DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
|
|
|
- Andrea Gordon
- 9 years ago
- Views:
Transcription
1 DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters (VSC) have for the first time been used for HVDC transmission in a real network. Experience from the design and commissioning of the transmission shows that the technology has now reached the stage where it is possible to build high voltage converters utilising Insulated Gate Bipolar Transistors (IGBTs). Operation and system tests have proved that the properties that have been discussed for many years regarding VSCs for HVDC are a reality now. They include independent control of active and reactive power, operation against isolated a.c. networks with no generation of their own, very limited need of filters and no need of transformers for the conversion process. This is only the first installation of VSC for HVDC. The development of semiconductors and control equipment is presently very rapid and it is evident that this technology will play an important role in the future expansion of electric transmission and distribution systems. 1. INTRODUCTION On March 1, 1997 power was transmitted on the world s first HVDC transmission with VSC converters between Hellsjön (Hn) and Grängesberg (Gbrg) in central Sweden. Since then extensive testing has been performed in order to prove that the Voltage Source HVDC technology fulfils the expectations that since long time have been expressed in different publications. This article describes the technology that has been utilised, the development of the project and the tests that have been performed during operation. So far the experience of tests and operation is most encouraging and the VSC seems to be very suitable for small scale HVDC as it can operate at any short circuit ratio, even against isolated a.c. networks with no other generators in the system. They can also connect isolated generators to the grid or to isolated loads.. VSC TECHNOLOGY AND PULSE WIDTH MODULATION (PWM) HVDC was originally developed from technologies used in industrial drive systems. There the PCC (Phase Commutated Converter) technology which is at present being used for HVDC has now almost entirely been replaced by VSC technology. The fundamental difference between these two technologies is that VSCs need components that can turn-off the current and not only turn it on as is the case with PCCs. Since in a VSC the current can be turned off, there is no need for a network to commutate against. In HVDC-applications it could then be advantageous to use the VSC technology especially to supply passive load networks, that is areas which lack rotating machines or which do not have enough power in the rotating machines (short circuit power too low). With the appearance of high switching frequency components, such as IGBTs it becomes advantageous to use Pulse Width Modulation (PWM) Technology. In a VSC converter the a.c. voltage is created by switching very fast between two fixed voltages. The
2 desired fundamental frequency voltage is created through low pass filtering of the high frequency pulse modulated voltage. See Figs. 1 and. +/- Ud Fig. 1. One phase of a VSC converter using PWM Ug Ug Uac even at switching frequencies in the khz range should be possible. 3.1 Co-operation with the local utility In 1994 the development on VSC converters was concentrated into a project to put two VSC converters for small-scale HVDC based on IGBTs into operation. Through co-operation with the local utility, VB-Elnät, it became possible to design the transmission for operation in a commercial network. An existing 1 km long 5 kv back-up a.c. line between Hellsjön and Grängesberg in central Sweden was made available for the project. VB-Elnät also provided space in the stations and connections to the a.c. networks. The transmission rating was determined to 3 MW, somewhat above the hydro generator rating at Hellsjön and with a direct voltage of ±1 kv d.c. The converter stations are connected to separate parts of an existing 1 kv a.c. network. Uac Fig.. The PWM pattern and the fundamental frequency voltage in a Voltage Source Converter With PWM it is possible to create any phase angle or amplitude (up to a certain limit) by changing the PWM pattern, which can be done almost instantaneously. Hereby, PWM offers the possibility to control both active and reactive power independently of each other. This makes the Pulse Width Modulated Voltage Source Converter a close to ideal component in the transmission network. From a system point of view it acts as a motor or generator without mass that can control active and reactive power almost instantaneously. Furthermore, it does not contribute to the short-circuit power since the a.c. current can be controlled. 3. THE HELLSJÖN PROJECT, A DEMONSTRATION FACILITY Development work on VSC converters has been going on for a long time within ABB. During this development it was realised that the IGBT should be a very interesting component, as it is a MOS-device and the power requirement for the control of the component is very low. By this series connection of many semiconductors with good voltage distribution 3. Simulation and testing During the development of the project the various characteristics and behaviours of VSC converters, PWM control, IGBT valves etc. were tested in digital and analogue simulations. Finally, the complete transmission stations were connected in a round power circuit at a laboratory in Ludvika. By the end of 1996, and after a comprehensive synthetic testing, the equipment was moved to the field for installation and testing. On March 1, 1997 power was transmitted between Hellsjön and Grängesberg in the Hellsjön Project, the world s first VSC HVDC transmission. 3.3 Converter design Main circuits The converter consists of the bridge, the converter control, the converter reactor, d.c. capacitor, and an a.c. filter. The bridge is a six-pulse bridge, two-level, with series connected IGBTs in each valve. Every IGBT is provided with an antiparallel diode. Auxiliary power to the gate drive unit is generated from the voltage across the IGBT. Turn on/off of each individual IGBT is ordered via an optical link from the control equipment on ground potential. The semiconductors are cooled with deionized water. The objective for the d.c. capacitor is primarily to provide a low inductive path for the turn-off current, and an energy storage to be able to control the power flow. The capacitor also reduces the harmonics on the d.c. side.
