SSPI-APPN OTES: PARALLEL C ONNECTIONS

Size: px
Start display at page:

Download "SSPI-APPN OTES: PARALLEL C ONNECTIONS"

Transcription

1 There are two distinct reasons to connect power supplies in parallel: Current Sharing and Redundancy. Combining of these reasons is common, and there are many ways to implement them. The unique considerations of paralleling deal mostly with the outputs of supplies, electrical and mechanical. The first step is to clearly identify the all of the objectives behind the intent to parallel. The are several segments of the electronics industry that are often associated with power supplies used in parallel for power and redundancy. They are Telecommunications, Mass Storage, Storage Area Networks, Real Time Computers, and Public Safety Systems. Below are common terms used when discussing power supplies used in parallel: TERMS DEFINED: Current Sharing: Refers to the division of the load among the supplies connected in parallel. The supplies will provide differing portions of the load by default unless measures are taken to balance the load. Current sharing is desirable for three reasons: (a) It increases the total amount of load current available. (b) It provides de-ration for the individual supplies, helping improve their potential long-term reliability. (c) It minimizes the potential for power bus glitches after a power supply has failed. In many redundant power supply applications, the supplies are carefully selected and implemented to provide both redundancy and current sharing. Doing so provides fault tolerance and de-ration to improve the longevity of all of the supplies. Additionally, sharing of the load keeps all supplies awake and conducting current. An idle power supply takes longer to come up to nominal output voltage. This could cause an unacceptable glitch on the power bus. Fault Tolerance: The goal of protecting a system from any single point of failure, in some systems multiple points of failure. The term can refer to simple paralleling or high tech power systems using redundant AC phases, Battery Back Up, N+1 hot swap power supplies, and remote, visual, and audible alarms. In the case of redundant AC phases, there are two power supply sections, or drawers, using separate AC phases. SPI has a great deal of experience designing fault tolerant power systems. Contact us directly to discuss a particular application. We can provide any pieces or all of the required power system hardware. 1 of 5

2 *Hot Swap: Used in most N+1 applications. Mounted in a rack, the individual supplies feature front panels, handles, guides, and live-insertion connectors for all electrical connections. The individual supplies can be inserted or removed without powering the system down. Isolation Diodes: Also called ORing or Blocking diodes, these are used for two primary reasons: (a) To prevent a failed supply from causing a general system shutdown in a fault condition. The diodes in a failed supply will block the current of good supplies from conducting into the failed supply. Without the diodes, the good supplies could see a short circuit condition. The system power would be lost. (b) When a power supply is inserted live into a system already powered up, its output capacitors would otherwise drain power from the power bus causing a disturbance. N+1 Redundancy: N equals the number of power supplies required for the load current. 1 is an extra supply providing redundancy should one of the N supplies fail. Parallel Connection: Connecting the + and - output leads of multiple supplies to the same respective points on a load. This increases the current available to the load but not the voltage. Serial connection has the opposite effect. Redundancy: The use of an extra supply provided as a backup. Used heavily in the telecommunications industry where system down time is unacceptable, power supply redundancy is a basic method used to create fault tolerance in a power system. * Note that the term Warm Swap has been gaining acceptance. It refers to the scenario where the power supplies have a front panel On/Off switch or an AC connector. The supplies can be switched on after insertion. This will eliminate pin to socket arching when that is a concern. When using power connectors that are safety agency approved for hot swapping, arching is generally not of concern. It is important to check if the hot swap power supplies under consideration have connectors that are safety agency approved specifically for hot swapping. If not, the power supply model should incorporate the on/off switch. Also, be sure to check the maximum pin current ratings from the individual safety agencies. Note that Switching Power s HS-250 and HS-350 series incorporate on/off switches. The higher power HS-500, HS-750, and HS-1000/1001 series use connectors that are safety agency approved for live insertion and do not have front panel switches on the catalog versions. 2 of 5

