Insertion Losses of Fiber Optical Connectors
|
|
|
- Kelley Parks
- 10 years ago
- Views:
Transcription
1 Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions
2 Table of contents 1 Origins of Insertion Losses of Optical Connectors 3 2 Specification of Insertion Losses 4 3 Measurement of Insertion Losses Origins of Measurement Errors Influence of Measurement Errors Influence of Reference Plug Quality Assurance at HUBER+SUHNER AG 9 4 Reference Power Measurement IEC Method B IEC Method C 11 5 Optical Time-Domain Reflectometry (OTDR) Bidirectional OTDR Measurement Accuracy of OTDR Measurement Unidirectional Multimode Measurement 14 6 Recommendations at Increased Losses 15 HUBER+SUHNER Excellence in Connectivity Solutions 2
3 1 Origins of Insertion Losses of Optical Connectors Fiber-optic connections usually consist of two connectors which are plugged in an adaptor. The major part of the connector is the ferrule in which the optical fiber is glued. Two ferrules are aligned in a so-called sleeve which is part of the adaptor. The insertion losses of fiber-optic connections are determined by the following parameters 1 : Origins of insertion losses Lateral misalignment of the fiber core Angular offset Mode-field diameter of the fibers Operating wavelength Origins of lateral misalignment Practical experience showed that lateral misalignment of the fiber core is by far the most important parameter 2. The origins of misalignment can be split in two causes. The first cause is the excentricity of the fiber core which means that the core is not exactly positioned at the center of the ferrule. These deviations come from manufac-turing tolerances of fibers and ferrules. The second cause are small alignment errors of the ferrules within the sleeve. These errors are consequences of the tolerances of the ferrule diameter and of the sleeve. Excentricity and ferrule alignment Sleeve alignment Ausrichtung im Sleeve Exentricity of fiber core Exzentrizität des Faserkerns 1 D. Marcuse, Loss Analysis of Single-Mode Fiber Splices, Bell System Tech. Journal, Vol. 56/6, This is especially valid for fiber-optic connectors with ceramic ferrules. HUBER+SUHNER Excellence in Connectivity Solutions 3
4 2 Specification of Insertion Losses Insertion losses of a class of fiber-optic connections are characterized by loss distributions. The manufacturer specifies the distribution in data sheets of fiber-optic connectors. The distribution of the insertion loss primarily depends on the distribution of the excentricities and the distribution of the alignment errors of the ferrule within the sleeve. The sum of these distributions results in the distribution of the insertion losses. Distribution of excentricity + Distribution of alignment = Distribution of losses The distribution of insertion losses is mainly specified by an average value and a 97% percentile. The 97% percentile means that out of 100 connections (assuming random mating of different connectors and adaptors) 97 connections have insertion losses smaller than the percentile value. The remaining three connections have losses larger than the percentile value. For instance, the distribution of the 0.1dB connection class of HUBER+SUHNER AG has a specified average value of 0.06dB and a 97% percentile of 0.15dB. In general, for all classes of connectors, the insertion losses of three percent of all connections can exceed the 97% percentile. These connections are fully within the specifications and are no quality defects. A single measurement is not significant for the performance of a connection class. Average value and 97% percentile specify the performance of the connection class 0.1dB connection class: 97% of IL values are smaller than 0.15dB Single measurements have no significance HUBER+SUHNER Excellence in Connectivity Solutions 4
5 HUBER+SUHNER AG guarantee for all delivered connectors and adaptors (out of a performance class) the specified distribution of the insertion losses. In case of external quality inspection, the customer has to measure the loss distribution of a sufficiently large quantity of connectors and adaptors (!) out of the same perform-ance class. Only deviations of the loss distribution indicate defective quality. Loss distribution specifies the performance of a connection class. 3 Measurement of Insertion Losses The measurement of insertion losses has to be performed carefully since various sources of statistic and deterministic errors can deteriorate the measurement result. Origins of measurement error Nominal value + Measurement error = Measurement result HUBER+SUHNER Excellence in Connectivity Solutions 5
