NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING
|
|
|
- Barrie Houston
- 10 years ago
- Views:
Transcription
1 RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section General Requirements Section General Communication Requirements Section Grounding and Bonding for Communications Section Pathways for Communication Systems Section Fire-stopping For Communication Systems Section Communication Equipment Room Fittings Section Communication Requirements for (RF) CATV System Section Communications Backbone Cabling Section ABF Fiber Optic Cabling Section Communications Horizontal Cabling Section Communications Connection Cords General Test Requirements PART I GENERAL 1. Transmission performance of structured cabling varies with length, connecting hardware, cords and total number of connections. The installer must take care to properly install the cabling components. To ensure that the installed structured cabling solution meets or exceeds the required performance it must be tested or certified. a. The requirements for each category of cabling (Cat5e, Cat6, or Cat6 A) and optical fiber optics links are located in the ANSI/TIA-568 series standards. b. Test equipment must meet the requirements set forth in the ANSI/TIA-568 series Standard for Field Test Equipment. c. All Copper testers shall be Level III. All fiber testers shall meet the requirements in ANSI/TIA-568. Field Power Meters shall meet the following: Accuracy ± 0.2 db Resolution 0.01 db Precision ± 0.15 db The Field light source shall meet the following: Accuracy ± 0.01 db Wavelength 850 ± 30 nm 1300 ± 50 nm 1310 ± 30 nm nm 2. The calibration on all test equipment shall be current. 3. The software in all test equipment shall be current. 4. Manufacturers a) The following manufacturer s testers are approved.
2 b) FLUKE c) DTX1800 d) OptiFiber OTDR e) DTX-CLT CertiFiber Optical Loss Test Set f) IDEAL g) LanTEK II h) LANTEK 6/6A/7G i) FIBERTEK j) Or other test equipment approved by NOCCCD 5. Systems Testing and Documentation. a) Provide installation testing of equipment where required by manufacturer s installation instructions. b) Provide complete end to end testing for all copper and fiber optic systems/channels based on latest applicable standards. Document all testing and submit with final as-built submittal package. c) For all controls and operating equipment, submit equipment/systems to at least three complete operational sequences, in which all equipment operations are tested, observed, and verified. d) Prior to substantial completion and project acceptance inspection, submit test reports to indicated scope of startup and operational tests, with results of testing for each specified operation. 6. Copper Cabling System Testing A. General: Copper cabling shall be tested and certified after installation as follows and as required for cable manufacturer s warranty. Twisted-pair copper cable channels shall be tested for continuity as specified below, presence of ac/dc voltage, and performance. All cabling shall be tested for conformance to horizontal cable specifications as outlined herein, and shall be tested according to test set manufacturer s instructions utilizing latest firmware and software. Testing shall include all of electrical parameters as specified under Product. All cables and termination hardware shall be 100 percent tested by installation contractor for defects in installation and to verify cable performance under installed conditions. All conductors of each installed cable shall be verified useable by Contractor prior to system acceptance. All cables shall be tested according to contract documents, manufacturer s warranty provisions, and best industry practices. If any of these are in conflict, Contractor shall comply with most stringent requirements. All defects in cabling system installation shall be repaired or replaced in order to ensure 100 percent useable conductors in all cables installed, at no additional cost to Owner. B. Continuity: Each pair of each installed cable shall be tested using a test unit that shows opens, shorts, polarity and pair-reversals, crossed pairs and split pairs. The test shall be recorded as pass/fail as indicated by test unit according to manufacturers recommended procedures, and referenced to appropriate cable identification number
3 and circuit or pair number. Any faults in wiring shall be corrected and cable re-tested prior to final acceptance. C. Length: Each installed cable link shall be tested for installed length using a TDR type device. The cables shall be tested from patch panel to patch panel, block to block, patch panel to outlet or block to outlet as appropriate. The cable length shall conform to maximum distances set forth in TIA/EIA-568-C standards and all other applicable standards specified in Appendix 1: Codes, Standards, and Informative References. Cable lengths shall be recorded, referencing cable identification number and circuit or pair number. For multi-pair cables, shortest pair length shall be recorded as length for cable. D. Factory testing: Every reel of cable shall be tested by cable manufacturer for all characteristics specified for cable type in this section. This testing shall be performed using a sweep test method and include frequencies specified for cable. A test report shall be available electronically, at no additional cost, for a minimum of five (5) years from the date of manufacture. The test report shall include the reel number, the date of the test, the Lot number, and test results for Return Loss (RL), Insertion Loss (Attenuation), Pair-to-Pair NEXT, and Power Sum NEXT Pair-to-Pair ELFEXT and Power Sum ELFEXT. The test report shall show the Worst Case Margin for the listed transmission characteristics. E. Test results: Test results shall be automatically evaluated by equipment, using most upto-date criteria from TIA/EIA-568-C standards and all other applicable standards specified in Appendix 1: Codes, Standards, and Informative References, and result shown as pass/fail. Test results shall be printed directly from test unit or from a download file using an application from test equipment manufacturer. The printed test results shall include all tests performed, expected test result and actual test result achieved. F. Test reports: Test reports for all factory testing and field test reports for copper cabling installation shall be submitted to the Owner s Representative and manufacturer prior to commissioning voice and data system and final contract payment. Refer to Submittals in this Section. 7. Optical Fiber Cable Testing A. General: Optical fiber cabling shall be tested and certified after installation as described below and as required for cable manufacturer s warranty. Fiber testing shall be performed on all fibers in completed end to end system. Testing shall consist of a bidirectional end to end test in accordance with applicable standards or a bi-directional end to end test performed by EIA/TIA A and all other applicable standards. The system loss measurements shall be provided at 850 and 1300 nanometers for multimode type glass and 1310 and 1550 nanometers for single-mode type glass. These tests shall also include continuity checking of each fiber. For spans greater than 90 meters, each tested span must test to a value less than or equal to value determined by calculating a link loss budget. For horizontal spans less than or equal to 90 meters, each
4 tested span must be less than or equal to 2.0 decibels. The insertion loss for each mated optical fiber connector pair shall not exceed 0.40 decibels. B. Pre-installation testing: Test all optical fiber cable for all fibers prior to installation of cable. C. Performance testing: Where links are combined to complete a circuit between devices, Contractor shall test each link from end to end to ensure performance of system. Only a basic link test is required. Contractor can optionally install patch cords to complete circuit and then test entire channel. The test method shall be same used for test described above. The values for calculating loss shall be those defined in applicable TIA/EIA standards in Appendix 1: Codes, Standards, and Informative References. D. Attenuation testing: Attenuation testing shall be performed with a stable launch condition using two-meter jumpers to attach test equipment to cable plant. The light source shall be left in place after calibration and power meter moved to far end to take measurements. E. Loss budget: All fiber cabling shall be tested at both wavelengths 850 nm and 1310 nm for multimode and 1300 nm and 1550 nm for single mode. F. The link attenuation shall be calculated using: a. The CommScope link Loss Calculator for CommScope installations b. The following calculation for other installations: Link Attenuation Allowance (db) + Cable Attenuation (db) + Connector loss (db) = Splice Insertion Loss (db) Where: Cable attenuation (db) = Cable attenuation (db/km) X Length (km) Connector loss (db) = Number of Connector pairs X Allowable connector loss (db) Splice Insertion Loss (db) = Number of Splices X Allowable Splice loss (db) G. Link loss: A mated connector to connector interface shall be considered a single connector. Loss numbers for installed link shall be calculated by taking sum of bidirectional measurements and dividing that sum by two. All links not meeting requirements of standard shall be brought into compliance by Contractor, at no additional cost to Owner. H. Documentation: Following final documentation shall be submitted to the owner s representative prior to commissioning data system and final contract payment according to Submittals in this section. I. Test results: Test results shall be automatically evaluated by equipment, using most upto-date criteria from all applicable standards and result shown as pass/fail. Test results shall be printed directly from test unit or from a download file using an application from test equipment manufacturer. The printed test results shall include all tests performed, expected test result and actual test result achieved. J. End to End Loss Data: final documentation shall be submitted to the owner s representative. 8. See Section Communication Building (RF) CATV Requirements 9. See Section ABF Fiber Optic Cabling Requirements
5 10. As Installed/ As Built Diagrams: Final documentation shall be submitted to the owner s representative. 11. Test Documentation A. Electronic Format One electronic copy of the Test Reports shall be provided. B. Certification Test Reports shall be submitted in electronic format using the appropriate software supplied by the test equipment manufacturer. The data format should be that of the test report software (i.e. *.flw files for Fluke). The contractor shall provide any necessary software to view and evaluate the test data. C. The following list is provided as a reference: D. Tester Test Report Software a. Fluke LinkWare E. Ideal LanTek Reporter F. Paper Format (Architect to review with NOCCCD) G. Provide test documentation in 3-ring binders within 2 weeks after completion of project testing. Binders shall be clearly marked on outside front cover and spine with words Test Results, project name, and date of completion (month and year). Major heading tabs, Horizontal and Backbone, shall divide binder. Each major heading shall be further sectioned by test type. Within horizontal and backbone sections, divide by tabs scanner test results by category, optical fiber attenuation test results, and continuity test results. Present test data within each section in sequence listed in administration records. H. Provide test equipment by name, manufacturer, model number and last calibration date at the end of document. Unless manufacturer specifies more frequent calibration cycle, annual calibration cycle shall be required on all test equipment used for this installation. I. Test document shall detail test method used and specific settings of equipment during test. Scanner tests shall be printed on 8 1/2 by 11 inches. Hand written test results (attenuation results and continuity results) shall be documented on a suitable test form. J. When repairs and re-tests are performed, note problem found and corrective action taken, and collocate in binder both failed and passed test data. END OF SECTION
SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
What testing is required for PREMISES Fiber Optic Cabling and the standards used
Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic
Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices
Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Attaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
SPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING 27 13 23
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
Generic Category 5e Cabling Specification
Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review
Copper Cabling Troubleshooting Handbook
NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The Automated DTX Series Diagnostics 5 Causes of Cabling
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
Gigabit Passive Optical Networks
White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions
Division 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
Online Warranty System Training Manual Installation Partner Application Process
Online Warranty System Training Manual Installation Partner Application Process The new online warranty application system makes it easier to apply for a warranty as all information will be completed and
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......
Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems
SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING
Enhanced Category 5 Cabling System Engineering for Performance
Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance
Total Solutions Verification
Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers
Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.
Commercial Building Telecommunications Cabling Standard Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
IS Network Services Senior Facilities Management Group 2 Hill Farms West Division of State Facilities
POSITION SUMMARY Under the general supervision of the DOA/DSF and the DSF Telecom Supervisor, this position works closely with other Agency Telecom Services, Voice Services, Network Services, and Wide
MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
LinkWareTM. Cable Test Management Software. Getting Started Guide
LinkWareTM Cable Test Management Software Getting Started Guide October 2002, Rev. 6 5/06 2002-2006 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies.
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing
SYSTIMAX Copper Solutions Designed for the Digital Generation
SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Structured Connectivity Solutions www.systimax.com SYSTIMAX Solutions is the global leader in the enterprise cabling sector with a
Special Specification 6033 Computerized Transportation Management System
6033 Special Specification 6033 Computerized Transportation Management System 1. DESCRIPTION Relocate computerized transportation management system (CTMS) equipment as shown on the plans and as described
2-Pair HDSL1 Adtran Fiber Optic Link System
ISSUE 2 June 01, 2004 Data Sheet #37 2-Pair HDSL1 Adtran Fiber Optic Link System Contents 1. General. 1 2. Application... 2 3. Housings.. 2 4. Installation 3 5. Provisioning. 5 6. LED Indicators. 6 7.
