1 Compatibility of Bend Optimized Multimode Fibers White Paper Issued September 2009

2 Optimized Low Bend for the Use of Fibers In The Home The current migration of optical fibers closer to and even into the home has increased service providers interests in new fibers with improved bending performance. After the successful introduction of low bend SM fibers, several leading fiber manufacturers have recently launched bend optimized versions of their premium high bandwidth (OM3, OM4) multimode fiber products, so as to reduce or even eliminate challenges encountered during fiber installations. To confirm their promises, we examined bend optimized OM3 fiber performances of different companies in real world conditions when compared to standard multimode fibers. The investigations proved that these bend optimized fibers are good candidates for loss and bend critical applications (such as indoor wiring) because of their higher immunity to bending losses, without loosing performances or compatibility to other standard high bandwidth multimode fibers. New fibers need improved bending performance for the use in the home Roger Krähenbühl, Ph.D. R+D Technology Fiber Optics Division HUBER+SUHNER AG 9100 Herisau, Switzerland Hanspeter Schiess Product Unit Manager Fiber Optics Division HUBER+SUHNER AG 9100 Herisau, Switzerland Claudio Cecchin Product Unit Manager Fiber Optics Division HUBER+SUHNER AG 9100 Herisau, Switzerland 2

3 New Challenges Created from new Applications Introduction Optical fibers have already been used for a long time in environments where small bends were not a major requirement. Recently, indoor and data center applications with tighter restrictions have led to investigations in the bending performance of optical fibers. First, the optical network market has seen a flurry of introductions of various grades of low bend radii singlemode fibers [1], with the consequence of recent updates to the low bend fiber standard (ITU G.657). Despite the absence of a bend insensitive multimode fiber standard, recently, extended band width (ISO/IEC OM3, OM4) multimode fiber (MMF) with enhanced macro bending performance were introduced [2][3], designed to reduce and, in some cases, eliminate the cable bending challenges encountered in installations in local area networks (LAN), data centers and other enterprise applications. Tighter restructions for the bending performance due to the use of optical fibers in indoor applications Compared with singlemode optical fibers, multimode fibers have a larger core that guide multiple modes (or rays) of light simultaneously. Modes traveling at the outside edge of the core have a longer distance to go than modes that travel near the center of the core (modal dispersion). To minimize this modal dispersion and thereby maximize bandwidth, special care is taken in the profile design of the refractive index [3]. Proper design (parabolic shape) will slow down modes with a shorter distance so that all modes arrive at the end of the fiber as close in time as possible. Such improvements resulted in products that fulfill bandwidth requirements as given in the OM3 and the just recently published OM4 standards. Important profile design When you bend a traditional optical fiber, the tendency is for the light to keep going straight and escape from the fiber. As the bend radius decreases, the amount of light that leaks out of the core increases. This escaped light causes signal degradation and increases the potential for transmission errors. To enhance bend performance in multimode fibers a unique approach is required (as compared to singlemode fiber) to influence the many modes of light traveling down the core without adversely affect fiber bandwidth (modes arriving simultaneously). After attempts to address bending in multimode fibers reaching only low bandwidth performance, new bend optimized multimode fibers now are able to deliver superior bandwidth performance in an ultra-bendable package without requiring any adjustments to standard field installation, termination monitoring, or maintenance procedures. The bend improvement in these new multimode fibers is achieved through the use of a specially engineered optical barrier (trench) that traps the many modes within the fiber core. This optical trench ensures that the outer modes, which traditionally have a higher tendency to "leak" out of a multimode fiber when it is subjected to bends, stay put [4]. By keeping these modes within the core of the fiber, much less of the information carrying signal is lost and more information gets to the end user without dropped packets or corrupted data. Preventing the escape of the light 3

4 New Challenges Created from new Applications Such bend optimized fibers claim to obtain extremely low bending loss at both 850nm and 1300nm, while keeping the advantages of existing OM3/OM4 fibers. These fibers should be bendable down to a radius of 7.5mm with less than 0.2dB added loss at 850nm. At a 15mm radius the added loss is less than 0.1dB. This is up to a 10x improvement in bend loss compared with traditional multimode bending standards (Table 1). To verify these claims, prove their usability and interoperability to standard MMF, we examined the most widely used products. We took the bend optimized fiber type MaxCap -BB-OM3/OM4 of Draka, ClearCurve OM3 fiber of Corning and LaserWave FLEX of OFS, to execute different tests and simulate daily use while comparing them to standard OM2 and OM3 fibers. Extremely low bending loss IEC ITU G Bend optimized Bending radius 37.5 mm 15 mm 15 mm 7.5 mm Number of turns Max 850 nm 0.5 db 1.0 db 0.1 db 0.2 db Max 1300 nm 0.5 db 1.0 db 0.3 db 0.5 db Table 1 Multimode bend standards and specifications given by the fiber manufacturers for the new bend optimized fibers. For the following tests these types of fibers and standard OM2/OM3 of the same manufacturers were used to fabricate properly but neutrally marked 0.9mm semi-tight tubes (Figure 1, left) and 2.0mm indoor type simplex cables (Figure 1, right). Figure 1 Bend optimized fibers (BO1-BO3) and standard OM2/OM3 fibers of different manufacturers in 0.9 mm semi-tight tubes (left) and in 2.0 mm indoor type simplex cables (right). 4

