2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
|
|
- Alicia Mosley
- 8 years ago
- Views:
Transcription
1 Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
2 Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value
3 Power Densities Continue To Rise
4 Think heat removal not cold air supply Four fundamental ways that heat can leave a small confined space like an office or closet Conduction Heat can be removed by flowing through the walls of the space Fan-assisted Ventilation Comfort Cooling Heat can be removed by cooler air that is brought in by ventilation of the space Heat can be removed by a comfort cooling system Dedicated A/C Heat can be removed by a dedicated air conditioner Every kilowatt of power used by the IT equipment creates a kilowatt of heat which must be removed
5 Wiring Closet Cooling Guide 105 Room Temperature (F) Conductive 400 CFM Fan Assist v 800 CFM Fan Assist Dedicated A/C 77 F Room Load (watts) Conductive Cooling 400 CFM Fan Assisted Ventilation 800 CFM Fan Assisted Ventilation Dedicated HVAC
6 Cooling Solutions for Wiring Closets Fan-assisted Ventilation Dedicated Cooling
7 Wiring Closet Ventilation Unit Rapidly deployable wall and ceiling mount heat removal for wiring closets {DELETE This box and add family Image here} Wiring Closet Ventilation Unit The most cost effective way to cool your wiring closet
8 Wiring Closet Ventilation Unit Airflow Diagram Conditioned air from outside the room enters via intake vent Wiring Closet Ventilation Unit pulls warm air from the room Conditioned air supplied to IT equipment Warm, exhaust air Rises Wiring Closet Ventilation Unit Warm air is exhausted from IT equipment
9 WCVU Specifications and Configuration Specifications: Airflow (High fan speed) CFM Airflow (Low fan speed) CFM Heat removal (High) KW Heat removal (Low) KW WCVU applications considerations: Unit must discharge into space that can handle the heat rejected Intake grille must connect to adjacent space that has sufficient conditioned air Rack Air Containment
10 Wiring Closet Ventilation Unit Product Design Benefits Dual fans Provides fault tolerance in the event of a fan failure Multiple mounting methods Flexible design allows for both dry wall and ceiling mount installations Hardwire capable For installations where hardwiring is required or preferred Easy to install Innovative design allows for fast, easy installation by almost anybody Selectable fan speed Selectable fan speed (high/low) via toggle switch provides option for max performance or quiet operation Wiring Closet Ventilation Unit LED status indicators Provides visual notification of fan failure Dry contact output Provides remote notification of failures when used with APC environmental monitoring unit or system
11 Wiring Closet Ventilation Unit Accessories Air Intake Grille for Wiring Closet Ventilation Unit Allows air from adjacent air conditioned space to enter room as Wiring Closet Ventilation Unit removes hot air from closet Wiring Closet Ventilation Unit
12 NetworkAIR PA Portable, self-contained air conditioning solution for small rooms and data closets NetworkAIR PA The only portable cooling solution designed for IT applications
13 NetworkAIR PA4000 Airflow Diagram Ducted Intake Unconditioned air from the ceiling plenum enters the condenser section of the unit Ducted Exhaust Exhaust hot condenser air out of the unit and back into the plenum space for processing by building system Room Air Intake Pulls in warm air from room Cool Air Distribution Delivers conditioned air to IT equipment. Provides up to 4 kw of cooling NetworkAIR PA
14 PA4000 Specifications and Configuration Cooling capacity 3.9 kw cooling at 95 F return air 2.4 kw cooling at 72 F return air Application considerations: Room must have ceiling plenum
15 NetworkAIR PA Product Design Benefits Ducted Intake Uses unconditioned air to reject the heat, rather than conditioned room air Condensate Pump Removes moisture from the system to ensure continuous operation Remote Management Manageable via Web, SNMP, telnet, ISX manager Ducted Exhaust Exhausts hot condenser air out of the room User Interface Provides on/off scheduling and automatic restart in case of power failure Cool Air Distribution Delivers cool air to heat sensitive electronic equipment Room Air Intake Pulls in warm air from room Air Filter NetworkAIR PA Minimizes airborne particles Casters Allow for mobility and easy installation
16 InfraStruXure InRow SC In-row air conditioning for server rooms and wiring closets InfraStruXure InRow SC The predictable solution for an unpredictable environment
17 Available Q3 InfraStruXure InRow SC 5 kw of Cooling Air cooled self-contained Half-rack footprint In-row architecture Network management card Condensate pump
18 Wiring Closet Solution Summary Conduction Do nothing Fan-assisted Ventilation Comfort Cooling Use the Wiring Closet Ventilation Unit (WCVU) Add a second WCVU for higher heat loads Not recommended Dedicated A/C Use the PA4000 or InfraStruXure InRow SC (available in Q3)
19 Specialty Applications for Wiring Closets Equipment with side-to-side air distribution High density loads
20 Rack Side Air Distribution Unit Air distribution for networking equipment with side to side airflow. Rack Side Air Distribution Unit The first air distribution product for high density equipment with side to side airflow
21 Rack Side Air Distribution Unit Airflow Diagram Conditioned Room Air Is: Pulled in from the cold aisle Redirected and Distributed to the equipment inlet Drawn in by the networking equipment Result: Final air path is front to back Equipment gets cool fresh air instead of hot exhaust air Rack Side Air Distribution Unit
22 Side ADU Specifications and Configuration Specifications: Airflow 260 CFM Capacity Up to 1.5 kw of cooling Application considerations: Can be installed in most 19 EIA-310-D racks Multiple Side Air Distributions Units can be installed in single rack
23 Rack Side Air Distribution Design Benefits Dual Fans Increases airflow from top to bottom of equipment A-B Power Input Feeds Redundant power, Maximizes uptime Independent Fan Control Switch Vary amount of airflow to equipment Turning Vane Discharge air from right or left side, up or down depending on piece of equipment requiring airflow Rack Side Air Distribution Unit
24 Rack Air Removal Unit SX Performance heat removal for high density equipment in NetShelter SX and VX enclosures Rack Air Removal Unit SX The only manageable rack heat removal solution
25 Rack Air Removal Unit SX Airflow Diagram Fans pull in rack equipment exhaust air Cable impedance is overcome by high powered fans Prevents recirculation of hot air into racked equipment inlet Ducted exhaust system (optional) delivers hot air to plenum Eliminates hot air from mixing with room air Proper airflow through the enclosure is ensured Cool inlet air moves freely to equipment in the rack Rack Air Removal Unit SX
26 ARU in a Small IT Room
27 ARU SX Specifications and Configuration ARU SX Specifications: Airflow Up to 2000 CFM Cooling Up to 23 kw of heat removal ARU SX is compatible with: NetShelter SX 42U-48U, 600mm and 750 mm racks NetShelter VX 42U-47U, 600mm and 750 mm racks ARU SX Application considerations: Ducting kit is strongly recommended Room should have drop ceiling
28 Rack Air Removal Unit SX Product Benefits Ducted Exhaust System (Optional) Removes hot air from the data center to prevent recirculation and eliminate air mixing Adjustable Mounting Frame Adjustable frame allows unit to mount on either 42U or 48U racks Zero U Solution Mounts to the rear of the rack, leaving valuable rack space for other equipment LCD Display Accessible without opening the door for easy operation. Allows user to locally monitor and control the unit Rack Air Removal Unit SX
29 Rack Air Removal Unit SX Product Benefits Redundant Fans In the event of a fan failure, remaining fans will provide increased airflow up to 12 kw Field Replaceable Components Fans and electronics module can be readily replace without uninstalling the unit Network Manageable View the user interface with a browser. Gives quick access from anywhere on the network Dual A-B Power Inputs Draws power from the UPS for power protection with dual feeds for redundancy InfraStruXure Manager Compatible Enables centralized management via APC s InfraStruXure Manager Temperature Monitoring (optional) Allows up to 3 remote sensors to monitor rack inlet temperature Rack Air Removal Unit SX
30 Small Cooling Solutions Summary Wiring Closet Ventilation Unit Removes hot air from wiring closets and small server rooms PA4000 Dedicated and portable cooling InfraStruXure InRow SC Dedicated cooling for wiring closets and small server rooms Side Air Distribution Unit Special application - provides cool air to equipment with sideto-side airflow Air Removal Unit SX Special application - removes heat from racks
31 Market Opportunity Wiring closets and small server rooms exist in a huge number of customer facilities, numbering in the millions. The growth of VOIP and POE and of technologies is creating cooling problems in these spaces.
32 Identify the Opportunity Finding a Need/Questions to ask: 1. Have you deployed Voice Over IP (VoIP) or Power Over Ethernet (POE) applications, or plan to in the near future? 2. Do you provide dedicated cooling to all of your wiring closets and small server rooms? 3. Is your network gear or servers failing prematurely? 4. Are you wiring closets hot?