6 Note that an insertion loss can not be assigned to a single connector. It is only possible to measure the insertion loss of a connection consisting of two connectors and one adaptor. 3.1 Origins of Measurement Errors In practice a large variety of measurement errors occur. By careful implementation of the measurement many of these errors can be avoided, however, some errors can not be prevented. Even under highest accurateness, the measurement is influenced by minimum errors of ±0.1 db (3σ). In the following, the different sources of errors are listed: Connection Usage of deficient connectors as reference connectors Usage of deficient adaptors Contamination of the fiber end-faces Contamination of the inner surface of the sleeve or of the outer surface of the ferrule. Scratches on the end-face Light source Power stability of the source Wavelength stability of the source Optical launch conditions for multimode measurements Power meter Accuracy of measurement and display accuracy Contamination of connector or sensor Illumination of the measurement sensor (photo diode) Influence of temperature Influence of polarization Cable Losses in measuring line (relevant at long distances, e.g. 0.3dB loss/km) Minimum bending radius HUBER+SUHNER Excellence in Connectivity Solutions 6
7 Measurement of power reference Stability of measurement setup (influence of temperature, etc) Systematic error caused by additional connection within measuring line ( IL 0.1dB) Method of measurement Power measurement with reference IEC method B Most accurate method since single connection can be measured. Power measurement with reference IEC method C Systematic error caused by additional connection within measuring line. OTDR measurement for obtaining reliable measurement results a careful bidirectional measurement is essential. Possible sources of errors are manifold (cf. 5). 3.2 Influence of Measurement Errors The measurement of insertion losses can be deteriorated by various errors (cf. 3.1). The sum of the negative influences can only be minimized by careful implementation of the measurement within a controlled environment and by using calibrated precision instruments. However, even under best conditions, it is difficult to achieve an accuracy better than ±0.1dB. In practice, measurement accuracy is max. ±0.1dB. Loss distribution is affected. This means that a loss of nominal 0.25dB can yield measurement results between 0.15dB and 0.35dB. Under a less controlled environment or with less precise measurement methods (e.g. OTDR), the spread can be considerably larger. When measuring losses of the 0.1dB connection class, the measurement error is equally large as the value to be measured. A precise measurement is hardly possible any more. If the customer performs a quality inspection of the 0.1dB class, the loss distribution has to be measured. However, as a result of the measurement error the loss distribution may be such strongly biased that the measurement has no signifi-cance any more. In that case, a larger amount of single measurement results yield values above 0.1dB although the products themselves fulfill the specifications. 0.1dB connection class: Measurement error is equally large as value to be measured. HUBER+SUHNER Excellence in Connectivity Solutions 7
8 3.3 Influence of Reference Plug The excentricity of the fiber core within the ferrule varies statistically. If a connector is randomly chosen out of a multitude, in the worst case, the excentricity can be almost out of specifications. When using such a connector within an adaptor, the connec-tion suffers from increased losses. Frequency Excentricity Connector Example of an extreme case of ferrule excentricity Distribution in m If such an unfavorable connector is used as reference plug within a measurement, the measurement yields increased losses even though the second connector (to be measured) is within specifications. The result is falsified by the reference plug. Note, not only single measurement results are falsified but the entire loss distribution. Reference plugs can deteriorate the measurements. For absolutely correct determination of the performance of a connection class, each measurement needs to be performed with different reference plugs. Only under such circumstances the reference plug features the nominal variance which is required for obtaining the correct loss distribution. However, this approach is not practicable by what the reference plug needs to be selected carefully. An unfavorable as well as a best choice of a reference plug affect adversely the measurements. The basic problem is that a single connector can never be characterized but only a pair of connectors within an adaptor. Additionally, a single connection can never character-ize the performance of a class of connectors. Only the loss distribution of a variety of connectors is significant. Proper choice of the reference plug is important for the quality of the measurement A contaminated or scratched reference plug can deteriorate the measurement result considerably. The same is valid for adaptors with worn or contaminated sleeves. HUBER+SUHNER Excellence in Connectivity Solutions 8
