Secure your electrical network. PACiS The Safety Solution for Healthcare Institutions
|
|
- Sabina Casey
- 8 years ago
- Views:
Transcription
1 Secure your electrical network The Safety Solution for Healthcare Institutions
2 Fast Secure : the solution for fault isolation and electrical network restoration in less than 500 ms
3 03 A Real Time System for Automatic Electrical Loop Re-configuration To ensure the continuity of supply and secure operation of electrical networks in hospitals and healthcare institutions, it is essential to be able to isolate the faulty section and safely re-energise the remaining installations. The fast response of the solution (<500 ms) goes well beyond the requirements of national standards and regulations, which typically impose a response in less than 2 seconds. The solution is fully customisable to match all electrical network topologies. Architecture The solution is based on an Ethernet IEC client-server architecture. MiCOM C264 real time Programmable Logic Controllers, inter-connected by a redundant fiber-optic network, manage the electrical network and connected equipments. MiCOM and Sepam Protection IEDs, Human-Machine Interfaces (HMI), fault detector Easergy T200, and gateways (GTW) will interface with your Building Management System (BMS) to complete the solution and increase the capabilities of your power system.
4 Modular & evolutive solution Standard communication : the solution for the continuity and security of your electrical networks
5 05 Protection Relays and Fault Detection Detection, protection and location of electrical faults are the key points in any application. Immediate and reliable fault detection & location is ensured through the use of the instantaneous information from MiCOM and Sepam protection relays or fault detector Easergy T200 integrated in. MiCOM and Sepam relays, in addition to their protection functions, provide measurement and all monitoring information required for efficient maintenance and easy post-fault analysis. When the short-circuit power of the units does not allow the MV bay fuses to blow, the MiCOM P114S relays ensure back-up protection on the outgoing feeders, thus preventing their definitive tripping. CUSTOMER BENEFITS Network re-energised in less than 500ms Capability to manage up to 60 substations Distributed automation schemes with self-adaptation to topology HV & MV electrical standards compliant Local generation and energy storage management Islanding and grid reconnection management Equipment and communication network permanent self-check
6 06 Components solutions are mainly based on MiCOM C264 devices interconnected via redundant fiber optical Ethernet IEC network. The MiCOM C264 is a real time PLC dedicated to the management, supervision and control of EHV, HV or MV electrical networks. MiCOM C264 is fully compatible with all IEC and ANSI electrical standards. Supervision Simulation PC systems can be complemented with one or several supervision PCs to monitor and control the network. Simulation and test modes may complement the solution. Web Access MiCOM C264 provides web access, allowing the display of measurement and logic data using a standard PC Web navigator. Gateway Connection to the site BMS is a native feature of systems based on standard communication protocols: OPC, MODBUS, PROFIBUS. MAIN FUNCTIONS Alarm Any alarm or event impacting the site electrical network can be transferred to an operator 24/7 using GSM call messages, SMS, text or web mail messages. Supervision of the electrical installation Fault location and analysis Electrical loop network management Transformer load shedding (optional) Emergency generator management Relay selectivity optimization
7 07 Applications The electrical network elements are managed using PLC IEDs connected together with the system. manages Integrated Solutions (cubicles or cabinets with power supply), and Centralised Solutions (hardwired data or distributed communication networks). Standard system includes: 5 electrical network management modes: Normal, Back-up, Maintenance, Inhibited and Test Mode Service restoration, islanding management and grid reconnection Automatic adaptation to topology Network power supply switchover: - to a second delivery substation - to a second back-up substation Capability to use disconnectors instead of circuit breaker Transformer load shedding Load management - via secondary substation transformers - via network disconnectors Compatible with any MV earthing method: Isolated / Direct / Resistance and Petersen Coil compensated Emergency generator and energy storage management: - Start and stop - Voltage and frequency control
