Performance Testing of an Acrytec Panel Industries ACRY-NC Series NC-25 (Insulated) Rainscreen Cladding Panel System
|
|
|
- Kellie Campbell
- 10 years ago
- Views:
Transcription
1 Performance Testing of an ACRY-NC Series NC-25 (Insulated) Rainscreen Cladding Panel System Prepared for:. 20 Floral Parkway, Unit B Concord, Ontario L4K 4R1 Attention: Mr. Rick Buna, President Trow Associates Inc Clark Boulevard BRBS A Brampton, Ontario February 28, 2011 Telephone: (905) Facsimile: (905)
2 Table of Contents 1. Introduction 1 2. General Description of Mock-up Test Sample 2 3. Methods and Results Summary of Results Air Tightness Water Tightness Wind Load Resistance Wind Load Resistance to Deflection Wind Load Resistance to Blow-Out (Ultimate Load) Surface Burning Characteristics Conclusion 14 i
3 1. Introduction As part of a broader technical evaluation program Trow Associates Inc. (Trow) was retained by (Acrytec) to carry out physical testing on a series of full-scale mock-up wall assemblies incorporating their new architectural, acrylic coated composite glass fibre-reinforced cement board (GFRC) rain-screen panel system, ACRY-NC Series. The intent of the technical evaluation was to ensure that the subject architectural panel was suitable for use for low-rise and high-rise buildings in the Province of Ontario. Accordingly, the information provided in this report is intended to be supplemental in nature and outlines the results of air tightness, water tightness, wind load, and fire testing carried out on the ACRY-NC Series NC-25 Insulated mock-up wall assembly. The air, water, and wind load testing was carried out in Trow s Building Science Laboratory in Brampton, Ontario. The fire tunnel testing was carried out by Exova in Mississauga, Ontario. A copy of the Exova Report is included in Appendix A of this report. For the program, testing was carried out using the applicable Standard ASTM procedures for static air and water leakage, in addition to wind load resistance evaluations. The primary tests conducted were: Air Tightness (infiltration) under incrementally increased positive static pressure differentials, up to a maximum of 300 Pascals; Water Tightness under incrementally increased positive static pressure differentials (simulated driving rain wind pressures) of 150, 200, 300, 400, 500, 600, and 700 Pascals with each pressure condition applied for a period of 15 minutes with the panel in a vertical position; Structural performance, resistance to deflection including blow-out, of the entire assembly under incrementally applied static pressure differentials, up to maximum design positive and negative loads of 3000 Pa; Structural performance, resistance to deflection including blow-out, of the rainscreen portion of the assembly under incrementally applied static pressure differentials, up to maximum design positive and negative loads of 3000 Pa and 3500 Pa, respectively; Flame Spread and Smoke Developed Rating based upon triplicate sample testing conducted in accordance with CAN/ULC-S The testing was conducted in Trow's Building Science Laboratory in Brampton, Ontario between April 1 st and February 14 th, Please note that with respect to compliance of the rain-screen cladding panel system to a set of performance parameters, as no specific criteria were provided, Trow has endeavoured to ensure that 1
4 the intent of the current Ontario Building Code Regulation (OBC) has been fulfilled taking into consideration the panel systems intended use for low-rise and high-rise applications. As part of the cladding panel system evaluation, Trow has provided a comprehensive generic description outlining the components and fabrication of the sample. Deviations in design or fabrication of the system(s) described may affect the system performance and as a consequence negate the relevance of the test results outlined in this report. The specifier, fabricator, or reader is advised to read Section 2.0 of the report carefully to insure that the as-built quality of the cladding panel assembly is the same as the assembly evaluated. 2. General Description of Mock-up Test Sample For the testing, Acrytec first constructed a 152 mm 18 gauge structural steel-stud back-up wall as described below. The stud wall was then anchored into a 38 mm x 286 mm sealed wood test buck (frame) using four standard hex-head M6 (6 mm diameter x 83 mm) bolts per side (one 50 mm from each corner and the remaining two at third-points (800 mm)) with a perimeter clearance between the stud wall and frame of 20 mm. In this configuration the interior face of the steel-stud wall was 85 mm from the interior face of the sealed wood test buck. From the interior outward, the completed sample assembly consisted of the following component elements: Eighteen (18) gauge, structural steel studs 400 mm O.C. Fiberglass-mat-faced gypsum core sheathing (Georgia-Pacific, DensGlass ), 12.7 mm thick, mechanically fastened to the steel studs using screws (bugle head fine thread, rustresistant, drill point drywall screws) at 200 mm O.C. Polyolefin membrane air retarder/moisture barrier, (Fiberweb, Inc., Typar ), 0.33 mm (12.9 mil) thick. The Polyolefin and gypsum sheathing were ultimately sealed to the 2
