Loss & Continuity Testing with MPO/ MTP Connectors

Size: px
Start display at page:

Download "Loss & Continuity Testing with MPO/ MTP Connectors"

Transcription

1 Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular installation issues. Here we give an overview of how to tackle various issues related to testing the cabling for these systems. We mainly discuss multimode systems, however single mode ribbon fiber systems share very many common practices. Typically these deployments are for 40G / 100G Ethernet. Cabling may be installed for 100G Ethernet even if the immediate requirement is 40G, to allow for later incremental bandwidth upgrades. The 24 fibers used for 100G Ethernet can alternatively be used to carry three 40G systems. So this allows a choice of upgrade paths, eg to upgrade incrementally to 120G aggregate capacity by adding two extra 40G channels, or replace a 40G system with a single 100G channel. Standards are in development for 400G Ethernet. The incremental cost of installing 24 fiber 100G cabling, instead of 12 fiber 40G cabling, is actually quite modest, particularly in comparison to later re-wiring and facility disruption. The major additional cabling complexity may be a patch panel with breakout connections, which provides connection flexibility for future deployment options. Standards Compliance Internationally recognised standards are now in place, which define just about everything to do with data centre design. Just in the area of fiber optic cabling, there are standards for fiber types (Typically multimode OM3. OM4 etc), cable types (fire retardance, bend resistance, riser cables etc), cable installation (fire stops, ducting etc) connectors (LC, MPO etc), labelling conventions, Ethernet, optical wavelengths (CWDM etc), optical safety (mandatory), and finally: cable acceptance testing. Page 1 of 6

2 There is one aspect of the standards for fiber acceptance testing that everyone can agree on: they are currently a work in progress, and this is particularly true of MPO testing. So at the project definition stage, it is a good idea to review and refine the fiber cable acceptance test requirements, which sensibly end up as a combination of standards based requirements and the mandatory atory requirements of the particular transmission equipment in use. A good review at this point can reduce project cost, increase facility utilisation, and increase the useful LAN lifetime. A Very Small Acceptable Optical Loss! The majority of LAN transmission sion systems using MPO/MTP connectors have extremely tight end-todb. This tiny loss figure creates unique challenges end optical loss requirements, perhaps around 1.5 for precision loss measuring for cable certification. Much of the currently available test equipment and procedures do not achieve a level of repeatability (accuracy) that gives confidence that the tight specification has been achieved. The two reasons for this tight specification are to minimise per port electronics cost, and also because these systems are dispersion limited, not power limited. These systems use 850 nm and 50 micron core fiber, and end to end length is usually limited (by dispersion) to around 300 meters. Inspection & Cleaning Connector condition and cleanliness is a very major consideration, and is a most common cause of problems. Absolutely essential is a good quality microscope with an MPO/MPT specific adaptor, a supply of suitable specific cleaning materials (more than one type is good), and adequate time and know-how to use them. The default available MPO cleaners tend to do a reasonable job of cleaning the fiber ends only, but extra cleaning materials should be available to clean alignment pins, and sometimes the whole connector end face. Inspection and cleaning should be performed every time before a connector is mated. Cabling Disturbance Because of the combination of very low loss requirements, high fiber complexity and modest connector performance, it is essential that final testing and commissioning are accomplished with the lowest possible level of disturbance to connections. Also, once loss testing is done, any cabling disturbance might require the loss testing to be repeated. This means that an unusually strict test regime is appropriate, so that each acceptance level is completed with exceptional confidence. You Page 2 of 6

