2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

Size: px
Start display at page:

Download "2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms"

Transcription

1 Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2 Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value

3 Power Densities Continue To Rise

4 Think heat removal not cold air supply Four fundamental ways that heat can leave a small confined space like an office or closet Conduction Heat can be removed by flowing through the walls of the space Fan-assisted Ventilation Comfort Cooling Heat can be removed by cooler air that is brought in by ventilation of the space Heat can be removed by a comfort cooling system Dedicated A/C Heat can be removed by a dedicated air conditioner Every kilowatt of power used by the IT equipment creates a kilowatt of heat which must be removed

5 Wiring Closet Cooling Guide 105 Room Temperature (F) Conductive 400 CFM Fan Assist v 800 CFM Fan Assist Dedicated A/C 77 F Room Load (watts) Conductive Cooling 400 CFM Fan Assisted Ventilation 800 CFM Fan Assisted Ventilation Dedicated HVAC

6 Cooling Solutions for Wiring Closets Fan-assisted Ventilation Dedicated Cooling

7 Wiring Closet Ventilation Unit Rapidly deployable wall and ceiling mount heat removal for wiring closets {DELETE This box and add family Image here} Wiring Closet Ventilation Unit The most cost effective way to cool your wiring closet

8 Wiring Closet Ventilation Unit Airflow Diagram Conditioned air from outside the room enters via intake vent Wiring Closet Ventilation Unit pulls warm air from the room Conditioned air supplied to IT equipment Warm, exhaust air Rises Wiring Closet Ventilation Unit Warm air is exhausted from IT equipment

9 WCVU Specifications and Configuration Specifications: Airflow (High fan speed) CFM Airflow (Low fan speed) CFM Heat removal (High) KW Heat removal (Low) KW WCVU applications considerations: Unit must discharge into space that can handle the heat rejected Intake grille must connect to adjacent space that has sufficient conditioned air Rack Air Containment

10 Wiring Closet Ventilation Unit Product Design Benefits Dual fans Provides fault tolerance in the event of a fan failure Multiple mounting methods Flexible design allows for both dry wall and ceiling mount installations Hardwire capable For installations where hardwiring is required or preferred Easy to install Innovative design allows for fast, easy installation by almost anybody Selectable fan speed Selectable fan speed (high/low) via toggle switch provides option for max performance or quiet operation Wiring Closet Ventilation Unit LED status indicators Provides visual notification of fan failure Dry contact output Provides remote notification of failures when used with APC environmental monitoring unit or system

11 Wiring Closet Ventilation Unit Accessories Air Intake Grille for Wiring Closet Ventilation Unit Allows air from adjacent air conditioned space to enter room as Wiring Closet Ventilation Unit removes hot air from closet Wiring Closet Ventilation Unit

12 NetworkAIR PA Portable, self-contained air conditioning solution for small rooms and data closets NetworkAIR PA The only portable cooling solution designed for IT applications

13 NetworkAIR PA4000 Airflow Diagram Ducted Intake Unconditioned air from the ceiling plenum enters the condenser section of the unit Ducted Exhaust Exhaust hot condenser air out of the unit and back into the plenum space for processing by building system Room Air Intake Pulls in warm air from room Cool Air Distribution Delivers conditioned air to IT equipment. Provides up to 4 kw of cooling NetworkAIR PA

14 PA4000 Specifications and Configuration Cooling capacity 3.9 kw cooling at 95 F return air 2.4 kw cooling at 72 F return air Application considerations: Room must have ceiling plenum

15 NetworkAIR PA Product Design Benefits Ducted Intake Uses unconditioned air to reject the heat, rather than conditioned room air Condensate Pump Removes moisture from the system to ensure continuous operation Remote Management Manageable via Web, SNMP, telnet, ISX manager Ducted Exhaust Exhausts hot condenser air out of the room User Interface Provides on/off scheduling and automatic restart in case of power failure Cool Air Distribution Delivers cool air to heat sensitive electronic equipment Room Air Intake Pulls in warm air from room Air Filter NetworkAIR PA Minimizes airborne particles Casters Allow for mobility and easy installation