5 Bending Performance Bending performance To determine the bending performance of all 0.9 mm type tube samples, standardized bending loss tests (IEC E11A) were carried out. Thereby the induced fiber attenuations for different number of turns, on mandrels with different radii at selected wavelength were monitored. The non-linear behavior of the results obtained for consecutive number of turns around a mandrel with r = 5 mm at λ = 850 nm (Figure 2, left) is an indication of the mode filtering (outer modes are less guided) effect of MMF bending. Together with the bending radius dependency (Figure 2, middle), it is apparent that bend optimized fibers (reddish lines) present a well improved bending loss behavior compared to standard OM2 and OM3 fibers (bluish lines) and clearly fulfill the performance specification (0.1 db for two turns around r = 7.5 mm at λ = 850 nm) as given in Table 1. The wavelength dependences (Figure 2, right), show a variation between the bend optimized fibers at longer wavelengths (e.g. BO3 shows worst transmission at 850 nm and best at 1625 nm), this could be an indication of slightly different bend optimized refractive index profiles. All of these bending measurements clearly indicate that the bend optimized fibers of all chosen manufacturers could make fiber installations less critical, and more flexible as they allow bending around tighter corners. Bending loss test Figure 2 Change of optical transmission for the different variants of fibers in 0.9 mm tubes depending on number of turns (right), mandrel radius (middle) and on wavelength (right). 5

6 Mechanical Characteristics Mechanical characteristics In real world installations fibers are often squeezed and crushed during and after installation through staples and other supporting features and they might have to endure temperature changes. To check and compare the mechanical and environmental reliability of the different fiber samples, crush tests (according IEC E3) and temperature cycling tests (according to IEC F1) using the 0.9mm tubes and the 2.0 mm cables were executed. Selected results are given in Figure 3. Crush tests Temperature cycling test In contrast to the case for SM fibers [1], bend optimized MM-fibers demonstrated no loss improvement during crush tests. Crushing the optical cable will not introduce macro bending into the fiber but micro bending. It is believed that micro bending has a random mode mixing effect (in contrast to mode filtering), resulting in the chaotic loss curves. The temperature change test showed a more similar behavior as in the macro bending tests. For this case, it is assumed that micro bending and macro bending are produced within the cable due to mantel material shrinkages during the low temperature cycles. As a result, the use of bend optimized fibers for manufacturing of optical cables improves only to a certain degree the optical performance under variable environmental conditions. Change of Attenuation [db] Crush Test: N/cm; 3x3x1 min OM2 OM3 A OM3 B λ=850nm BO1 BO2 BO Time [min] 50 Compressive Stress [N/cm] Change of Attenuation [db] Temperature Cycling Cables: Average OM2 BO1 OM3 A OM3 B BO2 BO3 λ=850nm Time [h] Temperature [C] Figure 3 Change of optical transmission for the three types of fibers in 0.9 mm tubes during short-term crush tests (left) and in 2.7 mm cables during temperature cycling (right). 6

7 Splicing Investigations Splicing investigations All indoor optical communication systems have to be connected to the legacy world, which typically operates using standard MMF. Sometimes this connection is performed by fusion splicing. However, bend optimized MMF may not splice seamlessly to other standard MMF due to dissimilar index profiles and number of modes within the fiber. To confirm the spliceability of the investigated fibers a systematic splicing field test (Figure 4, upper left, power meter loss measurements using encircled flux launch conditions according to IEC/PAS 62614) was carried out between all bend optimized to the standard OM3 fiber at 850nm wavelength. The measured loss distribution of the acquired splice loss data (80 connections per set) are summarized in Figure 4 (right). Splicing field test Although to some degree a splice boundary is clearly visible (Figure 4, pictures in the lower left), the spliceability of the three bend optimized fibers to standard OM3 fibers was very well confirmed, as only one or less splice among the 80 splices per combination failed. Furthermore, the measured splice loss was well within the allowed values and the small mean loss difference (0.02 db) between the different configurations can be explained by the limits (+/-0.01 db) given by the measurement setup. Figure 4 Test setup (upper left), photograph of the splices(lower left) and distribution of the measured loss distribution at λ=850 nm for the different splice configurations (right). 7