33 Build Value Show them that they have a problem: Install an Environmental Monitoring Unit and place temperature probes an the inlets of the IT equipment Temperatures above 77 F are outside of ASHRAE guidelines for data centers Key points that have resonated with IT personal about our solutions: Easy to install Network manageable Can quickly redeploy units in a new location
34 Tools and Reference Materials - InfraStruXure Designer Portal - UPS Selector - NetShelter Configurator - TestDrive.APCC.com - Partner Personal Page: On Demand NCPI trainings APC White Paper #59 The Different Types of Air Conditioning Equipment for IT Environments APC White Paper #69 Power and Cooling for VoIP and IP Telephony Applications APC White Paper #84 Network Critical Physical Infrastructure for Wireless LANs APC App Note #51 APC Power Protection for Nortel VoIP & IP Telephony Solutions APC Cooling for Wiring Closets Sales Opportunity Kit
35 Contact Information Fran Harrington x2293
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationCooling Solutions. for the IT environment
Cooling Solutions for the IT environment APC has the complete cooling solutions line for your data center needs. We offer a range of products to meet all density levels for wiring closets, small, medium,
More informationData Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions
Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
More informationSupporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products
More informationCooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms By Neil Rasmussen Brian Standley White Paper #68 Executive Summary Cooling for IT wiring closets is rarely planned and typically only implemented
More informationADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationPower and Cooling for VoIP and IP Telephony Applications
Power and Cooling for VoIP and IP Telephony Applications By Viswas Purani White Paper #69 Executive Summary Voice Over IP (VoIP) deployments can cause unexpected or unplanned power and cooling requirements
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationCooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationPortable Energy Efficient Data Centre Solution
Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationSmall Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
More informationTen Steps to Solving Cooling Problems Caused by High- Density Server Deployment
Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.
More informationChoosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
More informationCooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationAirflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationMovinCool Office Pro Series. The Portable Spot Cooling Solution
MovinCool Office Pro Series The Portable Spot Cooling Solution The Office Pro 2002 American Standard Inc. All rights reserved Losing Is Not An Option With The Office Pro Series. The loss of data and equipment
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationThe Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric
Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationHow To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationHow Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationBest Practices for Wire-free Environmental Monitoring in the Data Center
White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationData Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems
Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if
More informationSolutions for Network Closets
Harvard Medical School InfraStruXure Design Prevents Small Issues from Becoming Big Problems Our IT staff is tasked to deliver scalable, cutting-edge technology applications 24x7x365. One area that we
More informationBRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
More informationHow To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
More informationCalculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationFOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationEHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationBest Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
More informationAirflow Management Solutions
Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment
More information- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
More informationHigh Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
More informationAuxiliary HVAC RAM ProMaster. Standard Tie-in Extreme Climate System
Auxiliary HVAC RAM ProMaster Standard Tie-in Extreme Climate System Auxiliary HVAC High performance aftermarket heating and cooling systems engineered for vehicle specific platforms that minimize install
More informationDCIM Data Center Infrastructure Monitoring
DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.
More informationPower and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity
Power and Cooling Best Practices for IP Communications A White Paper from the Experts in Business-Critical Continuity Executive Summary IP telephony and Power over Ethernet (PoE) are driving the requirement
More informationUSER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationRack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationNetwork-critical Physical Infrastructure (NCPI) Vulnerability Assessment
Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment Explanation: Network-critical physical infrastructure (NCPI) is the foundation upon which IT networks reside. It consists of power,
More informationAvoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling
More informationAIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
More informationCoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
More informationServer Room, Data Centre Management and Monitoring Solutions
Server Room, Data Centre Management and Monitoring Solutions Published in October 2007 Management & Monitoring Solutions The ability to alert a business to disasters or potential performance issues at
More informationData Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More informationPower and Cooling for VoIP and IP Telephony Applications
White Paper Power and Cooling for VoIP and IP Telephony Applications Executive Summary The advent of IP telephony required the development of techniques that deliver power to IP phones from Ethernet LAN
More informationTechnology Corporation
1 White Paper Meeting The Increased Demand For Efficient Computer Room Cooling Server Cooling Problems: An Overview As microprocessors and other electronic components in servers grow more powerful, they
More informationSelecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More informationGlossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationRACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful
RACKMOUNT SOLUTIONS 1/7/2013 AcoustiQuiet /UCoustic User Guide The AcoustiQuiet /UCoustic User Guide provides useful hints, tips and advice to help maximize the thermal and acoustic properties of the cabinets.
More informationEnergy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
More informationBest Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?
More informationUnified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
More informationRack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationDriving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
More informationCreating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
More informationAEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
More informationAccess Server Rack Cabinet Compatibility Guide
Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationData Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n
Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons
More informationWireless Networks and Power Quality
Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider
More informationHow to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
More informationThe Efficient Data Centre: Space, Power and Cooling
The Efficient Data Centre: Space, Power and Cooling SPS-01 David Palmer Stevens Systems Integrator Manager, PANDUIT 1 the Journey from Coal to the Server 60% Lost through chimney 5-10% distribution loss
More informationLiebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
More informationJAWAHARLAL NEHRU UNIVERSITY
School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational
More informationSolutions for Network Closets
Harvard Medical School InfraStruXure Design Prevents Small Issues from Becoming Big Problems Our IT staff is tasked to deliver scalable, cutting-edge technology applications 24x7x365. One area that we
More informationRack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationCenter Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
More information(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
More information