5 wood buck using a combination of spray-in-place polyurethane foam insulation and exterior side surface applied ultra-low modulus self-leveling neutral cure silicone sealant. Extruded expanded polystyrene insulation (XEPS), 100 mm thick mechanically fastened to the structural steel studs at 400 mm O.C. Eighteen (18) gauge roll-formed G90 galvanized steel, metal channels (NC 25) mounted horizontally at the top and bottom of the panel and vertically at 380 mm O.C., over the XEPS insulation. Prior to mounting the metal channels, strips of self-healing acrylic adhesive flashing tape (3M 8067) are adhered to the back of the channels to ensure a continuous water seal at the XEPS interface (i.e., ensures the channel mounting screws remain watertight). The NC 25 channels were mechanically fastened through the XEPS, membranes, and sheathing into the steel studs at 400 mm O.C. using 152 mm long stainless steel #10 Pan Head Self-Drilling screws. The NC 25 channels are equipped with 5 mm diameter vent/drainage holes at 100 mm O.C. These channels also provide a nominal 25 mm gap between the XEPS and the back of the composite rain-screen cladding panel.. Prefinished, 15 mm thick, acrylic coated composite glass fibre-reinforced cement board (GFRC) rain-screen panels (ACRY-NC Series). The two 1220 mm x 2440 mm panels were mechanically fastened to the metal NC 25 channels using a combination of; polyurethane adhesive sealant (3M 540 Polyurethane Sealant) applied in a continuous manor over the exterior face of the metal channels and, 33 mm long stainless-steel selftapping #10 flat head screws at 600 mm O.C., countersunk to a depth of 4 mm. The screws were then concealed with the same acrylic coating employed on the exterior surface of the panel. Note: Prior to installation of the Acry-NC rain-screen cladding panel, a pressure tap had been installed near the centre of each panel at mid-height. This tap was employed to monitor the pressure differential across the rain-screen during the application of a pressure differential across the entire wall assembly. 3
6 The exterior perimeter top, side and 12 mm joint between the panels, were weather sealed with a low modulus, neutral cure silicone caulking (Tremco Spectrem 3). The weather seal was not applied at the bottom of the panel to ensure proper drainage. For the wind load testing of the rain-screen panel alone, the weather seal was applied at the bottom of the panel. Excluding the buck in its finished form, the mock-up panel had an overall dimension of 2450 mm (W) x 2440 mm (H). 4
7 3. Methods and Results 3.1 Summary of Results The summary of results along with, where applicable, the anticipated building code performance requirements are shown in the following table. Table 3.1: Summary of Test Results Test Test Parameters Test Results Result Air Tightness at P = 75 Pa Water Tightness N/A Q/A = 0.22 (l/s. m 2 ) N/A No water retention or penetration at Driving Rain Wind Pressure Loads given in Ontario Building Code Supplementary Standard SB-1 No water leakage or penetration at a 700 Pa pressure differential. Pass Wind Load Resistance Total Assembly Mechanically & Adhesive Fastened Mid-Span Deflection shall not be greater than 1/175 of length (13.94 mm) at a +/ Pa pressure differential. No damage, permanent deformation or member disengagement at +/ Pa pressure differential). Maximum centerline mid-span panel deflection at Pa. max = 5.63 mm No damage at +/ Pa Residual Deflection max residual = 0.13 mm Pass Wind Load Resistance Rain-Screen Panel Mechanically & Adhesive Fastened Mid-Span Deflection shall not be greater than 1/175 of length (13.94 mm) at a +/ Pa pressure differential. No damage, permanent deformation or member disengagement at +/ pressure differential. Maximum centerline mid-span panel deflection at Pa. max = 2.57 mm No damage at +/ Pa Residual Deflection max residual = 0.37 mm Pass Resistance To Ultimate Negative Wind Load Rain-Screen Panel Surface Burning Characteristics No damage, or permanent deformation or member disengagement at maximum achievable pressure differential. Testing in accordance with CAN/ULC S No observed damage prior to an Utimate Load of: P max < 7880 Pa Rounded Average Flame Spread Rating (FSR): 20 Rounded Average Smoke Developed Classification (SDC): 35 Pass Pass 5
