCM CBCM PHSVPR PHSVPR 2 TCS TCM CONTROL AND INDICATION 1) COMMUNICATION Protocols: Master: IEC Slave: IEC 101, IEC 104, Modbus, DNP3 Level 2 Interfaces: Ethernet: TX (RJ-45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232/485 D-sub 9, IRIG-B MEASUREMENT U L1 U L2 U L3 3 Uo> 59G 3U< 27 U2> 47O- Uo U1< 47U+ Object Ctrl 2) Ind 3) CB 1 - DC - 2 ES - 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object - I, U, Io, P, Q, E, pf, f - Symmetrical components - Limit value supervision - Power Quality functions Analog interface types 1) Current transformer 4 Voltage transformer 3 1) Conventional transformer inputs PQM3I PQM3I PQM3U PQM3V PQMU PQMV 3 3U> 59 2 f>/f<, df/dt 81 O I 79 PQUUB PQVUB REMARKS 6 MAP MAP FLOC 21FL 2 MV MV Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering Load GUID-7BCC1E2C-B ACDE-8354FE V2 EN Figure 1. Functionality overview of standard configuration A 4 ABB

5 Close Open U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC IA=0A IB=0A IC=0A IG=0. 0A VAB=0.00kV VBC=0. 00kV VCA=0. 00kV 3P=0kW 3Q=0kVAr ESC REF615 A Clear Clear Menu Help Configuration System HMI Time Authorization ESC A Clear Grid Automation Source U L1b U L2b U L3b RER615 Version 1.1 RECLOSER PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION D PROTECTION LOCAL HMI ALSO AVAILABLE 3I 2 2 Master Trip Lockout relay 94/86 I2> 46 I2/I1> 46PD 3I>/Io>BF 51BF/51NBF 3Ith>F 49F 3I> 51P-1 OR 3I>>> 50P/51P 2 3I> 67-1 IEC I O ANSI R L I O R L - Disturbance recorder - Event log - Fault recorder - Relay self-supervision - Load profile - Local/Remote push-button on LHMI - Recorded data - User management - Web HMI AND OR Io 3I>> 51P-2 Io>>> 50N/51N 3I>> 67-2 Io>> Io>> 51N-2 67N-2 OR 3 Yo> 21YN OR OR 3I2f> 68 2 Io> Io> 51N-1 67N-1 OR 3 Po> 32N OR Io> IEF 67NIEF Io>HA 51NHA 3I U L1 U L2 U L3 CONDITION MONITORING AND SUPERVISION FUSEF 60 R L CBCM CBCM PHSVPR PHSVPR 2 TCS TCM CONTROL AND INDICATION 1) COMMUNICATION Protocols: Master: IEC Slave: IEC 101, IEC 104, Modbus, DNP3 Level 2 Interfaces: Ethernet: TX (RJ-45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232/485 D-sub 9, IRIG-B MEASUREMENT Uo Uo> 59G Uo> 59G 2 MV MV 6 MAP MAP Uo FLOC 21FL U L1b U L2b U L3b Object Ctrl 2) Ind 3) CB 1 - DC - 2 ES - 2 1) Check availability of binary inputs/outputs from technical documentation 2) Control and indication function for primary object 3) Status indication function for primary object - I, U, Io, P, Q, E, pf, f - Symmetrical components - Limit value supervision - Power Quality functions Analog interface types 1) Current transformer 4 Voltage sensor 6 1) Conventional transformer inputs and combi sensor inputs PQM3I PQM3I PQM3U PQM3V PQMU PQMV 2) 3U< ) 3U< 27 U2> 47O- SYNC 25 O I 79 PQUUB PQVUB 2) 3U> 59 U1< 47U+ 2 1) 3U> 59 REMARKS Load U L1 U L2 U L3 1) Instances 1 and 2 2) Instance 3 2 f>/f<, df/dt 81 Optional function 3 No. of instances Calculated value Io/Uo OR Alternative function to be defined when ordering GUID-D0D32AE3-D6A0-45C3-82FE-2CDE8432F2B9 V2 EN Figure 2. Functionality overview of standard configuration D Table 1. Standard configurations Description Directional overcurrent and directional earth-fault protection with phase voltage-based protection and measurement functions, voltage protection and frequency protection, CB condition monitoring and CB control Directional overcurrent and directional earth-fault protection with phase voltage-based protection and measurement functions, voltage protection and frequency protection, synchro-check, CB condition monitoring, CB control and voltage sensor inputs Std. conf. A D ABB 5

6 Table 2. Supported functions Function IEC A D Protection 1)2) Three-phase non-directional overcurrent protection, low stage FPHLPTOC (1) 3) (1) 3) Three-phase non-directional overcurrent protection, high stage PHHPTOC (1) 3) (1) 3) Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1 1 Three-phase directional overcurrent protection, low stage FDPHLPDOC (2) 3) (2) 3) Three-phase directional overcurrent protection, high stage DPHHPDOC (1) 3) (1) 3) Non-directional earth-fault protection, low stage FEFLPTOC (1) 4)5) (1) 4)5) Non-directional earth-fault protection, high stage EFHPTOC (1) 4)5) (1) 4)5) Non-directional earth-fault protection, instantaneous stage EFIPTOC 1 5) 1 5) Directional earth-fault protection, low stage FDEFLPDEF (2) 5)6)7) (2) 5)6)7) Directional earth-fault protection, high stage DEFHPDEF (1) 5)6)7) (1) 5)6)7) Transient / intermittent earth-fault protection INTRPTEF (1) 5)6)7) (1) 5)6)7) Admittance based earth-fault protection EFPADM (3) 5)7)8) (3) 5)7)8) Wattmetric based earth-fault protection WPWDE (3) 5)7)8) (3) 5)7)8) Harmonics based earth-fault protection HAEFPTOC (1) 5)8) (1) 5)8) Negative-sequence overcurrent protection NSPTOC 2 2 Phase discontinuity protection PDNSPTOC 1 1 Residual overvoltage protection ROVPTOV (1) 7) (2) 9)10) Three-phase undervoltage protection PHPTUV (3) (3) 11) Three-phase overvoltage protection PHPTOV (3) (3) 11) Positive-sequence undervoltage protection PSPTUV (1) (1) Negative-sequence overvoltage protection NSPTOV (1) (1) Frequency protection FRPFRQ (2) (2) Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR 1 1 Circuit breaker failure protection CCBRBRF 1 1 Three-phase inrush detector INRPHAR 1 1 Master trip TRPPTRC 2 2 Multi-purpose protection MAPGAPC 6 6 Fault locator SCEFRFLO (1) (1) Power quality Current total demand distortion CMHAI (1) (1) Voltage total harmonic distortion VMHAI (1) (1) Voltage variation PHQVVR (1) (1) Voltage unbalance VSQVUB (1) (1) Control Circuit-breaker control CBXCBR ABB

7 Table 2. Supported functions, continued Function IEC A D Disconnector position indication DCSXSWI 2 2 Earthing switch indication ESSXSWI 2 2 Autoreclosing DARREC 1 1 Synchronism and energizing check SECRSYN 1 Condition monitoring and supervision Circuit-breaker condition monitoring SSCBR 1 1 Trip circuit supervision TCSSCBR 2 2 Fuse failure supervision SEQRFUF 1 1 Runtime counter for machines and devices MDSOPT 1 1 Voltage presence PHSVPR 1 1 Measurement Disturbance recorder RDRE 1 1 Three-phase current measurement CMMXU 1 1 Sequence current measurement CSMSQI 1 1 Residual current measurement RESCMMXU 1 1 Three-phase voltage measurement VMMXU 1 1(2) 12) Sequence voltage measurement VSMSQI 1 1(2) 12) Three-phase power and energy measurement PEMMXU 1 1 Frequency measurement FMMXU 1 1 Load profile LDPMSTA 1 1 Other Minimum pulse timer (2 pcs) TPGAPC 2 2 Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1 1 Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 1 1 Pulse timer (8 pcs) PTGAPC 2 2 Time delay off (8 pcs) TOFGAPC 2 2 Time delay on (8 pcs) TONGAPC 2 2 Set reset (8 pcs) SRGAPC 2 2 Move (8 pcs) MVGAPC 2 2 Generic control point (16 pcs) SPCGGIO 2 2 Remote generic control points SPCRGGIO 1 1 Local generic control points SPCLGGIO 1 1 Generic up-down counters UDFCNT 3 3 1, 2,... = number of included instances () = optional 1) All directional protection functions can also be used in the non-directional mode 2) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration 3) Only one can be ordered as an option at a time with OC or directional OC 4) Can be ordered as an option when OC is also chosen 5) Io selectable by parameter, Io measured by default 6) Can be ordered as an option when OC or directional OC is also chosen ABB 7

8 I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L Grid Automation 7) Uo calculated is always used 8) One of the three can be ordered as an option when directional OC and directional EF are chosen: Admittance based EF, Wattmetric based EF or Harmonics based EF 9) Uo calculated is always used with the first instance 10) UoB calculated is always used with the second instance 11) Voltage group B is always used with the third instance 12) Voltage group B is always used with the second instance 3. Protection functions To allow the customers to customize the relay according to their requirements, it can be ordered as a basic relay or enhanced with selected protection functions. The selection depends on the application, whether it is a compensated network, and whether the compensated network is with distributed generation or closed-loop feeders. As a standard offering, the relay includes non-directional overcurrent and non-directional earth-fault functions, as well as other protection functions commonly accepted as a means to significantly improve the grid reliability in recloser applications, such as breaker failure and negative-sequence overcurrent protection to detect a broken conductor. Alternatively, a more sensitive phase-discontinuity protection is available. Thermal protection, which is used for protecting feeders, cables and distribution transformers, is also included. The optional functionalities of the relay include more advanced methods to detect the earth faults in various distribution networks. On top of the permanent earth faults, the relay can be equipped with algorithms that can be used to detect intermittent and transient temporary faults. This can be used to localize possible future problem points in the distribution network, even before they develop to a fault that causes interruption in the power distribution seen by the end users. A syncrocheck function is offered with standard configuration D. The synchrocheck function ensures that the voltage, phase angle and frequency on either side of an open circuit breaker meet the conditions for a safe interconnection of two networks. Some advanced protection functions are optionally available in RER Application The recloser protection and control relay RER615 is suitable for a variety of applications, ranging from basic applications on the line recloser to sophisticated applications including distributed generation and demanding interlocking applications. Because of the large number of protection functions, the illustrated applications are only example applications which can be extended to meet tomorrow's requirements. O 3I RER615 3U O Std. conf. ANSI IEC A 67NIEF 46PD 49F 50P/51P 67/67N 79 Io> >IEF I2/I1> 3Ith>F 3I>>> 3I /Io O I GUID-DFFEAC20-C31D-4D65-9E2A-0B C8 V2 EN Figure 3. Selective protection in radial feeder Figure 3 illustrates selective protection in a radial feeder with autoreclosing functionality and advanced admittance-based earth-fault protection. Additionally, directional overcurrent protection for distributed generation applications is included. 8 ABB

