Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: Uptime Racks:
|
|
|
- Dina Wood
- 10 years ago
- Views:
Transcription
1 Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: Uptime Racks:
2 Server Rooms Description & Heat Problem Trends Calculating Cooling Load Cooling Strategies Best tcooling Practices Cooling Solutions Outline Portable Air Conditioners Air Conditioned Server Racks & Cabinets Ceiling Mount Air Conditioners Mini Split Systems Conclusion
3 Server Room Market Size Estimated U.S. Data Center Electricity Consumption by Market Segment (2011)* Segment Number of Servers (million) Electricity Share Total US Data Center Electricity Use (billion kwh/y) Small/Medium Server Rooms Enterprise/Corporate Data Centers Multi-Tenant Data Centers 4.9 (40%) 3.7 (30%) 2.7 (22%) Hyper-Scale Cloud 1.0 High-Performance (8%) 49% 27% 19% 5% In 2013, small and medium server rooms consumed an estimated 45.5 billion kilowatt-hrs of electricity. This is the equivalent annual output of 17 large (500-megawatt) coal-fired power plants, enough electricity to power all the households in New York City.* - The Natural Resource Defense Council, Aug 2014 Total (rounded) % 76.4 * Scaling Up Energy Efficiency Across the Data Center Industry: Evaluating Key Drivers and Barriers The Natural Resources Defense Council / August 2014
4 Server Room Description Servers / Telecom / UPS / Electrical Equipment Floor Space is a Premium: < 100 ft 2 Contents: 1 3 Server Racks Heat Load per Rack: kw Avg. (3,412 10,236 Btu/hr) Cooling: None / Building cooling during the day Remote location in building (afterthought) Room never designed to cool IT equipment Security: Locked Door and/or Locked Cabinet The average server room can easily contain more than $100,000 of IT equipment Multipurpose Room Server & Break Room -???
5 Power = Heat Server Room Heat Load Servers Smaller & More Powerful VOIP Telecom Equipment High powered switches & equipment Requires UPS support Heat = Electronic Equip Problems Reduced Life Reduced d Reliability Slower Network General Rule Product Heat Density Chart Every 10 C temperature t rise in nominal temperatures t produces a 50% reduction in the lifetime and long-term reliability of IT hardware - MIL-HDBK 217 / Arrhenius Models
6 Direct Costs Server Room Downtime Equipment costs for damaged equipment Employee wages for lost productivity & overtime Lost revenue due to systems being down Indirect Costs Reduced customer satisfaction Customers driven to competitors while your systems down Damaged brand perception / Negative public relations Downtime Costs* Banking: $5, /hr Retail: $9, /hr Media: $4, /hr Hospitality: $1, /hr Insurance: $14, /hr * Reference: Schneider Electric (assuming 40 employees)
7 Server Room Trends Number of server rooms increasing Network applications moved to the cloud (external and internal) Servers & IT hardware moved to colocations (multi-tenant tenant DC) Servers becoming more versatile Large data centers decreasing Physical size of server room is shrinking Amount of IT hardware is shrinking and need fewer cabinets IT hardware becoming smaller (less rack units) and denser Floor space is becoming prime real estate Server rooms become mission critical environments Reliable infrastructure (cooling, power, etc ) found in data centers Increased Efficiency
8 Determining the cooling load Calculate Cooling Load Incremental load from equipment Nameplate rating Usually overstated ASHRAE TC 9.9: Load during operating conditions Not adopted by all manufacturers / Information difficult to obtain UPS load Load from all the equipment connected to the UPS Dependent on time and day: Monitor for worst case scenario Other sources of heat Windows/outside id wall/lights/etc / t Do NOT use room dimensions: Comfort Cooling 400 sq. ft. = 1 Ton of A/C El t i l t j t d h t i Electrical power to rejected heat conversion 1 kw = 3,413 Btu/hr. 12,000 Btu/hr = 1 Ton of A/C (3.5 kw)
9 Cooling Strategies Cooling Strategies Primary cooling for IT equipment Server room is not air conditioned Nights & Weekends when building A/C if off Shut down building A/C when people are not in the building Supplemental Cooling Added denser IT equipment Seasonal: Summer or Winter Seasonal: Summer or Winter Redundancy / Emergency backup to primary cooling Planned or unplanned shut downs: Inexpensive insurance plan
10 Server room cooling efficiency Best Cooling Practices Spot Cool vs. Cooling Entire Room Area directly in front of IT equipment is critical to keep cool Back of the rack up to 25 F hotter than front Airflow pattern is front to back Close-coupled cooling Locate air conditioner as close to IT equipment as possible Prevents cold air from mixing with warm air Cold Aisle / Hot Aisle Use blanking panels for unoccupied rack space Prevents warm air from recirculating to the front of the rack Inlet air conditions to electronic equipment Recommend Temperatures: 64 F 81 F 2008 Recommended Range Min Max Temperatures ( F) Humidity Levels (%RH) Dew Point ( F) ASHRAE Thermal Guidelines for Data Processing Environments Data Center: Upper range temperatures acceptable tight controls/monitoring/redundancy Server rooms: 65 F 72 F Looser controls / no monitoring / no redundancy Extend UPS battery life to 5 years with lower temperatures