3 want to avoid going back in and disturbing things. For this reason, we suggest a phased approach as being most practical. Continuity Testing This is the most basic test: Does light get from end to end? As a minimum, this test is easily accomplished with a VFL source and one low quality breakout cable to connect to the VFL. Continuity testing usually doesn t need documenting. If a numbered low quality breakout cord is used each end, this could also double as a polarity test phase. The continuity test phase is usefully accompanied by thorough cleaning and inspection of the connectors. This achieves a few objectives. Bad connectors are the main cause of installation failures. Doing this here enables the installer to identify & re-work/replace bad connectors at the earliest (lowest cost) point, avoiding later cable disturbance. It also ensures that a bad connector does not contaminate the test cords or degrade other connectors. If the connector quality is inadequate, there may be little point proceeding further until this issue is fixed. Simple continuity testing has one big problem: it doesn t identify if fibers are swapped around. So for this we talk of: Polarity Testing Typically, the cable installation requires polarity testing, to ensure that a 1 n array of fibers at one end of a system, is correctly mapped to a 1 n array of fiber the other end. If the installation has a patch cable section so that connections can be split off to particular transmission equipment, niggling polarity mistakes can occur here. The polarity test needs a very high level of confidence, since if not 100% correct, there is no chance of a working outcome, and there could be a great deal of wasted work to find the swapped fibers. This will probably want a basic level of documenting, sufficient to record which fibers were tested, and the general array direction. Labelling You now have your system physically in place and light going to and fro in the right combinations. This is the perfect time to double-check and rectify all associated labelling, otherwise the next phase of loss testing could result in incorrect re-assembly due to discovered faults. Up to this point, the work has required a very methodical approach, however has otherwise been quite straightforward. Loss Testing Accuracy & Confidence Issues People use the terms repeatability, accuracy, reproducibility or uncertainty somewhat interchangeably. For loss testing in particular, there is little practical difference between them all, so we will use the term uncertainty. The real issue is what uncertainty happens when repeatedly measuring one item with different items of test equipment or test cords. Page 3 of 6

4 Quoted uncertainty values always imply a ± value, whether specifically mentioned or not. For example, a quoted uncertainty of 0.1dB is the same as ±0.1dB, usually with a 95% confidence level. As mentioned, the acceptable maximum loss figure may only be 1.5 db. If the test uncertainty is say 0.3 db, then measured losses from db are marginal, and the maximum test value for guaranteed operation is 1.2 db. So every small improvement in uncertainty, yields a usefully larger allowable measured loss level, which will reduce installation cost. This easily explains the previous care on planning test cords, doing cleaning etc. In practice, repeatability / accuracy is optimised by a number of factors: 1. Use of low loss Elite test cords, and ensuring they are in top condition. 2. Use of an Encircled Flux compliant test source, followed by a mandrel wrap. 3. Use of very accurate loss test equipment, remembering that you are working on the limits of achievable loss test accuracy. For typical 850 nm testing, do not use an InGaAs power meter detector, since it is too wavelength sensitive and so reduces practical accuracy. The light source must also be highly repeatable and stable when the connected test cord is moved around. 4. Rigorous inspection and cleaning every time a connector is mated. 5. Performing test cord verification at the start of the job. 6. Use of appropriate data recording systems, since there will be plenty of test data. Test Cords A major loss test consideration is the test cord loss performance. As can be seen from the table, Elite MPO / MTP cords are available with per connector / fiber loss of below 0.35 db. Otherwise standard cords are clearly inadequate for testing. Here are the USConnec specifications for these connectors, and also shows why it is so undesirable to disturb the cabling after testing. MM MT Elite Multimode MT Standard Multimode MT SM MT Elite Single-mode MT Standard Single-mode MT Insertion Loss 0.1 db Typical (All 0.35 db Maximum 0.20 db Typical (All 0.60 db Maximum 0.10 db Typical (All 0.35 db Maximum 0.25 db Typical (All 0.75 db Maximum Optical Return Loss > 20 db > 20 db > 60 db (8 Angle Polish) > 60 db (8 Angle Polish) Testing will probably need a combination of straight MPO-MPO test cords, and breakout cords. Also ensure that connector pin polarities are correct, since trying to swap these pins in the field is not viable. A few tested through-connects is also helpful. Spare test cords will be required, in case some get degraded or damaged. The typical application environment uses a mix of LC and multi fiber connectors. So naturally one might assume that LC MPO breakout test cords are an obvious choice. However SC MPO Page 4 of 6