8 3.2 Air Tightness The air tightness testing was carried out using procedures outlined in ASTM Standard E283 Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen. It should be noted, that as the test mock-up panel did not incorporate interior finishes such as, polyethylene vapour retarder and gypsum wall board, the mock-up was not considered a completed airtight wall assembly. In this sense, the mock-up was only equipped with an air retarder and drainage layer behind the rain-screen cladding. Accordingly, it was anticipated that the measured air leakages would likely be higher than those for a completed assembly. In this configuration the backup wall assembly would be more air permeable, which would potentially result in higher imposed loads on the rain-screen portion of the cladding, making it a potentially more severe condition than would be the case for a complete wall assembly. For the testing, the interior side of the test specimen was clamped in place and sealed to a large-scale test chamber using closed cell neoprene tape. A centrifugal fan connected to the test chamber was employed to provide pressure differentials of 25, 50, 75, 100, 150, 200, 250, and 300 Pa across the panel sample. The pressure differential was measured using Ashcroft XLDP pressure transducers and the airflow was measured using a laminar flow element. All Pressure and airflow data was continuously logged using the Omega OM-DAQPRO-5300 data logger at a rate of one (1) reading per second. The total panel air leakages were then divided by the area of the panel assembly to provide the air leakage rates for the test panel assembly. The results of the air leakage testing across the test assembly are provided in the following tables and graph. Table 3.2: Air Tightness Summary of Test Results Pressure Differential across Panel (Pa) Gross Panel Leakage (m 3 /hr) Gross Panel Leakage (l/s) Panel Area (m 2 ) Panel Leakage Rate (m 3 /hr)m -2 Panel Leakage Rate (l/s)m
9 3.3 Water Tightness The water tightness testing was carried out using the procedure outlined in ASTM Standard E331, Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. To determine water tightness characteristics of the wall assembly, the panel assembly was subjected to uniform applied simulated driving rain wind pressures (DRWP s) of 150, 200, 300, 400, 500, 600, and 700 Pa, each for an individual test period of 15 minutes. These values were selected to cover (and exceed) the range of DRWP s given in the Ontario Building Code (OBC) Supplementary Standard SB-1, which provides base DRWP s between 80 and 200 Pascals. These values are then modified for specific applications using a calculated exposure factor (C e ) taking into consideration the height of the building and the characteristics of the terrain surrounding the building. For perspective, the following example illustrates a more extreme DRWP application requirement: For a 150 m high building (approximately 50 storeys) in an open terrain, 200 Pascal application pressure, the DRWP for the building would increase by a factor of 1.71 (i.e. C e = 1.71) to a value of 342 Pascals. During and upon completion of each test, the panel was visually reviewed for water penetration, retention, or presence on interior surfaces. For the test, a centrifugal fan was employed to provide the 7
10 pressure differentials across the panel sample. A water spray grid mounted on a support frame suspended 450mm from the exterior surface of the sample was used to provide approximately 3.4 (L/min)/m 2 of water over the exterior face of the test specimen. The test panel was allowed to drain for a period of five (5) minutes between consecutive DRWP test levels. All pressure data was continuously logged during each test using the Omega OM-DAQPRO-5300 data logger at a rate of one (1) reading per second. This included the pressure differential across both the rain-screen and the total test assembly. The results of the water tightness testing are provided in the following Table. Table 3.3: Water Tightness Summary of Test Results Total ΔP (Pa) Rain-screen ΔP (Pa) Observations No water penetration through panel observed No water penetration through panel observed No water penetration through panel observed No water penetration through panel observed No water penetration through panel observed No water penetration through panel observed