Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems
|
|
|
- Gladys Nash
- 9 years ago
- Views:
Transcription
1 SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016
2 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING GUIDELINES 2 4. ACCEPTABLE ATTENUATION VALUES 4 5. RELATIVE POWER MEASUREMENTS 5 6. TEST PROCEDURE FOR SINGLE-FIBER TEST EQUIPMENT OVERVIEW TEST CORD PERFORMANCE VERIFICATION LINK SEGMENT TESTING 7 7. TEST PROCEDURE FOR MULTI-FIBER TEST EQUIPMENT OVERVIEW TEST CORD PERFORMANCE VERIFICATION LINK SEGMENT TESTING TIA AND ISO/IEC STANDARDS TROUBLESHOOTING CABLE PLANT DEFECT DETECTION AND RESOLUTION TEST EQUIPMENT CHECKLIST 16 APPENDIX A: ENCIRCLED FLUX LAUNCH CONDITIONS 17 APPENDIX B: MEASUREMENT WORKSHEETS 18
3 1. Introduction The following guidelines describe CommScope s recommended procedure for field testing multimode and singlemode cabling systems. CommScope only requires testing of link attenuation for Enterprise networks. While other fiber-optic cabling system parameters such as bandwidth are equally important, they are not normally adversely affected by the quality of the installation and therefore do not require field testing. This document describes how and where attenuation testing should be performed for Enterprise Systems, using both singlefiber and multi-fiber test equipments. This issue replaces the previous one dated February In addition, TIA-568-C.0 and its second addendum, TIA-568-C.0-2, provide standard requirements and guidelines for testing installed optical fiber cabling systems. Optical loss (link attenuation), length verification and polarity testing are defined therein as Tier 1 testing, while OTDR testing is Tier 2 and an optional test. IMPORTANT NOTE FOR MULTIMODE FIBER TESTING The fiber optic industry has long understood the importance of a consistent launch condition for accurate and repeatable multimode measurements in both the field and the factory. This has led to mode conditioning of the launch cord attached to the light source. For multimode fiber testing in the field, this mode conditioner has traditionally been a mandrel around which the launch cord is wrapped. Standards have recently been updated to specify Encircled Flux (EF) launch conditions. These new requirements are defined in TIA C (an adoption of IEC ed.2) and normatively referenced in TIA- 568-C.0-2 (August 2012), ISO/IEC and ISO/IEC It is important to note that customers who require compliance to these standards also require the use of EF launch conditions for all multimode cabling attenuation tests. This change was driven by the recognition that loss budgets have diminished as data rates have increased, thus necessitating more precise measurements. CommScope strongly recommends the use of optical test equipment that provides an Encircled Flux compliant launch condition, but at this time EF testing will not be a requirement for Partners requesting the warranty of SYSTIMAX installations. However if a customer requires TIA adherence, CommScope will not waive the EF testing requirement. CommScope will update these testing requirements as standards and product offerings continue to evolve. Review Appendix A for more information on Encircled Flux. 1
4 2. Passive Link Segments Attenuation testing should be performed on each passive link segment of the cabling system. A link segment consists of the cable, connectors, adapters and splices between two fiber-optic termination units (patch panels, information outlets, etc.). Each terminated fiber within a link segment should be tested. The link segment attenuation measurement includes the representative attenuation of connectors at the termination unit interface on both ends of the link, but does not include the attenuation associated with the active equipment interface. This is illustrated in Figure 1. Figure 1. Tested Link Segment 3. General Testing Guidelines SAFETY NOTE: Unterminated connectors may emit radiation if the far end is connected to a laser or LED. Do not view the end of a cable until absolutely sure that the fiber is disconnected from any laser or LED source. The best practice is to only view the end face of a connector through a videoscope, so that no direct eye contact to the laser light is possible. Inspection kits are available to view multi-fiber MPO connectors as well as single-fiber types. Multimode horizontal link segments should be tested in one direction at EITHER 850 nm or 1300 nm wavelength (Currently only 850nm source is available for Fluke Multi-fiber Pro, testing only at 850nm is required). Multimode backbone and composite link segments should be tested in one direction at 850 nm and 1300 nm wavelengths (For Fluke Multi-fiber Pro, only test at 850nm). Singlemode horizontal link segments should be tested in one direction at EITHER 1310 nm or 1550 nm wavelength. This applies for both single-fiber and multi-fiber test equipments. Singlemode backbone and composite link segments should be tested in one direction at BOTH 1310 nm and 1550 nm wavelengths. This applies for both single-fiber and multi-fiber test equipments Note 1: Horizontal link segments are short enough that attenuation differences caused by wavelengths are insignificant. As a result, single wavelength testing is sufficient. Backbone and composite links may be longer, and attenuation may strongly depend on wavelength in such links. Therefore, it is necessary to test at both wavelengths. Backbone distance varies based on application, please refer to Fiber Backbone Cabling in Buildings (WP ) for specific distances. Note 2: The minor attenuation differences due to test direction are on par with the accuracy and repeatability of the test method. Therefore, testing in only one direction normally suffices. However, test in both directions is required in following three cases: 1) Installation contains fibers of different core sizes. This is to detect inadvertent mixing of fibers with different core sizes, as the loss in one direction will differ from the loss in the other direction by at least 2 db if different core sizes are connected together (e.g., 50 μm connected to 62.5 μm) when measured using μm test cords. 2) When BIMMF and traditional fiber are mixed. 3) When field polished termination is performed. Note 3: Today s standards only ask for unidirectional Light Source and Power Meter (LSPM) testing, however many customers are requesting bidirectional results. While bidirectional LSPM testing may provide more data, there is a trade-off 2