9 I I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A A Clear R L Clear R L Clear R L I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A Clear R L Clear R L I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L A Clear R L I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A Clear R L Clear R L I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A Clear R L Clear R L I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L I I U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A A Clear R L Clear R L Grid Automation IEC and GOOSE IEC and GOOSE RER615 RER615 RER615 RER615 O O O O Fault RER615 RER615 RER615 RER615 RER615 RER615 O O O O O O Pre-fault state Post-fault state GUID-2B2034FA-A359-4FE7-B166-21CD9B V1 EN Figure 4. Fault detection, isolation and restoration in radial feeder Exact earth-fault and overcurrent protection enables autonomous fault detection, isolation and restoration, and can be achieved through IEC and GOOSE communication as illustrated in Figure 4. In the pre-fault state, the closed loop network is of radial type with one normal open point (NOP). The fault is accurately located between two circuit breakers, isolating the faulty part and allowing NOP to be closed. IEC and GOOSE O O 3I DG 3Ub 3U RER615 Std. conf. D O O ANSI IEC 21YN 1) 25 47O-/59 47U+/27 49F 50P/51P 67/67N Yo> 1) SYNC U2>/3U> U1</3U< 3Ith>F 3I>>> 3I /Io O I f</f>,df/dt 1) or 51NHA (Io>HA), 32N (Po> ) GUID-15D B19-49EA-95DF-4698B923C9CE V1 EN Figure 5. Protection of distributed generation plant The advanced protection functionality of RER615 ensures secure protection of distributed generation against faults, and early indication of loss-of-mains through IEC and GOOSE communication as seen in Figure 5. Safe reconnection is enabled by using the synchrocheck functionality. ABB 9

10 5. Supported ABB solutions RER615 integrates fully with other ABB products such as the grid automation controller COM600, MicroSCADA, SYS600, DMS600, and with ABB's secure, reliable and tested communication solutions, RER601 and the M2M gateway. ABB offers a solution which meets the demanding customer requirements regarding smart grids, and which also contributes to faster engineering. To facilitate and streamline the system engineering, ABB's relays are supplied with connectivity packages. The connectivity packages include a compilation of software and relay-specific information, including single-line diagram templates and a full relay data model. The data model also includes event and parameter lists. With the connectivity packages, the relays can be readily configured using PCM600 and integrated with the grid automation controller COM600 or the network control and management system MicroSCADA Pro. Compared to traditional hard-wired, inter-device signaling, peer-to-peer communication over a switched Ethernet LAN offers an advanced and versatile platform for power system protection. Among the distinctive features of the protection system approach, enabled by the full implementation of the IEC substation automation standard, are fast communication capability, continuous supervision of the integrity of the protection and communication system, and an inherent flexibility regarding reconfiguration and upgrades. At substation level, COM600 uses the data content of the baylevel devices to enhance substation level functionality. COM600 features a Web browser-based HMI, which provides a customizable graphical display for visualizing single-line mimic diagrams for switchgear bay solutions. The Web HMI of COM600 also provides an overview of the whole substation, including relay-specific single-line diagrams, which makes information easily accessible. Substation devices and processes can also be remotely accessed through the Web HMI, which improves personnel safety. In addition, COM600 can be used as a local data warehouse for the substation's technical documentation and for the network data collected by the devices. The collected network data facilitates extensive reporting and analyzing of network fault situations, by using the data historian and event handling features of COM600. The history data can be used for accurate monitoring of process and equipment performance, using calculations based on both real-time and history values. A better understanding of the process dynamics is achieved by combining time-based process measurements with production and maintenance events. COM600 can also function as a gateway and provides seamless connectivity between the substation devices and network-level control and management systems, such as MicroSCADA Pro and System 800xA. Table 3. Supported ABB solutions Product Grid automation controller COM600 MicroSCADA Pro SYS 600 System 800xA Version 4.0 SP1 or later 9.4 or later 5.1 or later 6. Control One circuit breaker can be controlled via the front panel HMI of RER615 or via a remote system.the relay also provides position indication for two disconnectors and two earthing switches. If the amount of available binary inputs or outputs of the chosen standard configuration is not sufficient, the configuration can be modified to release some binary inputs or outputs originally configured for other purposes. In this case, an external input/output module, for example, RIO600, can be integrated with the relay and its binary inputs and outputs used for the less time-critical binary signals of the application. example, regarding the make and carry and the breaking capacity. If the requirements for the control circuit of the primary device are not met, the use of external auxiliary relays should be considered. The optional, large, graphical LCD of the relay's HMI includes a single-line diagram with position indication for the relevant primary devices. Interlocking schemes required by the application are configured using the signal matrix or the application configuration function of PCM600. Depending on the standard configuration, the relay also has a synchrocheck function to ensure that the voltage, phase angle and frequency on either side of an open circuit breaker meet the conditions for a safe interconnection of two networks. The suitability of the relay's binary outputs selected for controlling primary devices should be carefully verified, for 10 ABB

11 7. Measurement The relay continuously measures the phase currents and voltages, the symmetrical components of the currents, and the residual current. The relay additionally offers frequency measurement. The relay also calculates the demand value of the current over a user-selectable, pre-set time frame, the thermal overload of the protected object, and the phase unbalance based on the ratio between the negative-sequence and positive-sequence current. Active and reactive power as well as residual voltage are also calculated. Power quality measurement, such as total harmonic values for both current and voltage, voltage sags and swells, and voltage unbalance, is supported. Furthermore, the relay offers three-phase power and energy measurement including power factor. The values measured can be accessed locally via the user interface on the relay's front panel or remotely via the communication interface of the relay. The values can also be accessed locally or remotely using the Web browser-based user interface. 8. Fault location The relay features an optional impedance-measuring fault location function suitable for locating short-circuits in radial distribution systems. Earth faults can be located in effectively and low-resistance earthed networks. Under circumstances where the fault current magnitude is at least of the same order of magnitude or higher than the load current, earth faults can also be located in isolated neutral distribution networks. The fault location function identifies the type of the fault and then calculates the distance to the fault point. An estimate of the fault resistance value is also calculated. The estimate provides information about the possible fault cause and the accuracy of the estimated distance to the fault point. 9. Disturbance recorder The relay is provided with a disturbance recorder with up to 12 analog and 64 binary signal channels. The analog channels can be set to record either the waveform or the trend of the currents and voltages measured. The analog channels can be set to trigger the recording function when the measured value falls below, or exceeds, the set values. The binary signal channels can be set to start a recording either on the rising or the falling edge of the binary signal or on both. By default, the binary channels are set to record external or internal relay signals, for example, the start or trip signals of the relay stages, or external blocking or control signals. Binary relay signals, such as protection start and trip signals, or an external relay control signal via a binary input, can be set to trigger the recording. Recorded information is stored in a non-volatile memory and can be uploaded for subsequent fault analysis. 10. Event log To collect sequence-of-events information, the relay has a non-volatile memory with a capacity of storing 1024 events with associated time stamps. The non-volatile memory retains its data also in case the relay temporarily loses its auxiliary supply. The event log facilitates detailed pre- and post-fault analyses of feeder faults and disturbances. The increased capacity to process and store data and events in the relay offers prerequisites to support the growing information demand of future network configurations. The sequence-of-events information can be accessed either locally via the user interface on the relay's front panel, or remotely via the communication interface of the relay. The information can also be accessed using the Web browserbased user interface, either locally or remotely. 11. Fault recorder The relay has the capacity to store the records of the 128 latest fault events. The records enable the user to analyze the power system events. The available measurement modes include DFT, RMS and peak-to-peak. Fault records store relay measurement values at the moment when any protection function starts. In addition, the maximum demand current with time stamp is separately recorded. By default, the records are stored in the non-volatile memory. Furthermore, the relay includes a load profile recorder capable of storing measurement values into the relay's memory. The selected measurement values averaged over the selected period, ranging from one minute to three hours, are stored in a non-volatile memory. Depending on the selected measurements and averaging period, the overall length of the load profile recording ranges from some days to several months, even a year, making this feature suitable for monitoring long-time load behavior for the interested loads. 12. Condition monitoring The condition monitoring functions of the relay constantly monitors the performance and the condition of the circuit breaker. The monitoring comprises the spring charging time, SF6 gas pressure, the travel time and the inactivity time of the circuit breaker. The monitoring functions provide operational circuit breaker history data, which can be used for scheduling preventive circuit breaker maintenance. 13. Trip-circuit supervision The trip-circuit supervision continuously monitors the availability and operability of the trip circuit. It provides opencircuit monitoring both when the circuit breaker is in its ABB 11