No water penetration through panel observed. A post test examination of the panel afer the testing did not indicate water penetration past the rainscreen portion of mock-up assembly. During the testing conducted at the 700 Pascal DRWP level no water leakage was observed. Based on the results of the testing, Trow would consider that the rain-screen panel evaluated meets or exceeds the intent of the OBC with respect to watertightness under conditions of wind driven rain as provided in Supplemental Standard SB Wind Load Resistance Wind Load Resistance to Deflection The wind load resistance to deflection testing was carried out in accordance with the procedures outlined in ASTM E330, Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. In this case, testing was carried out first by subjecting the entire assembly to both positive and negative wind loads and measuring the centerline deflections of the adhesive attached and mechanically fastened rain-screen panel sections. Upon completion of the initial testing, a square section, approximately 178 mm x 178 mm (7 x 7 ) of DenGlass sheathing, Typar building paper, and extruded expanded polystyrene insulation was removed at the midpoint of each of the rain-screen panel sections and the testing repeated. The weather seal was applied at the bottom of the panel. This testing was carried out to evaulate the effect 8
11 of applying the entire wind load across the rain-screen cladding portion of the mock-up assembly, which would represent a worst case in-situ scenario. For the testing, Novotechnik model TR-100 deflection transducers were installed on the test chamber structural members using magnetic clamps. Deflection was measured at the centre line of each rainscreen panel section to provide net mid-span deflection data. The panel was subjected to incrementally increasing pressure differentials of 50, 100, 200, 300, 400, 500, 750, 100, 1500, 2000, 2500, and 3000 Pa in the positive (inward) direction and the corresponding deflection measurements were recorded. The same procedure was employed in the negative (outward) direction. All pressure and deflection data was continuously logged using the Omega OM-DAQPRO-5300 data logger at a rate of one (1) reading per second. Trow first conducted the load testing on the intact sample (i.e., DensGlass sheathing and Typar intact). The load testing was then conducted with the pressure applied directly to the rain-screen portion of the panel sample at all pressure differentials in both directions. Trow conducted structural blow-out testing by subjecting the sample to increasing pressure differential in the negative (outward) direction. The pressure differential was increased until the sample either achieved blow-out failure or exceeded the maximum capacity of the blower. The results of the wind load resistance tests are outlined in Tables 3.4.1, 3.4.2, and subsequent graphs. Table 3.4.1: Results of Resistance to Wind Load Testing (Total Panel) Test No. Test Pressure (Pa) Deflection at Mid-Span of Left-Side Panel (mm) Deflection at Mid-Span of Right-Side Panel (mm) Maximum Allowable (L/175) (mm) max = 3.52 Res < max = 5.63 Res = 0.05 max = 2.97 Res = 0.13 max = 5.34 Res = 0.07 max = Res < max = Res < Table 3.4.2: Results of Resistance to Wind Load Testing (Rain-Screen Panel) Test No. Test Pressure (Pa) Deflection at Mid-Span of Left-Side Panel (mm) Deflection at Mid-Span of Right-Side Panel (mm) Maximum Allowable (L/175) (mm) max = 1.46 Res < max = 2.54 Res = 0.39 max = 1.49 Res = 0.07 max = 2.57 Res = 0.37 max = Res < max = Res < Based on an arbitrary value of 0.1% of the span of the member. 9
12 Acrytec Panel Industries: ACRY- NC GFRC Rainscreen Panel Positive Wind Load vs Deflection Left Rainscreen Panel Right Rainscreen Panel Total Assembly Linear (Left Rainscreen Panel) Linear (Right Rainscreen Panel) Linear (Total Assembly) Net Mid- Span Deflection (mm) Total Assembly = ΔP R² = Net Residual Deflection = mm Left (Mechanically & Adhesive Fastened) Panel = ΔP R² = Net Residual Deflection = mm Right (Mechanically & Adhesive Fastened) Panel = = ΔP R² = Net Residual Deflection = mm Pressure Differential (Pascals) Acrytec Panel Industries: ACRY- NC GFRC Rainscreen Panel Negative Wind Load vs Deflection 10 Left Rainscreen Panel Right Rainscreen Panel Total Assembly Linear (Left Rainscreen Panel) Linear (Right Rainscreen Panel) Linear (Total Assembly) Net Mid- Span Deflection (mm) Total Assembly = ΔP R² = Net Residual Deflection = mm Left (Mechanically Fastened) Panel = ΔP R² = Net Residual Deflection = mm Right (Mechanically Fastened) Panel = ΔP R² = Net Residual Deflection = mm Pressure Differential (Pascals) 10