9 3.4 Quality Assurance at HUBER+SUHNER AG How can HUBER+SUHNER AG guarantee the quality? The optical performance, i.e. the insertion loss, of each single connector is measured in production before delivery to the customer. A 100% quality inspection is per-formed. The end-control measurement is subject to an error of maximum ±0.1dB. Huber+Suhner AG perform 100% endquality inspection. For fully ensuring the specified quality and performance, all fibers, ferrules, and sleeves undergo a detailed receiving inspection. By means of mathematical models, the insertion losses can be determined accurately from the geometrical deviations of the components. This means the insertion loss is additionally measured by this indirect method. The comparison of the indirectly measured losses with the direct results guarantees the reliable and consistent quality of the products. Manufacturer guarantees performance by direct and indirect measurement. HUBER+SUHNER AG are a high-quality manufacturer of optical connectivity solutions. The company ever tries the best to deliver the highest quality for the satisfaction of the customer. 3 Die Messgenauigkeit von ±0.1dB (3σ-Wert) unter Produktionsbedingungen wird durch Vergleichsmessungen durch akkreditierte Schweizer Test und Kalibrationslabors sichergestellt. HUBER+SUHNER Excellence in Connectivity Solutions 9
10 4 Reference Power Measurement The most reliable method for determining the insertion loss is the comparison of a power reference P0 to a measured power P1, Insertion loss IL [db] = -10 log P 1 / P 0. The IEC norm describes in detail the correct implementation of the measurement. Amongst others, (1) a correct illumination of the fiber, (2) the usage of calibrated high-precision instruments, and (3) a one-hour thermal stabilization of the measurement setup are stringent requirements demanded by IEC. Correct implementation of the measurement according to IEC. 4.1 IEC Methode B A source (S) launches light into the fibers and mode filters (mf) guarantee the correct launch conditions. For measuring of the reference power P 0, the reference plug (RP) is directly attached to the power meter 4 (D). In a next step, the connector to be measured (DUT) is connected to the reference plug and power P 1 is measured. Method B measures the insertion loss between the reference plug (RP) and the test connector (DUT). Method B of IEC norm is the most accurate and most reliable measurement. This method yields the most accurate and reliable measurement results of insertion losses of a single connection. In case that other measurement methods (e.g. OTDR) result in differing losses, the more reliable results of method B have to be preferred 5. 4 The connector attached to the power meter (D) causes no additional losses provided that the power sensor is sufficiently large to detect the entire light. 5 Presumed that all measurements are performed with the same accurateness. HUBER+SUHNER Excellence in Connectivity Solutions 10
11 4.2 IEC Methode C In many cases, the cable to be measured can not be attached directly to the power meter (D). In this case, measurement method C has to be used. The reference setup for measuring P 0 includes a test cable with an additional connection. Subsequently, the cable to be measured (DUT) is inserted between the reference plugs (RP) to measure the power P 1. Note that the losses of two connections are measured simultaneously. The corresponding losses of the individual connectors can not be extracted. To obtain more accurate results the measured loss can be corrected by the (assumed) average value of the second connection. However, the level of inaccuracy is significantly increased compared to method B. Method C of IEC norm measures two connections simultaneously. This measurement is not an adequate method to accurately determine the insertion loss of a single connection. Nevertheless, if method C is used, the measurement error is increased by the insertion loss (>0.1dB) of the second connection. This method is mainly used to inspect the losses of pre-installed cables. In that case, an additional source of error is the physically separated measurement of the reference and of the DUT (influence of temperature, thermal stabilization, etc.). HUBER+SUHNER Excellence in Connectivity Solutions 11
12 5 Optical Time-Domain Reflectometry (OTDR) Optical Time-Domain Reflectometry performs not a direct measurement of insertion losses but is an estimation of the losses based on the back-scattered light 6. This method yields less accurate and less reliable results as compared to power meter measurement. A prerequisite for performing an OTDR estimate of losses is that exactly the same optical fiber is deployed in the entire line. As compared to practice, it is often the case that different types of optical fibers are installed. Already marginal differences in the effective refractive indices or of the core diameter can result in considerable errors (>0.5dB) at unidirectional measurements. Hence, single-ended OTDR tests yields unusable results 7. Renowned manufacturers of OTDR equipment (e.g., EXFO 8 ) emphasize the importance of bidirectional measurements for singlemode fibers. OTDR is not a direct measurement but an estimation. Single-ended tests yield wrong results. Although fibers delivered by different manufacturers or by different shipments are fully within specifications, minor tolerances and deviations always exist. These differences are sufficient to cause significant errors at single-ended OTDR tests. 