5 with the extra time required and the additional opportunity for dirt and dust to be introduced during the testing process. Bidirectional test results are optional; if used, the direction with the higher loss measurement would be used to determine pass/fail for the link. CommScope recommends multimode field tests to be performed with the Encircled Flux launch condition as defined in TIA C and IEC ed. 2. Defining a particular launch condition reduces measurement error and variability. This particular launch will produce field measurements that correlate well with component specifications. A mode conditioner device is recommended over the prior mandrel-wrapped cord method. Refer to Appendix A for more information. Note: When a mode conditioner device is not available, a high order mode loss (HOML) test can be performed to assess the launch condition of the test equipment and ensure it is in compliance per TIA C. In compliance with TIA/EIA C Optical Power Loss Measurements of Installed Multimode Fiber Cable Plant, IEC edition 2, Fibre-Optic Communication Subsystem Test Procedure Part 4-1: Installed cable plant Multimode attenuation measurement, TIA/EIA Measurement of Optical Power Loss of Installed Singlemode Fiber Cable Plant and IEC edition 2, Fibre-Optic Communication Subsystem Test Procedure Part 4-2: Installed cable plant Singlemode attenuation and optical return loss measurement, the following information should be recorded during the test procedure: 1. Names of personnel conducting the test 2. Type of test equipment used (manufacturer, model, serial number and calibration date*) 3. Date test is being performed 4. Optical source wavelength, spectral width 5. Fiber identification 6. End point locations 7. Test direction 8. Reference power measurement (when not using a power meter with a Relative Power Measurement Mode) 9. Measured attenuation of the link segment 10. Acceptable link attenuation *Test equipment should be calibrated according to the test equipment manufacturer s specifications. See Appendix B for sample measurement recording forms. IMPORTANT NOTE: Ensure that all connectors/modules are cleaned prior to mating test cords, trunk cables or patch cords. Contamination as small as mm can block the fiber core generating strong back reflections (low Return Loss) and may affect attenuation (Insertion Loss). Mating a contaminated connector to a clean connector will result in poor performance and can transfer contamination and permanently damage the connection. CommScope recommends that fiber optic connectors are inspected with a microscope prior to mating. Please refer to the CommScope Fiber Optic Connector and Adapter Cleaning Procedures and the CommScope Fiber Optic Connector Cleaning and Inspection kit for more detailed information. Also refer to Section 9 in this document. 3
6 4. Acceptable Attenuation Values LSPM testing is used to evaluate the overall loss of an entire optical link. Although individual component specifications can be reviewed on each component s specification sheet, simply adding these values together would likely overestimate the loss of that link. CommScope provides a link loss calculator that shall be used to determine the maximum acceptable loss for each link evaluated. This calculator can be downloaded from the website, or you can consult your local CommScope representative. Information to be selected or entered in the link loss calculator: 1. Select the fiber type and test wavelength combination from the pull-down menu 2. Select the unit of length in feet or meters from the pull-down menu 3. Enter the total link length under test 4. Enter the number of connections of each type 5. Enter the number of splices (each Qwik type connections counts as a connection plus a splice). An example of the format for the SYSTIMAX Fiber LinkLoss Calculator is available at is given in Figure 2-1. A similar version of the LinkLoss Calculator is available for evaluating the loss of Uniprise systems. The SYSTIMAX Link Loss Calculator is also available for mobile devices (Apple and Android) from the App Store on-line (see Figure 2-2). Figure 2-1 LinkLoss Calculator Example Figure 2-2 Mobile App A connection is defined as the joint made by mating fibers terminated with remate-able connectors (LC, SC, MPO, etc). For example, an LC connector pair composed of two connectors, in one adapter would count as only one connection within the link loss calculator. When using the InstaPATCH 360 module, each module actually contains two connection points. This equates to 1 x LC/SC/ST and 1 x MPO per module for the Fiber LinkLoss Calculator. The value provided is the maximum acceptable loss allowable to ensure that the solution will meet the performance as described in the CommScope Performance Specifications guides. Note that this loss will likely be LESS than would be defined by TIA and IEC standards. Additionally, this value will also likely be LESS than would be calculated by adding the potential maximum loss of all individual components together. 4
7 5. Relative Power Measurements If the power meter supports measurements relative to a reference measurement (in units of db), select this mode because such readings do not necessitate manual calculation. If the meter does not have a Relative Power Measurement mode, perform the following calculation to determine attenuation: Pref is the power level of the reference measurement. Psum is the power reading of the device under test. If Psum and Pref are in the same logarithmic units (dbm, dbμ, etc.): Attenuation (db) = Pref Psum If Psum and Pref are in the same linear units (Watts, milliwatts (mw), mircowatts (μw)): Attenuation (db) = 10 x LOG10 [Pref/Psum] Important Note: Both light source and power meter must be stabilized prior to measurement. The amount of time required depends on the temperature difference between unit storage space and test operation space. Allow a minimum of 5 minutes (could be up to 10+ minutes) of stabilization time before proceeding with test. Please refer to specific equipment operational guides for more details. Caution: Stable reference power levels are critical to the accuracy of subsequent attenuation measurements. Instability may arise from at least two common causes: battery health and mechanical changes at the connection to the source. Ensure the battery is in good operating condition and fully charged in both the source and power meter. Avoid disturbing the connection in any way from the source to the launch cord after the reference measurement. Disturbances include