13 Table 3.4.3: Negative Wind Load Testing Pressure Distribution P Wall (Pa) P rainscreen (Pa) P rainscreen (%) % % % % % % % % % % % Table provides an account of the pressure differentials across the rain-screen versus those applied across the entire mock-up wall assembly. This table indicates that under essentially static wind loading, the pressure across the rain-screen does not exceed 1% of the total wind load applied across the wall. While this may suggest that the rain-screen panel does not experience in-situ wind loading, this is not the case. Actual wind loading on the rain-screen will be dynamic in nature and will be dependent on a number of variables including the performance attributes of the back-up wall (substrate) and the rain-screen installation method. At the conclusion of each test, a visual examination of the panel was carried out. The results of the examination for all test configurations may be summarized as follows: For the testing conducted on the whole wall assembly: A visual review of the wall assembly revealed no damage or permanent deformation of the wall assembly (or any of its components) which would impair its intended function. The net residual deformation recorded on the exterior surface of the Acry-NC Series NC- 25 (Insulated) panel, within five (5) minutes after loads shown in the tables and graphs were removed, were less than 0.1% of the mid-span centerline span. For the testing conducted on the Acry-NC (Cladding) portion of the wall assembly: For the adhesive/mechanically fastened rain-screen portion of the wall panels, a visual review of the subject rain-screen panels revealed no damage or permanent deformation of the Acry-NC Series NC-25 panels or wall assembly (or any of its components) which would impair its intended function. The net residual deformations recorded on the exterior surface of the Acry-NC Series NC-25 panel, within five (5) minutes after loads shown in the tables and graphs were removed, were less than 0.1% of the mid-span centerline span for each panel. 11
14 The results of the wind load testing clearly demonstrate that the adhesive/mechanically fastened ACRY-NC Series NC-25 rain-screen panel assembly has the lone capacity to resist the full loads employed for the testing without exhibiting excessive deformation during live loading or permanent deformation upon release. Accordingly, within the load conditions employed for testing, Trow is of the view that the ACRY- NC Series NC-25 (Insulated) adhesive/mechanically fastened rain-screen panel meets the intent of the OBC with respect to resistance to wind load Wind Load Resistance to Blow-Out (Ultimate Load) The Wind Load Resistance to Blow-Out testing was again carried out in accordance with the procedures outlined in ASTM E330, Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. In this case, testing was conducted to the more severe condition of, negative wind loads directly applied across the adhesive/mechanically fastened rain-screen panel sections alone. As previously stated, this testing was employed to evaluate the effect of applying the entire wind load across the rain-screen cladding portion of the mock-up assembly, which would represent a worst case in-situ scenario. The results of the blow-out testing are given in the following graph and subsequent discussion. At an approximate negative wind load of 7.88 kpa the right side rain screen panel cracked vertically and was permanently damaged, resulting in a loss of chamber pressure. A post test examination of 12
15 the panel did not reveal evidence of any other damage to the ACRY-NC Series, NC 25 GFRC rainscreen cladding. In addition, the cladding did not detach from the substrate supports and remained in place on the sample wall. Again, within the load conditions employed for the blow-out (i.e, ultimate load) testing, Trow is of the view that the adhesive/mechanically fastened ACRY-NC Series NC-25 (Insulated) rain-screen panels meet the intent of the OBC with respect to resistance to wind load. 3.5 Surface Burning Characteristics The Acry-NC Series base panel is a non-combustible glass fibre reinforced cement board to which an architectural acrylic coating is applied. To establish the surface burning charicteristics of the finished Acry-NC Series rain-screen panel, Flame Spread and Smoke Developed Classifications based upon triplicate testing was conducted in accordance with CAN/ULC-S This testing was carried out by Exova and a copy of their report outlining the test methodoloy and results has been provided in Appendix B of this report. As stated in