5.1 Bidirectional OTDR Measurement The IEC Norm and manufacturers of OTDR equipment stringently demand a bidirectional measurement for singlemode fibers. Additional fiber sections L1 and L2 at sufficient length have to be used in order to overcome the attenuation dead zone of the instrument. A correct implementation of the bidirectional measurement yields reliable results. A unidirectional is an incorrect method generating unaccept-able errors. IEC and renowned manufacturers stringently require bidirectional OTDR measurements for singlemode fibers. In practice, unidirectional OTDR measurements are sometimes used due to cost saving or lack of expertise. However, single-ended tests are only able to detect sizeable errors within the network but can not be used for quality inspection of connectors or similar. 6 The so-called Rayleigh scattering is the origin of fiber attenuation 7 D. Eberlein, Lichtwellenleiter-Technik, Espert Verlag, 5. Auflage, C. Hamel, Bidirectional OTDR Testing: Multimode vs. Singlemode Fibers, EXFO Application Note 043. HUBER+SUHNER Excellence in Connectivity Solutions 12
13 5.2 Accuracy of OTDR Measurement The accuracy of the measurement depends on the so-called signal-to-noise ratio (SNR), which is influenced by the setting parameters of the instrument. A sub-optimum setting of the parameters results in poor SNR and large measurement errors 9. Since the measurement is not always performed by qualified personnel, modern instruments support choosing the optimum settings of parameters. The accuracy of an OTDR measurement depends on the instrument settings. Pulse Width: Short pulses increase the spatial resolution and can detect more accurately events. In contrast, the poorer SNR of short pulses decreases the accuracy. Averaging: Averaging of consecutive measurements increases the SNR. Hence, for maximum accuracy as many measurements as possible should be averaged. For optimum results, EXFO recommend an average time of three minutes at each measurement 10. Bandwidth and Sampling Rate: These parameters, which vary from instrument to instrument, determine to a large extent the quality of the measurement. Hand-held instruments feature usually inferior accuracies than lab instruments. Linearity: Modern instruments have a specified linearity of 0.05dB/dB. This means that a nominal attenuation of 1dB can be measured with an accuracy of 0.05dB. The displayed valued may vary between 0.95dB and 1.05dB. OTDR is not a direct measurement of the insertion loss but an estimation based on statistics and mathematical models. OTDR instruments may display the measurement results with an accuracy of 0.01dB. Note, the display accuracy has no relation to the measurement accuracy which is the crucial factor. 9 C. Hamel, J. Barnard, Optimizing OTDR Measurement Parameters, EXFO Application Note P. Talbot, C. Hamel, M.-C. Michel, OTDR and OLTS: Two different Tools for Specific Needs, EXFO Application Note 026. HUBER+SUHNER Excellence in Connectivity Solutions 13
14 5.3 Unidirectional Multimode Measurement An OTDR measurement of multimode fibers relies on different principles than a measurement of singlemode fibers. The measurement strongly depends on the distribution of the optical modes within the fiber. For that reason the accuracy of the measurement is lower and the reproducibility worse. In contrast to singlemode, unequal fibers have only a marginal impact on the result. Additionally, multimode losses depend on the direction of light propagation, hence the benefits of bidirec-tional measurements are reduced. OTDR measurements for multimode fibers are performed unidirectional. Only for multimode fibers a unidirectional measurement is correct. HUBER+SUHNER Excellence in Connectivity Solutions 14
15 6 Recommendations at Increased Losses At the technical approval of installed networks or at customer quality inspection the insertion losses of the fiber optic connection (cable and connectors) are verified. At the occurrence of increased losses the following procedure is recommended. The technician who performed the measurements needs to find out the origins of the increased losses. The following questions needs to be answered. Origin 1 Measurement method 2 Plugged Connection Measurement of increased losses Proper measurement method used? Sufficient accuracy of measurement? Errors minimized? Equipment calibrated? yes Connectors and adaptors cleaned? Connectors properly plugged? Same performance class of connectors used? yes Check of the measurement method Check of the plugged connections 3 Splice Only for pigtails: Fibers properly spliced? Splice precision sufficient? Splice equipment maintained according manual? yes Check of splices Clarification of facts by manufacturer An essential requirement is the application of the proper measurement method and the usage of accurate measurement equipment. Only if a sufficient measurement reliability and accuracy can be assured by the technician, this origin of errors can be excluded. A second step needs to check whether the fiber optic connection is properly installed. All plugged connectors and adaptors needs to be clean, the minimum bending radii are maintained, and no cable damages exist. Thirdly, if pigtails are used, the quality of all splices needs to be assured. In case of doubt, the spliced have to be renewed. If all previous reasons for increased losses can explicitly be excluded, it is recommenced to contact the manufacturer for clarification. HUBER+SUHNER Excellence in Connectivity Solutions 15