3 The converter generates characteristic harmonics related to the switching frequency. The ac currents are smoothed by the converter reactor and then the remaining harmonic contents in the ac bus voltage are reduced by a high-pass filter. Depending on the system requirements the converter may be equipped with two more components; Overvoltage limiter (chopper) for fast discharge of the d.c. capacitor if the d.c. voltage exceeds the maximum d.c. bus voltage for a deblocked converter. This function is realised by a fast switch and a resistor. DC line switches, if fast isolation of the converter is required at d.c. line faults. In this project both switches specified above are IGBT valves similar to the valves in the bridge. The main circuit components are as shown in Fig. 3. pattern is generated by the pulse width modulation (PWM) where the reference voltage is compared with the triangular carrier wave. 4. DEVELOPMENT TESTS 4.1 Control equipment The control system performance has been extensively tested in an analogue simulator. The main circuits in this low power simulator is represented by physical models with properties corresponding to full-scale components. The main advantage of the simulator is that control equipment identical to the full-scale system is used. The dynamic performance of the system has been studied during different types of disturbances in the system, such as faults in the a.c. system, d.c. faults and converter faults. Similar development of the control system has also been performed by digital simulation in the program EMTDC. The control equipment for the converter, main circuits and a.c. system have been represented in detail. 1 kv Fig. 3 Main circuit components kv To further ensure correct operation of the system a medium voltage test circuit was set up. The test circuit included two converters with a.c. reactors and filters and a representation of a d.c. overhead line. Each valve in the bridge was represented by one industrial IGBT. The control equipment was the actual equipment later delivered to site. In this test circuit normal operation of a HVDC transmission with VSC converters was verified. Steady state modes such as d.c. voltage control, active and reactive current control and also some fault conditions were checked. Control The fundamental frequency voltage across the reactor defines the power flow between the a.c. and d.c. sides. The converter firing control calculates a voltage time area across the converter reactor which is required to change the current through the reactor from actual value to the reference value. The active power flow between the converter and the a.c. network is controlled by changing the phase angle between the fundamental frequency voltage generated by the converter (Ug) and the a.c. voltage on the a.c. bus. The reactive power flow is determined by the amplitude of Ug which is controlled by the width of the pulses from the converter bridge. The current order to the controller is calculated from the set power/current order or the d.c. voltage control. A reference voltage, equal in phase and amplitude to the fundamental frequency component of the output voltage from the bridge Ug, is calculated. The pulse 4. VSC valve The most important task to solve was how to achieve an even voltage distribution between a large number of series connected IGBTs in a valve function. To accomplish this a special Gate Unit (GU) was designed which, together with a voltage divider across each IGBT, maintains a proper voltage division within the valve during both blocking and switching conditions. The GU and the voltage divider was developed by intensive testing of a stack of IGBTs switching in a single-pulse test circuit. The single-pulse test circuit consisted of one converter phase leg, one d.c. capacitor and a reactor of suitable size. The detailed behaviour of the switching transients was studied at IGBT turnon, IGBT turn-off and diode turn-off. Proper gate control combined with a small voltage divider made it possible to achieve both good voltage division and low switching losses.
4 4.3 Factory system test Before delivery to site the complete system was tested with full rated voltage (1 kv a.c. and ± 1 kv d.c.) and current. Each converter was first tested as a single unit operating as SVC. Then the two converters were connected and operated in round power mode as per Fig 4. 1 kv trip of the current controlling station with the power flow out from the d.c. system. In the first case the d.c. voltage will drop transiently and then the remaining station will take over the d.c. voltage control and continue to operate and control both the reactive power order and the d.c. voltage (transiently to a lower level) D C v o l t a g e k V 6 4 Hn Gbrg A c t i v e c u r r e n t r e f e r e n c e. Fig. 4. Factory system test The ac terminals were connected together which means that the active power only circulates between the converters, and the a.c. feeder only feeds the active power corresponding to the losses in the system. The reactive power could be altered in each converter independent of each other within the limit for the power flow in the feeder. This configuration allows full-scale test operation with a relatively weak feeder. Extensive tests were performed primarily to verify the steady state operation of the converter bridge and to check important performance of a valve with several series connected IGBTs. 5. COMMISSIONING Thanks to the factory testing of the complete system the commissioning at site was very fast. The two stations were commissioned one by one, operating as SVC, consuming and generating reactive power. This means that each station could be properly tested as a single unit independent of the other station. After that the two stations were connected to the d.c. overhead line and the flow of active power could start. A Fig. 5. Trip of the voltage controlling station If, instead, the current controlling station trips when the power flows into the connected a.c. system, the power into the d.c. system continues to flow via the other station, and further, the energy stored in inductance in the d.c. line and the converter will charge the d.c. capacitors. The resulting d.c. overvoltage will first be counteracted by a power reduction and also a short power reversal of the voltage controlling station. This station will continue to operate and control both the d.c. voltage and the ordered reactive power flow. 5.1 Steady-state operation and converter trip. Steady state operation was verified which means d.c. voltage control in one station and current control in the other. The dynamic performance at typical protective actions was demonstrated. These cases are; trip of the d.c. voltage controlling station with active power flow into the d.c. system
5 kv A D C v ol t a g e A c t i v e c u r r e n t r e f e r e n c e Fig. 6. Trip of the current controlling station In the event that the d.c. voltage increases too much, due to for example a long overhead d.c. line, the converter must be blocked temporarily and the d.c. side discharged by the chopper down to approximately rated voltage before the converter will be deblocked again. This power interruption can be very short, in the order of a few milliseconds. 5. Power system compatibility Commissioning also included measurements of the following properties of the converters. Sound power level Radio interference Harmonic distortion All three items are mainly related to the turn-on and turn-off of the valves. Sound Power Level The dominating sound generated in the converter station is related to the switching frequency. The different sources of sound within the converter station have been identified and the total sound level at different directions and distances has been measured. The sound level from the converter station did not exceed 4 db(a) at a distance of 4 m from the station fence which was the target for the design. Radio Interference (RI) RI measurements have been performed at Hellsjön and Grängesberg. The most appropriate standard defining the limits in this case is ENV (Railway application- Electromagnetic compatibility, Part 5: Fixed power supply installations). The railway standard requires a measurement at a distance of 3 m from the fence surrounding the installation. The measurements are performed at a distance of about 3 m from the radiating source in order to avoid electrical shielding from the surrounding fence of the HVDC station. The signal level at that distance from the fence has then been rescaled back to 3 m. The measured RI meet the required levels given in ENV for the frequency range 9 khz to 1 GHz. Harmonic Distortion The a.c. filter arrangements consist of a single branch high-pass filter on the a.c. side. The bank size is 1 % of rated converter power and the filter is tuned to the 4th harmonic, (q=1). The harmonic distortion level (THD) on the a.c. side at Hellsjön have been measured at various load conditions of the converter. The average level of the measured total harmonic distortion up to 3 khz was 3.8 %. This value can be compared with target levels of 5. % (IEEE Std ) or 8. % (Electra 149, Aug. 93 page 75 table I) for bus voltages below 69 and 45 kv respectively. The nominal a.c. bus voltage is 1.5 kv. The measured distortion corresponds to a THFF of %. 6. SYSTEM TESTS 6.1 Radial interconnection of synchronous generator and converter. The aim of the test is to prove the feasibility of feeding a VSC converter from an isolated synchronous generator. The operation mode is constant power control and a.c. voltage control at the synchronous generator and frequency control at the converter Main circuit The main circuit configuration at Hellsjön was as shown in Fig. 7. G Fig. 7. Isolated operation with the generator All a.c. lines were disconnected from the 1 kv bus.
6 6.1. Frequency control design. The exciter voltage control at the generator and the current control of the VSC are disregarded in the model analysis due to their fast dynamic behaviour with respect to the machine time constants. Included in the analysis is the machine inertia, the frequency calculation and the measurement filters. The control-law is mainly based on Equation 6-1 and the measurement filter functions. The control is based on a PI-regulator. Equation 6-1 d δ ω s = dt HS P m P ω s = πf H = 33. Where: [ s] n ( ) S n =Rated Machine Power P m= Mechanical Power P= Electric Power f= Nominal Frequency δ= Angular Position H= Per-Unit Inertia Constant Fig. 8. Frequency step from 48 Hz to 5 Hz. The frequency scale is 3 Hz/div and the power order scale is 1 kw/div. Fig. 9 shows a change of frequency from 5 to 48 Hz. The first curve is the frequency step response and the second is the power order to the converter. The converter increases the power transmission that leads to a reduced speed of the synchronous machine. While the machine inertia has an inertia time constant of 3.3 [s], the speed of change will be in the same order. The converter power transfer is limited to the direction from the synchronous generator, to prevent that the converter feeds power into the synchronous generator during the speed increase Frequency step response. The aim of this test is to show the step response due to a step in the frequency order reference. Fig. 8 shows a change of the frequency reference from 48 Hz to 5 Hz. The first curve is the frequency step response and the second curve from above is the power order to the converter. The converter reduces the power transmission and the synchronous generator will then increase its speed due to the reduced load. Fig. 9. Frequency step from 5 Hz to 48 Hz. The frequency scale is 3 Hz/div and the power order scale is 1 kw/div Steps in power to the synchronous machine. The aim of the test is to show the frequency response due to a power change in the synchronous generator.
7 1 kv Grängesberg X 13 X +/-1 kv DC 5 kv Uac T T 1 Fig. 1. Steps in power to the generator. The frequency scale is 3 Hz/div and the power order scale is 1 kw/div. 3 X 4 X 1 kv X Ubus 1 X Hellsjön The first case is a load change from 15 kw to about 1 MW and the second is a change back again from about 1 MW to 15 kw. The frequency deviation during the operation is less than.3 Hz. The power ramping in the machine is at its maximum rate. 6. Operation with a network without own generation One of the basic features of a VSC converter is its ability to feed power into an a.c. system with no other generation. The converter will alone control the frequency and the a.c. bus voltage and consequently operate as a generator with the active power fed from the d.c. line. The purpose of the tests were to verify the following; Start-up of the converter with or without a.c. auxiliary power. Both manual and protective transfer of power flow from an a.c. feeder to the converter. Synchronisation and reconnection of an a.c. feeder to an a.c. system fed by the converter. Performance at faults in the a.c. system. The configuration of the system was as shown in Fig. 11. Fig.11. System at isolated operation The 1 kv bus at Hellsjön substation is normally fed from a 5 kv a.c. line through transformer T. The HVDC converter is also connected to the same bus. The active power flow can be either to or from that bus via the d.c. line to the converter at Grängesberg 1 km away. The load along the a.c. line can be fed from either station by closing breaker 3 or 13. The available loads in isolated operation are approximately 7 kva in Hellsjön and 1.5 MW in Grängesberg. The tests described below were performed at Hellsjön. After these tests the power direction was reversed and Grängesberg operated isolated, but at a higher load than at Hellsjön Start-up of the converter with or without a.c. auxiliary power The d.c. side is first energised from Grängesberg by closing the a.c. breaker. Switches along the d.c. line are closed which means that the converter at Hellsjön is energised on the d.c. side. The converter at Grängesberg is deblocked in d.c. voltage control mode. The converter at Hellsjön is now the only voltage source in that system and can therefore determine both the a.c. voltage and the frequency. This is provided by the converter control equipment which generates a reference voltage for the PWM with fixed frequency and an amplitude required to have nominal a.c. bus voltage on the a.c. terminals of the converter station. In many applications it is likely that there will be no a.c. auxiliary power in the station before the converter is deblocked, which means that the converter has to start up without cooling equipment, and as soon as the converter has started, the valve cooling system can start up. The only auxiliary power required to start the isolated station is the power to the control equipment. Another feature which can be provided by the
8 converter is that the a.c. bus voltage can be ramped up in a smooth way to prevent transient overvoltages or inrush currents in transformers, for example. This test has been performed at maximum load at Hellsjön. Fig. 14. Transfer from active to passive network. Automatic order to transfer to a.c. voltage control. Fig. 1. Start-up of an isolated network 6.. Both manual and protective transfer of power flow from an a.c. feeder to the converter. The precondition for this test was that Hellsjön was fed from both the d.c. transmission and the transformer T. In case the transformer is taken out of operation manually the sequence will start by increasing the power over the d.c. line, by a power or current order to the converter control, until the current in the transformer is close to zero. The transformer breaker () is opened and the converter operates alone feeding the isolated load. The converter control has to transfer from power/current control to a.c. voltage control. In this case a logical signal can be used to order a transfer to a.c. voltage control mode. The transfer is very smooth as there is only a minor change in the power flow. However, detection that the a.c. system is isolated must be general and cover cases where the isolation occur far away from the converter. A criterion within the control equipment has also been used to order transfer from current control to a.c. voltage control. In this case it must be a small disturbance in the a.c. bus voltage which is used to detect the fact that the system is isolated. Fig. 13. Transfer from active to passive network. External order to transfer to a.c. voltage control With the same precondition as above but the power flow in the converter is low. If a protection will trip the transformer breaker the power flow has to be transferred over to the converter. This means that there will be a transient voltage drop on the a.c. bus until the power flow in the d.c. line has increased so that the prefault level is restored into the a.c. bus. Then normal a.c. bus voltage will be restored. Fig. 15. Protective transfer from active to passive network. External order to transfer to a.c. voltage control. The tests demonstrated that the converter can, with a minor transient, take over the required power supply to an a.c. network if all the other generators are tripped Synchronisation and reconnection of an a.c. feeder to an a.c. system fed by the converter The converter feeds the isolated a.c. system and the transformer feeder is now prepared to be connected again. To allow this operation the voltage generated by the converter and the voltage on the transformer terminals have to be synchronised. This can be achieved by altering the frequency reference for the converter. When the two voltages are synchronised the transformer breaker () can be closed. When the transformer and the converter are connected to the same bus, the converter can no longer alone determine the a.c. bus voltage and will therefore switch back to normal power/current control. This sequence is manually ordered and is similar to synchronising and connect an a.c. generator. All the required power in the a.c. system was provided by the converter before
9 the transformer was connected, the transfer can therefore be very smooth Protection co-ordination in a passive a.c. distribution system fed by a VSC. A VSC can be regarded as a three phase voltage source which has the ability to change the output three phase voltage quickly and independently. The behaviour of the a.c. distribution system will entirely depend on the control strategy of the VSC. Overcurrent condition In a passive network the a.c. bus voltage is proportional to the current injected into the system by the converter. The current order to the converter is generated by the a.c. voltage control. In case of a a.c. system fault the impedance decreases and consequently also the a.c. voltage drops. The a.c. voltage control increases the current order but it must be limited to maximum turn-off capability for the valve. As soon as the fault has been cleared by tripping the faulty line section the impedance in the system increases and the current order to the converter must be reduced to prevent an a.c. overvoltage. Normally maximum current capability for the VSC converter is determined by the requirements for steady state operation. This means that the current overload capability is very limited. If the loads are protected by overcurrent protection or fuses, the rated current for the load should be low enough compared to the converter rating to ensure safe isolation of the faulty part of the system. In case of a relatively large load compared to the converter rating, impedance protection is recommended. A consequence of the described properties is that settings for overcurrent protections and fuse ratings can be selected lower without jeopardising the security against false operation of the protection. The a.c. voltage can also be ramped up to prevent inrush currents. AC system faults with no overcurrent In cases where the fault will not cause any overcurrent in the system, such as single phase to ground faults in an impedance grounded system, the VSC will continue to operate with a.c. bus voltage control mode. It is very similar to the conventional distribution network supplied by a.c. generators or bulk power networks. In such cases, conventional earth fault protection systems can be used with the detection of zero sequence current or voltage or both. The basic performance of the converter at an a.c. fault which results in low a.c. bus voltage is that the converter increases the output current up to the current limit for the valve. During this time the faulty condition will be detected by a protection, overcurrent or impedance protection. The protection will trip the a.c. breaker and at the first current zero crossing the fault is disconnected and the converter has to rapidly reduce the current to avoid a.c. overvoltage when the system recovers. The worst condition for this case has been tested in the Hellsjön VSC installation, which means an a.c. fault when the converter is feeding a light load. The first fault applied was a three-phase short circuit on an outgoing a.c. line. The converter feeds the isolated a.c. system, then the line breaker (4) is closed with a three-phase fault on the a.c. line. The a.c. voltage drops and the converter current increases up to its limit and then the protection operates and clears the fault. When the fault has been cleared the converter limits the a.c. bus voltage during the system recovery by fast reduction of the current. The fault was detected by a standard overcurrent relay A similar test was performed with the fault instead applied on the 5 kv side of the transformer T. The converter was feeding the isolated a.c. system and then the a.c. breaker () was closed. ka kv B r e a k e r 4 c u r r e n t A C b u s v o l t a g e ( U b u s ) Fig. 16. AC system fault. Fault clearing with overcurrent protection Performance at faults in the a.c. system
10 In this case an impedance protection was installed on the 1 kv side of the transformer. This means that the protection should be selective not to operate for the inrush current but operate for the relatively low fault current. The fault current and fault clearing are similar to the case described above Asplund G, Eriksson K, Svensson K (1997) CIGRE SC14 Colloquium in South Africa 1997: DC Transmission based on Voltage Source Converter B r e a k e r c u r r e n t ka kv A C b u s v o l t a g e ( U b u s ) Fig. 17. AC system fault. Fault clearing with impedance protection 7. CONCLUSION For the first time an HVDC transmission based on Voltage Source Converter has been built, tested and operated. The experience from field tests with both active and isolated a.c. systems shows that converters with high frequency PWM is feasible to use for small scale HVDC. The VSC converter will also also provide the a.c. system with beneficial properties. The converter does not need many components compared to traditional HVDC. It does not even need a transformer, only phase reactors and fixed high pass filters. Despite this, active and reactive power can be controlled independently and extremely fast. The short circuit power of the receiving as network is of no importance. It is possible to operate even with receiving a.c. networks having no rotating machines. With the rapid development of semiconductors and control, one can foresee that HVDC using VSC converters will soon become a very interesting new option for the transmission of power. 8. REFERENCES Article:
HVDC Light, a tool for electric power transmission to distant loads
Presented at VI Sepope Conference, Salvador, Brazil, May 1998 HVDC Light, a tool for electric power transmission to distant loads by Gunnar Asplund Kjell Eriksson* Ove Tollerz ABB Power Systems AB ABB
HVDC Light and development of Voltage Source Converters
1 HVDC Light and development of Voltage Source Converters K. Eriksson, ABB Utilities Abstract- On March 10, 1997 was transmitted on the 3 MW HVDC Light transmission between Hellsjön and Grängesberg in
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
HVDC-VSC: transmission technology of the future
A bi-pole ± 285 kv HVDC line sandwiched between 3-phase 400 kv HVAC lines. HVDC-VSC: transmission technology of the future A new hybrid HVDC circuit technology using voltage source converters is only half
HVDC 2000 a new generation of high-voltage DC converter stations
HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters
Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters João Antunes, IST ([email protected]) Astract This paper is about multilevel converters used in High Voltage Direct Current
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
HVDC Technology for Large Scale Offshore Wind Connections
HVDC Technology for Large Scale Offshore Wind Connections Nandan Mahimkar, Gunnar Persson,Claes Westerlind, ABB AB, SE-771 80, Ludvika, Sweden, [email protected], [email protected],[email protected],
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
Brochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
Topics. HVDC Fundamentals
Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive C.S.Sharma, Tali Nagwani Abstract Sinusoidal Pulse Width Modulation variable speed drives are increasingly applied in many new industrial
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
The design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 [email protected] The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems
Project description Title: Power Electronics for Reliable and Energy efficient Renewable Energy Systems OBJECTIVES Principal objective Provide competence and decision basis for enabling reliable and energy
Knowing the FACTS. FACTS that enhance power quality in rail feeder systems
Knowing the FACTS FACTS that enhance power quality in rail feeder systems ROLF GRÜNBAUM, PER HALVARSSON, BJÖRN THORVALDSSON The increase in traffic on existing tracks combined with new high-speed rail