8 2011 Schneider Electric - All rights reserved Schneider Electric 35, rue Joseph Monier CS F Rueil Malmaison Cedex RCS Nanterre Capital social As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on recycled paper. Publishing: Sonovision Design: Schneider Electric Printing: France NRJED110004EN
An Alternative Approach to Improving SAIDI and SAIFI Indicators
An Alternative Approach to Improving SAIDI and SAIFI Indicators Philippe Deschamps - Schneider Electric Industries - France Jean-Christophe Orsini - Schneider Electric Industries - France Kaare Seest Rasmussen
More informationGain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server
Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that
More informationElectrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
More informationPermissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
More informationMedium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic
More informationA MODERN DISTRIBUTION MANAGEMENT SYSTEM FOR REGIONAL ELECTRICITY COMPANIES
A MODERN DISTRIBUTION MANAGEMENT SYSTEM FOR REGIONAL ELECTRICITY COMPANIES A Roberts, T Berry, W D Wilson Schneider Electric Ltd, UK SYNOPSIS This paper describes the features of a modern Distribution
More informationPower products and systems. Intelligent solutions for power distribution Zone concept
Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationADMS(Advanced Distribution Management System ) in Smart Grid
ADMS(Advanced Distribution Management System ) in Smart Grid 柯 佾 寬 博 士 Yi-Kuan Ke, Ph.D. 2014/03/28 Smart Grid Solution Smart Grid Solution Overview Smart Grid Solutions Smart Network Operation - Distribution
More informationChapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
More informationUnite your power network
Unite your power network StruxureWare Power Monitoring software Maximize operational efficiency, optimize power distribution, and improve bottom-line performance Healthcare StruxureWare Power Monitoring
More informationNu-Lec Training Modules
PTCC Controller Nu-Lec Training Modules Product Training Operator Training PTCC The Basics An overview of the construction and physical features of the Pole Top Control Cubicle PTCC Operation and Features
More informationEasily connect your switchboards to facility management solutions
Easily connect your switchboards to facility management solutions Acti 9 communication system gives your customers complete control of their installations 100% exclusive to Schneider Electric Acti 9: The
More informationMiCOM P432 and P439. Distance Protection and Control Units. Protection Relays
01 MiCOM P432 and P439 Distance Protection and Control Units The MiCOM P432 and P439 are cost effective one-box solutions for integrated numerical distance protection and control. P439 in case 40TE P432
More informationOptimize your power network with data-driven decisions
Optimize your power network with data-driven decisions StruxureWare Power Monitoring Expert software delivers the integrated information for maximizing network reliability and performance Power Monitoring
More informationRelion. Power system protection and automation reference Extending substation life cycle with IEC 61850
Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing
More informationInternet-Accessible Power Monitoring & Control Systems
Internet-Accessible Power Monitoring & Control Systems By GE Specification Engineers Keith B. Brock, P.E. Robert P. Hansen, PhD, P.E. Introduction Accessing electrical system information from any location
More informationFuture grid infrastructure Field tests of LVDC distribution
Future grid infrastructure Field tests of LVDC distribution LUT LVDC Research Group: Andrey Lana, Pasi Nuutinen, Antti Pinomaa, Tero Kaipia, Pasi Peltoniemi, Aleksi Mattsson, Jarmo Partanen Introduction
More informationLow voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
More informationOptions and monitoring
Additional outlets Energy distribution unit with two Schuko-outlets and four IEC-outlets. Rackmount module version with a height of 2 units. Parallel Distribution Box with Bypasss A compact distribution
More informationAn assurance of highlevel healthcare thanks to the availability of electric power
An assurance of highlevel healthcare thanks to the availability of electric power Secure power distribution and monitoring solution for operating theatres 24/24 7/ 7n Electric power constantly available
More informationABB North America. Substation Automation Systems Innovative solutions for reliable and optimized power delivery