disconnection, lateral side-loading, and axial tension. Any of these disturbances is cause for making a new reference measurement. The chances of encountering these disturbances may be minimized by securing the launch cord to the source test set by means of tape or cable tie applied at the launch conditioning device (described later). CommScope fiber solutions require the use of power meters that accept plugs of the type used to terminate the cabling system under test. CommScope recommends all multimode launch cord performance verifications and link attenuation measurements to be performed with the Encircled Flux launch condition as defined in TIA C and IEC ed. 2. See Appendix A for more information. Note: For multimode systems, HOML method can be used per TIA C if unable to secure a nearfield scanner or mode conditioner for EF verification/compliance. Caution: Laser light sources, including Vertical Cavity Surface Emitting Lasers (VCSELs), cannot meet the minimum spectral width requirements defined by TIA C for LSPMs. Therefore, laser and VCSEL sources are not accepted for certifying multimode fiber systems. LED sources are acceptable for certifying multimode fiber systems. CommScope fiber solutions require all singlemode performance verifications and link attenuation measurements to be performed with a launch test cord containing a single loop < 30mm (1.2 inches) in diameter to suppress multimode propagation. This loop may be created by either wrapping the cord around a mandrel or in free space by securing the cord to itself. 5
8 6. Test Procedure for Single-Fiber Test Equipment 6.1. Overview 1. Obtain a reference power level (see Section 5). 2. Verify test cord performance (see Section 6.2) 3. Measure link power throughput (see Section 6.3). 4. Record link attenuation (see Section 5 and Appendix B). Two worksheets in Appendix B may be used for recording measurement information. The first is for use with power meters that display absolute power levels without a selectable reference. The second is for power meters that display power levels relative to a measured reference level. Of course, today most test sets will allow the user to record the data within the test units to access electronically later. Electronic recording is the preferred method of recordkeeping Test Cord Performance Verification Two worksheets in Appendix B may be used for recording measurement information. The first is for use with power meters that display absolute power levels without a selectable reference. The second is for power meters that display power levels relative to a measured reference level. Of course, today most test sets will allow the user to record the data within the test units to access electronically later. Electronic recording is the preferred method of recordkeeping. In compliance with TIA/EIA C and TIA/EIA (and IEC equivalents), test cords shall be 3-5 meters long, and have the same fiber construction (i.e. core diameter and numerical aperture) as the link segment being tested. Before carrying out any test, clean the test cord connectors and test adapter. For multimode, HOML method can be used per TIA C if unable to secure a nearfield scanner or mode conditioner for EF verification/compliance. Procedure: 1. Prepare the required launch cord with the necessary launch conditioner to meet the Encircled Flux launch conditions for multilane multimode measurements or mode suppression loop for singlemode measurements. 2. Clean all test cords connectors and the test adapter per the manufacturer s instructions. 3. Follow the test equipment manufacturer s initial adjustment instructions. 4. Connect the launch cord between the light source and the power meter. See Figure 3. Figure Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode. Refer to Section 5 for more details. 6. Do NOT disconnect the launch cord from the light source. Disconnect the launch cord from the power meter. 7. Connect the receive cord between the power meter and launch cord using the test adapter. See Figure 4. Figure 4. 6
9 8. Record the Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement mode. This measurement provides the attenuation of the receive cord cable (very minimal) plus the connection between the launch and receive cords. The measured attenuation must be less than or equal to the corresponding value given in Table 1. Unacceptable attenuation measurements may be attributable to either of the test cords. Examine each cord with a portable video scope, and clean, polish, or replace if necessary. 9. Flip the ends of the receive cord so that the end originally connected to the power meter is now connected to the adapter, and the end originally connected to the adapter is now connected to the power meter. 10. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. The attenuation must be less than or equal to the corresponding value found in Table 1. If both measurements are found to be less than or equal to the values found in Table 1, the receive cord is acceptable for testing purposes. 11. Reverse the launch and receive cords, and repeat this test procedure from the beginning to verify the performance of the launch cord. Remember to remove the existing launch conditioner or loop from the former launch cord and apply the same to new launch cord (formerly the receive cord). Table 1. Acceptable Test Cord Attenuation Fiber Type Connection Type Between Test Cords ST or SC LC MPO 62.5 µm Multimode 0.30dB Max 0.20dB Max 0.2dB Max LazrSPEED 50 µm 0.30dB Max 0.20dB Max 0.2dB Max OptiSPEED and TeraSpeed 9 µm 0.55dB Max 0.30dB Max 0.3dB Max 6.3. Link Segment Testing Case 1: Matching Connector Types Between Test Equipment and Cabling In order to include all connections in the measurement, the One-cord Reference Method specified in TIA/EIA C (for multimode fibers) and TIA/EIA (for singlemode fibers) shall be used to test each link segment. In order to perform the one cord reference method, it is necessary that the receptacle on the power meter accept the plug type used on the cabling. Procedure: 1. Use verified test cords by following the procedure in Section Repeat procedure 1-4 from Section Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode and set the reading to 0.0 db. 4. Do NOT disconnect the launch cord from the light source. Disconnect the launch cord from the power meter. Connect the receive cord between the power meter and launch cord using the test adapter (see Figure 4). Verify that the connector loss is at or below the value shown in Table Separate the launch cord from the receive cord and connect to the ends of the system under test as shown in Figure 5. DO NOT disturb the connection to the source. Figure 5. 7