5 breakout cords are typically more robust, easier to handle, and offer slightly improved optical performance. However, SC-LC connections give inferior performance. Number the cords and label each end A/B. Test cords require Performance Verification before each use. This performance verification test is quite specific, and failure to do this preliminary test may invalidate all the following test results. The basic objective of the performance test is to ensure that the loss of the cords meets the basic accuracy requirements. However, there is a sting in this tail as follows: The test standards require a loss of eg 0.1 db or better for multimode fiber The elite average loss meets this specification However the actual per fiber maximum loss does not. We hope the standards folk will resolve this in due course. One potential way around this is that if the actual loss of each connection is recorded for each fiber during this test, then this loss can be used to compensate the following test results and improve accuracy. However in practice, this is excessively hard to implement, so the practical policy is to only use good cords. The Test Cord Verification Test is quite simple: test each test cord connector using two reference cords, and the loss of the connection must be within the allowed limit. In the case of MPO connectors, this will take a bit longer due to the number of fibers. What Test Uncertainty can I expect? This is a much discussed issue. Without going into any great detail, there are a few obvious pointers: The test cord performance test using Elite connectors could have losses of from db per connector, giving a per mated connector uncertainty of ±0.18 db, This means that any overall test uncertainty must be at least ±0.18 db, and is likely to be larger once other factors as included. However once the test cords are plugged into presumably lower grade cords, the loss there could possibly jump to db, giving a minimum per mated connector uncertainty of ±0.38 db. These are simple deductions based on connector specifications, and calculated uncertainty including all factors could only get worse. Alternatively, if suitable experiments are performed with the actual equipment and test cords, it may be possible to demonstrate a lower level of uncertainty, however this is specific to a particular item of test equipment, and particular test cords, and so has limited viability. General Loss Test equipment Choices There are three broad choices to make, which will depend on the scale of expected work: 1. Use a basic source and meter. This is excessively fiddly to perform, and so prone to error, since both instruments need moving for each fiber to be tested, so it s only sensible for a very small project. Page 5 of 6

6 2. Use a basic source and special MPO compatible meter, so that only the source needs moving for each fiber. For a modest equipment cost, this greatly simplifies testing. This also works for any fiber type, wavelength, or number of fibers per connector, or MPO pin configuration, so it has excellent flexibility, and the same equipment can be used for other work. A good choice for many mid-size projects, or cabling contractors. 3. A special MPO test set, However these usually only work at 850 nm and 12 fibers, so they are both expensive and inflexible, and so are useful for a specific large project. They are not so useful for testing breakout cables. Many such units on the market today also have InGaAs detectors, which significantly degrade their test accuracy at 850 nm. They have limited MPO pin configuration compatibility, which may limit referencing options. Whatever test equipment is selected will need some good reporting software. It may be a project requirement that it s impossible to modify the test results, to prevent tampering. Procedure Loss testing using solution 2 will generally proceed as follows (remembering to inspect and clean on each insertion): 1. Begin by verifying the test cords. Once these are proven to be adequate: 2. Reference the source and meter using a breakout cable and the desired number of reference cords. 3. Set up the MPO power meter at the far end of the test system 4. Start with the light source at fiber 1 on the breakout cable, take the loss reading 5. Move the light source only to the next fiber on the breakout cord, and take the loss reading 6. Etc 7. Go back to fiber 1 and note the reading (is within limits compared to the 1 st time) We found that using a Kingfisher light source KI2803 with power meter KI2600XL-Ge5, and this technique, the repeatability was determined by the test cords. Ease of testing and speed were both good, since only the source needed moving for each fiber. Loss testing using solution 1 will differ in that the power meter will need to be moved for each fiber. This coordinated shuffle greatly slows down the test process, and is error prone. Page 6 of 6

99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com

99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more

More information

What testing is required for PREMISES Fiber Optic Cabling and the standards used

What testing is required for PREMISES Fiber Optic Cabling and the standards used Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic

More information

Fibre optic testing best practices

Fibre optic testing best practices Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is

More information

Understanding Fiber Polarity: Implications at 10G, 40G, & 100G

Understanding Fiber Polarity: Implications at 10G, 40G, & 100G Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we

More information

Polymer Coated Fiber Cable (PCF)

Polymer Coated Fiber Cable (PCF) Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability

More information

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year

More information

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various

More information

The Need for Low-Loss Multifiber Connectivity

The Need for Low-Loss Multifiber Connectivity WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially

More information

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Cabling & Test Considerations for 10 Gigabit Ethernet LAN Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit

More information

Fiber in the Data Center

Fiber in the Data Center Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation

More information

How To Make A Data Center More Efficient

How To Make A Data Center More Efficient Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence

More information

Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices

Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether

More information

Overcoming OM3 Performance Challenges

Overcoming OM3 Performance Challenges White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management