11 Cooling Solutions Portable Systems Portable A/C Systems Self contained packaged air conditioner that is on wheels and easily moves from room to room Voltage: 115V, V, or 460V V Air or Water Cooled Heat Rejection: Ceiling plenum Capable of long duct runs Option to duct return / make-up air to condenser Condensation removal Tank: Empty periodically Pump to drain / sink / water line Plug-and-Play Installation Connect accessories (15-20 minutes) Non-standard applications may require contractor Cooling capacity: 1 5 Ton units available Cost Estimate: $3, ,000 Btu/hr. (3.5 kw) air conditioner
12 Cooling Solutions Portable Systems Pros Low cost Relocate unit from room to room Moves with tenant Plug and play installation No outdoor equipment Cooling capacity: 1 5 Tons Cons Floor space required Small heat load on building s a/c Typically not a problem Condensate removal Tank or condensate pump No humidity control
13 Cooling Solutions A/C Server Racks A/C Server Racks & Cabinets Self contained packaged air conditioner integrated into a server rack that easily moves from room to room Voltage: 115V Cabinet / Open 4 Post Rack / 2 Post Telco Rack Heat Rejection: Ceiling plenum Condensation removal Pump to drain/sink/water line Plug-and-Play Installation Connect accessories (15-30 mins) Cooling capacity: 13,000 Btu/hr. Close-coupled cooling Highly efficient Cools rack only Cold Aisle / Hot Aisle Cost Estimate: $5,150 13,000 Btu/hr. (3.8 kw) Air Conditioner Air Conditioned Racks Air Conditioned Cabinets
14 Cooling Solutions A/C Server Racks Pros No floor space required Close-coupled cooling: Highly efficient Relocate unit from room to room Moves with tenant Plug and play installation Reliable 10 year operation No outdoor equipment Works in most environments Cons Small heat load on building s a/c Typically not a problem Condensate removal Pump to drain/sink/water line No humidity control Delivers Cold Air in Front of IT Equipment
15 Cooling Solutions Ceiling Mount Systems Ceiling Mount A/C Systems Self contained packaged air conditioner that installs above the drop ceiling over the server room Voltage: 115V or 208V/230V Packaged system Air cooled Water cooled Condensation removal Pump to drain / sink / water line Gravity drain Contractor Installation Unit comes pre-charged with refrigerant Cooling capacity: 1 5 Ton units available Estimated Cost: $4,400 13,000 Btu/hr (3.8 kw) air conditioner: $2, Installation: $1,500.00
16 Cooling Solutions Ceiling Mount Systems Pros No floor space required Efficient cooling: front to back airflow Works in most environments No outdoor equipment Reliable: 10 years operation Cons Permanent installation Contractor/electrician needed for install Small heat load on building s a/c Typically not a problem Condensate removal Condensate pump No humidity control
17 Cooling Solutions Mini Split Systems Mini Split A/C Systems Consists of 2 units connected by refrigerant lines Indoor Unit: Inside server room Discharges cold air Refrigerant lines Transfers heat to the outdoor unit Outdoor Unit: Outside the building Discharges hot air to the environment Condensation removal Pump to drain / sink / water line Comfort Cooling Low sensible cooling: Temperature drop High Latent cooling: High moisture removal Contractor installation Mounting/electrical/refrigerant lines/condensate line Pre-charged refrigerant lines or charge at site Estimated Cost: $3,700 18,000 Btu/hr. (5.3kW) air Conditioner: $1,700 Oversize because of inefficiency & comfort cooling Installation: $2,000 Condenser Outdoor Unit Evaporator Indoor Unit Refrigerant Pipes
18 Cooling Solutions Mini Split Systems Pros Low cost No floor space required No affect on building s A/C system Installation Guidelines Wiring Closet Outside Building Indoor Unit Refrigerant Lines Cons Location restriction Maximum height difference: 25 Ft. 50 FT Maximum piping length: 50 Ft. Landlord approval Leasehold improvement A/C stays with building when lease is over Low reliability Not designed to operate 24/7/365 Does not operate when outside temps drop below 32 F Comfort Cooling High latent cooling (remove moisture): Poor for IT equipment Condensate removal Condensate pump No humidity control 25 FT Outdoor Unit
19 Cooling Solutions Comparison Chart Cost (25%) Efficient (30%) Install/Versatile/Reliable (45%) Overall Rating (25% + 30% + 45% = 100%) Portable A/C A/C Server Rack Ceiling Mount A/C Mini Split A/C $3,655 12,000 Btu/hr Includes only AC No contractor for installation No electrician needed: 115V $5,150 13,000 Btu/hr 36U Server Rack Includes AC + 36U Rack No contractor for installation No electrician needed: 115V $4,400 13,000 Btu/hr Includes AC + Installation Need contractor for installation Electrician needed $3,700 18,000 Btu/hr Includes AC + Installation Oversize for inefficiency Need contractor for installation Electrician needed Ability to spot cool Cold & warm air can mix Room dictates AC location AC is not close to IT equipment Can focus cooling to front of IT equip Cold air to front of rack Close-coupled cooling Airflow: Front to Back Cools only the space in front of rack Cold & warm air do not mix Cold air to front of rack Return air in back of rack Airflow: Front to Back Cools only the space in front of rack Need barrier to prevent air mixing Inefficient cools room Building dictates AC locale Oversize AC for inefficiency Comfort cooling Lower temp drop / Higher moisture removal Plug-and-Play Install Moves from room to room Requires floor space Store in closet for backup A/C Works in almost any environment Requires no floor space Plug-and-Play Install Moves from room to room Reliable 10 yrs continuous Works in almost any environment Requires no