ABB North America Substation Automation Systems Innovative solutions for reliable and optimized power delivery Substation Automation Systems Advanced substation automation, protection and control solutions
More informationDeveloping greener energy. Solutions for Hydro Power Plants
Developing greener energy Solutions for Hydro Power Plants Your challenges l To improve the design of your sites to reduce investment costs l To reduce operating costs and provide a continuous electricity
More informationTest & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More informationMONITORING DEVICE FITTED ON-BOARD A MV CIRCUIT-BREAKER, IN REMOTE AS WELL AS LOCAL ACCESS
MONITORING DEVICE FITTED ON-BOARD A MV CIRCUIT-BREAKER, IN REMOTE AS WELL AS LOCAL ACCESS Marc NOUVELLON marc_nouvellon@mail.schneider.fr Alain BILLET alain_billet@mail.schneider.fr Laurent GUISE laurent_guise@mail.schneider.fr
More informationPowerLogic communication devices. EGX100 Ethernet gateway EGX300 Integrated gateway-server. Technical data sheet
PowerLogic communication devices EGX100 Ethernet gateway EGX300 Integrated gateway-server Technical data sheet 2011 PowerLogic EGX100 Ethernet gateway PE86138 Function The EGX100 serves as an Ethernet
More informationNJP-400A NJP-401A. Safely into a new day. Advanced modular FIRE ALARM CONTROL PANEL with additional functionality. I m on FIRE (Bruce Springsteen)
Safely into a new day Advanced modular FIRE ALARM CONTROL PANEL with additional functionality NJP-400A NJP-401A I m on FIRE (Bruce Springsteen) EN 54-2, EN 54-4 Cert No. 1124a DESCRIPTION OP-400A, NJP-400A,
More informationWhat will MV switchgear look like in the future? by Jean-Marc Biasse
What will MV switchgear look like in the future? by Jean-Marc Biasse Table of contents Introduction... 2 Brief history of the technologies used in medium voltage switchgear and control gear... 4 Evolution
More informationGROUP OF SPANISH ELECTRICITY COMPANIES FOR STUDIES ON IEC 61850
GROUP OF SPANISH ELECTRICITY COMPANIES FOR STUDIES ON IEC 61850 MINIMUM COMMON SPECIFICATION FOR SUBSTATION PROTECTION AND CONTROL EQUIPMENT IN ACCORDANCE WITH THE IEC 61850 STANDARD EDITION MODIFICATION
More informationPower network telecommunication
www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,
More informationMiCOM P139. Feeder Management and bay Control. Multifunction IEDs. CustOMEr benefits. APPlICAtIOn
01 Feeder Management and bay Control The is a cost effective one-box solution for integrated numerical time-overcurrent protection and bay control. The broad spectrum of protection functions enables the
More informationOVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
More informationHow To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
More informationStruxureWare Power Monitoring Expert Data Center Edition. Power system intelligence and reliability for your entire infrastructure
StruxureWare Power Monitoring Expert Data Center Edition Power system intelligence and reliability for your entire infrastructure revolution A power system to meet your changing demands. 2 StruxureWare
More informationModicon M580 The next generation controller for PlantStruxure architecture
Modicon M580 The next generation controller for PlantStruxure architecture 3 5 ways the Modicon M580 will revolutionize your process Introducing Modicon M580 Built for truly open and efficient Ethernet
More informationTDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More informationIl Progetto INTEGRIS. Risultati e nuove prospettive per lo sviluppo delle Smart Grid October 2nd 2013 Brescia
Il Progetto INTEGRIS. Risultati e nuove prospettive per lo sviluppo delle Smart Grid October 2nd 2013 Brescia From INTEGRIS a solution architecture for energy smart grids Jean Wild - Schneider Electric
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationFeeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification
Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version
More informationNew Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems
International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System
More informationIEC 61850: Communication Networks and Systems in Substations
IEC 61850: Communication Networks and Systems in Substations Sistemi e strumenti per l'automazione, A. Flammini, AA2011-2012 Background I: Power Grid Sistemi e strumenti per l'automazione A. Flammini,
More informationCYBER SECURITY: SYSTEM SERVICES FOR THE SAFEGUARD OF DIGITAL SUBSTATION AUTOMATION SYSTEMS. Massimo Petrini (*), Emiliano Casale TERNA S.p.A.
21, rue d Artois, F-75008 PARIS D2-102 CIGRE 2012 http : //www.cigre.org CYBER SECURITY: SYSTEM SERVICES FOR THE SAFEGUARD OF DIGITAL SUBSTATION AUTOMATION SYSTEMS Massimo Petrini (*), Emiliano Casale
More informationSCADA Systems Automate Electrical Distribution
SCADA Systems Automate Electrical Distribution PC-based supervisory control and data acquisition systems increase uptime, cut costs and improve utilization. A White Paper from InduSoft Fabio Terezinho
More informationTechnical Specification Of Substation Protection & Control System with IEC 61850 BHEL s Perspective
Technical Specification Of Substation Protection & Control System with IEC 61850 BHEL s Perspective India Core Events 2008 September 24 th 2008 1 Background Stability & Reliability Data Storage Communication
More informationIndustrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards
Redundancy = Protection from Network Failure. Redundancy Standards WP-31-REV0-4708-1/5 Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards For a very
More informationEVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland fergus.malone@esbi.ie ESB International, Ireland paul.d.doyle@esbi.ie
More informationEaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
More informationParalleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationRemote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
More informationTechnical information. Typical Automatic Transfer Switch diagrams
Technical information Typical Automatic Transfer Switch diagrams Summary Standard Diagrams 2 - TRANSFER BETWEEN 2 SOURCES - 1 Bus bar - TRANSFER BETWEEN 2 SOURCES - 2 Bus bars - TRANSFER BETWEEN 2 SOURCES
More informationPower Solutions for Data Centers Metering and protection architecture guide
Power Solutions for Data Centers Metering and protection architecture guide The purpose of this guide is to provide technical guidelines to designers and field engineers who specify metering and protection
More informationISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
More informationBasics in Energy Information (& Communication) Systems Summary Substation Automation
Basics in Energy Information (& Communication) Systems Summary Substation Automation Dr. Johann Pohany, xxxx x xxx xxx xx Substation Integration and Automation Levels Integrated utility business operation
More informationSIPROTEC Protection Technology
SIPROTEC Protection Technology The Basis for Highest Availability of Supply Siemens AG 2012. Siemens All rights reserved. AG 2012 Infrastructure and Cities Objectives of this Brochure Objective The following
More informationMonitoring & Control of Small-scale Renewable Energy Sources
Small Scale Renewable Energy Sources and Energy Saving: 6-17 th July 2009 Monitoring & Control of Small-scale Renewable Energy Sources Dr G A Taylor Brunel Institute of Power Systems Brunel University,
More informationNEW. EVEN MORE data acquisition and test stand automation
NEW EVEN MORE data acquisition and test stand automation the new class of data The plug&play complete package User benefits Expert Series is the latest generation of data acquisition Complete hardware
More informationSquare D Model 6 Motor Control Centers
Square D Model 6 Motor Control Centers with Ethernet Communications What is industrial Ethernet? Over the past few years the use of Ethernet communications has spread into every corner of the business
More informationReyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
More informationDIgSILENT StationWare Protection Setting Management System
Dhofar Power Company DIgSILENT StationWare Protection Setting Management System Dr. A. A. Maqrashi B.Eng, MBA, M.Sc., Ph.D. www.albanah.com http://www.albanah.org/ss/showthread.php?701 1 Extreme Importance
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationGrid Automation Products. MicroSCADA Pro for substation automation
Grid Automation Products for substation automation Perfect control anywhere, anytime is an investment for today and tomorrow. Start, for instance, with monitoring or gateway functionality and integrate
More informationPersonalise energy solutions
spacelynk Personalise energy solutions Connected Space Grow your business in building automation energy and maintenance management Lighting and HVAC can cause over 70 % of the energy used in a building.
More informationRelion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE
Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power
More informationLow Voltage Products
Low Voltage Products ABB Power Quality Filters: The most efficient solution for active filtering of harmonics, smooth reactive power compensation and load balancing. Enabling trouble-free and efficient
More informationIEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
More informationMedium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions. www.schneider-electric.
Medium Voltage Distribution FLUVAC Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka Operation Maintenance Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists,
More informationPower Generator Switching for Power Engineers Inc. with. Distrix Software Defined Infrastructure. A Distrix Networks Case Study.
Power Generator Switching for Power Engineers Inc. with Distrix Software Defined Infrastructure A Distrix Networks Case Study November, 2015 2015 Distrix Networks Ltd. All Right Reserved 1 The project
More informationOVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
More informationData Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work.
Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work. Data security is first of all electrical Maximizing security while providing efficiency
More informationCatalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
More informationTesting Intelligent Device Communications in a Distributed System
Testing Intelligent Device Communications in a Distributed System David Goughnour (Triangle MicroWorks), Joe Stevens (Triangle MicroWorks) dgoughnour@trianglemicroworks.com United States Smart Grid systems
More informationPower-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More informationEducational solutions. MV/LV power grid design and operation laboratory
Educational solutions MV/LV power grid design and operation laboratory Presentation Context A growing development of the power supply requires a staff competent in its engineering, operation and maintenance.