16 HUBER+SUHNER AG Fiber Optics 9100 Herisau, Switzerland Phone +41 (0) Fax +41 (0) HUBER+SUHNER Excellence in Connectivity Solutions 16
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications
Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements
Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces
Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces WP1281 Issued: November 2015 Supersedes: 2012 Author: Dr. Russell Ellis ISO 9001 Registered Background
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
Module 13 : Measurements on Fiber Optic Systems
Module 13 : Measurements on Fiber Optic Systems Lecture : Measurements on Fiber Optic Systems Objectives In this lecture you will learn the following Measurements on Fiber Optic Systems Attenuation (Loss)
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
Compatibility of Bend Optimized Multimode Fibers White Paper. Issued September 2009
Compatibility of Bend Optimized Multimode Fibers White Paper Issued September 2009 Optimized Low Bend for the Use of Fibers In The Home The current migration of optical fibers closer to and even into the
Accurately Testing fibre Optic Cables
Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty
Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices
Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether
INSERTION-LOSS MEASUREMENT ACCURACY FOR FIBER-OPTIC COMPONENTS AN ANALYSIS
INSERTION-LOSS MEASUREMENT ACCURACY FOR FIBER-OPTIC COMPONENTS AN ANALYSIS Christopher T. Allen Ralph D. Taylor James R. Stone DIT-MCO International INSERTION-LOSS MEASUREMENT ACCURACY FOR FIBER-OPTIC
MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths
Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber
Presented at NOC/EC 2000 Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber Mary Adcox, Optical Fiber, Corning Incorporated As non-zero dispersion-shifted
SPLICE LOSS IN NON-ZERO DISPERSION-SHIFTED FIBERS
SPLICE LOSS IN NON-ZERO DISPERSION-SHIFTED FIBERS Mary E. White Sheila A. Cooper Corning Incorporated Corning, New York ABSTRACT As non-zero dispersion-shifted fibers (NZ-DSF), and the more recently introduced
Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing
Field Measurements of Deployed Fiber
Field Measurements of Deployed Fiber Robert J. Feuerstein Level 3 Communications, 1025 Eldorado Boulevard, Broomfield, Colorado 80021 [email protected] Abstract: New generations of ultra-long
FIBER OPTIC SYSTEM TEST PROCEDURES
FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not
Fiber Optic Specifications
Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry
Loss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
Why Expanded Beam types are essential in military and other harsh environment applications
White paper Fiber Optic Connectors Bliek 18 4941 SG RAAMSDONKSVEER NEDERLAND Telephone: +31 162 518 208 Fax: +31 162 518 216 E-mail: [email protected] Website: www.mcap.nl ABN-AMRO: 52.14.96.500 IBAN: NL28ABNA0521496500
M310 Data Center OTDR
Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
Optical Power Meter. Specification & User Manual
Optical Power Meter Specification & User Manual Page 1 of 9 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4
Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM
Testing and troubleshooting enterprise fiber-optic cabling Presenter: Neftali Usabal Fluke Networks - LATAM Agenda Testing Methods and Standards Why we test optical systems Terminology & types of testing
Measuring of optical output and attenuation
Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter
Plug - Type (Male/Female) Attenuators CAA series Singlemode
Plug - Type (Male/Female) Attenuators CAA series Singlemode Description: The plug-type singlemode attenuators are used directly on the ends of fiber optic jumpers prior to installation in adapters. These
USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION
USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION
spinner Measurement & Calibration equipment for network analyzers
spinner Measurement & Calibration equipment for network analyzers Edition B 2011 High Frequency Performance Worldwide www.spinner-group.com SPINNER test & calibration equipment for best measurement results
BLINK Triple-Play Connector
An innovative optical connector tailored to residential requirements forms the basis of the HUBER+SUHNER Fiber In The Home portfolio. Increased protection against soiling of the connector end surfaces,
What testing is required for PREMISES Fiber Optic Cabling and the standards used
Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic
What are Fibre Optics?