floor space Leasehold improvement Permanent installation Reliable 10 yrs continuous Works in almost any environment Requires no floor space Permanent installation Cold weather restrictions Not reliable comfort cooling Installation restrictions Low cost / reliable cooling solution Versatile AC for any environment 1 5 Tons available Better for larger rooms Requires floor space Moves from room to room End of lease Efficient: Close-coupled cooling Versatile AC for any environment Data center in cabinet Requires no floor space Small or big rooms Moves from room to room End of lease Efficient: Front to Back Airflow Versatile AC for any environment Permanent installation Requires no floor space Small or big rooms Need contractor/electrician for installation Low cost AC no floor space req. Inefficient cooling strategy Installation restrictions / limitations Comfort cooling Not for server room Need contractor/electrician for installation
20 Server Room Cooling - Conclusion Dedicated air conditioner system Electronic equipment benefits Increased life/reliability/server speed Improved security with locked door Selecting a cooling solution Budget Important but not sole deciding factor Over $100,000 worth of IT equipment inside room Efficiency Smaller A/C cools more IT equipment Lowers energy costs owers energy costs Versatile A/C systems works for specific building structures Portability vs. Permanent Installation: Moves with tenant Ease of installation Reliability Mission critical networks Designed for server room cooling Network downtime expensive direct and indirect costs
21 Server Room Cooling Questions Air Conditioned Server Racks & Cabinets Portable Air Conditioner Ceiling Mount Air Conditioner Mini Split Air Conditioner
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity
Liebert : The Right Cooling For IT Environments Precision Cooling For Business-Critical Continuity New Challenges To IT System Uptime Many IT professionals are finding that dedicated precision cooling
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Cooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms By Neil Rasmussen Brian Standley White Paper #68 Executive Summary Cooling for IT wiring closets is rarely planned and typically only implemented
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Reducing the Cost of Keeping Office Data Centers Cool
Reducing the Cost of Keeping Office Data Centers Cool Portable Spot Air Conditioners as Permanent Cooling Solutions A Guide for Facility Managers, IT Managers and Mechanical Contractors Today s office
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
MovinCool Office Pro Series. The Portable Spot Cooling Solution
MovinCool Office Pro Series The Portable Spot Cooling Solution The Office Pro 2002 American Standard Inc. All rights reserved Losing Is Not An Option With The Office Pro Series. The loss of data and equipment
Why Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Cooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx [email protected]
Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx [email protected] Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,
Tech Byte 27: Small Computer Room and IT Closet Cooling
Questions Answered in This Paper Sensible cooling capacity is the measuring stick for IT cooling capacity needs. What is the sensible cooling capacity of the comfort split system in comparison to the precision
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Best Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 [email protected] 1 What s the problem here?
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Calculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
The Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
Smaller. Quieter. Smarter.
Smaller. Quieter. Smarter. Product Guide Dehumidifiers Welcome to Aprilaire Aprilaire, Your Partners in Comfort offers a complete line of dehumidifiers designed to meet the ever increasing needs of today
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.
HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is
ECO-AIR AIR CONDITIONING www.northamericanhvac.com
INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Commercial Portable Air Conditioners
Commercial Portable Air Conditioners Air Rover commercial portable air conditioners provide the environmental stability and comfort required by today s sensitive equipment, allowing your business to avoid
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
How To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
HVAC Infrastructure Retrofit Solutions
Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Get the FACTS about SEER and Deliver Better Customer Value
What is SEER? SEER stands for Seasonal Energy Efficiency Ratio. It s a number that describes how well air-conditioning equipment works. A higher SEER means better efficiency and lower energy bills. SEER
AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR
AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR SERVICE CAPACITY (Value) : Rs. 15,40,000/- MONTH AND YEAR : July, 2014 OF PREPARATION PREPARED BY : Sh. Sunil Arora Investigator (Mechanical) 1. INTRODUCTION
Whole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
Using Portable Spot Air Conditioners in Industrial Applications
Using Portable Spot Air Conditioners in Industrial Applications Cooling People, Processes and Equipment In today s highly competitive manufacturing sector, companies are constantly looking for new ways