8 Optical Connectivity Optical connectivity The outer world can, besides fusion splicing, also be reached by optical connectors. Due to the different manufacturing process of the bend optimized fiber types, the question has arisen, if during the assembly process the endface will behave in a similar manner as for the standard MMF and if it will match the geometrical and quality criteria s. The manufactured 0.9mm tubes containing the three types of bend optimized OM3 fibers were assembled with LC-PC and SC-APC connectors using standard assembly processes (blind test, not knowing what type of fiber they were using). Fortunately, during the assembly process no special care was taken nor had to be. Closer examination under a high performance microscope (using 400x magnification) using white light for backside core illumination showed the slight difference of the modal distribution (see Figure 5). The variations of the visible faint light rings ("halo") around the 50m core indicate the slight different index profiles (trench location) for the bend optimized fiber among the three different manufacturers. Blind test Figure 5 Microscope picture of the fiber endfaces in the assembled ferrules (400x magnification). The measured endface geometries (radius, apex offset, fiber protrusion) of the fiber core were not distinguishable between the different samples and they stayed well within the tolerance range given by IEC /2. To prove the compatibility of the connectorized fiber assemblies to standard MMF their loss distributions were investigated at λ = 850 nm in a similar way as the splicing (encircled flux launch conditions). Mating loss results (LC-connector) for all combinations are given as box plots in Figure 6. Here the individual distributions resemble each other nicely and it can be stated that the connector performances are well compatible to standard OM3 fibers. Figure 6 Box plot (left) of the loss distribution for the different configurations indicating mean (horizontal line), 75 % (box) and 98 % (vertical line) range of measurement data. 8

9 Bandwidth Investigations Bandwidth investigations As mentioned it is very challenging to control bend loss and other waveguide properties simultaneously. Especially challenging is to keep the bandwidth performance, as even minor change from the optimum shape of the ideal graded index profile leads to degradations. To confirm the bandwidth behavior, the different fibers are characterized using differential mode delay (DMD). The DMD technique [5] incorporates stepping the output of a singlemode, fiber pigtailed 850 nm pulsed laser across the core of the fiber under test (FUT) in small (1 2 µm) increments. Exit pulses from the fiber at each radial launch position are then collected by a detector and sampling oscilloscope (blind test results for 300 m of OM3 and the three bend optimized fibers are shown in Figure 7 on the left). From these curves, using well defined weighting sets and transformation algorithm, the effective modal bandwidth (EMB) and overfilled modal bandwidth (OMBc) can be calculated. The calculated results for all measured fibers are given in the table in Figure 7. Calculation of the effective modal bandwith The measurements confirmed the specifications given by the fiber manufacturer. The difference (ripple) for high offset launch might be due to deviations in the index profile at the outer core range. To confirm the usability of these fibers in real system applications, 10Gb/s transmission bit error rate (BER) measurements for different configurations were made. A variable optical attenuator is inserted in the fiber loop of the optical data link to induce transmission degradation. Bit error rate are then measured for 300 m fibers on standard transport spools (FUT) at different attenuation levels. Figure 7 DMD measurement curves (left) and resulting effective modal bandwidth (EMB) and overfilled modal bandwidth (OMBc). 9

10 Bandwidth Investigations As BER test depend heavily upon applied components (transceivers) in the setup (Figure 8, upper left), two different transmitter/receiver (Tx/Rx) sets were used. Results (Figure 8, left) for these "worst" (lines) and "best" (dots) case show an 3 db power penalty for the different pairs. Whereas all bend optimized and standard OM3 fibers can transmit almost failure free 10Gb/s even at low optical power levels, the OM2 fiber fails (as expected since not rated for 10Gb/s transmission). A further parameter that normally influence the optical bandwidth is the launching condition. To simulate general use a simple but effective means, i.e. a cascade of 5 patchcords (PCs) using standard (low cost) MMF connectors was introduced in front of the FUT. The major effect of this cascade is increasing the mode power in higher order mode groups propagating more in the outer core region. The influence on the result is shown in Figure 8, (right) indicating that apart from fiber BO2, all the BER tested on the fibers are sensitive to change in launch condition (dot to dash-dots). BO1 shows the worst penalty increase of about 0.3 db, which is in line with the observed larger outer DMD of this fiber. The launching condition To simulate the fiber layout in a datacenter environment with many in- and outlets in fiber cabinets, an extended lay-out was made consisting of a cascade of 10 r = 5 mm full turns in the launching end of the FUT. Between each of the loops a fiber distance of about 1 m was present. The effect is usually positive as the added loss due to the heavy bending attenuates preferentially the higher order modes. This clearly shows (Figure 8, right, dash-dots to line) for fiber BO1 where the power penalty improves by about 0.3 db due to the inserted bends. Note that this is about equal to the added power penalty originating from the insertion of the launching configuration. This behavior of Fiber BO1 in contrast to BO2 (little influence due to inserted bends) can again be understood from its larger outer DMD performance. Simulation of the fiber layout in a datacenter environment Figure 8 BER measurement setups (upper row) and corresponding measurement curve. 10