3 CURRENT SHARING METHODS: There are three common ways to connect power supplies in parallel for the purposes of current sharing and redundancy: 1. Brute-force 2. Forced: Also known as Active or Third Wire Current Sharing 3. Zero Wire: Also known as Droop Regulation; Passive Current Sharing; Slope Programming Each method is unique from the others and has advantages and disadvantages of which the power systems designer should be well aware. Switching Power provides standard and custom products as well as support for all three types of current sharing. Brute-force Current Sharing: The simplest implementation possible, brute force paralleling connects two or more supplies together at the load with no additional circuitry used to create balanced loading among the supplies in parallel. The method can be used to increase the power available beyond that which one power supply can provide, and it can also provide redundancy. The unit with the highest output voltage conducts current first. In order to create the greatest possible degree of sharing, the user must set the output voltages as closely as possible and try to match the impedance from each supply to the load. Isolation diodes can be used. Cons: Flexible Scalable Inexpensive Ordinary power supplies can be used Requires precision adjustments of output voltages to achieve current sharing. The output wire length, gauge and connections must be closely matched. The higher set supply will conduct a greater portion of the load current causing reduced longevity for itself. This can also cause power bus glitches if the lower set supply is conducting too little when its load is stepped up quickly. This could occur if the higher set supply experiences a failure. 3 of 5

4 The current limit set point should be reset to % of rated output to reduce the potential for overstressing the individual supplies. Remote sensing cannot be used. The lower set supply would sense the higher set supply s output voltage. Interpreting this as its own output voltage, the lower set supply would shut down by closing its duty cycle. Forced Current Sharing: This method uses active circuitry to measure a power supply s output current and compare it to the outputs from the other paralleled supplies. A communications link called the third wire connects the supplies to one another. Active current sharing circuitry provides feedback to the supply s pulse width modulators adjusting their output voltages. There are many methods power supply manufacturers can choose from to feed back and adjust the current sharing ratios. This makes it difficult for power supplies from different manufacturers to current share together. Generally, doing so is considered impractical. Cons: Shares load evenly. Voltage regulation can be within +/-1%. The tightest of the three basic methods. Good power system scalability. Perceived as most high tech method. Remote sensing possible. No adjustments required. Single fault potential: Although a rare occurrence, the failure of the communications link (the 3 rd wire) could cause a general power system failure. Complexity is greater. More expensive. Not practical to match with supplies from other vendors or series. The current share bus (the 3 rd wire) may require external noise reduction components. System noise can interfere with the power system s behavior. 4 of 5

5 Zero Wire Current Sharing: This is a simple and reliable method of current sharing. Circuitry in the power supply measures its own output current and programs the output voltage up or down. As the load to a supply increases, its output voltage decreases linearly. In a two-supply system, for example, the supply with the higher output voltage will conduct first. Once its voltage is programmed down to a point at which its voltage is the same as the other supply, they will both conduct current evenly. Individual supplies do not know the existence of any other supply sharing the load current. They only react to the percentage of full load being drawn from them. Remote sensing should be utilized to maximize load regulation. Good load balancing. Inexpensive. Reliable. Best fault tolerance. Excellent scalability. Multiple sources possible. Remote sensing possible. No adjustments required. Cons: Voltage regulation +/-2%. Could be perceived as lower tech. Please contact Switching Power for additional information regarding the methods of sharing for power and redundancy. We would like to participate in your process, helping to make certain the power system is optimized. 5 of 5

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

I STAR COMPUTER CO., LTD

I STAR COMPUTER CO., LTD I STAR COMPUTER CO., LTD Mini Redundant Power Supply 300W+300W for IPC-Computer Model No. TC-300R8 Table of content 1. Introduction...1 2. Specification 2.1 Input Voltage...1 2.2 DC Output...1 2.3 PS-ON

More information

PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES

PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES GENERAL ATOMICS ENERGY PRODUCTS Engineering Bulletin PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES Joe Jichetti, Andrew Bushnell, Robert McDowell Presented at: IEEE Pulsed Power Conference June

More information

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor

More information

14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V

14.5GHZ 2.2KW CW GENERATOR. GKP 22KP 14.5GHz WR62 3x400V 14.5GHZ 2.2KW CW GENERATOR GKP 22KP 14.5GHz WR62 3x400V UTILIZATION OF GKP 22KP GENERATOR With its characteristics of power stability whatever the load, very fast response time at a pulse, low ripple,

More information

Series AMLDL-Z Up to 1000mA LED Driver

Series AMLDL-Z Up to 1000mA LED Driver FEATURES: Click on Series name for product info on aimtec.com Series Up to ma LED Driver Models Single output Model Input Voltage (V) Step Down DC/DC LED driver Operating Temperature range 4ºC to 85ºC

More information

Power Feeding Equipment for Optical Submarine Cable Systems

Power Feeding Equipment for Optical Submarine Cable Systems Power Feeding Equipment for Optical Submarine Cable Systems KANEKO Tomoyuki, CHIBA Yoshinori, KUNIMI Kaneaki, NAKAMURA Tomotaka Abstract A submarine cable system is fed power from power feeding equipment

More information

DC/DC power modules basics

DC/DC power modules basics DC/DC power modules basics Design Note 024 Ericsson Power Modules General Abstract This design note covers basic considerations for the use of on-board switch mode DC/DC power modules, also commonly known

More information

ELECTRONIC POWER SYSTEMS

ELECTRONIC POWER SYSTEMS ELECTRONIC POWER SYSTEMS TRADEOFFS BETWEEN SINGLE-PHASE & THREE-PHASE POWER WHITE PAPER: TW0057 1 Executive Summary Modern Electronic Systems are quite often powered from a three-phase power source. While

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

LOXONE 12 Channel Amplifier

LOXONE 12 Channel Amplifier LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room

More information

Edition Perfect combination 9 Power supplies Electronic P Edition kaging www clear order..biz information in the catalogue

Edition Perfect combination 9 Power supplies Electronic P Edition kaging www clear order..biz information in the catalogue 9 Power supplies Übersicht PROLINE Overview... 0 Power supplies Cabinets... 1 Wall mounted cases... 2 slimpower AC/DC switched-mode power supply 42 W, 3 HP Compact and low interference Accessories for

More information

Co-location Interconnect Power Panel (CIPP) Installation Guide

Co-location Interconnect Power Panel (CIPP) Installation Guide Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...

More information

Online UPS. PowerWalker VFI 1000R/1U

Online UPS. PowerWalker VFI 1000R/1U Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.

More information

LAP ENERGIA PARA DATACENTERS

LAP ENERGIA PARA DATACENTERS LAP ENERGIA PARA DATACENTERS Latin American Power. CABA, Argentina. 2 UPS INDOOR Latin American Power. CABA, Argentina. ALI ELITE SERIES Line Interactive UPS Tower/19 Rack Mount Versions 19 Rack Mount

More information

Power surges can also be generated by equipment in your facility such as:

Power surges can also be generated by equipment in your facility such as: Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

PowerGem Pro Uninterruptible Power Supply

PowerGem Pro Uninterruptible Power Supply Uninterruptible Power Supply User-friendly Intelligent Ultra reliable Range The Most Intelligent On-Line Double Conversion Power Protection System The range achieves higher reliability and greater immunity

More information

Bristol ControlWave Redundant Control

Bristol ControlWave Redundant Control October 19, 2007 - Page 1 Bristol ControlWave Redundant Control Redundant systems are offered for critical processes and harsh applications that require maximum operational readiness and system availability.

More information

X. Dealing with Signature Differences

X. Dealing with Signature Differences X. Dealing with Signature Differences One of the most often asked questions that Tracker users ask is "when is a different signature considered a fault?". Simply put, "what makes a bad signature?". To

More information

Wireless Networks and Power Quality

Wireless Networks and Power Quality Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider

More information

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection

More information

Balun Parameter Definitions & Measurement May 2004

Balun Parameter Definitions & Measurement May 2004 Balun Parameter Definitions & Measurement May 2004 Differential circuits are becoming more widely used in RF circuits for the same reason that they have been used for years in lower frequency circuits.