10 6. Record the power measurement (Psum) by either performing the calculations given in Section 5 or, if the meter is in relative power mode, by reading the value directly from the power meter. This measurement provides the attenuation of the link segment cable(s), splice(s) and connections, including the connections on its ends. If the measurement value is less than or equal to the value calculated using the LinkLoss calculator (see Section 4), the link segment attenuation is acceptable. If not acceptable see Section 9 for troubleshooting guidance Case 2: Different Connector Types Between Test Equipment and Cabling The One-cord Reference Method in TIA/EIA C (for multimode fibers) and TIA/EIA (for Singlemode fibers) assumes the test equipment has the same connector type as in the link under test. Today s equipment should have a meter port that can be replaced to match the field connector. This will allow the technician to adjust the connector types as needed to provide a true one-cord reference. CommScope requires the use of optical power loss meters directly compatible with the plugs installed on the cabling plant. However, currently there is no multi-fiber test equipment that can comply with this requirement. Hence the three-cord reference test method is necessary. The three-cord reference test method that was outlined in the March 2005 (Section 5.2.2) CommScope Fiber Testing Guidelines is no longer needed, except when testing InstaPATCH trunk cables only (see Section 7). This modified adaptation method is necessary when the optical power loss meter receptacle does not mate with the connector of the installed cabling. Note that the cord on the source side is not removed and therefore the source port does not need to be adjustable. A cord with different connector types on each end may be needed to connect to the source port and the field connector. Figure 6 and 7 show the test set-up to evaluate an optical link with LC connections and LC-SC patch cords when the test equipment provided has an SC optical source port and an adjustable meter port. Figure 6. Reference Set-up Figure 7. System Test Case 3: Link with MPO Trunk and MPO-LC (or SC,ST) Modules on Each End With the inevitable migration to applications using parallel optics technologies such as 40G/100G Ethernet, there is a need to test link segments consisting of MPO array cabling, as incorporated within the CommScope InstaPATCH 360 solutions. The MPO connector allows for the consolidation of many fibers within one array. Although typically provided with 12 fibers, an MPO may house 8 or 24 fibers less commonly, with other values of fibers possible. The discussion and figures will focus on 12-F MPO solutions, but the process is relevant to the others. As illustrated in the example in Figure 8, the MPOs are behind the wall and not connected directly to the test cords. If testing 2 fibers at a time, the technician must test all 12 fibers of the MPO link with 6 individual tests. In this case, the link can be tested through the single-fiber connections and the testing process follows the procedures outlined previously in this section. All 12 fibers could be tested simultaneously using multi-fiber test equipment, which will be discussed in Section 7. 8
11 Figure 8 Each MPO to LC (or SC, ST) module counts as two connections because the MPO and single-fiber connections make separate connections. When selecting number of connections within the LinkLoss calculator, add one connection for both the single-fiber and MPO connector for each module. In the test shown in Figure 8 above, there are two MPO connections and two LC connections. An example of how the LinkLoss calculator is used to determine the maximum loss for this link is show in Figure 9-1 and Figure 9-2. Figure 9-1 LinkLoss Calculator Example Figure 9-2 Mobile App In contrast, use of an MPO to single-fiber fanout cord (Figure 10) in place of a module will only count as one MPO connection because the single-fiber connector will be plugged directly into the electronics. Figure 10. MPO-LC harnesses may take the place of MPO-LC modules and LC duplex patch cords 9
12 6.3.4 Case 4: MPO Trunk Link In this case, there are no single-fiber connectors with which to attach traditional single-fiber test cords. In laboratory or factory settings, there would be test equipment available that could directly attach to the MPO trunk cable. This requires 12 output sources and either 12 input ports or an MPO port with a very wide area detector to accept the light from all 12 (or 24 fibers).this set-up is impractical for field-testing. CommScope recommends testing MPO trunks with multi-fiber test equipment (Fluke Multi-fiber Pro) that accepts MPO connectors, allowing it to test all 12 fibers in the MPO trunk simultaneously. Detailed procedure for such test will be outlined in Section 7. When multi-fiber test equipment is not available, follow procedure in this section to test with the traditional single-fiber type tester. To perform the MPO trunk link test, the technician should use an MPO to LC fanout cord (See Figure 10) to separate the MPO trunk into single-fiber channels. Because of the additional fanout cords, a three cord reference method is required to offset the additional loss of the test connections. The basic steps for performing field attenuation measurements of an MPO trunk are: 1. Verify test cord performance (see Section 6.2). 2. Obtain a reference power level with the series of three cords in place per the diagram on the top right of Figure Remove the middle patch cord and add a verified reference grade MPO-LC fanout test cord on each side. The fanout cords can be verified by ensuring the resulting power level does not exceed the values achieved in step 2 by more than 0.20dB. 4. Insert the MPO trunk in-between the two MPO-LC fanout cords and measure the loss at the first LC per the diagram in the lower left corner of Figure Record and measure the loss at the second LC and continue to the last connection. Figure 11. MPO Trunk Testing with Single-Fiber Test Equipment 10