16 InfraStruXure InRow SC In-row air conditioning for server rooms and wiring closets InfraStruXure InRow SC The predictable solution for an unpredictable environment

17 Available Q3 InfraStruXure InRow SC 5 kw of Cooling Air cooled self-contained Half-rack footprint In-row architecture Network management card Condensate pump

18 Wiring Closet Solution Summary Conduction Do nothing Fan-assisted Ventilation Comfort Cooling Use the Wiring Closet Ventilation Unit (WCVU) Add a second WCVU for higher heat loads Not recommended Dedicated A/C Use the PA4000 or InfraStruXure InRow SC (available in Q3)

19 Specialty Applications for Wiring Closets Equipment with side-to-side air distribution High density loads

20 Rack Side Air Distribution Unit Air distribution for networking equipment with side to side airflow. Rack Side Air Distribution Unit The first air distribution product for high density equipment with side to side airflow

21 Rack Side Air Distribution Unit Airflow Diagram Conditioned Room Air Is: Pulled in from the cold aisle Redirected and Distributed to the equipment inlet Drawn in by the networking equipment Result: Final air path is front to back Equipment gets cool fresh air instead of hot exhaust air Rack Side Air Distribution Unit

22 Side ADU Specifications and Configuration Specifications: Airflow 260 CFM Capacity Up to 1.5 kw of cooling Application considerations: Can be installed in most 19 EIA-310-D racks Multiple Side Air Distributions Units can be installed in single rack

23 Rack Side Air Distribution Design Benefits Dual Fans Increases airflow from top to bottom of equipment A-B Power Input Feeds Redundant power, Maximizes uptime Independent Fan Control Switch Vary amount of airflow to equipment Turning Vane Discharge air from right or left side, up or down depending on piece of equipment requiring airflow Rack Side Air Distribution Unit

24 Rack Air Removal Unit SX Performance heat removal for high density equipment in NetShelter SX and VX enclosures Rack Air Removal Unit SX The only manageable rack heat removal solution

25 Rack Air Removal Unit SX Airflow Diagram Fans pull in rack equipment exhaust air Cable impedance is overcome by high powered fans Prevents recirculation of hot air into racked equipment inlet Ducted exhaust system (optional) delivers hot air to plenum Eliminates hot air from mixing with room air Proper airflow through the enclosure is ensured Cool inlet air moves freely to equipment in the rack Rack Air Removal Unit SX

26 ARU in a Small IT Room

27 ARU SX Specifications and Configuration ARU SX Specifications: Airflow Up to 2000 CFM Cooling Up to 23 kw of heat removal ARU SX is compatible with: NetShelter SX 42U-48U, 600mm and 750 mm racks NetShelter VX 42U-47U, 600mm and 750 mm racks ARU SX Application considerations: Ducting kit is strongly recommended Room should have drop ceiling

28 Rack Air Removal Unit SX Product Benefits Ducted Exhaust System (Optional) Removes hot air from the data center to prevent recirculation and eliminate air mixing Adjustable Mounting Frame Adjustable frame allows unit to mount on either 42U or 48U racks Zero U Solution Mounts to the rear of the rack, leaving valuable rack space for other equipment LCD Display Accessible without opening the door for easy operation. Allows user to locally monitor and control the unit Rack Air Removal Unit SX

29 Rack Air Removal Unit SX Product Benefits Redundant Fans In the event of a fan failure, remaining fans will provide increased airflow up to 12 kw Field Replaceable Components Fans and electronics module can be readily replace without uninstalling the unit Network Manageable View the user interface with a browser. Gives quick access from anywhere on the network Dual A-B Power Inputs Draws power from the UPS for power protection with dual feeds for redundancy InfraStruXure Manager Compatible Enables centralized management via APC s InfraStruXure Manager Temperature Monitoring (optional) Allows up to 3 remote sensors to monitor rack inlet temperature Rack Air Removal Unit SX