Fibre Optics Fibre Optics? Fibre optics (optical fibres) are the guiding channels through which light energy propagates. These are long, thin strands of very pure glass about the diameter of a human hair
APPLICATION NOTE POLARIZATION MEASUREMENTS
OZ OPTICS LTD. APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS FAMILY OF POLARIZATION MAINTAINING COMPONENTS, SOURCES, AND MEASUREMENT SYSTEMS The information/data furnished in this document shall
Attaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
How To Read A Fiber Optic Sensor
2572-17 Winter College on Optics: Fundamentals of Photonics - Theory, Devices and Applications 10-21 February 2014 Optical Fiber Sensors Basic Principles Scuola Superiore Sant'Anna Pisa Italy Optical Fiber
Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
HoW confident are You about Your connector cleanliness?
HoW confident are You about Your connector cleanliness? Vincent Racine, Product Line Manager, Francis Audet, Advisor, CTO Offi ce, François Marcotte, Senior Technical Sales Specialist Gwennaël Amice, Senior
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
E190Q Lecture 5 Autonomous Robot Navigation
E190Q Lecture 5 Autonomous Robot Navigation Instructor: Chris Clark Semester: Spring 2014 1 Figures courtesy of Siegwart & Nourbakhsh Control Structures Planning Based Control Prior Knowledge Operator
An advanced Dark Fiber Monitoring System for Next Generation Optical Access Networks
An advanced Dark Fiber Monitoring System for Next Generation Optical Access Networks Min Cen, Jiajia Chen, Véronique Moeyaert, Patrice Mégret and Marc Wuilpart 18th Annual Workshop of the IEEE Photonics
Fiber Characterization Service
About JDSU JDSU s verifies the integrity and capacity of your fiber plant through the measurement of key fundamental properties, such as attenuation, reflectance, and dispersion. Comprehensive testing,
Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems
SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING
DIAMOND AVIM Connector
DIAMOND AVIM Connector Fiber optic connector for space applications Dr. François CALOZ, accredited laboratory Frédéric TAUGWALDER, Engineering DIAMOND SA - OCT. 2005 - ATELIER CONNECTIQUE - CNES 1 Motivation
Cable Analysis and Fault Detection using the Bode 100
Cable Analysis and Fault Detection using the Bode 100 By Stephan Synkule 2014 by OMICRON Lab V1.3 Visit www.omicron-lab.com for more information. Contact [email protected] for technical support.
Simulation and Best Design of an Optical Single Channel in Optical Communication Network
International Arab Journal of e-technology, Vol., No., June 11 91 Simulation and Best Design of an Optical Single Channel in Optical Communication Network Salah Alabady Computer Engineering Department,
The following terms are defined within the context of the fiber optic industry
The following terms are defined within the context of the fiber optic industry Adapter A mechanical media termination device designed to align and join fiber optic connectors. Often referred to as coupling,
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
Technical Datasheet Scalar Network Analyzer Model 8003-10 MHz to 40 GHz
Technical Datasheet Scalar Network Analyzer Model 8003-10 MHz to 40 GHz The Giga-tronics Model 8003 Precision Scalar Network Analyzer combines a 90 db wide dynamic range with the accuracy and linearity
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
Items Supplied. Frequency. Designation Description / Delivery Unit Order Number
Fiber Optic Cleaver D6 For Single- and Multimode Fibers Diamond blade for highest cleave quality and long life (typically > 10,000 cleaves) Fiber cleave length: 3.5 to 15 mm Fiber diameter: 125 µm nominal
Robot Perception Continued
Robot Perception Continued 1 Visual Perception Visual Odometry Reconstruction Recognition CS 685 11 Range Sensing strategies Active range sensors Ultrasound Laser range sensor Slides adopted from Siegwart
DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)
Features: DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) PATENT NUMBERS: CANADA 2,494,133, USA 7095931, 7295731 AND CHINA 1672073 Telcordia GR-468 qualified Available in versions for any wavelength
Live Fiber Monitoring in CWDM Networks
Live Fiber Monitoring in CWDM Networks Olivier Plomteux, Senior Product Line Manager, Optical Business Unit To cope with the signifi cant increase for storage and on-demand delivery of digital content,