12 closed and in its open position. It also detects loss of circuitbreaker control voltage. 14. Self-supervision The relay s built-in self-supervision system continuously monitors the state of the relay hardware and the operation of the relay software. Any fault or malfunction detected is used for alerting the operator. A permanent relay fault blocks the protection functions to prevent incorrect operation. 15. Fuse failure supervision The fuse failure supervision detects failures between the voltage measurement circuit and the relay. The failures are detected either by the negative sequence-based algorithm or by the delta voltage and delta current algorithm. Upon the detection of a failure, the fuse failure supervision function activates an alarm and blocks voltage-dependent protection functions from unintended operation. 16. Autoreclosing The relay includes a powerful and flexible multi-shot autoreclosing function. The autoreclosing function provides up to five programmable autoreclosing sequences, which can perform one to five successive autoreclosing shots of desired type and duration. 17. Hot line tag Standard configurations of the RER615 are delivered with the hot line tag security functionality that will block the close operation of recloser or breaker when enabled. Hot line tag functionality can be enabled either from the local HMI of the RER615 or from the external signal. 18. Access control To protect the relay from unauthorized access and to maintain information integrity, the relay is provided with a fourlevel, role-based authentication system with administratorprogrammable individual passwords for the viewer, operator, engineer and administrator level. The access control applies to the front-panel user interface, the Web browser-based user interface and PCM Inputs and outputs Depending on the selected standard configuration, the relay is equipped with different analog input channels. Standard configuraton A provides three phase-current inputs, one residual current input and three voltage inputs. Standard configuration D provides three phase-current inputs, one residual current input and six sensor voltage inputs or voltage transformers. The phase-current inputs are rated 1/5 A and the residual current input 0.2/1 A. The residual current is suitable for applications requiring sensitive earth-fault protection and which have core balance current transformers. As the residual current is usually limited to small values, it can also be used in applications where even the phase current is 5A. The three phase voltage inputs and the residual voltage input cover the rated voltages V. Both phase-to-phase voltages and phase-to-earth voltages can be connected. The nominal secondary voltage of voltage sensor inputs is user-programmable, supporting both capacitive and resistive voltage sensors from 5 kv up to 38 kv. The phase current input 1 A or 5 A, the residual current input 0.2 A or 1 A and the rated voltage of the residual voltage input are selected in the relay software. In addition, the binary input thresholds V DC are selected by adjusting the relay's parameter settings. All the binary input and output contacts are freely configurable with the Application Configuration or Signal Matrix tool in PCM600. Table 4. Number of physical connections in standard configurations Configuration Analog channels Binary channels Currents Voltages Inputs Outputs A 4 3 8(14) 1) 10(13) 1) D 4 6 2) ) With optional BIO0006 module 2) Support for voltage sensors or voltage transformer with the SIM0001 module 12 ABB

13 20. Station communication The relay supports a variety of communication protocols, including IEC and the most common remote control protocols IEC , IEC Modbus and DNP3. Operational information and controls are available through these protocols. However, some communication functionality, for example horizontal communication between the relays, is only possible through the IEC communication protocol. The IEC communication implementation supports all the monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC protocol. Disturbance recordings are available for any Ethernet-based application in the standard COMTRADE file format. The relay supports simultaneous event reporting to five different clients over the station bus. The relay can send binary signals to other devices (so-called horizontal communication) using the IEC GOOSE profile. Binary GOOSE messaging can, for example, be used for protection and interlocking-based protection schemes. The relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC standard. Furthermore, the relay supports the sending and receiving of analog values using GOOSE messaging. Analog GOOSE messaging enables fast transfer of the analog measurement values over the station bus. This facilitates, for example, the sharing of RTD input values, such as surrounding temperature, with other relay applications. All communication connectors, except for the front port connector, are placed on integrated optional communication modules. Modbus implementation supports RTU, ASCII and TCP modes. In addition to the standard Modbus functionality, the relay supports retrieval of timestamped events, changing the active setting group and uploading the latest fault records. If a Modbus TCP connection is used, four clients can be connected to the relay at the same time. Modbus serial and Modbus TCP can also be used in parallel and IEC and Modbus simultaneously, if required. In addition to the basic standard functionality, the relay supports changing of the active setting group and uploading of disturbance recordings in the IEC /104 format. DNP3 supports both serial and TCP modes for connection to one master. Changing of the active setting group is also supported. When the relay uses the RS-485 bus for serial communication, both 2-wire and 4-wire connections are supported. Termination and pull-up/down resistors can be configured with jumpers on the communication card, therefore no external resistors are required. The relay supports several time synchronization methods with a time-stamping resolution of 1 ms. SNTP and IEC can be used in Ethernet based time synchronization and IRIG-B is available with special time synchronization wiring. In addition, the relay supports time synchronization via the serial communication protocols Modbus, DNP3 and IEC ABB 13

14 U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L U kv P 0.00 kw Q 0.00 kvar IL2 0 A ESC A Clear R L DC + A F M P M USB LA POWER DC IN CONSOLE/RS1 RS OFF ON CONSOLE/RS1 ø 1 0 LAN 1 Grid Automation Primary Switchgear Control center IEC COM600 IEC Fiber optic NCC I I O O REF615 REF615 Secondary Switchgear Public GPRS VPN Tunnel VPN Tunnel M2M gateway 3I I IEC O RER615 RER601 GUID-CAE7C34B-3E89-42EE-94CE-401B01AC540F V1 EN Figure 6. System overview of utility communication Table 5. Supported station communication interfaces and protocols Interfaces/Protocols Ethernet Serial 100BASE-TX RJ BASE-FX LC RS-232/RS-485 Fibre-optic ST IEC MODBUS RTU/ASCII - - MODBUS TCP/IP - - DNP3 (serial) - - DNP3 TCP/IP - - IEC IEC = Supported 14 ABB

15 21. Technical data Table 6. Dimensions Description Width frame 177 mm case 164 mm Height frame 177 mm (4U) case 160 mm Depth 201 mm ( mm) Weight complete relay 4.1 kg plug-in unit only 2.1 kg Table 7. Power supply Description U aux nominal 24, 30, 48, 60 V DC Maximum interruption time in the auxiliary DC voltage without resetting the relay U aux variation % of U n ( V DC) Start-up threshold 19.2 V DC (24 V DC * 80%) Burden of auxiliary voltage supply under quiescent (P q )/operating condition Ripple in the DC auxiliary voltage Fuse type DC <12.0 W (nominal)/<18.0 W (max.) Max. 15% of the DC value (at frequency of 100 Hz) T4A/250 V Table 8. Energizing inputs Description Rated frequency 50/60 Hz Current inputs Rated current, I n 0.2/1 A 1) 1/5 A 2) Thermal withstand capability Continuously 4 A 1) 20 A For 1 s 100 A 1) 500 A Dynamic current withstand Half-wave value 250 A 1) 1250 A Input impedance <100 mω 1) <20 mω Voltage inputs Rated voltage V AC Voltage withstand Continuous For 10 s Burden at rated voltage 240 V AC 360 V AC <0.05 VA 1) Ordering option for residual current input 2) Residual current and/or phase current ABB 15

16 Table 9. Energizing inputs of SIM0001 Description Voltage sensor input Rated voltage 5 kv...38 kv 1) Continuous voltage withstand 125 V AC 2) Input impedance at 50/60 Hz 1 MΩ 3) Voltage inputs Rated voltage V AC Voltage withstand Continuous For 10 s Burden at rated voltage 240 V AC 360 V AC <0.05 VA 1) This range is covered with sensor division ratio of :1 2) Test to this voltage 3) Neutral input impedance is close to zero Table 10. Binary inputs Description Operating range Rated voltage Current drain Power consumption Threshold voltage Reaction time ±20% of the rated voltage V DC ma mw V DC 3 ms Table 11. Signal output with high make and carry Description 1) Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R <40 ms Minimum contact load 250 V AC/DC 5 A 15 A 30 A 1 A/0.25 A/0.15 A 100 ma at 24 V AC/DC 1) X100: SO1 X110: SO1, SO2 16 ABB

17 Table 12. Signal outputs and IRF output Description 1) Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry 0.5 s Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V DC Minimum contact load 250 V AC/DC 5 A 10 A 15 A 1 A/0.25 A/0.15 A 10 ma at 5 V AC/DC 1) X100: IRF,SO2 X110: SO3, SO4 Table 13. Double-pole power outputs with TCS function X100: PO3 and PO4 Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V DC (two contacts connected in a series) Minimum contact load 250 V AC/DC 8 A 15 A 30 A 5 A/3 A/1 A 100 ma at 24 V AC/DC Trip-circuit monitoring (TCS) Control voltage range Current drain through the monitoring circuit V AC/DC ~1.5 ma Minimum voltage over the TCS contact 20 V AC/DC ( V) Table 14. Single-pole power output relays X100: PO1 and PO2 Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V DC Minimum contact load 250 V AC/DC 8 A 15 A 30 A 5 A/3 A/1 A 100 ma at 24 V AC/DC Table 15. Front port Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s ABB 17

18 Table 16. Station communication link, fibre-optic Connector Fibre type 1) Wave length Max. distance Permitted path attenuation 2) LC ST MM 62.5/125 or 50/125 μm glass fibre core MM 62.5/125 or 50/125 μm glass fibre core 1300 nm 2 km <8 db nm 1 km <11 db 1) (MM) multi-mode fibre, (SM) single-mode fibre 2) Maximum allowed attenuation caused by connectors and cable together Table 17. IRIG-B Description IRIG time code format B004, B005 1) Isolation Modulation Logic level Current consumption Power consumption 500V 1 min Unmodulated TTL level ma mw 1) According to the IRIG standard Table 18. Degree of protection of flush-mounted relay Description Front side IP 54 Rear side, connection terminals IP 20 Table 19. Environmental conditions Description Operating temperature range ºC (continuous) Short-time service temperature range ºC (<16h) 1)2) Relative humidity Atmospheric pressure Altitude Transport and storage temperature range <93%, non-condensing kpa Up to 2000 m ºC 1) Degradation in MTBF and HMI performance outside the temperature range of ºC 2) For relays with an LC communication interface the maximum operating temperature is +70 ºC 18 ABB