30 Small Cooling Solutions Summary Wiring Closet Ventilation Unit Removes hot air from wiring closets and small server rooms PA4000 Dedicated and portable cooling InfraStruXure InRow SC Dedicated cooling for wiring closets and small server rooms Side Air Distribution Unit Special application - provides cool air to equipment with sideto-side airflow Air Removal Unit SX Special application - removes heat from racks

31 Market Opportunity Wiring closets and small server rooms exist in a huge number of customer facilities, numbering in the millions. The growth of VOIP and POE and of technologies is creating cooling problems in these spaces.

32 Identify the Opportunity Finding a Need/Questions to ask: 1. Have you deployed Voice Over IP (VoIP) or Power Over Ethernet (POE) applications, or plan to in the near future? 2. Do you provide dedicated cooling to all of your wiring closets and small server rooms? 3. Is your network gear or servers failing prematurely? 4. Are you wiring closets hot?

33 Build Value Show them that they have a problem: Install an Environmental Monitoring Unit and place temperature probes an the inlets of the IT equipment Temperatures above 77 F are outside of ASHRAE guidelines for data centers Key points that have resonated with IT personal about our solutions: Easy to install Network manageable Can quickly redeploy units in a new location

34 Tools and Reference Materials - InfraStruXure Designer Portal - UPS Selector - NetShelter Configurator - TestDrive.APCC.com - Partner Personal Page: On Demand NCPI trainings APC White Paper #59 The Different Types of Air Conditioning Equipment for IT Environments APC White Paper #69 Power and Cooling for VoIP and IP Telephony Applications APC White Paper #84 Network Critical Physical Infrastructure for Wireless LANs APC App Note #51 APC Power Protection for Nortel VoIP & IP Telephony Solutions APC Cooling for Wiring Closets Sales Opportunity Kit

35 Contact Information Fran Harrington x2293

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Cooling Solutions. for the IT environment

Cooling Solutions. for the IT environment Cooling Solutions for the IT environment APC has the complete cooling solutions line for your data center needs. We offer a range of products to meet all density levels for wiring closets, small, medium,

More information

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Cooling Strategies for IT Wiring Closets and Small Rooms

Cooling Strategies for IT Wiring Closets and Small Rooms Cooling Strategies for IT Wiring Closets and Small Rooms By Neil Rasmussen Brian Standley White Paper #68 Executive Summary Cooling for IT wiring closets is rarely planned and typically only implemented

More information

ADC-APC Integrated Cisco Data Center Solutions

ADC-APC Integrated Cisco Data Center Solutions Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Power and Cooling for VoIP and IP Telephony Applications

Power and Cooling for VoIP and IP Telephony Applications Power and Cooling for VoIP and IP Telephony Applications By Viswas Purani White Paper #69 Executive Summary Voice Over IP (VoIP) deployments can cause unexpected or unplanned power and cooling requirements

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Cooling Strategies for IT Wiring Closets and Small Rooms

Cooling Strategies for IT Wiring Closets and Small Rooms Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Portable Energy Efficient Data Centre Solution

Portable Energy Efficient Data Centre Solution Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Small Data / Telecommunications Room on Slab Floor

Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

MovinCool Office Pro Series. The Portable Spot Cooling Solution

MovinCool Office Pro Series. The Portable Spot Cooling Solution MovinCool Office Pro Series The Portable Spot Cooling Solution The Office Pro 2002 American Standard Inc. All rights reserved Losing Is Not An Option With The Office Pro Series. The loss of data and equipment

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

How To Power A Bladecenter H Servers

How To Power A Bladecenter H Servers Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if

More information

Solutions for Network Closets

Solutions for Network Closets Harvard Medical School InfraStruXure Design Prevents Small Issues from Becoming Big Problems Our IT staff is tasked to deliver scalable, cutting-edge technology applications 24x7x365. One area that we