11 Reliability Considerations and Conclusion Reliability considerations So far we ve only seen the benefits of using bend optimized MMF for optical cable installations. However, signal transmission reliability of an installed optical link must be viewed in terms of both optical loss and mechanical stability. With traditional rules for fiber management at large bend radii, fiber breakage has not been an issue. However, as fiber bend radii drop, fiber lifetime becomes an important consideration. Just take into account, that the stress on the fiber at 5mm bend radius is 2 times higher than at 10 mm bend radius and more than 6 times higher than on a fiber following the traditional 30 mm bend radius. Similar as for low bend SM fibers [1], the stress behavior can be calculated according to IEC leading to the expected failure probability during the lifetime of a bend fiber. If we consider a rack in a datacenter having 1000m of fiber bend at r = 30 mm, one out of 10 million racks will fail during a 20 year lifetime due to fiber break. If the fibers in the same racks are bent at r = 10 or even r = 5 mm we would see two fails among 100 or one among 10 racks, respectively. Viewing both optical loss and mechanical stability Conclusion Handling and installation testing has confirmed that no differences exist between standard 50-µm fiber and the bend optimized 50-µm OM3 fiber (of three different manufacturers) in terms of termination and splicing methods. Therefore, new products enabled with the bend optimized fibers are able to provide the standard performance that network designers expect and the added benefit of enhanced bend performance without sacrifices. The new bend optimized fibers have been extensively tested and compared in respect to the optical properties of standard multimode fibers. They have clearly proven better performance under bending, to some extent better mechanical and environmental behavior, as well as their compatibility to standard MMF. Normal splicing and manufacturing processes can be used to assemble connectors with these fibers while reaching similar optical performances. Taking reliability considerations into account, it can be concluded that bend optimized multimode fibers are recommended for bend and loss critical applications as they are a real advance to current standard multimode fibers, but they should be handled with appropriate care as all optical glass fibers. Bend optimized fibers guarantee the expected performance Note: For all of the above described investigations we used for standard: OM3 of Draka, for the bend optimized OM3 fibers: MaxCap -BB-OM3 of Draka, ClearCurve of Corning, and LaserWaveFlex of OFS ; for 0.9 mm tubes: 01-G50/CW-E9-F of HUBER+SUHNER, and for 2.0 mm cables: 01-G50/CWJH-E20-F of HUBER+SUHNER. Acknowledgement: The authors would like to thank the three fiber manufacturer for providing their bend optimized fibers, Draka Communications(G. Kuyt) for taking the DMD measurements, and HHI Berlin for making the BER test References: [1] R. Krähenbühl, et al., "Usability of low bend fibers for optical connectivity", HUBER+SUHNER white paper, [2] L. Molin, et al., "Low bending sensitivity of regular OM3/OM4 fibers in 10GbE applications", OFC 2010, JThA55. [3] Y. Sun, et al., "Specialty high bandwidth multimode fiber for optical interconnection", SPIE, vol. 7631, ACP 2009, TuZ3. [4] D. Donlagic, "A low bending loss multimode fiber transmission system", Optics Express, vol.17(24), p , [5] "Differential mode delay measurement of multimode fiber in the time domain",tia/eia , Dec

12 HUBER+SUHNER is certified according to ISO 9001, ISO 14001, ISO/TS and IRIS. WAIVER It is exclusively in written agreements that we provide our customers with warrants and representations as to the technical specifications and/or the fitness for any particular purpose. The facts and figures contained herein are carefully compiled to the best of our knowledge, but they are intended for general informational purposes only. HUBER+SUHNER AG Fiber Optics Division Degersheimerstrasse Herisau/Switzerland Tel Fax Bend optimized-fibers/4291/4743/ hubersuhner.com

Optical Fibers Fiber Optic Cables Indoor/Outdoor

Optical Fibers Fiber Optic Cables Indoor/Outdoor presents Optical Fibers Fiber Optic Cables Indoor/Outdoor Content Optical fiber function, types optical effects applications production of optical fibre Cable - general types Indoor Indoor / outdoor Outdoor

More information

With the advent of Gigabit Ethernet

With the advent of Gigabit Ethernet INTERNATIONAL JOURNAL OF NETWORK MANAGEMENT Int. J. Network Mgmt 2001; 11:139 146 (DOI: 10.1002/nem.396) The importance of modal bandwidth in Gigabit Ethernet systems By David N. Koon Ł This article deals

More information

Insertion Losses of Fiber Optical Connectors

Insertion Losses of Fiber Optical Connectors Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins

More information

The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper

The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper Optical Fiber WP1150 Issued: October 2007 Supersedes: October 2006 ISO 9001 Registered

More information

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts robertsc@corning.com Cabling considerations for DCs and

More information

Fiber Selection and Standards Guide for Premises Networks

Fiber Selection and Standards Guide for Premises Networks Fiber Selection and Standards Guide for Premises Networks WP1160 Issued: November 2013 Supersedes: November 2012 Authors: Carl Roberts and Dr. Russell Ellis Introduction There are several main types of

More information

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned) 1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled

More information

Laser-Optimized Fiber

Laser-Optimized Fiber FIBER FAQs Laser-Optimized Fiber Technical Resource: Tony Irujo Manager, Customer Technical Support FIBER FAQs Laser-Optimized Fiber As transmission speeds over optical fiber networks in the enterprise

More information

Fiber Optic Specifications

Fiber Optic Specifications Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will

More information

How To Get A Better Signal From A Fiber To A Coax Cable

How To Get A Better Signal From A Fiber To A Coax Cable Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom

More information

Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?

Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? GBE, as the name says, is Ethernet scaled up to gigabit speeds, providing a migration path from Ethernet at 10 MB/s to Fast Ethernet at 100 MB/s

More information

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of

More information

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Cabling & Test Considerations for 10 Gigabit Ethernet LAN Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit

More information

Plug - Type (Male/Female) Attenuators CAA series Singlemode

Plug - Type (Male/Female) Attenuators CAA series Singlemode Plug - Type (Male/Female) Attenuators CAA series Singlemode Description: The plug-type singlemode attenuators are used directly on the ends of fiber optic jumpers prior to installation in adapters. These

More information

MINIMIZING PMD IN CABLED FIBERS. Critical for Current and Future Network Applications

MINIMIZING PMD IN CABLED FIBERS. Critical for Current and Future Network Applications MINIMIZING PMD IN CABLED FIBERS Critical for Current and Future Network Applications David Mazzarese Technical Marketing Manager OFS Sturbridge, Mass. Polarization Mode Dispersion (PMD) is a serious problem

More information

10Gb/s SFP+ LRM 1310nm FP with PIN Receiver 220meters transmission distance

10Gb/s SFP+ LRM 1310nm FP with PIN Receiver 220meters transmission distance Feature 10Gb/s serial optical interface compliant to 802.3aq 10GBASE-LRM Electrical interface compliant to SFF-8431 specifications for enhanced 8.5 and 10 Gigabit small form factor pluggable module SFP+

More information

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables

More information

APPLICATION NOTE POLARIZATION MEASUREMENTS

APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS LTD. APPLICATION NOTE POLARIZATION MEASUREMENTS OZ OPTICS FAMILY OF POLARIZATION MAINTAINING COMPONENTS, SOURCES, AND MEASUREMENT SYSTEMS The information/data furnished in this document shall

More information

Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center

Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center WP6046 Issued: June 2012 Introduction Our world is in a rapid state of change in terms of the way we communicate and are connected

More information

Attaching the PA-A1-ATM Interface Cables

Attaching the PA-A1-ATM Interface Cables CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.

More information

Dispersion penalty test 1550 Serial

Dispersion penalty test 1550 Serial Dispersion penalty test 1550 Serial Peter Öhlen & Krister Fröjdh Optillion Irvine, January 2001 Dispersion penalty test, 1550 serial Page 1 SMF Transmission at 1550 nm Different from multi-mode transmission

More information

Module 13 : Measurements on Fiber Optic Systems

Module 13 : Measurements on Fiber Optic Systems Module 13 : Measurements on Fiber Optic Systems Lecture : Measurements on Fiber Optic Systems Objectives In this lecture you will learn the following Measurements on Fiber Optic Systems Attenuation (Loss)

More information

Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices

Optical Fiber Data Center Field Testing. ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Optical Fiber Data Center Field Testing ANSI/BICSI 002-2011 Data Center Design and Implementation Best Practices Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether

More information

Polymer Coated Fiber Cable (PCF)

Polymer Coated Fiber Cable (PCF) Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability

More information

Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces

Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces WP1281 Issued: November 2015 Supersedes: 2012 Author: Dr. Russell Ellis ISO 9001 Registered Background

More information

Fibre Channel Fiber Cabling

Fibre Channel Fiber Cabling OVERVIEW This paper will discuss the Fibre Channel standards for fiber cables at both 1Gb and 2Gb speeds, and also some discussion of departures from standard. Items discussed will be cable types, plug

More information

The Conversion Technology Experts. Fiber Optics Basics

The Conversion Technology Experts. Fiber Optics Basics The Conversion Technology Experts Fiber Optics Basics Introduction Fiber optic technology is simply the use of light to transmit data. The general use of fiber optics did not begin until the 1970s. Robert

More information

How To Make A Data Center More Efficient

How To Make A Data Center More Efficient Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence

More information

Accurately Testing fibre Optic Cables

Accurately Testing fibre Optic Cables Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty

More information

Measuring of optical output and attenuation

Measuring of optical output and attenuation Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter

More information

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: info@thefoa.org http://www.thefoa.org Technical Bulletin Guidelines For Testing

More information

Fibre optic testing best practices

Fibre optic testing best practices Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is

More information

INTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet.

INTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet. INTRODUCTION Fibre optics behave quite different to metal cables. The concept of information transmission is the same though. We need to take a "carrier" signal, identify a signal parameter we can modulate,

More information

Bandwidth analysis of multimode fiber passive optical networks (PONs)

Bandwidth analysis of multimode fiber passive optical networks (PONs) Optica Applicata, Vol. XXXIX, No. 2, 2009 Bandwidth analysis of multimode fiber passive optical networks (PONs) GRZEGORZ STEPNIAK *, LUKASZ MAKSYMIUK, JERZY SIUZDAK Institute of Telecommunications, Warsaw

More information

Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber

Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber Presented at NOC/EC 2000 Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber Mary Adcox, Optical Fiber, Corning Incorporated As non-zero dispersion-shifted

More information

CISCO 10GBASE X2 MODULES

CISCO 10GBASE X2 MODULES DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity

More information

Overcoming OM3 Performance Challenges

Overcoming OM3 Performance Challenges White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management

More information

IN LEITERPLATTEN INTEGRIERTE OPTISCHE VERBINDUNGSTECHNIK AUF DÜNNGLASBASIS

IN LEITERPLATTEN INTEGRIERTE OPTISCHE VERBINDUNGSTECHNIK AUF DÜNNGLASBASIS IN LEITERPLATTEN INTEGRIERTE OPTISCHE VERBINDUNGSTECHNIK AUF DÜNNGLASBASIS Dr. Henning Schröder henning.schroeder@izm.fraunhofer.de, phone: +49 30 46403 277 Outlook n Motivation n Manufacturing n Waveguide

More information

Data Center Design for 40/100G

Data Center Design for 40/100G Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an

More information

PURE : REliable planning of data center cabling

PURE : REliable planning of data center cabling PURE : REliable planning of data center cabling THE PURE EFFEct: TWICE AS MANY CONNEctionS AND 15 METERS MORE CHannEL LEngtH * PreCONNECT PURE is a milestone in the development of high-end IT cabling for

More information

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide

More information

Introduction to Optical Link Design

Introduction to Optical Link Design University of Cyprus Πανεπιστήµιο Κύπρου 1 Introduction to Optical Link Design Stavros Iezekiel Department of Electrical and Computer Engineering University of Cyprus HMY 445 Lecture 08 Fall Semester 2014

More information

Next Breakthrough Technologies: Trends in Datacenter for 100G and Beyond. Durgesh S Vaidya May 9, 2014

Next Breakthrough Technologies: Trends in Datacenter for 100G and Beyond. Durgesh S Vaidya May 9, 2014 Next Breakthrough Technologies: Trends in Datacenter for 100G and Beyond Durgesh S Vaidya May 9, 2014 Outline Motivation for Datacenter evolution Challenges and solutions OFS and Furukawa product roadmap

More information

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process

More information

Network Monitoring - Fibre TAP Modules

Network Monitoring - Fibre TAP Modules Network Monitoring - Fibre TAP Modules It all started with. Bend insensitive MM fibre Smaller diameter cables Cable with tighter bend radius Less space in the DC, More organised cable management Greater

More information

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements

More information

Loss & Continuity Testing with MPO/ MTP Connectors

Loss & Continuity Testing with MPO/ MTP Connectors Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular

More information

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher

More information

Discontinued. Volition. Fiber Optic Cable. 3Innovation

Discontinued. Volition. Fiber Optic Cable. 3Innovation Volition Fiber Optic Cable Tough enough to take it. Easy to handle. The Volition Network Solution from 3M includes horizontal and backbone cable with 62.5/125 µm and 50/125 µm multimode fiber, and 9/125

More information

Intel Ethernet SFP+ Optics

Intel Ethernet SFP+ Optics Product Brief Intel Ethernet SFP+ Optics Network Connectivity Intel Ethernet SFP+ Optics SR and LR Optics for the Intel Ethernet Server Adapter X520 Family Hot-pluggable SFP+ footprint Supports rate selectable

More information

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer tirujo@ofsoptics.com Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber

More information

FIBER OPTIC SYSTEM TEST PROCEDURES

FIBER OPTIC SYSTEM TEST PROCEDURES FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not

More information

What are Fibre Optics?

What are Fibre Optics? Fibre Optics Fibre Optics? Fibre optics (optical fibres) are the guiding channels through which light energy propagates. These are long, thin strands of very pure glass about the diameter of a human hair

More information

Fibre Optic Indoor/Outdoor Cable

Fibre Optic Indoor/Outdoor Cable Volition TM Fibre Optic Indoor/Outdoor Cable Tough enough to take it. Easy to handle. The Volition Network Solutions Indoor/Outdoor Fibre Optic Cable from 3M includes horizontal and backbone cable with

More information

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network WP4270 Issued: June 2011 Authors: Carl Roberts and Merrion Edwards Introduction

More information

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year

More information

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Features: SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS Low insertion loss < 0.2 db Excellent repeatability FC/PC, SC, ST, LC, MU, E2000 termination available Custom ferrule termination available Designed

More information

Security & Surveillance Cabling Systems

Security & Surveillance Cabling Systems Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.

More information

The following terms are defined within the context of the fiber optic industry

The following terms are defined within the context of the fiber optic industry The following terms are defined within the context of the fiber optic industry Adapter A mechanical media termination device designed to align and join fiber optic connectors. Often referred to as coupling,

More information

Different Types of Dispersions in an Optical Fiber

Different Types of Dispersions in an Optical Fiber International Journal of Scientific and Research Publications, Volume 2, Issue 12, December 2012 1 Different Types of Dispersions in an Optical Fiber N.Ravi Teja, M.Aneesh Babu, T.R.S.Prasad, T.Ravi B.tech

More information

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION

More information

HIGH POWER FREE SPACE AND FIBER PIGTAILED ISOLATORS

HIGH POWER FREE SPACE AND FIBER PIGTAILED ISOLATORS NEW HIGH POWER FREE SPACE AND FIBER PIGTAILED ISOLATORS Features: New! Reduced size and cost versions Reliable high power handling: As much as 80 Watts High Isolation, up to 50dB isolation possible from

More information

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH

More information

As today s evolving data centers

As today s evolving data centers IT CORNER Next Generation Optical Fiber Connectivity Solutions for the Mission Critical Data Center BY BILL CHARUK As today s evolving data centers confront bandwidth capacity challenges, the migration

More information

Enabling 21 st Century Connectivity

Enabling 21 st Century Connectivity Enabling 21 st Century Connectivity First MXC Adopters meeting March 11, 2014 MXC is a trademark of US Conec Presenters Victor Krutul Director Marketing, Intel Corp Mike Hughes Director, Product Management,

More information

BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers

BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers WP4259 Issued: January 2015 Brillouin Optical Time Domain Reflectometry The Brillouin Optical

More information

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer tirujo@ofsoptics.com Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards 40G & 100G

More information

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output

More information

Golden test for dispersion penalty 1550 Serial

Golden test for dispersion penalty 1550 Serial Golden test for dispersion penalty 1550 Serial Peter Öhlen, Krister Fröjdh (Optillion) Tampa, November 2000 Golden test for dispersion penalty, 1550 serial Page 1 SMF Transmission at 1550 nm Different

More information

Fiber Optic Terminus End Face Quality Standards

Fiber Optic Terminus End Face Quality Standards Introduction Fiber Optic Terminus End Face Quality Standards Good fiber optic performance relies on connectors that are manufactured properly. Specifically, optimal optical performance requires that the

More information

How To Make A Fibre Cable For A Data Centre

How To Make A Fibre Cable For A Data Centre LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF

More information

Fiber Optic. Passive Components Edition 2009

Fiber Optic. Passive Components Edition 2009 Fiber Optic Passive Components Edition 2009 Reliably connected to your network Your partner for system solutions The HUBER+SUHNER Group is a leading global supplier of components and systems for electrical

More information

Copper Patch Cords. Impact On Network Performance and Reliability

Copper Patch Cords. Impact On Network Performance and Reliability Copper Patch Cords Impact On Network Performance and Reliability 1 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on

More information

Cisco SFP Optics for Gigabit Ethernet Applications

Cisco SFP Optics for Gigabit Ethernet Applications Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit

More information

Large-Capacity Optical Transmission Technologies Supporting the Optical Submarine Cable System

Large-Capacity Optical Transmission Technologies Supporting the Optical Submarine Cable System Large-Capacity Optical Transmission Technologies Supporting the Optical Submarine Cable System INOUE Takanori Abstract As one of the foundations of the global network, the submarine cable system is required

More information

GOSB. Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection. Ordering Information. Applications. Features & Benefits

GOSB. Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection. Ordering Information. Applications. Features & Benefits GOSB Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 2 4 6 8 12 16 24 62.5/125-OM1 GOSB102 GOSB104 GOSB106

More information

Patch Cord Quality, Reliability and Performance. The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance

Patch Cord Quality, Reliability and Performance. The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance Patch Cord Quality, Reliability and Performance The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance White Paper 12/2003 Executive Summary The quality, reliability, and

More information

WHITE PAPER. 50 versus 62.5 micron multimode fiber

WHITE PAPER. 50 versus 62.5 micron multimode fiber WHITE PAPER 50 versus 62.5 micron multimode fiber www.ixiacom.com 915-6919-01 Rev. A, July 2014 2 Table of Contents What are 50μm fiber and 62.5μm fiber?... 4 Why two standards?... 4 Which technology should

More information

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large

More information

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) Features: DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES) PATENT NUMBERS: CANADA 2,494,133, USA 7095931, 7295731 AND CHINA 1672073 Telcordia GR-468 qualified Available in versions for any wavelength

More information

GLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics

GLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics Introduction Fiber optics deals with the light propagation through thin glass fibers. Fiber optics plays an important role in the field of communication to transmit voice, television and digital data signals

More information

Your Network. Our Connection. 10 Gigabit Ethernet

Your Network. Our Connection. 10 Gigabit Ethernet Your Network. Our Connection. 10 Gigabit Ethernet t Agenda Why 10G? Applicable 10GbE Standards Distance Restrictions Copper Fiber Fiber Repeaters 3R s Fiber Module Types Form Factors of 10G modules Future

More information

CISCO DWDM XENPAK. Main features of the Cisco DWDM XENPAK include:

CISCO DWDM XENPAK. Main features of the Cisco DWDM XENPAK include: DATA SHEET CISCO DWDM XENPAK OVERVIEW The Cisco Dense Wavelength-Division Multiplexing (DWDM) XENPAK pluggable allows enterprise companies and service providers to provide scalable and easy-to-deploy 10

More information

OFS AllWave Zero Water Peak (ZWP) single-mode

OFS AllWave Zero Water Peak (ZWP) single-mode The New Standard for Single-Mode Fiber Product Description OFS AllWave Zero Water Peak (ZWP) single-mode optical fiber is the industry s first full-spectrum fiber designed for optical transmission systems