the Exova report, The method, designated as CAN/ULC-S102-07, Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies, is designed to determine the relative surface burning characteristics of materials under specific test conditions. Results of less than three identical specimens are expressed in terms of Flame Spread Value (FSV) and Smoke Developed Value (SDV). Results of three or more replicate tests on identical samples produce average values expressed as Flame Spread Rating (FSR) and Smoke Developed Classification (SDC). In this case, testing was carried out in triplicate to establish FSR and SDC values for the Acry-NC Series panels. The Acry-NC samples provided to Exova were labelled Exterior Cladding Panel System (Red). From the Exova report: Table 3.5.1: Summary of Results Surface Burning Characteristics. Rounded Average Flame Spread Rating (FSR): 20 Test No. FSV SDV Average: Rounded Average Smoke Developed Classification (SDC): 35 13
16 4. Conclusion Based on the result of the result of the testing carried out on the, Acry-NC NC-25 Insulated rain-screen cladding panel Trow concluded: The ACRY-NC Series NC-25 (Insulated) rain-screen functions as an effective rainscreen cladding with respect to resistance to wind driven rains. Testing indicates that when installed on a suitable back-up wall, such as that described in this report, the rain-screen assembly successfully prevents interstitial and indoor water penetration under driving rain wind pressure up to 700 Pa. This performance level exceeds the anticipated requirements for low and high-rise buildings in excess of fifty-stories given in the current Ontario Building Code Regulation. The ACRY-NC Series NC-25 (Insulated) rain-screen panel assembly, mechanically and adhesive fastened to a suitable back-up wall as described in this report, successfully resists full wind loads up to 7.88 kpa. That is, the testing indicates that the rain-screen cladding assembly successfully resists deformation and remains in place when the subject positive and negative pressures are applied solely across the rain-screen panel. The recorded net mid-span deflections are well below the anticipated requirements for cladding systems employed for low rise and many highrise buildings given in the current Ontario Building Code Regulation. For the subject rain-screen panels, the levels of deflection measured under load were also below those required to cause cracking of the base GFRC boards employed for the Acry-NC Insulated rain-screen panel. The ACRY-NC Series (Insulated) rain-screen panels are non-combustible and have suitable Surface Burning Characteristics to meet OBC requirements for use as an exterior cladding material for low and high-rise buildings for both combustible and non-combustible construction, with a rounded Average Flame Spread Rating (FSR): 20, and a rounded Average Smoke Developed Classification (SDC): 35. Trow Associates Inc. Renny Chung, B. Eng., LEED AP Façade Engineering Group Building Engineering Team (BET) Greg Hildebrand, C.E.T., M.Sc. (Eng.) Head, Façade Engineering Group Building Engineering Team (BET) 14
17 ACRY-NT (GFRC) Rainscreen Cladding Panel System Appendix A: Test Sample Drawing
18
19 ACRY-NT (GFRC) Rainscreen Cladding Panel System Appendix B: Exova Report No (A)
20 ELECTRONIC DRAFT COPY CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" A Report To: Acrylic Panel Industries 20 Floral Parkway, Unit B Concord, Ontario L4K 4R1 Phone: (905) [email protected] Attention: Chris Finlay Submitted by: Fire Testing Report No (A) 6 Pages Date: August 9, 2010
21 CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" Page 2 of 6 For: Acrylic Panel Industries Report No (A) ACCREDITATION To ISO/IEC for a defined Scope of Testing by the Standards Council of Canada SPECIFICATIONS OF ORDER Determine the Flame Spread and Smoke Developed Classifications based upon triplicate testing conducted in accordance with CAN/ULC-S102-07, as per Trow P.O. # BR and Exova Quotation No RV1 accepted July 6, Exova SAMPLE IDENTIFICATION (Exova sample identification number S0495-1) Exterior cladding panel system, identified as: "Red". TEST PROCEDURE The method, designated as CAN/ULC-S102-07, "Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies", is designed to determine the relative surface burning characteristics of materials under specific test conditions. Results of less than three identical specimens are expressed in terms of Flame Spread Value (FSV) and Smoke Developed Value (SDV). Results of three or more replicate tests on identical samples produce average values expressed as Flame Spread Rating (FSR) and