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

How To Calculate Total Cooling Requirements For Data Center

How To Calculate Total Cooling Requirements For Data Center Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)

More information

Calculating Total Cooling Requirements for Data Centers

Calculating Total Cooling Requirements for Data Centers Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

FOXAIR 60/50 ALL MODELS

FOXAIR 60/50 ALL MODELS FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

Airflow Management Solutions

Airflow Management Solutions Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Auxiliary HVAC RAM ProMaster. Standard Tie-in Extreme Climate System

Auxiliary HVAC RAM ProMaster. Standard Tie-in Extreme Climate System Auxiliary HVAC RAM ProMaster Standard Tie-in Extreme Climate System Auxiliary HVAC High performance aftermarket heating and cooling systems engineered for vehicle specific platforms that minimize install

More information

DCIM Data Center Infrastructure Monitoring

DCIM Data Center Infrastructure Monitoring DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.

More information

Power and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity

Power and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity Power and Cooling Best Practices for IP Communications A White Paper from the Experts in Business-Critical Continuity Executive Summary IP telephony and Power over Ethernet (PoE) are driving the requirement

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Rack Power Distribution. Worldwide

Rack Power Distribution. Worldwide Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment

Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment Explanation: Network-critical physical infrastructure (NCPI) is the foundation upon which IT networks reside. It consists of power,

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Server Room, Data Centre Management and Monitoring Solutions

Server Room, Data Centre Management and Monitoring Solutions Server Room, Data Centre Management and Monitoring Solutions Published in October 2007 Management & Monitoring Solutions The ability to alert a business to disasters or potential performance issues at

More information

Data Centre Infrastructure Assessment

Data Centre Infrastructure Assessment Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Power and Cooling for VoIP and IP Telephony Applications

Power and Cooling for VoIP and IP Telephony Applications White Paper Power and Cooling for VoIP and IP Telephony Applications Executive Summary The advent of IP telephony required the development of techniques that deliver power to IP phones from Ethernet LAN

More information

Technology Corporation

Technology Corporation 1 White Paper Meeting The Increased Demand For Efficient Computer Room Cooling Server Cooling Problems: An Overview As microprocessors and other electronic components in servers grow more powerful, they

More information

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

RACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful

RACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful RACKMOUNT SOLUTIONS 1/7/2013 AcoustiQuiet /UCoustic User Guide The AcoustiQuiet /UCoustic User Guide provides useful hints, tips and advice to help maximize the thermal and acoustic properties of the cabinets.

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Best Practices in HVAC Design/Retrofit

Best Practices in HVAC Design/Retrofit Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Rack Power Distribution

Rack Power Distribution The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Access Server Rack Cabinet Compatibility Guide

Access Server Rack Cabinet Compatibility Guide Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n

Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction. 670 Deer Road n Cherry Hill, NJ 08034 n 877.429.7225 n Data Center Cooling: Fend Off The Phantom Meltdown Of Mass Destruction How To Preserve Your Servers And Prevent Overheating Your high-performance, multiprocessor servers are working hard, computing tons

More information

Wireless Networks and Power Quality

Wireless Networks and Power Quality Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

The Efficient Data Centre: Space, Power and Cooling

The Efficient Data Centre: Space, Power and Cooling The Efficient Data Centre: Space, Power and Cooling SPS-01 David Palmer Stevens Systems Integrator Manager, PANDUIT 1 the Journey from Coal to the Server 60% Lost through chimney 5-10% distribution loss

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

JAWAHARLAL NEHRU UNIVERSITY

JAWAHARLAL NEHRU UNIVERSITY School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational

More information

Solutions for Network Closets

Solutions for Network Closets Harvard Medical School InfraStruXure Design Prevents Small Issues from Becoming Big Problems Our IT staff is tasked to deliver scalable, cutting-edge technology applications 24x7x365. One area that we

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

(Examples of various colocation sites)

(Examples of various colocation sites) Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company

More information