Loss & Continuity Testing with MPO/ MTP Connectors
|
|
|
- Emmeline Thompson
- 10 years ago
- Views:
Transcription
1 Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular installation issues. Here we give an overview of how to tackle various issues related to testing the cabling for these systems. We mainly discuss multimode systems, however single mode ribbon fiber systems share very many common practices. Typically these deployments are for 40G / 100G Ethernet. Cabling may be installed for 100G Ethernet even if the immediate requirement is 40G, to allow for later incremental bandwidth upgrades. The 24 fibers used for 100G Ethernet can alternatively be used to carry three 40G systems. So this allows a choice of upgrade paths, eg to upgrade incrementally to 120G aggregate capacity by adding two extra 40G channels, or replace a 40G system with a single 100G channel. Standards are in development for 400G Ethernet. The incremental cost of installing 24 fiber 100G cabling, instead of 12 fiber 40G cabling, is actually quite modest, particularly in comparison to later re-wiring and facility disruption. The major additional cabling complexity may be a patch panel with breakout connections, which provides connection flexibility for future deployment options. Standards Compliance Internationally recognised standards are now in place, which define just about everything to do with data centre design. Just in the area of fiber optic cabling, there are standards for fiber types (Typically multimode OM3. OM4 etc), cable types (fire retardance, bend resistance, riser cables etc), cable installation (fire stops, ducting etc) connectors (LC, MPO etc), labelling conventions, Ethernet, optical wavelengths (CWDM etc), optical safety (mandatory), and finally: cable acceptance testing. Page 1 of 6
2 There is one aspect of the standards for fiber acceptance testing that everyone can agree on: they are currently a work in progress, and this is particularly true of MPO testing. So at the project definition stage, it is a good idea to review and refine the fiber cable acceptance test requirements, which sensibly end up as a combination of standards based requirements and the mandatory atory requirements of the particular transmission equipment in use. A good review at this point can reduce project cost, increase facility utilisation, and increase the useful LAN lifetime. A Very Small Acceptable Optical Loss! The majority of LAN transmission sion systems using MPO/MTP connectors have extremely tight end-todb. This tiny loss figure creates unique challenges end optical loss requirements, perhaps around 1.5 for precision loss measuring for cable certification. Much of the currently available test equipment and procedures do not achieve a level of repeatability (accuracy) that gives confidence that the tight specification has been achieved. The two reasons for this tight specification are to minimise per port electronics cost, and also because these systems are dispersion limited, not power limited. These systems use 850 nm and 50 micron core fiber, and end to end length is usually limited (by dispersion) to around 300 meters. Inspection & Cleaning Connector condition and cleanliness is a very major consideration, and is a most common cause of problems. Absolutely essential is a good quality microscope with an MPO/MPT specific adaptor, a supply of suitable specific cleaning materials (more than one type is good), and adequate time and know-how to use them. The default available MPO cleaners tend to do a reasonable job of cleaning the fiber ends only, but extra cleaning materials should be available to clean alignment pins, and sometimes the whole connector end face. Inspection and cleaning should be performed every time before a connector is mated. Cabling Disturbance Because of the combination of very low loss requirements, high fiber complexity and modest connector performance, it is essential that final testing and commissioning are accomplished with the lowest possible level of disturbance to connections. Also, once loss testing is done, any cabling disturbance might require the loss testing to be repeated. This means that an unusually strict test regime is appropriate, so that each acceptance level is completed with exceptional confidence. You Page 2 of 6
3 want to avoid going back in and disturbing things. For this reason, we suggest a phased approach as being most practical. Continuity Testing This is the most basic test: Does light get from end to end? As a minimum, this test is easily accomplished with a VFL source and one low quality breakout cable to connect to the VFL. Continuity testing usually doesn t need documenting. If a numbered low quality breakout cord is used each end, this could also double as a polarity test phase. The continuity test phase is usefully accompanied by thorough cleaning and inspection of the connectors. This achieves a few objectives. Bad connectors are the main cause of installation failures. Doing this here enables the installer to identify & re-work/replace bad connectors at the earliest (lowest cost) point, avoiding later cable disturbance. It also ensures that a bad connector does not contaminate the test cords or degrade other connectors. If the connector quality is inadequate, there may be little point proceeding further until this issue is fixed. Simple continuity testing has one big problem: it doesn t identify if fibers are swapped around. So for this we talk of: Polarity Testing Typically, the cable installation requires polarity testing, to ensure that a 1 n array of fibers at one end of a system, is correctly mapped to a 1 n array of fiber the other end. If the installation has a patch cable section so that connections can be split off to particular transmission equipment, niggling polarity mistakes can occur here. The polarity test needs a very high level of confidence, since if not 100% correct, there is no chance of a working outcome, and there could be a great deal of wasted work to find the swapped fibers. This will probably want a basic level of documenting, sufficient to record which fibers were tested, and the general array direction. Labelling You now have your system physically in place and light going to and fro in the right combinations. This is the perfect time to double-check and rectify all associated labelling, otherwise the next phase of loss testing could result in incorrect re-assembly due to discovered faults. Up to this point, the work has required a very methodical approach, however has otherwise been quite straightforward. Loss Testing Accuracy & Confidence Issues People use the terms repeatability, accuracy, reproducibility or uncertainty somewhat interchangeably. For loss testing in particular, there is little practical difference between them all, so we will use the term uncertainty. The real issue is what uncertainty happens when repeatedly measuring one item with different items of test equipment or test cords. Page 3 of 6
4 Quoted uncertainty values always imply a ± value, whether specifically mentioned or not. For example, a quoted uncertainty of 0.1dB is the same as ±0.1dB, usually with a 95% confidence level. As mentioned, the acceptable maximum loss figure may only be 1.5 db. If the test uncertainty is say 0.3 db, then measured losses from db are marginal, and the maximum test value for guaranteed operation is 1.2 db. So every small improvement in uncertainty, yields a usefully larger allowable measured loss level, which will reduce installation cost. This easily explains the previous care on planning test cords, doing cleaning etc. In practice, repeatability / accuracy is optimised by a number of factors: 1. Use of low loss Elite test cords, and ensuring they are in top condition. 2. Use of an Encircled Flux compliant test source, followed by a mandrel wrap. 3. Use of very accurate loss test equipment, remembering that you are working on the limits of achievable loss test accuracy. For typical 850 nm testing, do not use an InGaAs power meter detector, since it is too wavelength sensitive and so reduces practical accuracy. The light source must also be highly repeatable and stable when the connected test cord is moved around. 4. Rigorous inspection and cleaning every time a connector is mated. 5. Performing test cord verification at the start of the job. 6. Use of appropriate data recording systems, since there will be plenty of test data. Test Cords A major loss test consideration is the test cord loss performance. As can be seen from the table, Elite MPO / MTP cords are available with per connector / fiber loss of below 0.35 db. Otherwise standard cords are clearly inadequate for testing. Here are the USConnec specifications for these connectors, and also shows why it is so undesirable to disturb the cabling after testing. MM MT Elite Multimode MT Standard Multimode MT SM MT Elite Single-mode MT Standard Single-mode MT Insertion Loss 0.1 db Typical (All 0.35 db Maximum 0.20 db Typical (All 0.60 db Maximum 0.10 db Typical (All 0.35 db Maximum 0.25 db Typical (All 0.75 db Maximum Optical Return Loss > 20 db > 20 db > 60 db (8 Angle Polish) > 60 db (8 Angle Polish) Testing will probably need a combination of straight MPO-MPO test cords, and breakout cords. Also ensure that connector pin polarities are correct, since trying to swap these pins in the field is not viable. A few tested through-connects is also helpful. Spare test cords will be required, in case some get degraded or damaged. The typical application environment uses a mix of LC and multi fiber connectors. So naturally one might assume that LC MPO breakout test cords are an obvious choice. However SC MPO Page 4 of 6
5 breakout cords are typically more robust, easier to handle, and offer slightly improved optical performance. However, SC-LC connections give inferior performance. Number the cords and label each end A/B. Test cords require Performance Verification before each use. This performance verification test is quite specific, and failure to do this preliminary test may invalidate all the following test results. The basic objective of the performance test is to ensure that the loss of the cords meets the basic accuracy requirements. However, there is a sting in this tail as follows: The test standards require a loss of eg 0.1 db or better for multimode fiber The elite average loss meets this specification However the actual per fiber maximum loss does not. We hope the standards folk will resolve this in due course. One potential way around this is that if the actual loss of each connection is recorded for each fiber during this test, then this loss can be used to compensate the following test results and improve accuracy. However in practice, this is excessively hard to implement, so the practical policy is to only use good cords. The Test Cord Verification Test is quite simple: test each test cord connector using two reference cords, and the loss of the connection must be within the allowed limit. In the case of MPO connectors, this will take a bit longer due to the number of fibers. What Test Uncertainty can I expect? This is a much discussed issue. Without going into any great detail, there are a few obvious pointers: The test cord performance test using Elite connectors could have losses of from db per connector, giving a per mated connector uncertainty of ±0.18 db, This means that any overall test uncertainty must be at least ±0.18 db, and is likely to be larger once other factors as included. However once the test cords are plugged into presumably lower grade cords, the loss there could possibly jump to db, giving a minimum per mated connector uncertainty of ±0.38 db. These are simple deductions based on connector specifications, and calculated uncertainty including all factors could only get worse. Alternatively, if suitable experiments are performed with the actual equipment and test cords, it may be possible to demonstrate a lower level of uncertainty, however this is specific to a particular item of test equipment, and particular test cords, and so has limited viability. General Loss Test equipment Choices There are three broad choices to make, which will depend on the scale of expected work: 1. Use a basic source and meter. This is excessively fiddly to perform, and so prone to error, since both instruments need moving for each fiber to be tested, so it s only sensible for a very small project. Page 5 of 6
6 2. Use a basic source and special MPO compatible meter, so that only the source needs moving for each fiber. For a modest equipment cost, this greatly simplifies testing. This also works for any fiber type, wavelength, or number of fibers per connector, or MPO pin configuration, so it has excellent flexibility, and the same equipment can be used for other work. A good choice for many mid-size projects, or cabling contractors. 3. A special MPO test set, However these usually only work at 850 nm and 12 fibers, so they are both expensive and inflexible, and so are useful for a specific large project. They are not so useful for testing breakout cables. Many such units on the market today also have InGaAs detectors, which significantly degrade their test accuracy at 850 nm. They have limited MPO pin configuration compatibility, which may limit referencing options. Whatever test equipment is selected will need some good reporting software. It may be a project requirement that it s impossible to modify the test results, to prevent tampering. Procedure Loss testing using solution 2 will generally proceed as follows (remembering to inspect and clean on each insertion): 1. Begin by verifying the test cords. Once these are proven to be adequate: 2. Reference the source and meter using a breakout cable and the desired number of reference cords. 3. Set up the MPO power meter at the far end of the test system 4. Start with the light source at fiber 1 on the breakout cable, take the loss reading 5. Move the light source only to the next fiber on the breakout cord, and take the loss reading 6. Etc 7. Go back to fiber 1 and note the reading (is within limits compared to the 1 st time) We found that using a Kingfisher light source KI2803 with power meter KI2600XL-Ge5, and this technique, the repeatability was determined by the test cords. Ease of testing and speed were both good, since only the source needed moving for each fiber. Loss testing using solution 1 will differ in that the power meter will need to be moved for each fiber. This coordinated shuffle greatly slows down the test process, and is error prone. Page 6 of 6
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
What testing is required for PREMISES Fiber Optic Cabling and the standards used
Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various
The Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
Fiber in the Data Center
Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation
How To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices
Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
Measuring of optical output and attenuation
Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter
MPO. Fast Fibre Solution for Data Centres
MPO Fast Fibre Solution for Data Centres Benefits The Plug & Play MPO solution of Nexans Cabling Solutions provides a comprehensive line of pre-terminated and pre-tested assemblies to meet the current
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
Arista 40G Cabling and Transceivers: Q&A
Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
Network Monitoring - Fibre TAP Modules
Network Monitoring - Fibre TAP Modules It all started with. Bend insensitive MM fibre Smaller diameter cables Cable with tighter bend radius Less space in the DC, More organised cable management Greater
Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
Fibre Channel Fiber Cabling
OVERVIEW This paper will discuss the Fibre Channel standards for fiber cables at both 1Gb and 2Gb speeds, and also some discussion of departures from standard. Items discussed will be cable types, plug
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village
Brno, Marec 2014 Physical Infrastructure trends and certification requirements for Datacenters Ing. Peter Potrok PROFiber Networking s.r.o. Psiber s Global Village London Munich San Diego Boston Paris
Accurately Testing fibre Optic Cables
Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty
How To Make A Fibre Cable For A Data Centre
LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF
Kit Highlights and Key Features
AF-OLK6 Series Fiber Optic Test kit (Data Storage Kit) Product: OLK6 Series Date: Aug:2007 Rev: 01 Description The AF-OLK6 series test kits are the complete solution necessary for the installer to test,
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning
TEST & INSPECTION Featured Data Center Products M310 Enterprise OTDR with TruEvent Technology Designed for Enterprise Network Testing, Troubleshooting and Documentation, the M310 with TruEvent technology
Optimizing Infrastructure Support For Storage Area Networks
Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle
Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM
Testing and troubleshooting enterprise fiber-optic cabling Presenter: Neftali Usabal Fluke Networks - LATAM Agenda Testing Methods and Standards Why we test optical systems Terminology & types of testing
Zone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network
Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts [email protected] Cabling considerations for DCs and
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable
Fiber Optic Cable Assemblies Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable 1 Cable assemblies used in patch panels (Fiber Distribution Units) are an essential interface
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Optical Power Meter. Specification & User Manual
Optical Power Meter Specification & User Manual Page 1 of 9 Copyright 2011 reserves the right to modify specifications without prior notice Table of Contents 1. Description and Features.......3 2. Specification......4
12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)
1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
ST800K-U Optical Power Meter. User Manual V1.0
User Manual V1.0 Contents 1. Summary... 1 2. Functions... 2 3. Specifications... 2 4. Layout... 4 5. Operation... 5 6. Maintenance... 7 7. Faults & Solutions... 8 8. Appendix A...9 9. Appendix B...11 10.
Field Measurements of Deployed Fiber
Field Measurements of Deployed Fiber Robert J. Feuerstein Level 3 Communications, 1025 Eldorado Boulevard, Broomfield, Colorado 80021 [email protected] Abstract: New generations of ultra-long
MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths
The Conversion Technology Experts. Fiber Optics Basics
The Conversion Technology Experts Fiber Optics Basics Introduction Fiber optic technology is simply the use of light to transmit data. The general use of fiber optics did not begin until the 1970s. Robert
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
Reliable, Consistent, Quality
Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic
Enterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS
Features: SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Low insertion loss < 0.2 db Excellent repeatability FC/PC, SC, ST, LC, MU, E2000 termination available Custom ferrule termination available Designed
Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels
Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1 Introduction Data centers are the central location for data interchange and are found in enterprises, government
7.4 3M No Polish Connector
Cap Fibre Splice Element Description 3M No Polish Connector (NPC) enables fast, on-site installation of 250μm and 900μm connections utilizing a one piece, pre-assembled design. The SC compatible connector
DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)
Features: DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) PATENT NUMBERS: CANADA 2,494,133, USA 7095931, 7295731 AND CHINA 1672073 Telcordia GR-468 qualified Available in versions for any wavelength
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
CISCO 10GBASE X2 MODULES
DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
SECURE Fiber Optic Products
SECURE Fiber Optic Products LC SECURE Fiber Optic Products (Pages 9 and 10) LC SECURE Connectors, Cable Assemblies and Adapters MPO SECURE Fiber Optic Products (Pages 11 and 12) MPO SECURE Cable Assemblies
Fiber Coupler Overview
Fiber Coupler Overview Couplers High channel density Pitch Reducing Optical Fiber Array (PROFA) with or without spot-size reduction: Builds on proven spot-size converting (SSC) technology - highest spatial
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable
Overview Models HP 0.5 m Multimode OM3 LC/LC Optical Cable HP 1 m Multimode OM3 LC/LC Optical Cable HP 2 m Multimode OM3 LC/LC Optical Cable HP 5 m Multimode OM3 LC/LC Optical Cable HP 15 m Multimode OM3