19 Table 20. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 khz burst disturbance test IEC IEC , class III IEEE C Common mode 2.5 kv Differential mode 2.5 kv 3 MHz, 10 MHz and 30 MHz burst disturbance test IEC IEC , class III Common mode 2.5 kv Electrostatic discharge test IEC IEC IEEE C Contact discharge 8 kv Air discharge 15 kv Radio frequency interference test 10 V (rms) f = 150 khz...80 MHz 10 V/m (rms) f = MHz 10 V/m f = 900 MHz 20 V/m (rms) f = MHz IEC IEC , class III IEC IEC , class III ENV IEC , class III IEEE C Fast transient disturbance test IEC IEC IEEE C All ports 4 kv Surge immunity test IEC IEC Communication 1 kv, line-to-earth Other ports 4 kv, line-to-earth 2 kv, line-to-line Power frequency (50 Hz) magnetic field immunity test IEC Continuous s Pulse magnetic field immunity test 300 A/m 1000 A/m 1000 A/m 6.4/16 µs IEC Damped oscillatory magnetic field immunity test IEC s 100 A/m 1 MHz 400 transients/s Power frequency immunity test Binary inputs only IEC IEC , class A Common mode 300 V rms Differential mode 150 V rms ABB 19

20 Table 20. Electromagnetic compatibility tests, continued Description Type test value Reference Emission tests EN 55011, class A IEC Conducted MHz <79 db (µv) quasi peak <66 db (µv) average MHz <73 db (µv) quasi peak <60 db (µv) average Radiated MHz <40 db (µv/m) quasi peak, measured at 10 m distance MHz <47 db (µv/m) quasi peak, measured at 10 m distance Table 21. Insulation tests Description Type test value Reference Dielectric tests Impulse voltage test 2 kv, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication 5 kv, 1.2/50 μs, 0.5 J 1 kv, 1.2/50 μs, 0.5 J, communication IEC and IEC IEC and IEC Insulation resistance measurements >100 MΩ, 500 V DC IEC and IEC Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC Table 22. Mechanical tests Description Reference Requirement Vibration tests (sinusoidal) Shock and bump test IEC (test Fc) IEC IEC (test Ea shock) IEC (test Eb bump) IEC Class 2 Class 2 Seismic test IEC Class 2 Table 23. Environmental tests Description Type test value Reference Dry heat test 96 h at +55ºC IEC h at +85ºC 1) Cold test Damp heat test 96 h at -25ºC 16 h at -40ºC 6 cycles (12 h + 12 h) at +25 C +55 C, humidity >93% IEC IEC Change of temperature test 5 cycles (3 h + 3 h) at -25 C C IEC Storage test 96 h at -40ºC 96 h at +85ºC IEC IEC ) For relays with an LC communication interface the maximum operating temperature is +70 o C 20 ABB

21 Table 24. Product safety Description LV directive Reference 2006/95/EC Standard EN (2005) EN (2009) Table 25. EMC compliance Description EMC directive Reference 2004/108/EC Standard EN (2000) EN (2007) Table 26. RoHS compliance Description Complies with RoHS directive 2002/95/EC ABB 21

22 Protection functions Table 27. Three-phase non-directional overcurrent protection ((F)PHxPTOC) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz FPHLPTOC PHHPTOC and PHIPTOC ±1.5% of the set value or ±0.002 I n ±1.5% of set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Start time 1)2) Minimum Typical Maximum PHIPTOC: I Fault = 2 set Start value 16 ms 19 ms 23 ms I Fault = 10 set Start value 11 ms 12 ms 14 ms PHHPTOC and FPHLPTOC: I Fault = 2 x set Start value 22 ms 24 ms 25 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <30 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) ±5.0% of the theoretical value or ±40 ms 3)4) Suppression of harmonics RMS: No suppression DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression P-to-P+backup: No suppression 1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Includes the delay of the heavy-duty output contact 4) Valid for FPHLPTOC 22 ABB

23 Table 28. Three-phase non-directional overcurrent protection (FPHxPTOC) main settings Parameter Function (Range) Step Start FPHLPTOC I n 0.01 PHHPTOC I n 0.01 PHIPTOC I n 0.01 Time multiplier FPHLPTOC PHHPTOC Operate delay time FPHLPTOC ms 10 PHHPTOC ms 10 PHIPTOC ms 10 Operating curve type 1) FPHLPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1, -2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19, -20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34, -35, -36, -37, -38, -39 PHHPTOC PHIPTOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time 1) For further reference, see Operation characteristics table ABB 23

24 Table 29. Three-phase directional overcurrent protection ((F)DPHxPDOC) Operation accuracy Depending on the frequency of the current/voltage measured: f n ±2 Hz FDPHLPDOC DPHHPDOC Current: ±1.5% of the set value or ±0.002 I n Voltage: ±1.5% of the set value or ±0.002 U n Phase angle: ±2 Current: ±1.5% of the set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Voltage: ±1.5% of the set value or ±0.002 U n Phase angle: ±2 Start time 1)2) Minimum Typical Maximum I Fault = 2.0 set Start value 38 ms 43 ms 46 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) ±5.0% of the theoretical value or ±40 ms 3)4) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Measurement mode and Pol quantity = default, current before fault = 0.0 I n, voltage before fault = 1.0 U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of 1.5 to 20 4) Valid for FDPHLPDOC 24 ABB

25 Table 30. Three-phase directional overcurrent protection (FDPHxPDOC) main settings Parameter Function (Range) Step Start value FDPHLPDOC In 0.01 DPHHPDOC In 0.01 Time multiplier DPHxPDOC Operate delay time DPHxPDOC ms 10 Directional mode DPHxPDOC 1 = Non-directional 2 = Forward 3 = Reverse angle DPHxPDOC Operating curve type 1) FDPHLPDOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1, -2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19, -20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34, -35, -36, -37, -38, -39 DPHHPDOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 1) For further reference, refer to the Operating characteristics table Table 31. Non-directional earth-fault protection ((F)EFxPTOC) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz FEFLPTOC EFHPTOC and EFIPTOC ±1.5% of the set value or ±0.002 I n ±1.5% of set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Start time 1)2) Minimum Typical Maximum EFIPTOC: I Fault = 2 set Start value I Fault = 10 set Start value 16 ms 11 ms 19 ms 12 ms 23 ms 14 ms EFHPTOC and EFLPTOC: I Fault = 2 set Start value 22 ms 24 ms 25 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <30 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) ±5.0% of the theoretical value or ±40 ms 3)4) Suppression of harmonics RMS: No suppression DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression 1) Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of ) Valid for FEFLPTOC ABB 25

26 Table 32. Non-directional earth-fault protection (FEFxPTOC) main settings Parameter Function (Range) Step Start value FEFLPTOC I n EFHPTOC I n 0.01 EFIPTOC I n 0.01 Time multiplier FEFLPTOC EFHPTOC Operate delay time FEFLPTOC ms 10 EFHPTOC ms 10 EFIPTOC ms 10 Operating curve type 1) FEFLPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1, -2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19, -20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34, -35, -36, -37, -38, -39 EFHPTOC EFIPTOC Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time 1) For further reference, see Operation characteristics table 26 ABB

27 Table 33. Directional earth-fault protection ((F)DEFxPDEF) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz FDEFLPDEF DEFHPDEF Current: ±1.5% of the set value or ±0.002 I n Voltage ±1.5% of the set value or ±0.002 U n Phase angle: ±2 Current: ±1.5% of the set value or ±0.002 I n (at currents in the range of I n ) ±5.0% of the set value (at currents in the range of I n ) Voltage: ±1.5% of the set value or ±0.002 U n Phase angle: ±2 Start time 1)2) Minimum Typical Maximum DEFHPDEF I Fault = 2 set Start value 42 ms 44 ms 46 ms FDEFLPDEF I Fault = 2 set Start value 61 ms 64 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <30 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) ±5.0% of the theoretical value or ±40 ms 3)4) Suppression of harmonics RMS: No suppression DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression 1) Set Operate delay time = 0.06 s,operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of ) Valid for FDEFLPDEF ABB 27

28 Table 34. Directional earth-fault protection (FDEFxPDEF) main settings Parameter Function (Range) Step Start FDEFLPDEF I n DEFHPDEF I n 0.01 Directional mode FDEFLPDEF and DEFHPDEF 1 = Non-directional 2 = Forward 3 = Reverse Time multiplier FDEFLPDEF DEFHPDEF Operate delay time FDEFLPDEF ms 10 DEFHPDEF ms 10 Operating curve type 1) FDEFLPDEF Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1, -2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19, -20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34, -35, -36, -37, -38, -39 DEFHPDEF Definite or inverse time Curve type: 1, 3, 5, 15, 17 Operation mode FDEFLPDEF and DEFHPDEF 1 = Phase angle 2 = IoSin 3 = IoCos 4 = Phase angle 80 5 = Phase angle 88 1) For further reference, refer to the Operating characteristics table Technical data Table 35. Transient/intermittent earth-fault protection (INTRPTEF) Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: f n ±2 Hz ±1.5% of the set value or ±0.002 Uo Operate time accuracy ±1.0% of the set value or ±20 ms Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5 28 ABB

29 Table 36. Transient/intermittent earth-fault protection (INTRPTEF) main settings Parameter Function (Range) Step Directional mode INTRPTEF 1=Non-directional 2=Forward 3=Reverse - Operate delay time INTRPTEF ms 10 Voltage start value (voltage start value for transient EF) INTRPTEF Un 0.01 Operation mode INTRPTEF 1=Intermittent EF 2=Transient EF - Peak counter limit (Min requirement for peak counter before start in IEF mode) INTRPTEF Min operate current INTRPTEF In 0.01 Table 37. Admittance-based earth-fault protection (EFPADM) Operation accuracy 1) At the frequency f = f n ±1.0% or ±0.01 ms (In range of ms) Start time 2) Minimum Typical Maximum 56 ms 60 ms 64 ms Reset time Operate time accuracy Suppression of harmonics 40 ms ±1.0% of the set value of ±20 ms -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Uo = 1.0 Un 2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements. ABB 29

30 Table 38. Admittance-based earth-fault protection (EFPADM) main settings Parameter Function (Range) Step Voltage start value EFPADM U n 0.01 Directional mode EFPADM 1 = Non-directional 2 = Forward 3 = Reverse Operation mode EFPADM 1 = Yo 2 = Go 3 = Bo 4 = Yo, Go 5 = Yo, Bo 6 = Go, Bo 7 = Yo, Go, Bo Operate delay time EFPADM ms 10 Circle radius EFPADM ms 0.01 Circle conductance EFPADM ms 0.01 Circle susceptance EFPADM ms 0.01 Conductance forward EFPADM ms 0.01 Conductance reverse EFPADM ms 0.01 Conductance tilt Ang EFPADM Susceptance forward EFPADM ms 0.01 Susceptance reverse EFPADM ms 0.01 Susceptance tilt Ang EFPADM Table 39. Wattmetric based earth-fault protection (WPWDE) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz Current and voltage: ±1.5% of the set value or ±0.002 I n Power: ±3% of the set value or ±0.002 P n Start time 1)2) Reset time Typically 63 ms Typically 40 ms Reset ratio Typically 0.96 Operate time accuracy in definite time mode Operate time accuracy in IDMT mode Suppression of harmonics ±1.0% of the set value or ±20 ms ±5.0% of the set value or ±20 ms -50 db at f = n f n, where n=2,3,4,5, 1) Io varied during the test. Uo = 1.0 U n = phase to earth voltage during earth fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, f n = 50 Hz, results based on statistical distribution of 1000 measurement. 2) Includes the delay of the signal output contact. 30 ABB

31 Table 40. Wattmetric based earth-fault protection (WPWDE) main settings Parameter Function (Range) Step Directional mode WPWDE 2 = Forward 3 = Reverse Current start value WPWDE I n Voltage start value WPWDE U n Power start value WPWDE P n Reference power WPWDE P n angle WPWDE Time multiplier WPWDE Operating curve type WPWDE Definite or inverse time Curve type: 5, 15, 20 Operate delay time WPWDE ms 10 Min operate current WPWDE I n Min operate voltage WPWDE U n 0.01 Table 41. Harmonics earth-fault protection (HAEFPTOC) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±5% of the set value or ±0.004 I n Start time 1)2) Reset time Typically 77 ms Typically 40 ms Reset ratio Typically 0.96 Operate time accuracy in definite time mode Operate time accuracy in IDMT mode 3) Suppression of harmonics ±1.0% of the set value or ±20 ms ±5.0% of the set value or ±20 ms -50 db at f = f n -3 db at f = 13 f n 1) Fundamental frequency current = 1.0 I n. Harmonics current before fault = 0.0 I n, harmonics fault current 2.0 Start value. Results based on statistical distribution of 1000 measurement. 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of Table 42. HAEFPTOC main settings Parameter Function (Range) Step Start value HAEFPTOC I n 0.01 Time multiplier HAEFPTOC Operate delay time HAEFPTOC ms 10 Minimum operate time HAEFPTOC ms 10 Operating curve type HAEFPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 ABB 31

32 Table 43. Three-phase overvoltage protection (PHPTOV) Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 1.1 set Start value 22 ms 24 ms 26 ms Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Typically 40 ms Depends of the set Relative hysteresis <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Start value = 1.0 U n, Voltage before fault = 0.9 U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 1.20 U n, Start value multiples in range of Table 44. Three-phase overvoltage protection (PHPTOV) main settings Parameter Function (Range) Step Start value PHPTOV U n 0.01 Time multiplier PHPTOV Operate delay time PHPTOV ms 10 Operating curve type 1) PHPTOV Definite or inverse time Curve type: 5, 15, 17, 18, 19, 20 1) For further reference, see Operation characteristics table Table 45. Three phase undervoltage protection (PHPTUV) Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 0.9 set Start value 62 ms 64 ms 66 ms Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Typically 40 ms Depends on the set Relative hysteresis <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Start value = 1.0 U n, Voltage before fault = 1.1 U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Minimum Start value = 0.50, Start value multiples in range of ABB

33 Table 46. Three-phase undervoltage protection (PHPTUV) main settings Parameter Function (Range) Step Start value PHPTUV U n 0.01 Time multiplier PHPTUV Operate delay time PHPTUV ms 10 Operating curve type 1) PHPTUV Definite or inverse time Curve type: 5, 15, 21, 22, 23 1) For further reference, see Operation characteristics table Table 47. Positive-sequence undervoltage protection (PSPTUV) Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 0.99 set Start value U Fault = 0.9 set Start value 51 ms 43 ms 53 ms 45 ms 54 ms 46ms Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Suppression of harmonics Typically 40 ms Depends of the set Relative hysteresis <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Start value = 1.0 U n, Positive sequence voltage before fault = 1.1 U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact Table 48. Positive-sequence undervoltage protection (PSPTUV) main settings Parameter Function (Range) Step Start value PSPTUV U n Operate delay time PSPTUV ms 10 Voltage block value PSPTUV U n 0.01 Table 49. Frequency protection (FRPFRQ) Operation accuracy f>/f< ±10 mhz df/dt ±100 mhz/s (in range df/dt < 5 Hz/s) ± 2.0% of the set value (in range 5 Hz/s < df/dt < 15 Hz/s) Start time f>/f< <80 ms df/dt <120 ms Reset time Operate time accuracy <150 ms ±1.0% of the set value or ±30 ms ABB 33

34 Table 50. Frequency protection (FRPFRQ) main settings Parameter Function (Range) Step Operation mode FRPFRQ 1 = Freq< 2 = Freq> 3 = df/dt 4 = Freq< + df/dt 5 = Freq> + df/dt 6 = Freq< OR df/dt 7 = Freq> OR df/dt Start value Freq> FRPFRQ f n Start value Freq< FRPFRQ f n Start value df/dt FRPFRQ f n /s Operate Tm Freq FRPFRQ ms 10 Operate Tm df/dt FRPFRQ ms 10 Table 51. Negative-sequence overvoltage protection (NSPTOV) Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 1.1 set Start value U Fault = 2.0 set Start value 33 ms 24 ms 35 ms 26 ms 37 ms 28 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode Suppression of harmonics <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Negative-sequence voltage before fault = 0.0 U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact Table 52. Negative-sequence overvoltage protection (NSPTOV) main settings Parameter Function (Range) Step Start value NSPTOV U n Operate delay time NSPTOV ms 1 34 ABB

35 Table 53. Residual overvoltage protection (ROVPTOV) Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Start time 1)2) Minimum Typical Maximum U Fault = 1.1 set Start value 55 ms 56 ms 58 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode Suppression of harmonics <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Residual voltage before fault = 0.0 U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact Table 54. Residual overvoltage protection (ROVPTOV) main settings Parameter Function (Range) Step Start value ROVPTOV U n Operate delay time ROVPTOV ms 1 Table 55. Negative phase-sequence overcurrent protection (NSPTOC) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±1.5% of the set value or ±0.002 I n Start time 1)2) Minimum Typical Maximum I Fault = 2 set Start value I Fault = 10 set Start value 22 ms 14 ms 24 ms 16 ms 25 ms 17 ms Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode <35 ms ±1.0% of the set value or ±20 ms Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, 1) Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 I n, Start value multiples in range of ABB 35

36 Table 56. Negative phase-sequence overcurrent protection (NSPTOC) main settings Parameter Function (Range) Step Start value NSPTOC I n 0.01 Time multiplier NSPTOC Operate delay time NSPTOC ms 10 Operating curve type 1) NSPTOC Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 1) For further reference, see Operation characteristics table Table 57. Phase discontinuity protection (PDNSPTOC) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±2% of the set value Start time Reset time <70 ms Typically 40 ms Reset ratio Typically 0.96 Retardation time Operate time accuracy in definite time mode Suppression of harmonics <35 ms ±1.0% of the set value or ±20 ms DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 58. Phase discontinuity protection (PDNSPTOC) main settings Parameter Function (Range) Step Start value (Current ratio setting I 2 / I 1 ) PDNSPTOC % 1 Operate delay time PDNSPTOC ms 1 Min phase current PDNSPTOC I n 0.01 Table 59. Circuit breaker failure protection (CCBRBRF) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±1.5% of the set value or ±0.002 I n Operate time accuracy Retardation time ±1.0% of the set value or ±20 ms <20 ms 36 ABB

37 Table 60. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function (Range) Step Current value (Operating phase current) Current value Res (Operating residual current) CCBRBRF I n 0.05 CCBRBRF I n 0.05 CB failure mode (Operating mode of function) CCBRBRF 1 = Current 2 = Breaker status 3 = Both - CB fail trip mode CCBRBRF 1 = Off 2 = Without check 3 = Current check - Retrip time CCBRBRF ms 10 CB failure delay CCBRBRF ms 10 CB fault delay CCBRBRF ms 10 Table 61. Three-phase thermal overload protection for feeders (T1PTTR) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 I n (at currents in the range of I n ) Operate time accuracy 1) ±2.0% of the theoretical value or ±0.50 s 1) Overload current > 1.2 Operate level temperature Table 62. Three-phase thermal overload (T1PTTR) main settings Parameter Function (Range) Step Env temperature Set (Ambient temperature used when the AmbSens is set to Off) Current multiplier (Current multiplier when function is used for parallel lines) T1PTTR C 1 T1PTTR Current reference T1PTTR I n 0.01 Temperature rise (End temperature rise above ambient) Time constant (Time constant of the line in seconds) Maximum temperature (temperature level for operate) Alarm value (Temperature level for start (alarm) Reclose temperature (Temperature for reset of block reclose after operate) Initial temperature (Temperature raise above ambient temperature at startup) T1PTTR C 0.1 T1PTTR s 1 T1PTTR C 0.1 T1PTTR C 0.1 T1PTTR C 0.1 T1PTTR C 0.1 ABB 37

38 Table 63. Three-phase inrush current detection (INRPHAR) Operation accuracy At the frequency f = f n Current measurement: ±1.5% of the set value or ±0.002 I n Ratio I2f/I1f measurement: ±5.0% of the set value Reset time +35 ms / -0 ms Reset ratio Typically 0.96 Operate time accuracy +35 ms / -0 ms Table 64. Three-phase inrush detection (INRPHAR) main settings Parameter Function (Range) Step Start value (Ratio of the 2nd to the 1st harmonic leading to restraint) INRPHAR % 1 Operate delay time INRPHAR ms 1 Table 65. Multipurpose protection (MAPGAPC) Operation accuracy ±1.0% of the set value or ±20 ms Table 66. Multipurpose analog protection (MAPGAPC) main settings Parameter Function (Range) Step Start value MAPGAPC Operate delay time MAPGAPC ms 100 Operation mode MAPGAPC Over Under - Table 67. Fault locator function (SCEFRFLO) Measurement accuracy At the frequency f = f n Impedance: ±2.5% or ±0.25 Ω Distance: ±2.5% or ±0.16 km/0.1 mile XC0F_CALC: ±2.5% or ±50 Ω IFLT_PER_ILD: ±5% or ± ABB

39 Table 68. Fault locator (SCEFRFLO) main settings Parameter Function (Range) Step Z Max phase load SCEFRFLO Ω 0.1 Ph leakage Ris SCEFRFLO Ω 1 Ph capacitive React SCEFRFLO Ω 1 R1 line section A SCEFRFLO Ω/pu X1 line section A SCEFRFLO Ω/pu R0 line section A SCEFRFLO Ω/pu X0 line section A SCEFRFLO Ω/pu Line Len section A SCEFRFLO pu Table 69. Operation characteristics Parameter Operating curve type Operating curve type (voltage protection) (Range) 1 = ANSI Ext. inv. 2 = ANSI Very. inv. 3 = ANSI Norm. inv. 4 = ANSI Mod inv. 5 = ANSI Def. Time 6 = L.T.E. inv. 7 = L.T.V. inv. 8 = L.T. inv. 9 = IEC Norm. inv. 10 = IEC Very inv. 11 = IEC inv. 12 = IEC Ext. inv. 13 = IEC S.T. inv. 14 = IEC L.T. inv 15 = IEC Def. Time 17 = Programmable 18 = RI type 19 = RD type 5 = ANSI Def. Time 15 = IEC Def. Time 17 = Inv. Curve A 18 = Inv. Curve B 19 = Inv. Curve C 20 = Programmable 21 = Inv. Curve A 22 = Inv. Curve B 23 = Programmable ABB 39

40 Control functions Table 70. Autoreclosing (DARREC) Operate time accuracy ±1.0% of the set value or ±20 ms Table 71. Synchrocheck (SECRSYN) Operation accuracy Depending on the frequency of the voltage measured: f n ±1 Hz Voltage: ±3.0% of the set value or ±0.01 U n Frequency: ±10 mhz Phase angle: ±3 Reset time <50 ms Reset ratio Typically 0.96 Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms Table 72. Synchronism and energizing check (SECRSYN) main settings Parameter Function (Range) Step Live dead mode SECRSYN -1 = Off 1 = Both Dead 2 = Live L, Dead B 3 = Dead L, Live B 4 = Dead Bus, L Any 5 = Dead L, Bus Any 6 = One Live, Dead 7 = Not Both Live Difference voltage SECRSYN U n 0.01 Difference frequency SECRSYN f n Difference angle SECRSYN Synchrocheck mode SECRSYN 1 = Off 2 = Synchronous 3 = Asynchronous Control mode SECRSYN 1 = Continuous 2 = Command Dead line value SECRSYN U n 0.1 Live line value SECRSYN U n 0.1 Close pulse SECRSYN ms 10 Max energizing V SECRSYN U n 0.01 Phase shift SECRSYN Minimum Syn time SECRSYN ms 10 Maximum Syn time SECRSYN ms 10 Energizing time SECRSYN ms 10 Closing time of CB SECRSYN ms ABB

41 Measurement functions Table 73. Three-phase current measurement (CMMXU) Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz ±0.5% or ±0.002 I n (at currents in the range of I n ) Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression Table 74. Current sequence components (CSMSQI) Operation accuracy Depending on the frequency of the measured current: f/f n = ±2 Hz ±1.0% or ±0.002 I n at currents in the range of I n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 75. Three-phase voltage measurement (VMMXU) Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz At voltages in range U n ±0.5% or ±0.002 U n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression Table 76. Voltage sequence components (VSMSQI) Operation accuracy Depending on the frequency of the voltage measured: f n ±2 Hz At voltages in range U n ±1.0% or ±0.002 U n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 77. Residual current measurement (RESCMMXU) Operation accuracy Depending on the frequency of the current measured: f/f n = ±2 Hz ±0.5% or ±0.002 I n at currents in the range of I n Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, RMS: No suppression ABB 41

42 Table 78. Three-phase power and energy (PEMMXU) Operation accuracy At all three currents in range I n At all three voltages in range U n At the frequency f n ±1 Hz Active power and energy in range PF > 0.71 Reactive power and energy in range PF < 0.71 ±1.5% for power (S, P and Q) ±0.015 for power factor ±1.5% for energy Suppression of harmonics DFT: -50 db at f = n f n, where n = 2, 3, 4, 5, Table 79. Frequency measurement (FMMXU) Operation accuracy ±10 mhz (in measurement range Hz) 42 ABB

43 Supervision functions Table 80. Fuse failure supervision (SEQRFUF) Operate time 1) NPS function U Fault = 1.1 set Neg Seq voltage Lev U Fault = 5.0 set Neg Seq voltage Lev <33 ms <18 ms Delta function ΔU = 1.1 set Voltage change rate <30 ms ΔU = 2.0 set Voltage change rate <24 ms 1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements Table 81. Motor run time counter (MDSOPT) Description Motor run-time measurement accuracy 1) ±0.5% 1) Of the reading, for a stand-alone relay, without time synchronization. Table 82. Voltage presence (PHSVPR) Operation accuracy Depending on the frequency of the measured voltage: f n ±2 Hz ±1.5% of the set value or ±0.002 U n Operation time accuracy ±1.0% of the set value or ±20 ms Table 83. Voltage presence (PHSVPR) main settings Parameter Function (Range) Step Num of phases PHSVPR 1=1 out of 3 2=2 out of 3 3=3 out of 3 V live value PHSVPR U n 0.1 V live time PHSVPR ms 1 ms V dead value PHSVPR U n 0.1 V dead time PHSVPR ms 1 ms ABB 43

44 22. Local HMI The relay is available with two optional displays, a large one and a small one. The large display is suited for relay installations where the front panel user interface is frequently used and a single line diagram is required. The small display is suited for remotely controlled substations where the relay is only occasionally accessed locally via the front panel user interface. Both LCD displays offer front-panel user interface functionality with menu navigation and menu views. However, the large display offers increased front-panel usability with less menu scrolling and improved information overview. In addition, the large display includes a user-configurable single line diagram (SLD) with position indication for the associated primary equipment. Depending on the chosen standard configuration, the relay displays the related measuring values, apart from the default single line diagram. The SLD view can also be accessed using the Web browser-based user interface. The default SLD can be modified according to user requirements by using the Graphical Display Editor in PCM600. The local HMI includes a push button (L/R) for local/remote operation of the relay. When the relay is in the local mode, it can be operated only by using the local front panel user interface. When the relay is in the remote mode, it can execute commands sent from a remote location. The relay supports the remote selection of local/remote mode via a binary input. This feature facilitates, for example, the use of an external switch at the substation to ensure that all relays are in the local mode during maintenance work and that the circuit breakers cannot be operated remotely from the network control center. IECA V3 EN IECA V3 EN Figure 7. Small display Figure 8. Large display Table 84. Small display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) 5 20 Large, variable width (13x14 pixels) 4 8 or more 1) Depending on the selected language Table 85. Large display Character size 1) Rows in the view Characters per row Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 8 8 or more 1) Depending on the selected language 44 ABB

45 23. Mounting methods By means of appropriate mounting accessories the standard relay case can be flush mounted, semi-flush mounted or wall mounted. The flush mounted and wall mounted relay cases can also be mounted in a tilted position (25 ) using special accessories. Further, the relays can be mounted in any standard 19 instrument cabinet by means of 19 mounting panels available with cut-outs for one or two relays. Flush mounting Semi-flush mounting Semi-flush mounting in a 25 tilt Rack mounting Wall mounting Mounting to a 19" equipment frame Panel cut-out for flush mounting: Height: ±1 mm Width: ±1 mm Mounting methods: IECA V4 EN IECA V4 EN IECA V4 EN Figure 9. Flush mounting Figure 10. Semi-flush mounting Figure 11. Semi-flush with a 25º tilt 24. Relay case and plug-in unit For safety reasons, the relay cases for current measuring relays are provided with automatically operating contacts for short-circuiting the CT secondary circuits when a relay unit is withdrawn from its case. The relay case is further provided with a mechanical coding system preventing current measuring relay units from being inserted into a relay case for a voltage measuring relay unit and vice versa, that is, the relay cases are assigned to a certain type of plug-in unit. 25. Selection and ordering data Use the ABB Library to access the selection and ordering information and to generate the order number. 26. Accessories and ordering data Table 86. Mounting accessories Item Semi-flush mounting kit Wall mounting kit Inclined semi-flush mounting kit Order number 1MRS MRS MRS rack mounting kit with cut-out for one relay 1MRS rack mounting kit with cut-out for two relays 1MRS ABB 45

