The Application and Benefits of Multi-phase Auto-reclosing
|
|
|
- Eileen Scott
- 10 years ago
- Views:
Transcription
1 he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double circuit overhead transmission lines. Multi-phase auto-reclosing, which has been applied since the early 1960 s in Japan can overcome these disadvantages. We describe the method of multi-phase auto-reclosing and the benefits that can be achieved in transient system stability and our experience in the application of multi-phase auto-reclosing in Japan. Keywords: double circuit transmission lines, discrimination of fault phase, high-speed auto-reclosing, multi-phase auto-reclosing, single-phase auto-reclosing, three phase auto-reclosing 1. Introduction Auto-reclosing is an important technique for the speedy restoration of faults, improvement of system stability and the prevention of power system disturbances. In Japan overhead transmission lines for EHV networks generally consist of double circuit lines because of the limited size of land areas. For the purpose of improving transient stability, multi-phase auto-reclosing has been applied to double-circuit lines in Japan since the 1960 s. ingle- and three-phase auto-reclosing, being globally applied had been in use before multi-phase auto-reclosing was adopted. hese methods present problems in terms of transient stability because auto-reclosing can be unsuccessful for multi-phase and double circuit faults when these methods are applied. We believe that multi-phase auto-reclosing will play an increasingly important role in power networks around the world as one of the key tools and techniques available to utilities in assisting them in improving power system stability and security. In this * Power ystem Control Dept., OHIBA COP., Japan. (tetsuya. [email protected]) paper we have discussed the impact of multi-phase auto-reclosing and the problems that need to be solved. Firstly, for the successful application of multi-phase auto-reclosing, the ability to discriminate the faulted phase and the system interconnection is necessary. A PCM current differential protection relay is appropriate for these purposes. his kind of relay can easily recognize the system interconnection by using communication circuits, through which the relays on both terminals can transmit the state of circuit breakers to one another. econdly, a short dead time is effective for system stability. But for higher voltages a longer duration is needed to recover the interpole insulation on circuit breakers. o solve this problem many methods which extinguish the secondary arc voltage in a short a time as possible for transmission lines have been proposed. We briefly introduce the results of a study in Japan and finally we report a number of examples of lightning faults on EHV networks and the effect of multi-phase auto-reclosing. his technique has been applied to EHV networks in Japan since 1960.
2 2. Conventional auto-reclosing method For the purpose of improving transient stability, auto-reclosing is applied. Globally single- and three-phase auto-reclosing are applied to overhead double circuit transmission lines. 2.1 ingle-phase auto-reclosing In single-phase auto-reclosing only the faulted phase is tripped for earth faults and the voltage phase angle difference between both terminals can be small enough to continue the supply of power during tripping of the faulted phase. his method can be applied to both single and double circuit overhead transmission lines. 3.1 Method of multi-phase auto-reclosing On Multi-phase auto-reclosing, if at least two different phases remain in a power transmission state, all the phases tripped can be reclosed. his idea is based on the fact that one transmission line has six phases for a double-circuit line. Multi-phase auto-reclosing method includes both single and three-phase auto-reclosing. For example if a three-phase fault occurs on one of the lines of a double-circuit line configuration and a single-phase fault occurs on the other, auto-reclosing is performed. able I presents details of the faulted phases for faults on double circuit lines installed on the same towers. Figure 2.1 ingle-phase auto-reclosing 2.2 hree-phase auto-reclosing In three-phase auto-reclosing a faulted line trips as per a multi-phase fault and auto-reclosing is performed on the condition that there is a system interconnection between the two terminals of the healthy line. Figure2.2 hree-phase auto-reclosing 2.3 Disadvantage of single- and three-phase auto-reclosing ingle- and three-phase auto-reclosing have the following disadvantages and cause a deterioration in the transient stability. -ingle-phase auto-reclosing is unsuccessful for a multi-phase fault. -hree-phase auto-reclosing is unsuccessful for a double-circuit fault. 3. Multi-phase auto-reclosing As an alternative multi-phase auto-reclosing can be applied and provide a solution to the problems described when using single- and three-phase auto-reclosing for the case explained in section 2. able I Details of faulted phases of double circuit lines on the same tower Fault phase ripping and reclosing No #1 line #2 line A B C A B C #1 line #2 line 1 1φ 2 3φF 3 3φF 4 1φ 5 1φ 1φ 6 2φ 7 1φ 1φ 8 2φ 1φ 9 3φF 3φF 10 3φ 11 2φ 1φ 12 2φ 2φ 13 3φ 1φ 14 3φF 3φF 15 3φF 3φF :Fault -:he line is out of service 1φ : single-phase tripping and reclosing 2φ : two-phase tripping and reclosing 3φ : three-phase tripping and reclosing 3φF : three-phase final tripping If multi-phase auto-reclosing is applied, auto-reclosing is possible for the cases indicated by the shaded region on table I. 3.2 Effect of multi-phase auto-reclosing When using single- and three-phase auto-reclosing on double-circuit lines, if a multi-phase fault occurs on the line or a same phase single-phase fault occurs on the double-circuit line, the effect on transient stability is small. But if a multiple fault occurs on a double-circuit line, power transmission on the double-circuit line will be lost. A loss of such a transmission route can cause major power supply interruption with consequent disruption to load or expose the network to potential system stability problems. Alternatively, when using multi-phase auto-reclosing
3 on double-circuit lines, if the above fault occurred, the phase angle difference will be small enough to permit the continuation of the supply of power during tripping the faulted phase. Figure shows the relationship between the effective power and the voltage phase angle from the occurrence of the fault to the reclosing of the circuit breaker. On the phase angle curve, power transits from point A of Pu, on which the synchronous generator normally operates in the double circuit line, to point G in the case of a three phase to earth fault. here is a transit from Point H to point C, when the fault is removed of angular difference θ 2 and the effect of the deceleration energy is to reduce the angle. he angle transits from θ 5 on which auto-reclosing operates to θ 6 until the acceleration energy ( 3 ) is equal to the deceleration energy. Because the output of the generator is above Pu, the angular difference is forced to reduce. Finally the energy is restored to the stable operation angle (θ 0 ). Figure elation to the angular difference on double circuit lines able II shows a summary of the auto-reclosing. able II Methods of auto-reclosing Method Outline chematic diagram ingle-phase autoreclosing On EHV overhead single circuit transmission line the only fault phase trips in single-phase to ground fault and the phase reclosing after dead time. Multi-phase autoreclosinh On EHV overhead double circuit transmission lines the only fault phases trip in multi-phase fault. In service on double circuit lines In service on one line wo phases to earth fault hree phases to earth fault 4. echnical problem In order to apply multi-phase auto-reclosing, it is necessary to confirm with certainty the system interconnection between both terminals and discriminate the fault phase(s). he higher the voltage level, the longer the time required to recover the interpole insulation on circuit breakers. o solve this problem many methods which extinguish the secondary arc voltage in a reduced time have been proposed. 4.1 Faulted phase discrimination and system interconnection For application to multi-phase auto-reclosing, the ability to discriminate the faulted phase and the system interconnection for at least two phases is required. he PCM current differential protection relay has solved the above problem. he current data for each phase in the transmission line terminals is sent between terminals and the relay performs differential protection using the current data. herefore the relay can discriminate the faulted phase. he status of each phase of the circuit breaker is transmitted and the relay is able to recognize the system interconnection. 1) Configuration of PCM current differential relay Figure shows an example of the construction of the PCM current differential relays used in Japan. he current for each phase of the transmission line terminal is sampled 12 times per cycle at rated power frequency by the data acquisition unit DAU. ampling is performed simultaneously for both terminals, and the currents are converted into 12-bit digital data. he current data is converted into serial data and transmitted to the other terminals. he serial data received from the remote terminal is converted to parallel and is acquired by the differential discriminator DD, which uses a microprocessor. he DD performs differential protection using the acquired data. hree-phase autoreclosing A fault line trips in fault and recloses after a certain period of time. O: Circuit breaker trips C: Circuit breaker closes
4 A B and 1000kV. It has been approximately 1 second at 500kV, and more than 4 seconds at 1000kV. DAU Legend IV: F : H : A/D : DD : /P: P/ : : : I/V F H A/D DD Current-voltage converter Filter ampling holding circuit Analog-digital converter Differential discriminator erial-parallel converter Parallel-serial converter ransmitter eceiver /P P/ same to terminal A Figure PCM current differential relay system 2) Block diagram for checking system interconnection Figure shows the block diagram for checking the system interconnection. he relay at terminal A acquires the status of each phase of the CB and D at terminal B via the communication circuit. he system interconnection is checked using the CB and D status at terminal A and B. Fromparallel line CBD-Ⅰ CBD-Ⅱ CBD-Ⅲ Fromcommication circuit CBD-1 CBD-2 CBD-3 Fromparallel line CB-1 CB-2 CB-3 D Checking interconnection phase fromparallel line O O O Detect circuit for healthy two phases O ystem interconnection Figure Interconnection check for multi-phase auto-reclose 4.2 econdary arc extinguishing in UHV systems We expect that the system interconnection will consist of UHV systems in the near future. Multi-phase auto-reclosing is necessary in order to avoid double-circuit outages and to ensure transient stability. econdary arc extinguishing time in UHV transmission lines is longer than in EHV transmission lines because of the electrostatic induction from the parallel line and healthy phases after tripping the faulted phases. Dependent upon environmental factors the arc cannot often be extinguished within an ordinary dead time. herefore it is an important technique to shorten the time for arc extinguishing. he relationship between the dielectric strength and the recovery time depends upon the voltage level, the length of the transmission line and the weather conditions. Figure 4.2 shows the relationship between the dielectric strength and the recovery time at 500kV Breakdown voltage kv Figure 4.2 elation between dielectric strength and recovery time 1) Method of extinguishing the secondary arc current - High speed grounding switch he following methods can be used to extinguish the secondary arc current: -he secondary arc current caused by static coupling is extinguished using a zero-phase sequence compensating reactor. -o physically ground the faulted phases to extinguish the secondary arc current, namely high speed grounding switch (HG). he time required to extinguish the arc depends on the lightning outage performance in the case of the former method. Especially, the time is longer in case of faults on double circuit lines. Otherwise the time is stable for any lightning outage performance. Figure shows the HG method. After the faulted phases have opened, grounding the faulted phases by closing the HG extinguishes the secondary arc and then the HG are opened. Circuit breaker (CB) High speed grounding switch Breakdown voltage kv ime after fault occur (s) ime after fault occur (s) Circuit breaker(cb) High speed grounding switch Figure High speed grounding switching method 2) Improvement in reliability he HG method requires both speed and reliability to execute the following sequence: 1 Fault occurs 2 Opening CB on the faulted phases 3 Closing HG on the faulted phases 4 (Extinguishing the second arc) 5 Opening HG on the faulted phases
5 6 Closing CB on the faulted phases (auto-reclosing) Closing the HG before opening the CB or closing the CB during the closure of the HG can lead to the failure of the HG method. For this reason the HG must check for opening of the CB for the fault and closing the HG. he following are practical examples. 1) Checking ing for the faulted phases he condition of ing in the faulted phase is the following electrical and mechanical condition: - he electrical condition is that the protection differential output signal from the current differential relay cleared following its operation for the fault - he mechanical condition is that the CB is open at both terminals. If these conditions are satisfied, the command for closing the HG is output. eclosing condition Diff relay output erminal A erminal B NO Figure Condition of closing HG HG closing Output signal 2) Checking closing HG he condition for reclosing the CB is that the HG at both terminals are closed and the condition for auto-reclosing are satisfied. Figure shows a block scheme for opening the HG at both terminals. erminal A erminal B Figure HG open check Checking HG open Output signal he status of the HG is acquired via the communication circuit. 3) Field test result of HG In Japan a field test for HG has been conducted over three years. Figure shows the field test result for a 275kV transmission line applied to the HG method. he measured data provided the following result: 1) Effective value of induced voltage from the healthy lines is from about 15 to 20kV. 2) Effective value of HG current is about 5.5A. 3) It takes 30ms to extinguish the secondary arc. he period measured is taken from tripping of the faulted phase to the appearance of the induced voltage. Line voltage Line current HG current ime scale 1sp=1.67ms Closing HG Figure Field test result of HG his result shows that the coordination of system protection is vital. As the secondary arc is spontaneously extinguished before closing the HG in this case as applied at the 275kV level, it does not show that the HG method is effective for extinguishing the arc. But the induced voltage disappears while closing the HG. herefore the method would be able to extinguish secondary arc. ecently the method has been applied to 765kV transmission lines in Korea. 5 Actual data of multi-phase auto-reclosing in Japan In Japan multi-phase auto-reclosing has been applied since the 1960 s in EHV transmission lines where there is no problem with respect to generator shaft torque in large capacity power stations. able III shows details of the faulted phases for faults on double circuit lines installed on the same towers at HV and
6 EHV levels. For double circuit faults; the rate of double circuit faults in which multi-phase auto-reclosing performs auto-reclosing for both double circuit lines, increases by about 30% in comparison to single- and three-phase auto-reclosing methods. his contributes to transient stability. able III Details of faulted phases for faults on double circuit lines at HV and EHV voltage levels Number of faulty phase Per Per Circuit Double circuit Line 1 Line 2 (1980~1985) Lighting Faults eferenc e Diagram Nunber of Faults ate(%) Classification D1 eference [1] uzuki et al. tudy of protection scheme for 1000kV networks IEEJ ransactions on Power and Energy B 1994,7/8PP [2] J.Kobayashi et al. he state of the art of multi-circuit and multi-terminal overhead transmission line protection systems associated with telecommunication systems Cigre,1990 [3] he limitation of transient stability on the power system of the unbalanced fault Central esearch Institute of Electric Power Industry 87075, 1988,07 [4] H.Yamakawa et al. Performance evaluation for the protection and control for 1000kV networks Protective relay system reserch 1997,09 [5] K.Yanagihashi et al. Field est Data of 275kV ransmission Line s Multi-Pole eclosing with High peed Grounding ystem. IEEJ ransactions on Power and Energy B 1995 [6] Y.ekine et al. UHV transmission. he journal of the IEEJ Vol.102, No.11, Nov., 1982 PP D2 D3 D otal Legend : ingle circuit faults D1: ingle phase auto-reclosing performs high-speed auto-reclosing for double circuit lines. D2: ingle phase auto-reclosing perform high-speed auto-reclosing for one of double circuit lines. Multi-phase auto-reclosing performs one for double circuit lines. D3: ingle-phase auto-reclosing cannot perform high-speed auto-reclosing. Multi-phase auto-reclosing performs high-speed auto-reclosing for double circuit lines. D4: Impossible with any auto-reclosing scheme. 6. Conclusion In this paper we have shown that multi-phase auto-reclosing method is available for double circuit transmission lines. We introduce the HG method which is effective in speedily extinguishing secondary arc at the 765kV level and above and is viewed as key to the success of multi-phase auto-reclosing. Multi-phase auto-reclosing can make a major contribution system stability.
ECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Power products and systems. Intelligent solutions for power distribution Zone concept
Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.
(e) condition based maintenance means a set of maintenance actions based on continuous or frequent assessment of equipment condition, which is obtained from either of or a combination of embedded sensors,
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China
ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Guidelines for ATS selection: How to choose the right transfer solution for your power application.
Power topic #7012 Technical information from Cummins Power Generation Inc. Guidelines for ATS selection: How to choose the right transfer solution for your power application. > White Paper By Gary Olson,
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
IESO Supply Deliverability Guidelines
PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System
Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV
FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003
F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify
Transmission Protection Overview
Transmission Protection Overview 2012 Hands-On Relay School Brian Smyth Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with transmission
Staged-Fault Testing of Distance Protection Relay Settings
10.2478/v10048-012-0014-9 MEASUREMENT SCIENCE REVIEW, Volume 12, No. 3, 2012 Staged-Fault Testing of Distance Protection Relay Settings J. Havelka 1, R. Malarić 1, K. Frlan 2 1 Faculty of Electrical Engineering
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
Topics. HVDC Fundamentals
Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse
How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Developing an Agent-based Backup Protection System for Transmission Networks
Power Systems and Communications Infrastructures for the Future, Beijing, September 2002 Developing an Agent-based Backup Protection System for Transmission Networks X. R. Wang* Member IEEE, K. M. Hopkinson**
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Calculation of Voltage Sag Indices for Distribution Networks
Calculation of Voltage Sag Indices for Distribution Networks Juan A. Martinez-Velasco, Member, IEEE, Jacinto Martin-Arnedo, Nonmember Abstract This paper is presenting the main results of a work aimed
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
TDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Electric utilities may vary in their application of end-to-end testing
An Application Case of End-to-End Relay Testing of Communication-Based Protection Schemes Using GPS-Synchronized Secondary Injection Feature by J. Ariza, Megger USA G. Ibarra, CFE, Mexico Electric utilities
Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template
Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister [email protected] Date
Isolated-Parallel UPS Configuration
Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well
25 Distribution System Automation
Chap25 exe 21/06/02 8:30 Page 442 Distribution System Automation Introduction 25.1 Factors influencing the application of automation to distribution networks 25.2 Primary distribution system automation
APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES
APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES J. Ariza G. Ibarra Megger, USA CFE, Mexico Abstract This paper reviews
Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850
Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing
15LINE PROTECTION WITH PILOT RELAYS
15LINE PROTECTION WITH PILOT RELAYS Pilot relaying is the best type for line protection. It is used whenever high-speed protection is required for all types of short circuits and for any fault location.
Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
Local Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Distribution Automation Handbook. Section 8.13 Backup Protection
Distribution Automation Handbook Section 8.13 Backup Protection 2 Contents 8.13 Backup Protection... 3 8.13.1 Introduction... 3 8.13.1.1 REQUIREMETS FOR BACKUP PROTECTIO... 3 8.13.1.2 JUSTIFICATIO OF RESERVE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
FREJA Win Software for FREJA relay testing system
Software for FREJA relay testing system A Megger Group Company Software for FREJA relay testing system In FREJA Win, the all-round General instrument program serves as a convenient, easy to understand,
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
AORC Technical meeting 2014
AORC Technical meeting 2014 http : //www.cigre.org C4-1012 Alarm System Improvement in the Northern Region Dispatching Center of Thailand Mr. Manu PONGKAEW, Mr. Phathom TIPSUWAN Electricity Generating
1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L HITLESS PROTECTION SWITCHING
1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L APPLICATION NOTE AN-357 1.0 INTRODUCTION In today's highly competitive market, high quality of service, QOS, and reliability is
Low Cost Automatic Transmission Line Sectionalizing
Low Cost Automatic Transmission Line Sectionalizing The Ohio State University Distinction Project Autumn 2009 Andrew Dulmage EXECUTIVE SUMMARY This report contains detailed information about the design,
Transmissão em Corrente Contínua
Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB Basic considerations Traditional
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
FIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
Wide Area Monitoring Current Continental Europe TSOs Applications Overview
Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
Mladen Kezunovic Texas A&M University
INTEGRATING DATA AND SHARING INFORMATION FROM VARIOUS IEDs TO IMPROVE MONITORING, CONDITION-BASED DIAGNOSTIC, MAINTENANCE, ASSET MANAGEMENT AND OPERATION TASKS Introduction Mladen Kezunovic Texas A&M University
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
NPCC Regional Reliability Reference Directory # 8 System Restoration
NPCC Regional Reliability Reference Directory # 8 Task Force on Coordination of Operations Revision Review Record: October 21, 2008 Adopted by the Members of the Northeast Power Coordinating Council, Inc.
EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
Electrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
Chapter 5. System security and ancillary services
Chapter 5. System security and ancillary services 1 Introduction Markets for electrical energy can function only if they are supported by the infrastructure of a power system. System should continue to
Teleprotection Schemes and Equipment. James W. Ebrecht Young Power Equipment Scottsdale, AZ
* Teleprotection Schemes and Equipment James W. Ebrecht Young Power Equipment Scottsdale, AZ Teleprotection Schemes And Equipment ~ ~ Relay Relay Teleprotection Communications channel Teleprotection Protection
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*
Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver
www.siemens.com/fusesaver Siemens Fusesaver Highest availability and cost savings for your MV distribution network Answers for infrastructure and cities. 2 In high demand: An intelligent solution Improving
Study on Differential Protection of Transmission Line Using Wireless Communication
Study on Differential Protection of Transmission Line Using Wireless Communication George John.P 1, Agna Prince 2, Akhila.K.K 3, Guy Marcel 4, Harikrishnan.P 5 Professor, Dept. of EEE, MA Engineering College,
Preliminary Results from Present Cigre Survey
Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH
Transformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out
Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System
Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION
White Paper - July 2012. ATS021-ATS022 Automatic transfer switching
White Paper - July 202 02-022 Automatic transfer switching 02-022 Automatic transfer switching Index. Introduction...2 2. Description of... Switching logics...6 Transformer for the main and generator
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
New Technologies for Electric Power Distribution Systems
New Technologies for Electric Power Distribution Systems 158 New Technologies for Electric Power Distribution Systems to Unify Protection/ Units so They Can Be Incorporated into Intelligent Substations
New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems
International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System
SPECIFICATION COG-2007
Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On
GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS
TR TSY 000757 GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS 1. Introduction.... 1.1 Purpose and Scope 1.2 Organization.. 1.3 Reason for Reissue From Technical Advisory
Phase Balancing of Distribution Systems Using a Heuristic Search Approach
Phase Balancing of Distribution Systems Using a Heuristic Search Approach Lin, Chia-Hung*, Kang, Meei-Song**, Chuang, Hui-Jen**, and Ho, Chin-Ying** *National Kaohsiung University of Applied Sciences **Kao
Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor
DOI 10.7603/s40707-013-0008-5 Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor Surya Hardi, Muhd. Hafizi, Muzamir Isa, Rohana Ismail Abstract This paper presents
Protection and Substation Automation. Training Programmes
Protection and Substation Automation Training Programmes Protection and Substation Automation Training Programme Overview The objective of the Training Program is to provide education and training to make
Underground vs. Overhead Transmission and Distribution
electric power engineering Underground vs. Overhead Transmission and Distribution Your Power System Specialists June 9, 2009 1 NATIONAL TRENDS Municipalities have passed laws requiring new distribution
International Review of Grid Connection Requirements related with Voltage Dips for Wind Farms
International Review of Grid Connection Requirements related with Voltage Dips for Wind Farms J. A. Fuentes, M. Cañas, A. Molina, E. Gómez, F. Jiménez Abstract In this work, the Spanish grid code is compared
Automated test systems for distribution transformers Part II. Detailed analysis of the test system features EVENTS ABSTRACT KEYWORDS
TESTS EVENTS ABSTRACT Distribution transformers are used worldwide and in very large quantities as a link between regional mediumvoltage networks and local low-volt age distribution systems. To ensure
FACTS. Solutions to optimise network performance GRID
Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing
How To Limit Voltage Unbalance
Engineering Recommendation No.10 of the Electricity Distribution Code Limits for Voltage Unbalance in the Electricity Supply System Version 1.0 30th November 2005 Prepared by: Abu Dhabi Distribution Company,
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Telecommunications Switching Systems (TC-485) PRACTICAL WORKBOOK FOR ACADEMIC SESSION 2011 TELECOMMUNICATIONS SWITCHING SYSTEMS (TC-485) FOR BE (TC)
PRACTICAL WORKBOOK FOR ACADEMIC SESSION 2011 TELECOMMUNICATIONS SWITCHING SYSTEMS (TC-485) FOR BE (TC) Department of Electronic Engineering NED University of Engineering and Technology, Karachi LABORATORY
HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER
OPTIMUM EFFICIENCY AND FLEXIBLE USE HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER One of the many requirements of the modern inverter is a broad, coordinated input and MPP voltage range with a
Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches
21, rue d Artois, F-75008 PARIS C6 _113 _2012 CIGRE 2012 http : //www.cigre.org Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing
Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE
Electrical Considerations for HVDC Transmission Lines Joe Mooney, PE POWER Engineers has met the standards and requirements of the Registered Continuing Education Program. Credit earned on completion of
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
NET METERING SUB-CODE. for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana
for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana JANUARY 2015 1 Table of Contents PART A: BACKGROUND... 1 1 Introduction... 1 1.1 Objective... 1 1.2 Status... 1 2
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques
Drives AC Drives Using PWM Techniques Power Conversion Unit The block diagram below shows the power conversion unit in Pulse Width Modulated (PWM) drives. In this type of drive, a diode bridge rectifier
Integration of Supervisory Control and Data Acquisition Systems Connected to Wide Area Networks
Hitachi Review Vol. 53 (2004), No. 3 169 Integration of Supervisory Control and Data Acquisition Systems Connected to Wide Area Networks Mitsuya Kato Katsufumi Watahiki Tatsuyuki Suzuki OVERVIEW: Continued
Trip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
Calculating voltage dips in power systems using probability distributions of dip durations and implementation of the Moving Fault Node method
Calculating voltage dips in power systems using probability distributions of dip durations and implementation of the Moving Fault Node method Master of Science Thesis MIKAEL WÄMUNDSON Department of Energy