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made

More information

SCD Server. SCD Server Pro

SCD Server. SCD Server Pro SCD Server SCD Server Pro SCD Server & SCD Server Pro 9850-000387-01 - Page 1 of 8 SCD Server and SCD Server Pro The SCD Server is a 2U high DMX generator, running the ZerOS Operating System and emulating

More information

Motherboard- based Servers versus ATCA- based Servers

Motherboard- based Servers versus ATCA- based Servers Motherboard- based Servers versus ATCA- based Servers Summary: A comparison of costs, features and applicability for telecom application hosting After many years of struggling for market acceptance, it

More information

M1000 Process Alarm Monitor

M1000 Process Alarm Monitor Data Sheet Process Alarm Monitor Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

Multi-Protocol decoder 76 200 with Load regulation

Multi-Protocol decoder 76 200 with Load regulation Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder

More information

HFE1600 Series 1600W 1U Hot Swap Front End Power Supplies

HFE1600 Series 1600W 1U Hot Swap Front End Power Supplies 25.2W/in 3 power density Internal ORing MOSFET & Current Share Climate Savers Computing efficiency standards Up to 8000W in 1U rack Single and dual output 1U racks PMBus option HFE1600 Series 1600W 1U

More information

APPLICATION NOTES: Dimming InGaN LED

APPLICATION NOTES: Dimming InGaN LED APPLICATION NOTES: Dimming InGaN LED Introduction: Indium gallium nitride (InGaN, In x Ga 1-x N) is a semiconductor material made of a mixture of gallium nitride (GaN) and indium nitride (InN). Indium

More information

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems ANTI-THEFT SYSTEM 1995 Volvo 850 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems 850 DESCRIPTION & OPERATION WARNING: Deactivate air bag system before performing any service operation. For 1995

More information

Advanced Monolithic Systems

Advanced Monolithic Systems Advanced Monolithic Systems FEATURES Three Terminal Adjustable or Fixed oltages* 1.5, 1.8, 2.5, 2.85, 3.3 and 5. Output Current of 1A Operates Down to 1 Dropout Line Regulation:.2% Max. Load Regulation:.4%

More information

Fuses. Introduction. Measuring is knowing. Who chooses?

Fuses. Introduction. Measuring is knowing. Who chooses? Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure

More information

Considerations When Specifying a DC Power Supply

Considerations When Specifying a DC Power Supply Programming Circuit White Paper Considerations When Specifying a DC Power Supply By Bill Martin, Sales/Applications Engineer Every automated test system that tests electronic circuit boards, modules or

More information

What is a multimeter?

What is a multimeter? What is a multimeter? A multimeter is a devise used to measure voltage, resistance and current in electronics & electrical equipment It is also used to test continuity between to 2 points to verify if

More information

Specification Requirements DBL 700MX and 1000MX Series UPS

Specification Requirements DBL 700MX and 1000MX Series UPS Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without

More information

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family AC/DC Power Supply Reference Design Advanced SMPS Applications using the dspic DSC SMPS Family dspic30f SMPS Family Excellent for Digital Power Conversion Internal hi-res PWM Internal high speed ADC Internal

More information

Net Optics Learning Center Presents The Fundamentals of Passive Monitoring Access

Net Optics Learning Center Presents The Fundamentals of Passive Monitoring Access Net Optics Learning Center Presents The Fundamentals of Passive Monitoring Access 1 The Fundamentals of Passiv e Monitoring Access Copy right 2006 Net Optics, Inc. Agenda Goal: Present an overview of Tap

More information

ABB Drives. User s Manual HTL Encoder Interface FEN-31

ABB Drives. User s Manual HTL Encoder Interface FEN-31 ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

VX 2400 Dimmer User's Manual

VX 2400 Dimmer User's Manual TM VX 2400 Dimmer User's Manual 21-2119C Manual Revision 1.01 Software Version 1.0 10 March 1994 Table of Contents 1. General Description...3 1.1. Standard Features:...3 2. Installing Options...4 2.1.

More information

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS TSB #: 74 Date: 9/7/2013 Initial Once Read: In this technical bulletin we have listed diagnostic advice relating to the Holden VE/WM HVAC & A/C system. This information

More information

Open Rack Hardware v1.0

Open Rack Hardware v1.0 Open Rack Hardware v1.0 Authors: Pierluigi Sarti, System Designer Steve Mills, Mechanical Engineer 1 Scope This document describes the technical specifications for the custom rack that houses Open Compute

More information

The Different Types of UPS Systems

The Different Types of UPS Systems The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.

More information

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. 7I29 MANUAL Rev 1.5 CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. THE 7I29 IS INTENDED FOR USE BY OEMS THAT WILL INTEGRATE IT INTO A SYSTEM WITH INTERLOCKS AND

More information

Digital Controllers ACTUATOR COMPATABILITY

Digital Controllers ACTUATOR COMPATABILITY Product Specification 36502B DESCRIPTION APECS DPG-21XX-00X Digital Controllers The DPG-21XX-00X digital controller is used primarily to govern diesel or gas fueled engines of generator sets. This microprocessor-based,

More information

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

GWS250 Series Instruction Manual

GWS250 Series Instruction Manual GWS250 Series Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure Summary Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure This is a general procedure on how to replace Pathfinder 48-10kW shelf with a Cordex 3.6kW shelf. Part Numbers 010-567-20

More information

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS TR TSY 000757 GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS 1. Introduction.... 1.1 Purpose and Scope 1.2 Organization.. 1.3 Reason for Reissue From Technical Advisory

More information

Application Note. Line Card Redundancy Design With the XRT83SL38 T1/E1 SH/LH LIU ICs

Application Note. Line Card Redundancy Design With the XRT83SL38 T1/E1 SH/LH LIU ICs Application Note Design With the XRT83SL38 T1/E1 SH/LH LIU ICs Revision 1.3 1 REDUNDANCY APPLICATIONS INTRODUCTION Telecommunication system design requires signal integrity and reliability. When a T1/E1

More information

CX Zoner Installation & User Guide

CX Zoner Installation & User Guide CX Zoner Installation & User Guide Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel +44 (0)114 244 7051 Fax +44 (0)114 242 5462 e-mail info@cloud.co.uk web site http://www.cloud.co.uk

More information

Low Cost Pure Sine Wave Solar Inverter Circuit

Low Cost Pure Sine Wave Solar Inverter Circuit Low Cost Pure Sine Wave Solar Inverter Circuit Final Report Members: Cameron DeAngelis and Luv Rasania Professor: Yicheng Lu Advisor: Rui Li Background Information: Recent rises in electrical energy costs

More information

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

GAMATRONIC ELECTRONIC INDUSTRIES LTD. GAMATRONIC GAMATRONIC ELECTRONIC INDUSTRIES LTD. History In house Activities International Awards Info-Tech 2012 Vendor Landscape Research WORLD REPRESENTATION Modular Solutions Single Phase Power Solutions

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer

More information

Power Quality. Uninterruptible Power Supply

Power Quality. Uninterruptible Power Supply Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning

More information

Domains. Seminar on High Availability and Timeliness in Linux. Zhao, Xiaodong March 2003 Department of Computer Science University of Helsinki

Domains. Seminar on High Availability and Timeliness in Linux. Zhao, Xiaodong March 2003 Department of Computer Science University of Helsinki Domains Seminar on High Availability and Timeliness in Linux Zhao, Xiaodong March 2003 Department of Computer Science University of Helsinki 1 1. Introduction The Hardware Platform Interface (HPI) is developed

More information

Installation Fleet Tracker (SBC3)

Installation Fleet Tracker (SBC3) Installation Fleet Tracker (SBC3) VERSION DATUM AUTOR DATEINAME 1.0 1. NOVEMBER 2011 SM EINBAU FLOTTENSBC3_ENGLISCH_V10.DOCX The installation should be done by qualified personnel, who is experienced in

More information

SVC400P/SVC800P. 4/8 Camera Live Tracking Vehicle DVR Installation Manual. Version 1.0

SVC400P/SVC800P. 4/8 Camera Live Tracking Vehicle DVR Installation Manual. Version 1.0 SVC400P/SVC800P 4/8 Camera Live Tracking Vehicle DVR Installation Manual Version 1.0 1. MAIN FEATURES... 2 2. PRODUCT OVERVIEW... 2 3. DIMENSIONS... 4 4. PACKAGE CONTENTS... 5 5. MOUNTING AND ENVORNMENTAL

More information

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications

More information

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

MN1010 Evaluation Kit v3 User Guide

MN1010 Evaluation Kit v3 User Guide 1 Evaluation Kit Introduction The MN1010 Evaluation Kit is designed to allow the user to quickly evaluate the Micro Modular Technologies MN1010 GPS receiver module. This kit can be used in either a laboratory

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Contents. Installing the upgrade memory kit in the G450 and G430 Media Gateway May 2014 1

Contents. Installing the upgrade memory kit in the G450 and G430 Media Gateway May 2014 1 Contents Installing the upgrade memory kit in the G450 / G430 Media Gateway... 3 Equipment ordering... 3 Inserting or replacing a RAM card... 4 Inserting or replacing a RAM card in the G450... 4 Replacing

More information

RCP-1000 / RCP-1U Instruction Manual

RCP-1000 / RCP-1U Instruction Manual RCP- / RCP-U Instruction Manual . Safety Guidelines.... Introduction of Series Models.... Introduction.... Features.... Order Information....4 Main Specification.... Mechanical Specification and Input

More information

Infinity C DC to DC Power System

Infinity C DC to DC Power System PRODUCT OVERVIEW Infinity C DC to DC Power System Models 663-664 Negative (663) or Positive (664) Output Large plant features in a small plant package Battery management including discharge test Industry

More information

Analysis of identification technologies and an automatic lock for school lockers

Analysis of identification technologies and an automatic lock for school lockers EUROPEAN JOURNAL FOR YOUNG SCIENTISTS AND ENGINEERS Analysis of identification technologies and an automatic lock for school lockers David Marn Abstract The main objective of the project was the improvement

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

High Power Programmable DC Power Supplies PVS Series

High Power Programmable DC Power Supplies PVS Series Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient

More information

Build A Video Switcher. Reprinted with permission from Electronics Now Magazine September 1997 issue

Build A Video Switcher. Reprinted with permission from Electronics Now Magazine September 1997 issue Build A Video Switcher Reprinted with permission from Electronics Now Magazine September 1997 issue Copyright Gernsback Publications, Inc.,1997 BUILD A VIDEO SWITCHER FRANK MONTEGARI Watch several cameras

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

BXR 300C BXR 300R. Owner, s Manual P/N 040294

BXR 300C BXR 300R. Owner, s Manual P/N 040294 THE SOUND THAT CREATES LEGENDS BXR 300C BXR 300R Owner, s Manual P/N 040294 INTRODUCTION The Fender BXR 300 AMPLIFIER is the most recent effort in state of the art bass amplifier technology, and is a member

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

Residential Gateway (RG) Battery Backup

Residential Gateway (RG) Battery Backup Residential Gateway (RG) Battery Backup BU3DC000-12V User Manual Table of Contents Page Introduction... 3 Safety Information... 3 System Requirements... 3 Package Contents... 4 Recycling... 4 Product Layout

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

GTS-4E Hardware User Manual. Version: V1.1.0 Date: 2013-12-04

GTS-4E Hardware User Manual. Version: V1.1.0 Date: 2013-12-04 GTS-4E Hardware User Manual Version: V1.1.0 Date: 2013-12-04 Confidential Material This document contains information highly confidential to Fibocom Wireless Inc. (Fibocom). Fibocom offers this information

More information

Cold-Junction-Compensated K-Thermocoupleto-Digital Converter (0 C to +1024 C)

Cold-Junction-Compensated K-Thermocoupleto-Digital Converter (0 C to +1024 C) 19-2235; Rev 1; 3/02 Cold-Junction-Compensated K-Thermocoupleto-Digital General Description The performs cold-junction compensation and digitizes the signal from a type-k thermocouple. The data is output

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system

Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Model #: SMART500RT1U 500VA line interactive 1U rack/tower UPS 7 outlets with 1 switchable load bank Simultaneous

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

Contents. : AEOS Blue cabling and technical aspects. NEDAP N.V. IDEAS Information Bulletin No: H032. Date : 12 January 2016

Contents. : AEOS Blue cabling and technical aspects. NEDAP N.V. IDEAS Information Bulletin No: H032. Date : 12 January 2016 NEDAP N.V. IDEAS Information Bulletin No: H032 Date : 12 January 2016 Concerns : AEOS Blue cabling and technical aspects AEOS Blue units can easily be connected to each other using the 485bus. This document

More information

EAGLE Power over Ethernet Products for IP Powering Applications. Flexibility, Simplicity and Value LAN POWER SYSTEMS. Trend Datacom USA, Inc.

EAGLE Power over Ethernet Products for IP Powering Applications. Flexibility, Simplicity and Value LAN POWER SYSTEMS. Trend Datacom USA, Inc. EAGLE Power over Ethernet Products for IP Powering Applications Flexibility, Simplicity and Value LAN POWER SYSTEMS Trend Datacom USA, Inc. Presentation Agenda IEEE802.3af PoE Technology Definitions and

More information

COBRA Power over Ethernet Products for IP Surveillance Applications LAN POWER SYSTEMS. Trend Datacom USA, Inc.

COBRA Power over Ethernet Products for IP Surveillance Applications LAN POWER SYSTEMS. Trend Datacom USA, Inc. COBRA Power over Ethernet Products for IP Surveillance Applications LAN POWER SYSTEMS Trend Datacom USA, Inc. Presentation Agenda IEEE802.3af PoE Technology Definitions and Implementations IP Surveillance

More information

F2400 FOM II Series Fiber Optic Modem Technical Manual

F2400 FOM II Series Fiber Optic Modem Technical Manual F2400 FOM II Series Fiber Optic Modem Technical Manual T1 Revision B Copyright April 2003 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com A030430283T PROPRIETARY DATA All data

More information

Operating Manual UWAPS-TINY Series

Operating Manual UWAPS-TINY Series Operating Manual UWAPS-TINY Series Powecon Oy WWW.POWECON.FI 1/9 Table of content 1 Warranty...3 2 Safety information...3 3 Abbreviations and terminology...3 4 List of appendices...4 5 Introduction...4

More information

DELL RAID PRIMER DELL PERC RAID CONTROLLERS. Joe H. Trickey III. Dell Storage RAID Product Marketing. John Seward. Dell Storage RAID Engineering

DELL RAID PRIMER DELL PERC RAID CONTROLLERS. Joe H. Trickey III. Dell Storage RAID Product Marketing. John Seward. Dell Storage RAID Engineering DELL RAID PRIMER DELL PERC RAID CONTROLLERS Joe H. Trickey III Dell Storage RAID Product Marketing John Seward Dell Storage RAID Engineering http://www.dell.com/content/topics/topic.aspx/global/products/pvaul/top

More information

Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert

More information

TIMING SIGNALS, IRIG-B AND PULSES

TIMING SIGNALS, IRIG-B AND PULSES TIMING SIGNALS, IRIG-B AND PULSES Document No. PD0043200B July 2013 Arbiter Systems, Inc. 1324 Vendels Circle, Suite 121 Paso Robles, CA 93446 U.S.A. (805) 237-3831, (800) 321-3831 http://www.arbiter.com

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information