Smoke Developed Classification (SDC). Although the procedure is applicable to materials, products and assemblies used in building construction for development of comparative surface spread of flame data, the test results may not reflect the relative surface burning characteristics of tested materials under all building fire conditions. SAMPLE PREPARATION For each test, the samples consisted of 3 sections of material, each approximately 533 mm in width by 2438 mm in length by 16 mm in thickness. The sections were butted together to form the requisite specimen length. Prior to testing, the samples were conditioned at a temperature of 23 ± 3 C and a relative humidity of 50 ± 5%. During testing, the samples were self-supporting. The testing was performed on: Test #1: Test #2: Test #3: SUMMARY OF TEST PROCEDURE The tunnel is preheated to 85 C, as measured by the backwall-embedded thermocouple located 7090 mm downstream of the burner ports, and allowed to cool to 40 C, as measured by the backwall-embedded thermocouple located 4000 mm from the burners. At this time the tunnel lid is raised and the test sample is placed along the ledges of the tunnel so as to form a continuous ceiling 7315 mm long, 305 mm above the floor. The lid is then lowered into place.
22 CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" Page 3 of 6 For: Acrylic Panel Industries Report No (A) SUMMARY OF TEST PROCEDURE (continued) Upon ignition of the gas burners, the flame spread distance is observed and recorded every 15 seconds. Flame spread distance versus time is plotted, ignoring any flame front recessions. Calculations are based on comparison with flame spread characteristics of select red oak, determined in calibration trials and arbitrarily established as 100. If the area under the curve (A) is less than or equal to 29.7 m min, FSV = 1.85 A; if greater, FSV = 1640/(59.4-A). The Smoke Developed Value is determined by comparing the area under the obscuration curve for the test sample to that of inorganic reinforced cement board and red oak, established as 0 and 100, respectively. Exova TEST RESULTS SAMPLE FSV SDV "Exterior Cladding Panel System (Red)" Test # Test # Test # Average: Rounded Average Flame Spread Rating (FSR): 20 Rounded Average Smoke Developed Classification (SDC): 35 Observations of Burning Characteristics - The samples ignited approximately 2 to 2.5 minutes after exposure to the test flame. - The flame fronts advanced to maximum distances of 1.5, 1.4 and 1.5 metres at approximately 4, 4, and 4.5 minutes into each respective test. - Smoke Developed and temperature were recorded during the tests (see accompanying charts). Note: This is an electronic copy of the report. Signatures are on file with the original report. Robert A. Carleton, Fire Testing. Ian Smith, Fire Testing. Note: This report and service are covered under Exova Canada Inc. Standard Terms and Conditions of Contract which may be found on the Exova website ( or by calling
23 CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" Page 4 of 6 For: Acrylic Panel Industries Report No (A) Sample:"Exterior Cladding Panel System (Red)" Exova Test #1 of 3 6 FLAME SPREAD Flame Spread in Metres Red Oak (FSV=100) Sample Time in Minutes % Light Absorption SMOKE DEVELOPED Red Oak (SDV=100) 80 Sample Time in Minutes 400 TEMPERATURE Temperature ( C) Time in Minutes FSV SDV 20 34
24 CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" Page 5 of 6 For: Acrylic Panel Industries Report No (A) Sample:"Exterior Cladding Panel System (Red)" Exova Test #2 of 3 6 FLAME SPREAD Flame Spread in Metres Red Oak (FSV=100) Sample Time in Minutes % Light Absorption SMOKE DEVELOPED Red Oak (SDV=100) Sample Time in Minutes 400 TEMPERATURE Temperature ( C) Time in Minutes FSV SDV 18 34
25 CAN/ULC-S102 Surface Burning Characteristics of "Exterior Cladding Panel System (Red)" Page 6 of 6 For: Acrylic Panel Industries Report No (A) Sample:"Exterior Cladding Panel System (Red)" Exova Test #3 of 3 6 FLAME SPREAD Flame Spread in Metres Red Oak (FSV=100) Sample Time in Minutes SMOKE DEVELOPED % Light Absorption Red Oak (SDV=100) Sample Time in Minutes 400 TEMPERATURE 300 Temperature ( C) Time in Minutes FSV SDV 19 37
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE Report to: Ceramitex Inc. 520 Clarke Rd. London, Ontario
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
Window Sill Details for Effective Drainage of Water
Construction Technology Update No. 76 Window Sill Details for Effective Drainage of Water By M.A. Lacasse and M.M. Armstrong Satisfactory window performance demands a good product and proper installation.