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8
Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category
Field Measurements of Deployed Fiber
Field Measurements of Deployed Fiber Robert J. Feuerstein Level 3 Communications, 1025 Eldorado Boulevard, Broomfield, Colorado 80021 [email protected] Abstract: New generations of ultra-long
Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)
within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
FIBER OPTIC SYSTEM TEST PROCEDURES
FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
Fiber Optic Specifications
Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
European Normative EN50173-1. system
European Normative EN50173-1 for generic/structured cabling system Pietro Nicoletti Studio Reti s.a.s piero[at]studioreti.it www.studioreti.it Cabl-New-2003-Engl - 1 P. Nicoletti: see note pag. 2 Copyright
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages)
Lynx Broadband Installation Manual for Residential Packages with a 20 db Amp Quick Start Guide (first two pages) 1. Be sure that your kit includes all the parts shown in the Check the Equipment section
Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications
Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements
IT Cabling Solutions
IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? GBE, as the name says, is Ethernet scaled up to gigabit speeds, providing a migration path from Ethernet at 10 MB/s to Fast Ethernet at 100 MB/s
home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised
Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;
Cisco - Calculating the Maximum Attenuation for Optical Fiber Links
Page 1 of 5 Calculating the Maximum Attenuation for Optical Fiber Links Document ID: 27042 Contents Introduction Prerequisites Requirements Components Used Conventions What is Attenuation? Wavelength Estimate
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
FIBER OPTIC CABLE PLANT DOCUMENTATION
C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting
SECTION 680 FIBER OPTIC CABLE DESCRIPTION
680 SECTION 680 FIBER OPTIC CABLE DESCRIPTION 680.01.01 GENERAL A. The work under this section shall consist of furnishing, installing, and testing all underground and outdoor fiber optic cables. B. All
Gigabit Switching Ethernet Media Converters - Product User Guide
Gigabit Switching Ethernet Media Converters - Product User Guide PL0338 Issue3 Introduction These Tyco Electronics Gigabit Media Converters translate between 1000Base-T copper and 1000Base-X fiber optic
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel
Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,
Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District
15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications
SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes:
SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL 1.01 Summary A. Section Includes: 1. The ISS shall furnish all labor, materials, equipment, services and incidentals
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
Loss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
Accurately Testing fibre Optic Cables
Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty
Cisco SFP Optics for Gigabit Ethernet Applications
Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit
Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM
WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Insertion Losses of Fiber Optical Connectors
Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins
Copper Patch Cords. Impact On Network Performance and Reliability
Copper Patch Cords Impact On Network Performance and Reliability 1 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on
Measuring of optical output and attenuation
Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
TURBOTEST 400 Fiber Optic Certification Test Set User s Guide
TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n 2002, AFL Telecommunications,
Optical Power Meter. Specification & User Manual
Optical Power Meter Specification & User Manual Page 1 of 9 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4
Fiber Characterization Service
About JDSU JDSU s verifies the integrity and capacity of your fiber plant through the measurement of key fundamental properties, such as attenuation, reflectance, and dispersion. Comprehensive testing,
FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
Network Design Incorporated
Network Design Incorporated Network Design Incorporated specializes in the design, installation and project management of Information Transport Systems (ITS) and the various technology solutions utilizing
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS
UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS University of Toronto Scarborough Cable Systems Specification 1/23 Network Administrators Glenn Attwood Manager,
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.
SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts
Telecommunications Training Catalog
Open Enrollment & Contract Courses Online Training Customized Training Technical Assistance Telecommunications Training Catalog Boost Your Knowledge BitRate with Us! The Telecommunications Training Program
Perle 10/100 Ethernet Media Converters
Perle 10/100 Ethernet Media Converters Installation Guide S-110-XXXXXX S-110-XXXXXX-XT P/N 5500302-16 (Rev B) Overview This document contains instructions necessary for the installation and operation of