More informationMedium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
More informationSeize the benefits of green energy and the smart grid
Seize the benefits of green energy and the smart grid Electrical energy storage system for buildings optimizes self-consumption, costs, and reliability Are you getting the most from your onsite energy
More informationExecutive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
More informationSus tain.ability. 2012 Honeywell Users Group Asia Pacific. Annemarie Diepenbroek, Greg Belcher Experion Overview and New Solutions
Sus tain.ability. 2012 Honeywell Users Group Asia Pacific Annemarie Diepenbroek, Greg Belcher Experion Overview and New Solutions 2 Experion PKS Orion: Reshaping Automation Process knowledge in the field
More informationDOE Wind Consortium Project. Wind Energy Research and Development. Jay Giri. IIT, Chicago July 20 th, 2011. Jay.giri@alstom.com. Copyright ALSTOM Grid
DOE Wind Consortium Project Wind Energy Research and Development IIT, Chicago July 20 th, 2011 Jay Giri Jay.giri@alstom.com Possible Impacts of Wind Power on Grid Operations (Source: IEA Wind Task 25,
More informationLine differential protection and control RED615 Compact and versatile solution for utility and industrial power distribution systems
Relion 65 series Line differential protection and control RED65 Compact and versatile solution for utility and industrial power distribution systems Ideal selectivity for twoend line differential protection
More informationSOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
More informationApplication-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template
Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date
More informationUPS system for emergency lighting and smoke extraction
UPS system for emergency lighting and smoke extraction Requirements There are a number of standards that apply to emergency lighting and smoke extraction systems (for example: NFS 61-940 [France only]
More informationHow To Use Safety System Software (S3)
SPECIFICATION DATA Safety System Software (S3) APPLICATION Safety System Software (S 3 ) is a robust, full featured configuration, diagnostic, programming and real-time monitoring package for integrators
More informationValidation of PROFINET plants
PI Competence Center &PI Training Center Validation of PROFINET plants Paolo Ferrari & CSMT Gestione s.c.a.r.l. Facoltà di Ingegneria, Università di Brescia, Via Branze 38-25123 Brescia (Italy) Tel: +39-030-6595111
More informationSubstation Automation and Smart Grid
GE Energy Substation Automation and Smart Grid John D. McDonald, P.E. GM, T&D Marketing IEEE PES Past President IEEE Division VII Director IEEE Fellow The Smart Grid POWERING POTENTIA L Current Situation
More informationExperience in Design, Engineering, Testing and Implementation of Electrical Systems for a Large Gas Processing Plant
Experience in Design, Engineering, Testing and Implementation of Electrical Systems for a Large Gas Processing Plant By Prabhat K. Saxena Eric Meyer Pi Roy and Nizar Saeed Table of Contents Abstract...p
More informationEmirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
More informationManagement of electric vehicle fleet charging
Management of electric vehicle fleet charging March 2011 / White paper by Maël Cazals and Gilles Vidalenche Make the most of your energy SM Revision #1 Contents Introduction... p 3 What is an electric
More informationCommunicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
More informationAPPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES
APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES J. Ariza G. Ibarra Megger, USA CFE, Mexico Abstract This paper reviews
More informationFailsafe Protection for Utility Critical Infrastructure
Failsafe Protection for Utility Critical Infrastructure Introduction PUCs maintain a crucial part of the nation s CI that provide essential services to the public, business and government. Reliable CI
More informationModbus Communications System for Micrologic A, P, and H Trip Units
Modbus Communications System for Micrologic A, P, and H Trip Units (Four-Wire Modbus System without Smart System Communication) Instruction Bulletin 0613IB1201 R06/15 06/2015 Retain for future use. Hazard
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationDistribution System Automation
ES 586b Course Project Report Distribution System Automation Prepared By Palak Parikh Ph.D. Scholar, Electrical and Computer Engineering Department, University of Western Ontario. Abstract Electric power
More informationTutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements
Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements - Two (2) MiCOM Px4x IEDs with Version 2 implementation of IEC 61850 - Two (2) Cat 5E Ethernet cable - An Ethernet switch 10/100 Mbps - MiCOM
More informationGalaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
More informationThe Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
More information