Field Installable Optical Connector for Cables
Field Installable Optical Connector for Cables Daigo Saito 1, Kazuhiro Takizawa 1, Kazuya Ogata 1, and Tan Khee Yen Serin 2 With the rapid expansion of fiber to the home (FTTH) in Japan, mechanical splices
The High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
Secure/Keyed LC System Solutions Overview
Secure/Keyed LC System Solutions Overview Designing performance and efficiency into your secure network Introduction In recent years, physically discrete fiber connection systems have emerged to respond
MTP Optical Fibre Configurations
MTP Optical Configurations ackground The Excelerator MPO range from Excel utilises the MTP Elite connector manufactured by US Conec. The range is made up of: MTP to MTP Trunk Cables MTP to LC s MTP Patch
DIAMOND AVIM Connector
DIAMOND AVIM Connector Fiber optic connector for space applications Dr. François CALOZ, accredited laboratory Frédéric TAUGWALDER, Engineering DIAMOND SA - OCT. 2005 - ATELIER CONNECTIQUE - CNES 1 Motivation
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
NaviTEK II. idealnwd.co.uk. Save money through using a single multifunction device for testing copper and fibre networks
Save money through using a single multifunction device for testing copper and fibre networks Increase efficiency by simplifying and accelerating cable installation and network troubleshooting Reduce downtime
Industry solutions: Broad cast
Industry solutions: Broad cast BC 2 industry solutions: Broadcast Optical Cable Corporation s broad range of Fiber Optic Broadcast Cables are specifically designed for real-time transmission of high definition
Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems
SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram
Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher
HIGH QUALITY FOR DATA CENTRES ACCESSORIES AND INFRASTRUCTURE. PRODUCT CATALOG 12/2014 PRO-ZETA a.s.
HIGH QUALITY ACCESSORIES AND INFRASTRUCTURE FOR DATA CENTRES PRODUCT CATALOG 12/2014 PRO-ZETA a.s. COMPANY PROFILE PROZETA is a high tech IT company founded in 1991, providing hardware distribution, connectivity
Data Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
FIBER OPTIC ISOLATORS
Features: >0W Optical power handling capability Polarization Sensitive and Insensitive versions Product offerings over 3 000 nm wavelength range High isolation levels and low return loss Low Insertion
Modern Data Center needs 10 th of April, 2014. Andrew Sedman, RCDD Head of Training and Technical Service R&M
Modern Data Center needs 10 th of April, 2014 Andrew Sedman, RCDD Head of Training and Technical Service R&M From the Classical Data Center to the Cloud Prior to cloud computing, a physical server handled
DATA CENTRES POWERED BY EXCEL
DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,
Enabling 21 st Century Connectivity
Enabling 21 st Century Connectivity First MXC Adopters meeting March 11, 2014 MXC is a trademark of US Conec Presenters Victor Krutul Director Marketing, Intel Corp Mike Hughes Director, Product Management,
M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry
TIER-1/TIER-2 FIBER CERTIFICATION KITS
MaxTester 940 Fiber Certifier OLTS TIER-1/TIER-2 FIBER CERTIFICATION KITS EXFO s Fiber Certification kits cover all test requirements to perform clear, fast and first-time-right system acceptance. This
SignalTEK II. Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers
Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers Increase efficiency through simplifying and accelerating cable installation including
Attaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
Plug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
ETD Fiber Optic Products
ETD Fiber Optic Products ETD manufactures and supplies a wide range of passive fiber optic components and solutions for the European Data, Telecom and FTTX environment. ETD has worked in the Fiber Optic
Cable Assemblies. Features and Benefits
Features and Benefits Flame-retardant jacket Rugged and durable Superior Performance Testing Every termination is tested to ensure the highest in network performance State-Of-The-Art Manufacturing Processes
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network WP4270 Issued: June 2011 Authors: Carl Roberts and Merrion Edwards Introduction
AMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports
Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports (800-0037) Doc. PUBTPASXSFPU Rev., 07/08 Contents Introduction.... Key Features... Unpacking and Inspection....3 Product
APPLICATION NOTE POLARIZATION MEASUREMENTS
OZ OPTICS LTD. APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS FAMILY OF POLARIZATION MAINTAINING COMPONENTS, SOURCES, AND MEASUREMENT SYSTEMS The information/data furnished in this document shall
Insertion Losses of Fiber Optical Connectors
Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins
M310 Data Center OTDR
Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone
MTP Solutions. MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS
MTP Solutions MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS 1 MTP Solutions for High Density Networks The Right MTP Solution Reduce deployment time and improve