13 7. Test Procedure for Multi-fiber Test Equipment 7.1. Overview 1. Obtain a reference power level (see Section 5). 2. Verify test cord performance (see Section 7.2) 3. Measure link power throughput (see Section 7.3). 4. Record link attenuation (see Section 5 and Appendix B). Two worksheets in Appendix B may be used for recording measurement information. The first is for use with power meters that display absolute power levels without a selectable reference. The second is for power meters that display power levels relative to a measured reference level. Of course, today most test sets will allow the user to record the data within the test units to access electronically later. Electronic recording is the preferred method of recordkeeping. The following sections focus on Fluke MultiFiber Pro tester, which accepts Male MPO connection at the source and power meter. Testing methods may be adjusted for other test equipments that accept Female MPO connections Test Cord Performance Verification To preserve the integrity of the source bulkhead, a stationary launch cord is recommended to reduce connects and disconnects to minimize damage. A launch extension cord serves the purpose of gender conversion without the need of replacing the launch cord to properly mate with the test link. EF compliance shall be verified at the end of launch cord, excluding the launch extension cord. In compliance with TIA/EIA C and TIA/EIA (and IEC equivalents), test cords shall be 3-5 meters long, and have the same fiber construction (i.e. core diameter and numerical aperture) as the link segment being tested. Before carrying out any test, clean the test cord connectors and test adapter. For multimode, HOML method can be used per TIA C if unable to secure a nearfield scanner or mode conditioner for EF verification/compliance. All reference-grade cords are tested by the manufacturer, with test data provided. CommScope highly recommends verifying the quality of all required test cords prior to link testing. Required cords: Cord Description Minimum QTY Female-Male Large Core Test Lead 1 Male-Male Large Core Test Lead 1 Male-Male Cord 2 Female-Male Cord 2 Female-Female Cord Female-Male Test Cord Verification 1. Prepare the required launch cord with the necessary launch conditioner to meet the Encircled Flux launch conditions for multimode measurements or mode suppression loop for Singlemode measurements. 2. Clean all test cords connectors and the test adapter per the manufacturer s instructions. 3. Follow the test equipment manufacturer s initial adjustment instructions. 4. Set up reference channel per Figure 12. Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode and set the reading to 0.0dB. Refer to Section 5 for more details. 11
14 Figure Do NOT disturb the connection at the light source. Disconnect the launch cord from the large core test lead. 6. Insert the Female-Male Device Under Test (DUT) between the launch cord and the large core test lead. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. Record the attenuation, and it must be less than or equal to the corresponding value found in Table 1. This step completes the verification of the Female-Male test cord Male-Male Test Cord Verification 1. Prepare the required launch cords with the necessary launch conditioner to meet the Encircled Flux launch conditions for multimode measurements or mode suppression loop for Singlemode measurements. 2. Clean all test cords connectors and the test adapter per the manufacturer s instructions. 3. Follow the test equipment manufacturer s initial adjustment instructions. 4. Set up reference channel per Figure 13. Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode and set the reading to 0.0dB. Refer to Section 5 for more details. Figure Do NOT disturb the connection at the light source. Remove the large core test lead. 6. Insert the Male-Male DUT between the launch cord and power meter. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. Record the attenuation, which must be less than or equal to the corresponding value found in Table Reverse the order of Male-Male DUT. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. Record the attenuation, which must be less than or equal to the corresponding value found in Table Female-Female Test Cord Verification 1. Prepare the required launch cord with the necessary launch conditioner to meet the Encircled Flux launch conditions or multimode measurements or mode suppression loop for Singlemode measurements. 2. Clean all test cords connectors and the test adapter per the manufacturer s instructions. 3. Follow the test equipment manufacturer s initial adjustment instructions. 4. Set up reference channel per Figure 14. Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode and set the reading to 0.0dB. Refer to Section 5 for more details. 12
15 Figure Do NOT disturb the connection at the light source. Disconnect the launch cord from power meter. 6. Insert the Female-Female DUT and a verified Male-Male large core test lead between the launch cord and power meter. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. This attenuation must be less than or equal to the corresponding value found in Table Reverse the order of Female-Female DUT. Record the new Power Measurement (Psum). Perform the calculations given in Section 5 if not using Relative Power Measurement Mode. Record the attenuation, which must be less than or equal to the corresponding value found in Table Link Segment Testing Procedure: 1. Use verified reference cords by following the procedure in Section Prepare the required launch cord with the necessary launch conditioner for multimode measurements or mode suppression loop for Singlemode measurements. 3. Clean the test cord connectors. 4. Follow the test equipment manufacturer s initial set-up instructions. 5. Set up corresponding reference channel for each DUT. Refer to Figure 15. Figure Record the Reference Power Measurement (Pref) or, preferably, select the power meter s Relative Power Measurement Mode and set the reading to 0.0 db. 7. DO NOT disturb the connection to the source. Disconnect at breakpoint and insert DUT and verified reference cord if specified. 8. Record the power measurement (Psum) by either performing the calculations given in Section 5 or, if the meter is in relative power mode, by reading the value directly from the power meter. This measurement provides the attenuation of the link segment cable(s), splice(s) and connections, including the connections on its ends. If the measurement value is less than or equal to the value calculated using the LinkLoss calculator (see Section 4), the link segment attenuation is acceptable. If not acceptable see Section 9 for troubleshooting guidance. Note: When using the LinkLoss calculator, ensure all measured connections are accounted for. For example, in the Female-Female DUT setup, the measured link attenuation must be compared against LinkLoss result of two MPO connections (one at breakpoint and second one between DUT and verified reference cord). In the Female-Male DUT setup, there are two MPO connections. In the Male-Male DUT, three MPO connections must be accounted for. 13