École Supérieure d'optique
Conference on Education and Training in Optics & Photonics Marseille, 27 th October 2005 An Optical Time Domain Reflectometry Set-Up for Laboratory Work at École Supérieure d'optique École Supérieure d'optique
Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable
Fiber Optic Cable Assemblies Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable 1 Cable assemblies used in patch panels (Fiber Distribution Units) are an essential interface
Christine E. Hatch University of Nevada, Reno
Christine E. Hatch University of Nevada, Reno Roadmap What is DTS? How Does it Work? What Can DTS Measure? Applications What is Distributed Temperature Sensing (DTS)? Temperature measurement using only
Fiber Optic. Passive Components Edition 2009
Fiber Optic Passive Components Edition 2009 Reliably connected to your network Your partner for system solutions The HUBER+SUHNER Group is a leading global supplier of components and systems for electrical
Testing Fiber Optic Cables. Rudy De Winter C.N. Rood [email protected]
Testing Fiber Optic Cables Rudy De Winter C.N. Rood [email protected] LAN, WAN, MAN,... Testing Fiber Optic Cables The Goal: A network Testing Fiber Optic Cables The OSI Reference Model Application
Fiber-to-the-Home/FTTH
Hands-On Design, Installation, Maintenance & Troubleshooting Active and Passive Optical Networks Course Description This Hands-On 2-day course is designed to provide technicians with Hands-On practical
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised
Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;
Agilent E6020B FTTx OTDR
Agilent E6020B FTTx OTDR Fast and Cost-effective Fiber Installation for Access Networks Technical Data Sheet Introducing the New FTTx OTDR Agilent's new E6020B FTTx OTDR is a cost-effective, easy to use
BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers
BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers WP4259 Issued: January 2015 Brillouin Optical Time Domain Reflectometry The Brillouin Optical
PURE : REliable planning of data center cabling
PURE : REliable planning of data center cabling THE PURE EFFEct: TWICE AS MANY CONNEctionS AND 15 METERS MORE CHannEL LEngtH * PreCONNECT PURE is a milestone in the development of high-end IT cabling for
Cisco - Calculating the Maximum Attenuation for Optical Fiber Links
Page 1 of 5 Calculating the Maximum Attenuation for Optical Fiber Links Document ID: 27042 Contents Introduction Prerequisites Requirements Components Used Conventions What is Attenuation? Wavelength Estimate
PIPELINE LEAKAGE DETECTION USING FIBER-OPTIC DISTRIBUTED STRAIN AND TEMPERATURE SENSORS WHITE PAPER
PIPELINE LEAKAGE DETECTION USING FIBER-OPTIC DISTRIBUTED STRAIN AND TEMPERATURE SENSORS WHITE PAPER Lufan Zou and Taha Landolsi OZ Optics Limited, 219 Westbrook Road, Ottawa, ON, Canada, K0A 1L0 E-mail:
TCOM 370 NOTES 99-4 BANDWIDTH, FREQUENCY RESPONSE, AND CAPACITY OF COMMUNICATION LINKS
TCOM 370 NOTES 99-4 BANDWIDTH, FREQUENCY RESPONSE, AND CAPACITY OF COMMUNICATION LINKS 1. Bandwidth: The bandwidth of a communication link, or in general any system, was loosely defined as the width of
HIGH POWER FREE SPACE AND FIBER PIGTAILED ISOLATORS
NEW HIGH POWER FREE SPACE AND FIBER PIGTAILED ISOLATORS Features: New! Reduced size and cost versions Reliable high power handling: As much as 80 Watts High Isolation, up to 50dB isolation possible from
Optical Fibers Fiber Optic Cables Indoor/Outdoor
presents Optical Fibers Fiber Optic Cables Indoor/Outdoor Content Optical fiber function, types optical effects applications production of optical fibre Cable - general types Indoor Indoor / outdoor Outdoor
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
Agilent 8510-13 Measuring Noninsertable Devices
Agilent 8510-13 Measuring Noninsertable Devices Product Note A new technique for measuring components using the 8510C Network Analyzer Introduction The majority of devices used in real-world microwave
ILX Lightwave Corporation www.ilxlightwave.com
# 14 Optimizing TEC Current Optimizing TEC Drive Current This Application Note discusses methods for optimizing the TEC drive current for optimum operation in heating and cooling applications. BACKGROUND
Field Testing Multimode 10 Gb/s (and beyond) Fiber Permanent Links
White Paper April 2011 WP-15 Field Testing Multimode 10 Gb/s (and beyond) Fiber Permanent Links Best Practices to Minimize Costs by Ensuring Measurement Repeatability, Reproducibility and Accuracy Authors:
Application Note Noise Frequently Asked Questions
: What is? is a random signal inherent in all physical components. It directly limits the detection and processing of all information. The common form of noise is white Gaussian due to the many random
Module Connectors and Cable Specifications
Module Connectors, page 1 Cables and Adapters, page 2 Cleaning the Fiber-Optic Connectors, page 6 Module Connectors RJ-45 Connector The RJ-45 connector is used to connect a Category 3, Category 5, Category
Patch Cord Quality, Reliability and Performance. The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance
Patch Cord Quality, Reliability and Performance The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance White Paper 12/2003 Executive Summary The quality, reliability, and
Fiber Optics: Fiber Basics
Photonics Technical Note # 21 Fiber Optics Fiber Optics: Fiber Basics Optical fibers are circular dielectric wave-guides that can transport optical energy and information. They have a central core surrounded
Fiber Optic Terminus End Face Quality Standards
Introduction Fiber Optic Terminus End Face Quality Standards Good fiber optic performance relies on connectors that are manufactured properly. Specifically, optimal optical performance requires that the
Power Amplifier Gain Compression Measurements
Technical Brief Power Amplifier Gain Compression Measurements GPIB Private Bus Sweep Out Sweep In Pulse In AC Mod Out Blank/Marker Out Blanking In Overview The 1 db gain compression of an amplifier describes
Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus
Please do not remove this manual from from the lab. It is available at www.cm.ph.bham.ac.uk/y2lab Optics Introduction Optical fibres are widely used for transmitting data at high speeds. In this experiment,
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper Optical Fiber WP1150 Issued: October 2007 Supersedes: October 2006 ISO 9001 Registered
and LP 11 are illustrated at right.
Fiber Basics Optical fibers are circular dielectric waveguides that can transport optical energy and information. They have a central core surrounded by a concentric cladding with slightly lower (by 1%)
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? GBE, as the name says, is Ethernet scaled up to gigabit speeds, providing a migration path from Ethernet at 10 MB/s to Fast Ethernet at 100 MB/s
Fiber Optic Connections in the Sea
Abstract Fiber Optic Connections in the Sea Matt Christiansen, SEA CON / Brantner & Associates, Inc. This paper provides an overview of fiber optic connector design and considerations for their use in
Subsea Asset Monitoring using Distributed Fiber Optic Sensing
Subsea Asset Monitoring using Distributed Fiber Optic Sensing Carlos Borda Omnisens S.A. Subsea Asia Conference June 2014 Agenda Who is Omnisens? Distributed Fiber Optic Monitoring Power Umbilicals Flow
Amplified High Speed Fiber Photodetectors
Amplified High Speed Fiber Photodetectors User Guide (800)697-6782 [email protected] www.eotech.com Page 1 of 7 EOT AMPLIFIED HIGH SPEED FIBER PHOTODETECTOR USER S GUIDE Thank you for purchasing your Amplified
SIGNAL GENERATORS and OSCILLOSCOPE CALIBRATION
1 SIGNAL GENERATORS and OSCILLOSCOPE CALIBRATION By Lannes S. Purnell FLUKE CORPORATION 2 This paper shows how standard signal generators can be used as leveled sine wave sources for calibrating oscilloscopes.
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Kit Highlights and Key Features
AF-OLK6 Series Fiber Optic Test kit (Data Storage Kit) Product: OLK6 Series Date: Aug:2007 Rev: 01 Description The AF-OLK6 series test kits are the complete solution necessary for the installer to test,
Transmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
We bring quality to light. MAS 40 Mini-Array Spectrometer. light measurement
MAS 40 Mini-Array Spectrometer light measurement Features at a glance Cost-effective and robust CCD spectrometer technology Standard USB interface Compatible with all Instrument Systems measuring adapters
Tracing Live or Dark FTTx PONs through Splitter using OFL280
Introduction AFL s PON-optimized OFL280-103 FlexTester is ideally suited for both out-of-service installation testing, as well as in-service fault location on FTTx PON networks. The OFL280-103 s unique
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output