46 27. Tools The relay is delivered as a pre-configured unit. The default parameter setting values can be changed from the front-panel user interface, the Web browser-based user interface (Web HMI) or the PCM600 tool in combination with the relayspecific connectivity package. The Protection and Control IED Manager PCM600 offers extensive relay configuration functions such as relay signal configuration, application configuration, graphical display configuration including single line diagram configuration, and IEC communication configuration including horizontal GOOSE communication. When the Web browser-based user interface is used, the relay can be accessed either locally or remotely, using a Web browser (Internet Explorer). For security reasons, the Web browser-based user interface is disabled by default. The interface can be enabled with PCM600 or via the front panel user interface. The functionality of the interface can be limited to read-only access through PCM600. The relay connectivity package is a collection of software and specific relay information, which enable system products and tools to connect and interact with the relay. The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and set-up times. Further, the connectivity packages for this product series relays include a flexible update tool for adding one additional local HMI language to the relay. The update tool is activated using PCM600, and it enables multiple updates of the additional HMI language, thus offering flexible means for possible future language updates. Table 87. Tools Configuration and setting tools PCM600 Version 2.6 or later Web-browser based user interface IE 7.0, IE 8.0 or IE 9.0 RER615 Connectivity Package 1.1 or later 46 ABB

47 Table 88. Supported functions Function Web HMI PCM600 Relay parameter setting Saving of relay parameter settings in the relay Signal monitoring Disturbance recorder handling Alarm LED viewing Access control management Relay signal configuration (Signal Matrix) - Modbus communication configuration (communication management) - DNP3 communication configuration (communication management) - IEC communication configuration (communication management) - IEC /104 communication configuration (communication management) - Saving of relay parameter settings in the tool - Disturbance record analysis - XRIO parameter export/import - Graphical display configuration - Application configuration - IEC communication configuration, GOOSE (communication configuration) - Phasor diagram viewing - Event viewing Saving of event data on the user's PC - Online monitoring - = Supported ABB 47

48 28. Connection diagrams L1 L2 L3 Positive Current Direction a n N A RER615 X120 X100 P1 P2 P1 S1 S2 P2 S1 S X V N V N V N 1/5A N 1/5A N 1/5A N 0.2/1A N U1 U2 U3 IL1 IL2 IL3 Io BI 1 BI 2 BI 3 BI 4 BI 5 2) IRF PO1 PO2 SO1 SO2 PO3 TCS1 PO4 TCS2 + Uaux BI X BI 7 BI 8 BI 1 BI 2 BI 3 1) SO1 SO2 SO3 SO4 X BI 4 BI 5 BI 6 1) SO1 SO2 SO3 1) Order selectable -Optional 2) The relay features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached X GUID-EB2E66DA-219E-423A-BE97-C478B253B5C0 V2 EN Figure 12. Connection diagram for the A configuration 48 ABB

49 L1 L2 L3 Positive Current Direction RER615 P1 P2 S1 S2 X /5A N 1/5A N 1/5A N 0.2/1A N BI 1 BI 2 BI 3 BI 4 1) IL1 IL2 IL3 Io IRF PO1 PO2 SO1 SO2 + Uaux - X X U1 U2 U3 PO3 TCS1 PO4 TCS No Connection No Connection U1B U2B U3B X BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 SO1 SO2 SO3 SO4 X BI 7 13 BI 8 1) The relay features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached GUID-08A9DCFE D F2D82B6B8E V2 EN Figure 13. Connection diagram for the D configuration ABB 49

50 29. References The portal provides information on the entire range of distribution automation products and services. 30. Functions, codes and symbols All available functions are listed in the table. All of them may not be applicable to all products. You will find the latest relevant information on the RER615 protection and control relay on the product page. Scroll down the page to find and download the related documentation. 50 ABB

51 Table 89. Functions included in the relay Function IEC IEC IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage, instance 1 FPHLPTOC1 3I> (1) 51P-1 (1) PHHPTOC1 3I>> (1) 51P-2 (1) PHIPTOC1 3I>>> (1) 50P/51P (1) FDPHLPDOC1 3I> -> (1) 67-1 (1) FDPHLPDOC2 3I> -> (2) 67-1 (2) DPHHPDOC1 3I>> -> (1) 67-2 (1) FEFLPTOC1 Io> (1) 51N-1 (1) EFHPTOC1 Io>> (1) 51N-2 (1) EFIPTOC1 Io>>> (1) 50N/51N (1) Directional earth-fault protection, low stage, instance 1 FDEFLPDEF1 Io> -> (1) 67N-1 (1) Directional earth-fault protection, low stage, instance 2 FDEFLPDEF2 Io> -> (2) 67N-1 (2) Directional earth-fault protection, high stage, instance 1 DEFHPDEF1 Io>> -> (1) 67N-2 (1) Transient/intermittent earth-fault protection, instance 1 INTRPTEF1 Io> -> IEF (1) 67NIEF (1) Admittance based earth-fault protection, instance 1 EFPADM1 Yo> -> (1) 21YN (1) Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2) Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3) Wattmetric based earth-fault protection, instance 1 WPWDE1 Po> -> (1) 32N (1) Wattmetric based earth-fault protection, instance 2 WPWDE2 Po> -> (2) 32N (2) Wattmetric based earth-fault protection, instance 3 WPWDE3 Po> -> (3) 32N (3) Harmonics based earth-fault protection, instance 1 HAEFPTOC1 Io>HA (1) 51NHA (1) Negative-sequence overcurrent protection, instance 1 NSPTOC1 I2> (1) 46 (1) Negative-sequence overcurrent protection, instance 2 NSPTOC2 I2> (2) 46 (2) Phase discontinuity protection, instance 1 PDNSPTOC1 I2/I1> (1) 46PD (1) Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1) Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2) Three-phase undervoltage protection, instance 1 PHPTUV1 3U< (1) 27 (1) Three-phase undervoltage protection, instance 2 PHPTUV2 3U< (2) 27 (2) Three-phase undervoltage protection, instance 3 PHPTUV3 3U< (3) 27 (3) Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1) Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2) Three-phase overvoltage protection, instance 3 PHPTOV3 3U> (3) 59 (3) ABB 51

52 Table 89. Functions included in the relay, continued Function IEC IEC IEC-ANSI Positive-sequence undervoltage protection, instance 1 PSPTUV1 U1< (1) 47U+ (1) Negative-sequence overvoltage protection, instance 1 NSPTOV1 U2> (1) 47O- (1) Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1) Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81 (2) Three-phase thermal protection for feeders, cables and distribution transformers, instance 1 T1PTTR1 3Ith>F (1) 49F (1) Circuit breaker failure protection, instance 1 CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1) Three-phase inrush detector, instance 1 INRPHAR1 3I2f> (1) 68 (1) Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1) Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1) Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2) Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3) Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4) Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5) Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6) Fault locator, instance 1 SCEFRFLO1 FLOC (1) 21FL (1) Power quality Current total demand distortion, instance 1 CMHAI1 PQM3I (1) PQM3I (1) Voltage total harmonic distortion, instance 1 VMHAI1 PQM3U (1) PQM3V (1) Voltage variation, instance 1 PHQVVR1 PQMU (1) PQMV (1) Voltage unbalance, instance 1 VSQVUB1 PQUUB (1) PQVUB (1) Control Circuit-breaker control, instance 1 CBXCBR1 I <-> O CB (1) I <-> O CB (1) Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1) Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2) Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1) Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2) Autoreclosing, instance 1 DARREC1 O -> I (1) 79 (1) Synchronism and energizing check, instance 1 SECRSYN1 SYNC (1) 25 (1) Condition monitoring and supervision Circuit-breaker condition monitoring, instance 1 SSCBR1 CBCM (1) CBCM (1) Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Fuse failure supervision, instance 1 SEQRFUF1 FUSEF (1) 60 (1) Runtime counter for machines and devices, instance 1 MDSOPT1 OPTS (1) OPTM (1) Voltage presence, instance 1 PHSVPR1 PHSVPR(1) PHSVPR(1) Measurement 52 ABB

53 Table 89. Functions included in the relay, continued Function IEC IEC IEC-ANSI Disturbance recorder, instance 1 RDRE1 DR (1) DFR (1) Three-phase current measurement, instance 1 CMMXU1 3I (1) 3I (1) Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1) Residual current measurement, instance 1 RESCMMXU1 Io (1) In (1) Three-phase voltage measurement, instance 1 VMMXU1 3U (1) 3V (1) Three-phase voltage measurement, instance 2 VMMXU2 3U (B) (1) 3V (B) (1) Sequence voltage measurement, instance 1 VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1) Sequence voltage measurement, instance 2 VSMSQI2 U1, U2, U0 (B) (1) V1, V2, V0 (B) (1) Three-phase power and energy measurement, instance 1 PEMMXU1 P, E (1) P, E (1) Frequency measurement, instance 1 FMMXU1 f (1) f (1) Load profile, instance 1 LDPMSTA1 LOADPROF (1) LOADPROF (1) Other Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP (1) TP (1) Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP (2) TP (2) Minimum pulse timer (2 pcs, second resolution), instance 1 Minimum pulse timer (2 pcs, minute resolution), instance 1 TPSGAPC1 TPMGAPC1 TPS (1) TPS (1) TPM (1) TPM (1) Pulse timer (8 pcs), instance 1 PTGAPC1 PT (1) PT (1) Pulse timer (8 pcs), instance 2 PTGAPC2 PT (2) PT (2) Time delay off (8 pcs), instance 1 TOFGAPC1 TOF (1) TOF (1) Time delay off (8 pcs), instance 2 TOFGAPC2 TOF (2) TOF (2) Time delay on (8 pcs), instance 1 TONGAPC1 TON (1) TON (1) Time delay on (8 pcs), instance 2 TONGAPC2 TON (2) TON (2) Set reset (8 pcs), instance 1 SRGAPC1 SR (1) SR (1) Set reset (8 pcs), instance 2 SRGAPC2 SR (2) SR (2) Move (8 pcs), instance 1 MVGAPC1 MV (1) MV (1) Move (8 pcs), instance 2 MVGAPC2 MV (2) MV (2) Generic control point (16 pcs), instance 1 SPCGGIO1 SPCGGIO (1) SPCGGIO (1) Generic control point (16 pcs), instance 2 SPCGGIO2 SPCGGIO (2) SPCGGIO (2) Remote generic control points, instance 1 SPCRGGIO1 SPCRGGIO (1) SPCRGGIO (1) Local generic control points, instance 1 SPCLGGIO1 SPCLGGIO (1) SPCLGGIO (1) Generic up-down counters, instance 1 UDFCNT1 UDCNT (1) UDCNT (1) Generic up-down counters, instance 2 UDFCNT2 UDCNT (2) UDCNT (2) Generic up-down counters, instance 3 UDFCNT3 UDCNT (3) UDCNT (3) ABB 53

54 31. Document revision history Document revision/date Product version History A/ First release B/ Content updated C/ Content updated to correspond to the product version 54 ABB

55 55

56 Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI VAASA, Finland Phone Fax Copyright 2015 ABB. All rights reserved.

Relion product family. Grid Automation Remote Monitoring and Control REC615 Product Guide

Relion product family. Grid Automation Remote Monitoring and Control REC615 Product Guide Relion product family Grid Automation Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...12 6. Control...13

More information

Relion 615 series. Transformer Protection and Control RET615 Product Guide

Relion 615 series. Transformer Protection and Control RET615 Product Guide Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions...14 4. Application... 15 5. Supported ABB solutions...

More information

Relion 611 series. Feeder Protection and Control REF611 Product Guide

Relion 611 series. Feeder Protection and Control REF611 Product Guide Relion 611 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...7 5. Supported ABB solutions...9 6.

More information

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version

More information

Line differential protection and control RED615 Compact and versatile solution for utility and industrial power distribution systems

Line differential protection and control RED615 Compact and versatile solution for utility and industrial power distribution systems Relion 65 series Line differential protection and control RED65 Compact and versatile solution for utility and industrial power distribution systems Ideal selectivity for twoend line differential protection

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...11 4. Application...11 5. Supported ABB solutions...14

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide Relion 605 series Feeder protection and control / Feeder protection Product Guide Product version: 2.2FP1 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

Relion 630 series. Motor Protection and Control REM630 Product Guide

Relion 630 series. Motor Protection and Control REM630 Product Guide Relion 630 series Motor Protection and Control Product Guide Contents 1. Description... 3 2. Application... 3 3. Preconfigurations... 7 4. Protection functions...12 5. Control... 12 6. Measurement... 12

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

Relion 615 series. Transformer Protection and Control RET615 Product Guide

Relion 615 series. Transformer Protection and Control RET615 Product Guide Relion 615 series Transformer Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...14 4. Application...14 5. Supported ABB solutions...18

More information

Relion 611 series. Feeder Protection and Control REF611 Application Manual

Relion 611 series. Feeder Protection and Control REF611 Application Manual Relion 611 series Feeder Protection and Control REF611 Document ID: 1MRS757456 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document and parts

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

Relion 615 series. Voltage Protection and Control REU615 Product Guide

Relion 615 series. Voltage Protection and Control REU615 Product Guide Relion 615 series Voltage Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...7 4. Application...7 5. Supported ABB solutions...9 6.

More information

Relion 620 series. Feeder Protection and Control REF620 Product Guide

Relion 620 series. Feeder Protection and Control REF620 Product Guide Relion 620 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Default configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...15

More information

Capacitor Protection Relay SPAJ 160 C. Product Guide

Capacitor Protection Relay SPAJ 160 C. Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

How To Protect Your Power Supply From Dangerous Currents And Voltages

How To Protect Your Power Supply From Dangerous Currents And Voltages ids ACOS 300 Protection equipment for medium and highvoltage grids ACOS 300 Protection Devices Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Relion 615 series. Motor Protection and Control REM615 Application Manual

Relion 615 series. Motor Protection and Control REM615 Application Manual Relion 615 series Motor Protection and Control REM615 Document ID: 1YHT530017D05 Issued: 2014-05-14 Revision: B Product version: 4.1 Copyright 2014 ABB. All rights reserved Copyright This document and

More information

Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual

Relion 611 series. Feeder Protection and Control REF611 Modbus Point List Manual Relion 611 series Feeder Protection and Control REF611 Modbus Document ID: 1MRS757463 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

How To Replace Ancienti'S Ref615R

How To Replace Ancienti'S Ref615R Relion 615 series Feeder protection and control REF615R Product guide Table of contents 1. Description...3 2. Standard configurations...4 3. Protection functions...6 4. Application...7 5. Supported ABB

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Relion 620 series. Motor protection and control REM620 ANSI Product guide

Relion 620 series. Motor protection and control REM620 ANSI Product guide Relion 620 series Motor protection and control REM620 ANSI Product guide Table of contents 1. Description... 3 2. Standard configurations... 3 3. Protection functions... 8 4. Application... 8 5. Supported

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Station Automation Series COM600 Protection and control from ABB Future-proof Concept: Extensive Substation System Integration and Interoperability The Station Automation Series COM600 is a dedicated system

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Combined overcurrent & earth-fault relay. Type SPAJ 140 C

Combined overcurrent & earth-fault relay. Type SPAJ 140 C Combined overcurrent & earth-fault relay Type SPAJ 140 C ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

MPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card

MPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card Machinery Protection Card Type FEATURES Continuous on-line Machinery Protection Card Real-time measurement and monitoring using state-of-the-art DSP techniques Fully VME-compatible slave interface Fully

More information

T200, PTP/IEEE 1588 Grandmaster Clock and

T200, PTP/IEEE 1588 Grandmaster Clock and T200, PTP/IEEE 1588 Grandmaster Clock and NTP Time Server with high accuracy GPS receiver, OCXO or Rubidium oscillator 1 Bd d Armor 22300 LANNION - FRANCE [email protected] 1 HEOL-T200 : PERFORMANCE

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Applications. diris_826_a_1_gb_cat

Applications. diris_826_a_1_gb_cat Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Test & Data Management Software

Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

Power network telecommunication

Power network telecommunication www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Relion Protection and Control. 611 series Technical Manual

Relion Protection and Control. 611 series Technical Manual Relion Protection and Control 611 series Document ID: 1MRS757454 Issued: 2011-11-18 Revision: A Product version: 1.0 Copyright 2011 ABB. All rights reserved Copyright This document and parts thereof must

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Communicate and view data from meters with one simple device

Communicate and view data from meters with one simple device Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

E-Series protective relay family

E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays E-Series protective relay family Reliable protection for every application Eaton s E-Series relay

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

PLA 44. Power quality analyzer. User and service manual. BMR trading

PLA 44. Power quality analyzer. User and service manual. BMR trading PLA 44 Power quality analyzer User and service manual version 1.2 BMR Lipovka 17 516 01 Rychnov n. Kn. 1 Tel: +420 774 415 703 Fax: +420 494 533 602 Content 1. Front panel...3 5.6.1. List of events...8

More information

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

FREJA 300 Relay Testing System

FREJA 300 Relay Testing System Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

DC Electronic Loads 8500 series

DC Electronic Loads 8500 series Data Sheet DC Electronic Loads 8500 series 2400W 600 W - 1200 W 300 W Versatile & Economical DC Electronic Loads The 8500 series Programmable DC Electronic Loads can be used for testing and evaluating

More information

TDMS Test & Data Management Software

TDMS Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

IEC 61850 in ZX Gas-insulated medium voltage switchgear

IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Just as the supply of electrical power is becoming more and more important in a networked world, demands for the integration of electrical

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

Arc Protection Relay REA 10_. Product Guide

Arc Protection Relay REA 10_. Product Guide Arc Protection Relay REA 10_ Product Guide Issued: 1May 1999 Status: Updated Version: D / 22.06.2005 Data subject to change without notice Features Loop-type sensor fiber, radial sensor fiber or lens-type

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet Multi-Range Programmable DC Power Supplies 1200 W / 3000 W Multi-Range DC Power Supplies Features & Benefits Any model can replace several supplies on your bench or in your rack. Unlike conventional

More information

Low Voltage Products

Low Voltage Products Low Voltage Products ABB Power Quality Filters: The most efficient solution for active filtering of harmonics, smooth reactive power compensation and load balancing. Enabling trouble-free and efficient

More information

For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation.

For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation. PRELIMINARY TECHNICAL INFORMATION Three-phase Digital SCR Firing Board HIGHLIGHTS - Up to 480 V AC input supply voltage - Up to 700 V AC sync input - DSP controlled - Digital or analog input signaling

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Feeder Protection Relay. Technical Reference Manual - ANSI Version

Feeder Protection Relay. Technical Reference Manual - ANSI Version 1MRS755535 Issued: 30.01.2005 Version: E/18.11.2011 Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4. Product documentation...

More information

Power quality monitoring and analysis with reliability

Power quality monitoring and analysis with reliability Power quality monitoring and analysis with reliability PowerLogic CM4000 series circuit monitors Buildings Industry Data Center Intelligent metering and control devices Whether in offices, classrooms,

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850 Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing

More information

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5 T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet PowerLogic power-monitoring units PM5350 power meter Technical data sheet Mid-range metering PM5350 Functions and characteristics PE86278 The PowerLogic PM5350 power meter offers all the measurement capailities

More information

Measuring and monitoring units VAMP 96 VAMP 260 WIMO 6CP10

Measuring and monitoring units VAMP 96 VAMP 260 WIMO 6CP10 Measuring and monitoring units VAMP 96 Measuring and monitoring units Main characteristics Intelligent measuring and monitoring units The VAMP and WIMO meters come with an extensive selection of pre-configured

More information