More information

Plug & Play Universal Systems

Plug & Play Universal Systems Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution

More information

RLH 2 Wire Digital Phone Fiber Link Card System

RLH 2 Wire Digital Phone Fiber Link Card System RLH Industries, Inc. The leader in rugged fiber optic technology. USER GUIDE! Unconditional Lifetime Warranty U-008 2014C-0924 RLH 2 Wire Digital Phone Fiber Link Card System CARD INSTALLATION INFORMATION

More information

The Need for Low-Loss Multifiber Connectivity

The Need for Low-Loss Multifiber Connectivity WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially

More information

Vector Network Analyzer Techniques to Measure WR340 Waveguide Windows

Vector Network Analyzer Techniques to Measure WR340 Waveguide Windows LS-296 Vector Network Analyzer Techniques to Measure WR340 Waveguide Windows T. L. Smith ASD / RF Group Advanced Photon Source Argonne National Laboratory June 26, 2002 Table of Contents 1) Introduction

More information

200-Micron Single-Mode Fiber Enables New Cable Designs Copyright 2014 OFS FITEL, LLC

200-Micron Single-Mode Fiber Enables New Cable Designs Copyright 2014 OFS FITEL, LLC 200-Micron Single-Mode Fiber Enables New Cable Designs Copyright 2014 OFS FITEL, LLC Since single-mode optical fiber was first introduced in the early 1980 s, little has changed in its basic geometric

More information

Fiber in the Data Center

Fiber in the Data Center Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation

More information

Next Generation Optical Fibre: Making Your Broadband Network Go Further

Next Generation Optical Fibre: Making Your Broadband Network Go Further Next Generation Optical Fibre: Making Your Broadband Network Go Further WP2401 Issued: April 2011 Authors: Dr. Merrion Edwards and Vanesa Diaz Introduction As a recent blockbuster video on YouTube called

More information

On Cables and Connections A discussion by Dr. J. Kramer

On Cables and Connections A discussion by Dr. J. Kramer KRAMER ELECTRONICS LTD. On Cables and Connections A discussion by Dr. J. Kramer We are frequently asked - "what length of cable can I use for a specific application?" Seemingly a simple question, but the

More information

USB 3.1 Channel Loss Budgets

USB 3.1 Channel Loss Budgets USB 3.1 Channel Loss Budgets Page 1 1 Introduction 1.1 Background This document describes the loss budgets for USB 3.1 interconnect channels. As the basis for the electrical compliance channels, loss budgets

More information

Plastic Optical Fiber for In-Home communication systems

Plastic Optical Fiber for In-Home communication systems Plastic Optical Fiber for In-Home communication systems Davide Visani 29 October 2010 Bologna E-mail: davide.visani3@unibo.it Summary Reason for Fiber in the Home (FITH) FITH scenario Comparison of CAT5

More information

DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND

DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND THE THREE-DIMENSIONAL DISTRIBUTION OF THE RADIANT FLUX DENSITY AT THE FOCUS OF A CONVERGENCE BEAM

More information

Industry solutions: Broad cast

Industry solutions: Broad cast Industry solutions: Broad cast BC 2 industry solutions: Broadcast Optical Cable Corporation s broad range of Fiber Optic Broadcast Cables are specifically designed for real-time transmission of high definition

More information

Properties and Potential Applications of a Bend Optimised Singlemode Optical Fibre

Properties and Potential Applications of a Bend Optimised Singlemode Optical Fibre Properties and Potential Applications of a Bend Optimised Singlemode Optical Fibre Tomas Jendel 1, Svante Töyrä 1 and Ian Davis 2 1 Ericsson Network Technologies AB, Hudiksvall, Sweden +46-650-36843 tomas.jendel@ericsson.com

More information

GOSN. Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection. Ordering Information. Applications. Features & Benefits

GOSN. Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection. Ordering Information. Applications. Features & Benefits GOSN Central Loose Tube Cables Outdoor A-DQ(ZN)B2Y Standard Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 2 4 6 8 12 16 24 62.5/125-OM1 GOSN102 GOSN104 GOSN106

More information

Limiting factors in fiber optic transmissions

Limiting factors in fiber optic transmissions Limiting factors in fiber optic transmissions Sergiusz Patela, Dr Sc Room I/48, Th. 13:00-16:20, Fri. 9:20-10:50 sergiusz.patela@pwr.wroc.pl eportal.pwr.wroc.pl Copying and processing permitted for noncommercial

More information

GOWN. Central Loose Tube Cables Outdoor, Steel Wire Armor (SWA) A-DQ(ZN)2YB2Y Full Rodent Protection. Ordering Information.

GOWN. Central Loose Tube Cables Outdoor, Steel Wire Armor (SWA) A-DQ(ZN)2YB2Y Full Rodent Protection. Ordering Information. GOWN Central Loose Tube Cables Outdoor, Steel Wire Armor (SWA) A-DQ(ZN)2YB2Y Full Rodent Protection Ordering Information Belden European Part Numbers Fibre type / count 2 4 6 8 12 16 24 62.5/125-OM1 GOWN102

More information