16 8. TIA and ISO/IEC Standards ISO/IEC covers Implementation and Operation of Customer Premises Cabling: Testing of Optical Fiber Cabling and references. IEC for installed multimode fiber optic cable plant attenuation measurement IEC for installed Singlemode fiber optic cable plant attenuation measurement Besides the TIA/EIA C and TIA/EIA standards already discussed, ANSI/TIA 568-C.0 covers additional guidelines for field testing length, loss and polarity of optical fiber cabling systems. Table 2 provides the link configurations and the associated reference test methods required by the different standards. All intended for single-fiber testing only. Table 2. Link Configurations and Associated Reference Test Methods Optimal for this configuration on the ends of the link under test Number of end connection losses included in measurement Commonly used description IEC ed.2 and ANSI/TIA C description (multimode) IEC ed.2 description (Singlemode) TIA description (Singlemode) (Note 1) Adapters on both ends 2 1-cord reference method Annex A, Onecord reference method Method 1a, One jumper-cable measurement Method A.1, One jumper-cable measurement Plugs on both ends 0 3-cord reference method Annex B, Threecord reference method Method 1c, Three jumper-cable measurement Method A.3, Three jumpercable measurement Plug on one end, adapter on the other end 1 2-cord reference method Annex C, Twocord reference method Method 1b, Two jumper-cable measurement Method A.2, Two jumper-cable measurement Note: CommScope anticipates that ANSI/TIA A will be an adoption of IEC edition 2. The CommScope testing guidelines are in accordance with TIA and IEC series of standards. The one-cord reference method is the most commonly used because most links under test stop at a patch panel on each end and are tested before equipment cords are deployed. Optical Time Domain Reflectometer (OTDR) test is optional for verifying CommScope enterprise systems. 14
17 9. Troubleshooting Link attenuation exceeding expectations may arise from several reasons. These include contamination, defects in the cable plant, or improper test equipment usage. MPO solutions are particularly susceptible to contamination because of the number of fibers, number of connections, and tight loss budgets. Frequent cleaning may be required Cable Plant Defect Detection and Resolution Contamination is the most common cause of optical loss within connections. For multimode and Singlemode cabling the test cords and the ports under test should be clean and free of damage in accordance with IEC Check connector end-faces for dirt and defects (see Table 3, Figures 16 & 17, and check link segment for broken fiber, poor splices and tight bends. Table 3. Possible Cause Adhesive bead left on the tip of a connector Resolution Examine connectors with a portable microscope and re-polish if necessary Poorly polished connectors (see Figure 17) Examine connectors with a portable microscope and re-polish if necessary Dirty connectors and/or adapters (see Figure 16) Examine connections and clean per manufacturer s instructions Broken fiber Poor mechanical or fusion splices Excessively tight bends in the cabling Patch cord does not match the fiber type (compare jacket color and print statement) of the behind-thewall cabling Identify break with a Visible Fault Locator or OTDR and splice fiber or replace cable Identify poor splices with a Visible Fault Locator or OTDR and re-splice if necessary Identify tight bends by inspection or with a Visible Fault Locator or OTDR and increase the bend radius above minimum specifications Replace test leads to match BTW cabling. Reset the reference and retest. Figure 16. Dirty Connectors (Pictures courtesy of Fluke Networks) Figure
18 9.2. Test Equipment Checklist Check Test Cord Conformance Follow Section 6.2 and 7.2 to verify that the performance of test cords used conform to the values given in Table 1. Check Light Source Conformance Ensure the source and launch cord combination meets launch condition specifications and the source meets requirements for center wavelength and spectral width according to the standards referenced within Section 3 and Appendix A. Check Reference Level Stability Ensure battery operated equipment batteries are in good condition with sufficient charge. Ensure that the connection of launch cord to the light source is not disturbed after the reference level measurement. Disturbances include disconnection and reconnection, lateral or axial stresses such as tugging, bumping the connector, or bending the cordage. Any of these may introduce measurement errors. 16
19 Appendix A: Encircled Flux Launch Conditions IEC ed.2 and ANSI/TIA C define a precision launch condition using a metric called Encircled Flux. This metric was established to reduce the measurement variability that is often observed between different test sets due to variations in the launch condition. Reducing this variability is important because loss budgets have become smaller as data rates have increased. Previously defined CPR-plus-mandrel-wrap prescriptions are incapable of assuring sufficiently small variability between test sets. Encircled Flux compliance is determined using a near-field imaging instrument and analysis software that measures the light distribution at the output end of a test launch cord when transmitting light from the intended test source. Although it is possible to produce a compliant native launch at the output port of the source, a mode conditioning device is typically required between the light source port and the launch test cord output to create a compliant condition. Reference grade launch cords are generally required to meet the launch specifications. Reference grade cords and launch conditioning devices may be available from the test set manufacturer. Following the test set manufacturer's recommendations should produce a compliant launch condition without necessitating actual near-field image verification in the field. Figure 18 illustrates the use of such mode conditioning devices applied near the output of the sources in a bidirectional test. Figure 18 A High Order Mode Loss (HOML) test can be performed to qualify source and test lead should the launch condition of source and test lead be unknown, and a mode conditioner/launch analyzer is not available. This test should be performed per the guidance of ANSI-TIA C. The foreword in this document provides background and guidance to performing the test. Also required is a mandrel as defined in the above referenced document and known good reference test cords. CommScope recommends the use of CommScope's supplied test cords. Test Reference Cords are available from Commscope in various configurations and can be ordered through Commscope customer service. 17