More information

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General

More information

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process

More information

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH

More information

Measuring of optical output and attenuation

Measuring of optical output and attenuation Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter

More information

MPO. Fast Fibre Solution for Data Centres

MPO. Fast Fibre Solution for Data Centres MPO Fast Fibre Solution for Data Centres Benefits The Plug & Play MPO solution of Nexans Cabling Solutions provides a comprehensive line of pre-terminated and pre-tested assemblies to meet the current

More information

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables

More information

Arista 40G Cabling and Transceivers: Q&A

Arista 40G Cabling and Transceivers: Q&A Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range

More information

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide

More information

Network Monitoring - Fibre TAP Modules

Network Monitoring - Fibre TAP Modules Network Monitoring - Fibre TAP Modules It all started with. Bend insensitive MM fibre Smaller diameter cables Cable with tighter bend radius Less space in the DC, More organised cable management Greater

More information

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing

More information

How To Properly Maintain A Fiber Optic Infrastructure

How To Properly Maintain A Fiber Optic Infrastructure How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope

More information

Fibre Channel Fiber Cabling

Fibre Channel Fiber Cabling OVERVIEW This paper will discuss the Fibre Channel standards for fiber cables at both 1Gb and 2Gb speeds, and also some discussion of departures from standard. Items discussed will be cable types, plug

More information

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009 Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made

More information

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village Brno, Marec 2014 Physical Infrastructure trends and certification requirements for Datacenters Ing. Peter Potrok PROFiber Networking s.r.o. Psiber s Global Village London Munich San Diego Boston Paris

More information

Accurately Testing fibre Optic Cables

Accurately Testing fibre Optic Cables Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty

More information

How To Make A Fibre Cable For A Data Centre

How To Make A Fibre Cable For A Data Centre LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF

More information

Kit Highlights and Key Features

Kit Highlights and Key Features AF-OLK6 Series Fiber Optic Test kit (Data Storage Kit) Product: OLK6 Series Date: Aug:2007 Rev: 01 Description The AF-OLK6 series test kits are the complete solution necessary for the installer to test,

More information

Obsolete Fiber Technology? Not in my Data Center!

Obsolete Fiber Technology? Not in my Data Center! Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are

More information

TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning

TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning TEST & INSPECTION Featured Data Center Products M310 Enterprise OTDR with TruEvent Technology Designed for Enterprise Network Testing, Troubleshooting and Documentation, the M310 with TruEvent technology

More information

Optimizing Infrastructure Support For Storage Area Networks

Optimizing Infrastructure Support For Storage Area Networks Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle

More information

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction... LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper

More information

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM Testing and troubleshooting enterprise fiber-optic cabling Presenter: Neftali Usabal Fluke Networks - LATAM Agenda Testing Methods and Standards Why we test optical systems Terminology & types of testing

More information

Zone Distribution in the Data Center

Zone Distribution in the Data Center Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling

More information

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of

More information

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts [email protected] Cabling considerations for DCs and

More information

Patch Cords for Data Center Applications

Patch Cords for Data Center Applications Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable Fiber Optic Cable Assemblies Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable 1 Cable assemblies used in patch panels (Fiber Distribution Units) are an essential interface

More information

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING

More information

Optical Power Meter. Specification & User Manual

Optical Power Meter. Specification & User Manual Optical Power Meter Specification & User Manual Page 1 of 9 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4

More information

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned) 1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled

More information

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized

More information

Upgrading Path to High Speed Fiber Optic Networks

Upgrading Path to High Speed Fiber Optic Networks SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method

More information

ST800K-U Optical Power Meter. User Manual V1.0

ST800K-U Optical Power Meter. User Manual V1.0 User Manual V1.0 Contents 1. Summary... 1 2. Functions... 2 3. Specifications... 2 4. Layout... 4 5. Operation... 5 6. Maintenance... 7 7. Faults & Solutions... 8 8. Appendix A...9 9. Appendix B...11 10.

More information

Field Measurements of Deployed Fiber

Field Measurements of Deployed Fiber Field Measurements of Deployed Fiber Robert J. Feuerstein Level 3 Communications, 1025 Eldorado Boulevard, Broomfield, Colorado 80021 [email protected] Abstract: New generations of ultra-long

More information

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths

More information

The Conversion Technology Experts. Fiber Optics Basics

The Conversion Technology Experts. Fiber Optics Basics The Conversion Technology Experts Fiber Optics Basics Introduction Fiber optic technology is simply the use of light to transmit data. The general use of fiber optics did not begin until the 1970s. Robert

More information

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide

More information

Reliable, Consistent, Quality

Reliable, Consistent, Quality Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic

More information

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

Enterprise Networks EMEA. Core Products FOR DATA CENTRES Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for

More information

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Features: SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Low insertion loss < 0.2 db Excellent repeatability FC/PC, SC, ST, LC, MU, E2000 termination available Custom ferrule termination available Designed

More information

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1 Introduction Data centers are the central location for data interchange and are found in enterprises, government

More information

7.4 3M No Polish Connector

7.4 3M No Polish Connector Cap Fibre Splice Element Description 3M No Polish Connector (NPC) enables fast, on-site installation of 250μm and 900μm connections utilizing a one piece, pre-assembled design. The SC compatible connector

More information

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) Features: DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) PATENT NUMBERS: CANADA 2,494,133, USA 7095931, 7295731 AND CHINA 1672073 Telcordia GR-468 qualified Available in versions for any wavelength

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

CISCO 10GBASE X2 MODULES

CISCO 10GBASE X2 MODULES DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity

More information

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large

More information

SECURE Fiber Optic Products

SECURE Fiber Optic Products SECURE Fiber Optic Products LC SECURE Fiber Optic Products (Pages 9 and 10) LC SECURE Connectors, Cable Assemblies and Adapters MPO SECURE Fiber Optic Products (Pages 11 and 12) MPO SECURE Cable Assemblies

More information

Fiber Coupler Overview

Fiber Coupler Overview Fiber Coupler Overview Couplers High channel density Pitch Reducing Optical Fiber Array (PROFA) with or without spot-size reduction: Builds on proven spot-size converting (SSC) technology - highest spatial

More information

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber

More information

HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable

HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable Overview Models HP 0.5 m Multimode OM3 LC/LC Optical Cable HP 1 m Multimode OM3 LC/LC Optical Cable HP 2 m Multimode OM3 LC/LC Optical Cable HP 5 m Multimode OM3 LC/LC Optical Cable HP 15 m Multimode OM3

More information

Field Installable Optical Connector for Cables

Field Installable Optical Connector for Cables Field Installable Optical Connector for Cables Daigo Saito 1, Kazuhiro Takizawa 1, Kazuya Ogata 1, and Tan Khee Yen Serin 2 With the rapid expansion of fiber to the home (FTTH) in Japan, mechanical splices

More information

The High Cost of a Low-Cost Cable Certification Tester

The High Cost of a Low-Cost Cable Certification Tester The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester

More information

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH

More information

Secure/Keyed LC System Solutions Overview

Secure/Keyed LC System Solutions Overview Secure/Keyed LC System Solutions Overview Designing performance and efficiency into your secure network Introduction In recent years, physically discrete fiber connection systems have emerged to respond

More information

MTP Optical Fibre Configurations

MTP Optical Fibre Configurations MTP Optical Configurations ackground The Excelerator MPO range from Excel utilises the MTP Elite connector manufactured by US Conec. The range is made up of: MTP to MTP Trunk Cables MTP to LC s MTP Patch

More information

DIAMOND AVIM Connector

DIAMOND AVIM Connector DIAMOND AVIM Connector Fiber optic connector for space applications Dr. François CALOZ, accredited laboratory Frédéric TAUGWALDER, Engineering DIAMOND SA - OCT. 2005 - ATELIER CONNECTIQUE - CNES 1 Motivation

More information

How To Get A Better Signal From A Fiber To A Coax Cable

How To Get A Better Signal From A Fiber To A Coax Cable Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom

More information

NaviTEK II. idealnwd.co.uk. Save money through using a single multifunction device for testing copper and fibre networks

NaviTEK II. idealnwd.co.uk. Save money through using a single multifunction device for testing copper and fibre networks Save money through using a single multifunction device for testing copper and fibre networks Increase efficiency by simplifying and accelerating cable installation and network troubleshooting Reduce downtime

More information

Industry solutions: Broad cast

Industry solutions: Broad cast Industry solutions: Broad cast BC 2 industry solutions: Broadcast Optical Cable Corporation s broad range of Fiber Optic Broadcast Cables are specifically designed for real-time transmission of high definition

More information

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING

More information

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher

More information

HIGH QUALITY FOR DATA CENTRES ACCESSORIES AND INFRASTRUCTURE. PRODUCT CATALOG 12/2014 PRO-ZETA a.s.

HIGH QUALITY FOR DATA CENTRES ACCESSORIES AND INFRASTRUCTURE. PRODUCT CATALOG 12/2014 PRO-ZETA a.s. HIGH QUALITY ACCESSORIES AND INFRASTRUCTURE FOR DATA CENTRES PRODUCT CATALOG 12/2014 PRO-ZETA a.s. COMPANY PROFILE PROZETA is a high tech IT company founded in 1991, providing hardware distribution, connectivity

More information

Data Center Design for 40/100G

Data Center Design for 40/100G Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an

More information

FIBER OPTIC ISOLATORS

FIBER OPTIC ISOLATORS Features: >0W Optical power handling capability Polarization Sensitive and Insensitive versions Product offerings over 3 000 nm wavelength range High isolation levels and low return loss Low Insertion

More information

Modern Data Center needs 10 th of April, 2014. Andrew Sedman, RCDD Head of Training and Technical Service R&M

Modern Data Center needs 10 th of April, 2014. Andrew Sedman, RCDD Head of Training and Technical Service R&M Modern Data Center needs 10 th of April, 2014 Andrew Sedman, RCDD Head of Training and Technical Service R&M From the Classical Data Center to the Cloud Prior to cloud computing, a physical server handled

More information

DATA CENTRES POWERED BY EXCEL

DATA CENTRES POWERED BY EXCEL DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,

More information

Enabling 21 st Century Connectivity

Enabling 21 st Century Connectivity Enabling 21 st Century Connectivity First MXC Adopters meeting March 11, 2014 MXC is a trademark of US Conec Presenters Victor Krutul Director Marketing, Intel Corp Mike Hughes Director, Product Management,

More information

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780 Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry

More information

TIER-1/TIER-2 FIBER CERTIFICATION KITS

TIER-1/TIER-2 FIBER CERTIFICATION KITS MaxTester 940 Fiber Certifier OLTS TIER-1/TIER-2 FIBER CERTIFICATION KITS EXFO s Fiber Certification kits cover all test requirements to perform clear, fast and first-time-right system acceptance. This

More information

SignalTEK II. Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers

SignalTEK II. Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers Increase efficiency through simplifying and accelerating cable installation including

More information

Attaching the PA-A1-ATM Interface Cables

Attaching the PA-A1-ATM Interface Cables CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.

More information

Plug & Play Universal Systems

Plug & Play Universal Systems Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution

More information

ETD Fiber Optic Products

ETD Fiber Optic Products ETD Fiber Optic Products ETD manufactures and supplies a wide range of passive fiber optic components and solutions for the European Data, Telecom and FTTX environment. ETD has worked in the Fiber Optic

More information

Cable Assemblies. Features and Benefits

Cable Assemblies. Features and Benefits Features and Benefits Flame-retardant jacket Rugged and durable Superior Performance Testing Every termination is tested to ensure the highest in network performance State-Of-The-Art Manufacturing Processes

More information

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network WP4270 Issued: June 2011 Authors: Carl Roberts and Merrion Edwards Introduction

More information

AMP NETCONNECT Data Center Cabling Solutions

AMP NETCONNECT Data Center Cabling Solutions AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports

Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports (800-0037) Doc. PUBTPASXSFPU Rev., 07/08 Contents Introduction.... Key Features... Unpacking and Inspection....3 Product

More information

APPLICATION NOTE POLARIZATION MEASUREMENTS

APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS LTD. APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS FAMILY OF POLARIZATION MAINTAINING COMPONENTS, SOURCES, AND MEASUREMENT SYSTEMS The information/data furnished in this document shall

More information

Insertion Losses of Fiber Optical Connectors

Insertion Losses of Fiber Optical Connectors Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins

More information

M310 Data Center OTDR

M310 Data Center OTDR Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone

More information

MTP Solutions. MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS

MTP Solutions. MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS MTP Solutions MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS 1 MTP Solutions for High Density Networks The Right MTP Solution Reduce deployment time and improve

More information