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Solar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: [email protected]
HVDC GRIDS FOR OFFSHORE AND ONSHORE TRANSMISSION Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: [email protected] SUMMARY The objective with this
POWER TRANSMISSION FROM OFFSHORE WIND FARMS
POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred
Transmissão em Corrente Contínua
Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB Basic considerations Traditional
Power Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions
Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia Voltage Source Converter based Power Quality Solutions Olivier Suter ABB Holdings Sdn. Bhd., Div. APAN Automation
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson
A firewall against disturbances in high-voltage grids Lennart Carlsson Interconnections between grids are desirable because they not only permit economies through the sharing of reserves, but they also
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs
APPLICATION NOTE AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs by J.M. Bourgeois ABSTRACT Power MOSFET and IGBT gate drives often face isolation and high voltage constraints. The gate drive described
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
FACTS. Solutions to optimise network performance GRID
Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
B4-102 CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC
21, rue d'artois, F-75008 Paris http://www.cigre.org B4-102 Session 2004 CIGRÉ CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC B. D. RAILING G. MOREAU L. RONSTRÖM* J. J. MILLER P. BARD
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION Pramod Ghimire 1, Dr. Alan R. Wood 2 1 ME Candidate Email: [email protected] 2 Senior Lecturer: Canterbury University
A Live Black-start Capability test of a Voltage Source HVDC Converter
CIGRÉ-676 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 A Live Black-start Capability test of a Voltage Source HVDC
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal
May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208
Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer [email protected] Rotating Machinery Diagnostics & Instrumentation
Wide Area Monitoring Current Continental Europe TSOs Applications Overview
Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*
EMI in Electric Vehicles
EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Analysis of AC-DC Converter Based on Power Factor and THD
Website: www.ijetae.com (SSN 50-459, SO 900:008 Certified Journal, Volume 3, ssue, February 03) Analysis of AC-DC Converter Based on Power Factor and THD Shiney.S.Varghese, Sincy George Department of Electrical
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
Design and Applications of HCPL-3020 and HCPL-0302 Gate Drive Optocouplers
Design and Applications of HCPL-00 and HCPL-00 Gate Drive Optocouplers Application Note 00 Introduction The HCPL-00 (DIP-) and HCPL-00 (SO-) consist of GaAsP LED optically coupled to an integrated circuit
Cahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA
Speed Control Methods of Various Types of Speed Control Motors Kazuya SHIRAHATA Oriental Motor Co., Ltd. offers a wide variety of speed control motors. Our speed control motor packages include the motor,
Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2
Electromagnetic Compatibility (EMC) Low-Frequency Standards Summary IEC 61000-3-2: Limits for harmonic current emissions (equipment input current 16A per phase) IEC 61000-3-4: Limitation of emission of
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
Holly STATCOM FACTS to replace critical generation, operational experience
Holly STATCOM FACTS to replace critical generation, operational experience A. Oskoui, B. Mathew, Member, IEEE, J.-P. Hasler, M. Oliveira, Member, IEEE, T. Larsson, Member, IEEE, Å. Petersson, E. John,
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION.
SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION. R. Grünbaum ABB Power Systems AB, AC Systems Division, Sweden. INTRODUCTION Modern society relies
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: [email protected]).
Connection of micro-generation to the electricity distribution network
Connection of micro-generation to the electricity distribution network Network recommendation YA9:09 Sivu 1(20) CONTENTS INTRODUCTION...3 1. MARKINGS AND DEFINITIONS...3 2. DEFINITION OF MICRO-GENERATION
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
Relationship between large subject matter areas
H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN DC AND DC, AND FOR USE WITH MAINS OR SIMILAR POWER SUPPLY SYSTEMS; CONVERSION OF DC OR AC INPUT POWER INTO SURGE OUTPUT POWER;
Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
Voltage Source HVDC Overview Mike Barnes Tony Beddard
Voltage Source HVDC Overview Mike Barnes Tony Beddard Note: This is a version with images removed which have copyrighted other than from the University of Manchester, for web publication. Should a conference
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
Renewable Energy Grid Integration
Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters ) Classification of AC to AC converters Same frequency variable magnitude AC power AC controllers AC power Frequency converters (Cycloconverters)