20 Appendix B: Measurement Worksheets Test Instrument Data Sheet LIGHT SOURCE Manufacturer: Model: Serial Number: Launch Condition Compliance Methodology (Check One): Mandrel CPR EF HOML Spectral Width: 850 nm: 1300 nm: 1310 nm: 1550 nm: Launch Condition Compliance Methodology: 850 nm: 1300 nm: 1310 nm: 1550 nm: Power Meter Manufacturer: Model: Serial Number: 18
21 Link Attenuation Measurement Record for Power Meters Displaying Absolute Power Levels Test Personnel: Date: Light Source Test Location: Power Meter Test Location: Wavelength: Reference Power Measurement (Pref): Page of # Fiber Identification 1 Power (P sum ) Link Seg. Attn. (db) Acceptable Attn. (db) # Fiber Identification 25 Power ( P sum ) Link Seg. Attn. (db) Acceptable Attn. (db)
22 Link Attenuation Measurement Record for Power Meters Display Relative Power Levels Test Personnel: Date: Light Source Test Location: Power Meter Test Location: Wavelength: Reference Power Measurement (Pref): Page of # Fiber Identification Power ( P sum ) Link Seg. Attn. (db) Acceptable Attn. (db) # Fiber Identification Power ( P sum ) Link Seg. Attn. (db) Acceptable Attn. (db) Visit our Web site or contact your local CommScope representative for more information. All trademarks identified by or are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services CommScope, Inc. All rights reserved. TP EN (05/16) 20
What testing is required for PREMISES Fiber Optic Cabling and the standards used
Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices
Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
Accurately Testing fibre Optic Cables
Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications
Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer
SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
Loss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM
Testing and troubleshooting enterprise fiber-optic cabling Presenter: Neftali Usabal Fluke Networks - LATAM Agenda Testing Methods and Standards Why we test optical systems Terminology & types of testing
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
Module 13 : Measurements on Fiber Optic Systems
Module 13 : Measurements on Fiber Optic Systems Lecture : Measurements on Fiber Optic Systems Objectives In this lecture you will learn the following Measurements on Fiber Optic Systems Attenuation (Loss)
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning
TEST & INSPECTION Featured Data Center Products M310 Enterprise OTDR with TruEvent Technology Designed for Enterprise Network Testing, Troubleshooting and Documentation, the M310 with TruEvent technology
Fiber Optic Specifications
Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will
Measuring of optical output and attenuation
Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter
Insertion Losses of Fiber Optical Connectors
Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper Optical Fiber WP1150 Issued: October 2007 Supersedes: October 2006 ISO 9001 Registered
A Guide to Patch Cord Management
SYSTIMAX Solutions A Guide to Patch Cord Management www.commscope.com Contents A Guide to Patch Cord Management 1 Best Practice for Copper Cabling 2 Planning 2 Preparation 3 Patching 4 Validation 5 Best
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
FIBER OPTIC SYSTEM TEST PROCEDURES
FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not
USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION
USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION
12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)
1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces
Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces WP1281 Issued: November 2015 Supersedes: 2012 Author: Dr. Russell Ellis ISO 9001 Registered Background
Gigabit Passive Optical Networks
White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions
Module Connectors and Cable Specifications
Module Connectors, page 1 Cables and Adapters, page 2 Cleaning the Fiber-Optic Connectors, page 6 Module Connectors RJ-45 Connector The RJ-45 connector is used to connect a Category 3, Category 5, Category
Data Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
7.4 3M No Polish Connector
Cap Fibre Splice Element Description 3M No Polish Connector (NPC) enables fast, on-site installation of 250μm and 900μm connections utilizing a one piece, pre-assembled design. The SC compatible connector
The Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
How To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
Attaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
Laser-Optimized Fiber
FIBER FAQs Laser-Optimized Fiber Technical Resource: Tony Irujo Manager, Customer Technical Support FIBER FAQs Laser-Optimized Fiber As transmission speeds over optical fiber networks in the enterprise
Mini-HDMI Series MINIATURE MULTIMODE FIBER OPTIC HDMI TRANSMISSION SYSTEM
Mini-HDMI Series MINIATURE MULTIMODE FIBER OPTIC HDMI TRANSMISSION SYSTEM BCI reserves the right to make changes to the products described herein without prior notice or consent. No liability is assumed
APPLICATION NOTE POLARIZATION MEASUREMENTS
OZ OPTICS LTD. APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS FAMILY OF POLARIZATION MAINTAINING COMPONENTS, SOURCES, AND MEASUREMENT SYSTEMS The information/data furnished in this document shall
SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation
Optical Power Meter. Specification & User Manual
Optical Power Meter Specification & User Manual Page 1 of 9 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4
www.commscope.com Data Center Topology Guide
www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server
ST800K-U Optical Power Meter. User Manual V1.0
User Manual V1.0 Contents 1. Summary... 1 2. Functions... 2 3. Specifications... 2 4. Layout... 4 5. Operation... 5 6. Maintenance... 7 7. Faults & Solutions... 8 8. Appendix A...9 9. Appendix B...11 10.
Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels
Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1 Introduction Data centers are the central location for data interchange and are found in enterprises, government
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
European Normative EN50173-1. system
European Normative EN50173-1 for generic/structured cabling system Pietro Nicoletti Studio Reti s.a.s piero[at]studioreti.it www.studioreti.it Cabl-New-2003-Engl - 1 P. Nicoletti: see note pag. 2 Copyright
FiberBasix 50 Handheld Testers Series comprising the els-50 light source and epm-50 power meter
Series comprising the els-50 light source and epm-50 power meter 2011 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET SHARE LEADERSHIP AWARD The Delivering ultimate simple, CD/PMD accurate characterization
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......
CISCO 10GBASE X2 MODULES
DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
FIBRE-OPTICS POWER METER INSTRUCTION MANUAL
FIBRE-OPTICS POWER METER INSTRUCTION MANUAL FIBRE-OPTICS POWER METER ELLMAX ELECTRONICS LTD. Unit 29, Leyton Business Centre, Etloe Road, Leyton, London E10 7BT, England Tel: 020-8539 0136 Fax: 020-8539
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
Cisco SFP Optics for Gigabit Ethernet Applications
Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit
TURBOTEST 400 Fiber Optic Certification Test Set User s Guide
TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n 2002, AFL Telecommunications,
SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS
Features: SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Low insertion loss < 0.2 db Excellent repeatability FC/PC, SC, ST, LC, MU, E2000 termination available Custom ferrule termination available Designed
CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE
ORTRONICS : UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
How To Use The Visifault Visual Fault Locator
VisiFault Visual Fault Locator Instruction Sheet The VisiFault Visual Fault Locator (VFL) is a visible light source that helps you trace optical fibers, check fiber continuity, and find faults such as
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
M310 Data Center OTDR
Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? GBE, as the name says, is Ethernet scaled up to gigabit speeds, providing a migration path from Ethernet at 10 MB/s to Fast Ethernet at 100 MB/s
Kit Highlights and Key Features
AF-OLK6 Series Fiber Optic Test kit (Data Storage Kit) Product: OLK6 Series Date: Aug:2007 Rev: 01 Description The AF-OLK6 series test kits are the complete solution necessary for the installer to test,
DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)
Features: DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) PATENT NUMBERS: CANADA 2,494,133, USA 7095931, 7295731 AND CHINA 1672073 Telcordia GR-468 qualified Available in versions for any wavelength
BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers
BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers WP4259 Issued: January 2015 Brillouin Optical Time Domain Reflectometry The Brillouin Optical
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry
Agilent E6020B FTTx OTDR
Agilent E6020B FTTx OTDR Fast and Cost-effective Fiber Installation for Access Networks Technical Data Sheet Introducing the New FTTx OTDR Agilent's new E6020B FTTx OTDR is a cost-effective, easy to use
Gigabit Ethernet Copper-to-Fiber Converters
Gigabit Ethernet Copper-to-Fiber Converters GFT-10XX Standard multi-mode & single-mode 1000BASE-T GFT-1055E Extended Reach Multi-Mode over standard fiber GFT-1037A/B Single-Fiber, Bi-Directional Single-Mode
MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
Plug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
Infrastructure for the next three generations
Infrastructure for the next three generations Demand for bandwidth and storage is expanding at a breathtaking rate within the data center, which means that the environment is rapidly evolving, making the
SECURE Fiber Optic Products
SECURE Fiber Optic Products LC SECURE Fiber Optic Products (Pages 9 and 10) LC SECURE Connectors, Cable Assemblies and Adapters MPO SECURE Fiber Optic Products (Pages 11 and 12) MPO SECURE Cable Assemblies
Reliable, Consistent, Quality
Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic
HP ProCurve High-Speed Transceivers Installation Guide
HP ProCurve High-Speed Transceivers Installation Guide Introduction The HP ProCurve High-Speed Transceivers can be installed into a number of HP ProCurve networking devices to provide 100 Mbps and 1000
SYSTIMAX Solutions. Intelligent Infrastructure (ipatch) Solutions Guide. www.commscope.com. www.commscope.com 1
SYSTIMAX Solutions Intelligent Infrastructure (ipatch) Solutions Guide 1 Vision + Knowledge = Control SYSTIMAX Intelligent Infrastructure Solutions: Add intelligence to copper and fiber structured cabling
TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report
TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report Peter L. Pondillo Standards Committee Chairman Corning Incorporated March 2012 Liz to update Fiber Optics LAN Section Overview: Part
Optimizing Infrastructure Support For Storage Area Networks
Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle
The 8-Fiber Solution for Today s Data Center
The 8-Fiber Solution for Today s Data Center Bill Charuk, SR Product Manager, Data Center Solutions Introduction Data center infrastructure is constantly evolving. Fiber optic installations have used the
Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus
Please do not remove this manual from from the lab. It is available at www.cm.ph.bham.ac.uk/y2lab Optics Introduction Optical fibres are widely used for transmitting data at high speeds. In this experiment,
SimpliFiber Pro. Users Manual. Optical Power Meter and Fiber Test Kits
SimpliFiber Pro Optical Power Meter and Fiber Test Kits Users Manual September 2008 2008 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. LIMITED
Perle 10/100 Ethernet Media Converters
Perle 10/100 Ethernet Media Converters Installation Guide S-110-XXXXXX S-110-XXXXXX-XT P/N 5500302-16 (Rev B) Overview This document contains instructions necessary for the installation and operation of