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
The better way to build TM. Installation Manual. EXTERIOR WALL SIPs
The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual
BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building
Architectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.
ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
PERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
The Case for Cross Laminated Timber: Part 2
Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
7 INNOVATIONS IN SECONDARY DRAINAGE SYSTEMS
7 INNOVATIONS IN SECONDARY DRAINAGE SYSTEMS K. F. YAROSH Dow Corning S.A., Parc Industriel-Zone C, B-7180 Seneffe, Belgium SUMMARY: This paper will review innovative internal backup secondary drainage
Confort 26. Sliding Systems. Sapa Building System
Confort 26 Sliding Systems Sapa Building System Confort 26 is Sapa s thermally insulated sliding system for windows and doors. Available as two- and three-rail solution. Among its features, there are
Guidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
WINDOW INSTALLATION GUIDE
WINDOW INSTALLATION GUIDE is not responsible for or liable for any use or misuse of the information contained in this window installation guide. Window Installation Guide This guide provides basic information
EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
AUTHORIZATION TO MARK
AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
WHI 90-Minute Rated Veneered Door Frame Installation Instructions
No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,
SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION
SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION 2.0: OCTOBER 14, 2008 October 14, 2008 Client: Attn: Subject:
10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions
Y Parts Included: Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Tools Required: Power Driver Drill Bit (Determined by fastener) Driver Bit (Determined by fastener)
Evaluation Report CCMC 13278-R MemBrain
Evaluation Report CCMC 13278-R MemBrain MasterFormat: 07 26 10.01 Issued: 2007-06-27 Re-evaluation: 2016-07-19 Re-evaluation due: 2019-06-27 1. Opinion It is the opinion of the Canadian Construction Materials
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1826 Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT. awipanels.com From freezing, sub-zero temperatures to Contents dry heat or high humidity, Mother Nature continually tests the limits of building envelopes. That's
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing Schluter -KERDI-BOARD The universal substrate for tiles Flat. Level. Plumb. Square. No matter the quality, cost, or extravagance of
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING IMPORTANT NOTICES AND INFORMATION Read these instructions in their entirety prior to installing windows. Any local building code requirements
The Optimum Basement Wall
The Optimum Basement Wall Solutions to the Wet Blanket Basement Problem February 27 th, 2014 1 Adapting to Change! We ve made significant advances in water management. Customers no longer accept that musty
LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council RETAINED ON U.S.
ICC-ES Legacy Report ER-5043* Reissued March 2004 www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code DIVISION: 09
TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.
Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.
TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40
TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Superform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
Product Information. Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: [email protected]
Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: [email protected] Product Information 6320-2 Danville Rd. Mississauga, Ontario Canada L5T 2L7 TABLE OF CONTENTS Sheet Product Alusion Sheet Products.......................................................
Discipline: Structural Issued 04-26-06
California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This
TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
The WANZ Guide to Window Installation
The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
How To Control Water Penetration In A Window
WATER PENETRATION CONTROL FOR WINDOWS A SERVICE LIFE APPROACH David R. Ricketts, P.Eng. 1 and Silvio Plescia, P.Eng. 2 INTRODUCTION Building envelope performance problems and their close link to poor window
WINDOW PANNING AND TRIMS
OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.
PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
CONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
Gypsum Board Systems Manual
CertainTeed Gypsum Board Systems Manual Fire Resistance and Sound Control Design Manual Division 09 GYPSUM BOARD SYSTEMS MANUAL TABLE OF CONTENTS Introduction General Fire Resistance...1 Sound Control...3
City of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
Guidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten