4 -do- - New added Clause 14: Transformer & metallic box sealing facility:
|
|
- Irene Hardy
- 7 years ago
- Views:
Transcription
1 Subject: Amendment in Technical Specification for Outdoor types Distribution Transformers upto and including 100 KVA (i.e 16 to 100 KVA) with & without CSP (Completely Self Protected) features. Sr. Technical No. Specification No. 1. S-174/DD-177/2008 for Outdoor types Distribution Transformers upto and including 100 KVA (i.e. 16 to 100 KVA) with & without CSP (Completely Self Protected) Existing Clause Clause : The LV bushings shall be housed within the metallic enclosure with sealing arrangement so as to avoid any possibility of tapping of supply from the busing terminal. The enclosure shall be made with sheet metal of thickness not less than 2mm and powder coated. Enclosure shall have provision for pad locking arrangements. This metallic enclosure should have different compartments for housing each item i.e LT CT meter, LT CT s, LT Capacitor, MCCB (if provided),gsm/gprs Modem (The failure of any item does not effect the working of other items) and insulated aluminum bus bar of suitable size should be provided to cater full load capacity of transformer. Amended Clause Clause : The LV bushings shall be housed within the metallic enclosure with sealing arrangement so as to avoid any possibility of tapping of supply from the busing terminal. The enclosure shall be made with sheet metal of thickness not less than 2mm and powder coated. Enclosure shall have provision for pad locking arrangements. This metallic enclosure should have different compartments for housing each item i.e LT CT meter, LT CT s, LT Capacitor, MCCB (if provided),gsm/gprs Modem (The failure of any item does not effect the working of other items). 2. -Do FASTENERS: The Clause 5.14 may be added with: 2 Nos. anti-theft fasteners of steel on two diagonally opposite corners of the tank shall be provided. All nuts & pins shall be adequately locked. 3. -Do- - New added Clause 13: LT PVC Cables The DTs shall be supplied with appropriate size of Single Core Cable(s) (unarmored) of ISI mark and duly type tested from reputed testing house / laboratory. The owner shall have the exclusive right to demand for type tests certificates or copy of ISI
2 manufacturing license from the manufacturer/ supplier of the cable The rating/quantity of LT Cables shall be as follows:- Sr. No. Capacity of T/Fs Size of Cable 1 16 KVA S/c- 25 mm² 2 25 KVA S/c- 50 mm² 3 63 KVA S/c- 120 mm² KVA S/c- 185 mm² Length of cable required 4 -do- - New added Clause 14: Transformer & metallic box sealing facility: The transformer should have facility to seal the transformers Top Plate & its body and also the metal box, housing the other equipment(s) like CTs, LT CT meter etc. along with the transformer. The metal box shall have pad-lock arrangement & complete protection from dirt, rain water & other pollutants and shall comply to IP:55 protection or better. The complete unit of transformer(s) and all other accessories shall be supplied by putting all of them in circuit. 5 -do - New added Clause 15: RATING AND TERMINAL MARKING PLATES: There shall be rating plates on the transformer containing the information specified in clause 15.2 of IS:2026-
3 1977 (part-i). Total 50% & 100% load losses of the transformer should also be mentioned on the rating plate. The following additional information must also be punched on the plate and imposed two opposite sides of the body of the T/F. i) Purchase order No. & date ii) Date of inspection iii) Property of DHBVN iv) Make v) Guarantee period. 6 -do - New added Clause 16: GUARANTEED PARTICULARS: TECHNICAL The guaranteed technical particulars of the transformers shall be given by the tenderer (Annexure-I) along with the tender. Tender without GTP shall be out rightly rejected. 7 -do- - New added Clause 17: Rating of Capacitor The rating of Capacitor to shall be as follows:- Sr. Capacity Rating of No. of T/Fs capacitor 1 16 KVA 5 KVAR 2 25 KVA 9 KVAR 3 63 KVA 22 KVAR KVA 36 KVAR GM/P&D CGM/Commercial CGM/P&D CGM/MM
4 Subject: - Amendment in Technical Specification. Sr. Technical No. Specification No. 1. S-174/DD- 177/2008 for Out Door Type Distribution Transformer i.e. 16 to 100 KVA Existing Clause Core Clamping for Amorphous metal Transformers Core clamping shall be with top and bottom U- shaped core clamps made of sheet steel clamped HT steel tie rods for efficient clamping MS core clamps shall be painted with varnish or oil-resistant paint MS rods shall be used as tie rods Suitable provision shall be made in the bottom core clamp/ bottom plate of the transformer to arrest movement of the active part. Amended Clause Core Clamping for Amorphous metal Transformers Core clamping shall be with top and bottom U-shaped core clamps made of sheet steel clamped HT steel tie rods for efficient clamping Core clamps shall be painted with varnish or oilresistant paint Suitable provision shall be made in the bottom core clamp/ bottom plate of the transformer to arrest movement of the active part MS rods shall be Deleted used as tie rods The pressure of corrugated tank should be as per standard mentioned in clause 2.0 of specification Terminal connectors: The LV bushing and HV bushing stems shall Deleted
5 be provided with suitable terminal connectors so as to connect the jumper without disturbing the bushing stem. Connectors shall be with eye bolts so as to receive 55 sq. mm. conductor for HV. Terminal connectors must have type tested as per IS : The bushings shall conform to the relevant standards specified and shall be outdoor. The bushing rods and nuts shall be made of brass material 12 mm diameter for both HT & LT. The bushings shall be fixed to the transformers on side with straight pockets and in the same plane or the top cover. The tests as per latest IS 2099 and IS7421 shall be conducted on the transformer bushings The bushings shall conform to the relevant standards specified and shall be outdoor. The bushing rods and nuts shall be made of brass material 12 mm diameter for both HT & LT. The bushings shall be fixed to the transformers on side with straight pockets. The tests as per latest IS 2099 and IS7421 shall be conducted on the transformer bushings CGM/P&D CGM/Comml. CGM/MM GM/P&D
6 Subject: Amendment in Technical Specification No.S-174/DD-177/2008 for Outdoor types Distribution Transformers upto and including 100 KVA (i.e 16 to 100 KVA) with & without CSP (Completely Self Protected) features. Technical Sr. Specification No No. 1. S-174/DD- 177/2008 for Outdoor types Distribution Transformers upto and including 100 KVA (i.e. 16 to 100 KVA) with & without CSP (Completely Self Protected) Existing Clause Clause The LV bushings shall be housed within the metallic enclosure with sealing arrangement so as to avoid any possibility of tapping of supply from the busing terminal. The enclosure shall be made with sheet metal of thickness not less than 2mm and powder coated. Enclosure shall have provision for pad locking arrangements. This metallic enclosure should have different compartments for housing each item i.e LT CT meter, LT CT s, LT Capacitor, MCCB (if provided),gsm/gprs Modem (The failure of any item does not effect the working of other items) and insulated aluminum bus bar of suitable size should be provided to cater full load capacity of transformer. Amended Clause Clause : The LV bushings shall be housed within the metallic enclosure with sealing arrangement so as to avoid any possibility of tapping of supply from the bushing terminal. The enclosure shall be made with sheet metal of thickness not less than 2mm and powder coated. Enclosure shall have provision for pad locking arrangements and shall have IP-55 or better protection. This metallic enclosure should have different compartments for housing each item i.e LT CT meter, LT CT s, LT Capacitor, MCCB (if provided),gsm/gprs Modem (The failure of any item does not effect the working of other items). 2. -Do- Clause 5.14: The Clause 5.14 may be added with: 2 Nos. anti-theft fasteners of steel on two diagonally opposite corners of the tank shall be provided. All nuts & pins shall be adequately locked. 3. -Do- Clause No. 13 Clause 13: LT PVC Cables The DTs shall be supplied with appropriate size of Single Core Cable(s) (unarmored) of ISI mark and duly type tested from reputed testing house / laboratory. The owner shall have the exclusive right to demand for type tests certificates or copy of ISI manufacturing license from the manufacturer/ supplier of the cable The rating/quantity of LT Cables shall be as follows:-
7 Sr. No. Capacity of T/Fs Size of Cable 1 16 KVA S/c- 25 mm² 2 25 KVA S/c- 50 mm² 3 63 KVA S/c- 120mm² S/c- KVA 185mm² Length of cable required 4 -do- Clause No. 14 Clause 14: Transformer & metallic box sealing facility: The transformer should have facility to seal the transformers Top Plate & its body and also the metal box, housing the other equipment(s) like CTs, LT CT meter etc. along with the transformer. The metal box shall have pad-lock arrangement & complete protection from dirt, rain water & other pollutants and shall comply to IP:55 protection or better. The complete unit of transformer(s) and all other accessories shall be supplied by putting all of them in circuit. 5 -do Clause No. 15 Clause 15: RATING AND TERMINAL MARKING PLATES: There shall be rating plates on the transformer containing the information specified in clause 15.2 of IS: (part-i). Total 50% & 100% load losses of the transformer should also be mentioned on the rating plate. The following additional information must also be punched on the plate and imposed two opposite sides of the body of the T/F. i) Purchase order No. & date ii) Date of inspection iii) Property of DHBVN iv) Make v) Guarantee period.
8 6 -do Clause No. 16 Clause 16: GUARANTEED PARTICULARS: TECHNICAL The guaranteed technical particulars of the transformers shall be given by the tenderer (Annexure-I) along with the tender. Tender without GTP shall be out rightly rejected. 7 -do- Clause No. 17 Clause 17: Rating of Capacitor The rating of Capacitor shall be as follows:- Sr. Capacity Rating of No. of T/Fs capacitor 1 16 KVA 5 KVAR 2 25 KVA 9 KVAR 3 63 KVA 22 KVAR KVA 36 KVAR GM/P&D, CGM/P&D CGM/Commercial CGM/MM, DHBVN, Hisar. DHBVN, Hisar. DHBVN, Hisar. DHBVN, Hisar.
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
More informationTECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before
More informationTECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)
TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) (SPECIFICATION NO. DIST/MM-II/03/2005) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationUGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationSPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:
REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range
More informationCLAMPS CONNECTORS & EQUIPOTENTIAL RING
CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationTechnical Specification for 12kV Padmounted Distribution Substations (Rectangular Type)
Ergon Energy Corporation Limited Joint Ergon Energy/Energex Technical Specification for 12kV Padmounted Distribution Substations (Rectangular Type) JTS02-02-01 Specification JTS02-02-01 Ver 9 Contents
More informationHow To Launch A Rocket From A Formica
Building the Basic Bottle Rocket Launch Pad Materials: -Formica double-sink countertop cutout. This can be easily and cheaply obtained from a local company that manufactures and/or installs countertops.
More informationNordson Automatic Spray Gun Support Kits
Nordson Automatic Spray Gun Support Kits Customer Product Manual Issued / For parts and technical support, call the Finishing Customer Support Center at (800) -99. This document is subject to change without
More informationTS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
More informationAluminium Standard. Technical Data. Included in delivery
luminium Standard UL / cul Robust aluminium enclosure for mechanical engineering and automation technology Fixing options for s and mounting plates Usable in wide temperature area Technical ata aterial:
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
More informationHVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
More informationExpanding a 40-Type Cabinet
Expanding a 40-Type Cabinet using the 3M Add-On Terminal 4220P 400-Pair and Jumper Trough Instructions January 2006 Table of Contents 1.0 General... 3 2.0 Cabinet Overall Descriptions... 3 3.0 Tools Required...
More informationIssued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1
Issued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1 INDEX SECTION WTR01: ELECTRICAL CONNECTIONS PRIMARY.. Page 1 SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS.. Page 9 SECTION WTR02:
More informationBILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT
More informationGUIDE TO LV SWITCHGEAR & FORMS OF SEPARATION
GUIDE TO LV SWITCHGEAR & FORMS OF SEPARATION CONTENTS INDEX...PAGE # PRODUCT EXAMPLES Mobile Battery Charging Unit... 3 PRODUCT EXAMPLES Form 4 Type 5 PDU - C/W Isolating Transformer... 3 PRODUCT EXAMPLES
More informationWall Mounted Products
Metallic Indoor PK Termination Boxes Prysmian Part Numbers: see below Metallic PK Termination Boxes are designed for the termination, branching and distribution of fibre optic cables in telecommunication,
More informationCustomer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
More informationSCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY
More informationMAHARSHI DAYANAND UNIVERSITY ROHTAK (A State University established under Haryana Act No. 25 of 1975) NAAC accredited A Grade
MAHARSHI DAYANAND UNIVERSITY ROHTAK (A State University established under Haryana Act No. 25 of 1975) NAAC accredited A Grade NOTICE INVITING TENDER Sealed tenders on item basis are invited on behalf of
More informationSPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST
TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST ANNEXURE I Sl.No. Description for BHEL Requirement Offered Deviation Scope of supply, erection and commissioning: 1 The scope of this specification covers
More informationTECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRANSFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001)
TECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRANSFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE
More informationCABINET OPTIONS AND DESIGNATORS
CABINET OPTIONS AND DESIGNATORS Hinges: ~Stainless steel lift off Nuts and Bolts: ~ Stainless steel Hardware: ~ Handles and Corbin locks are stainless steel or zinc plated Windows: ~ Lexan Backboards:
More informationDESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: -
PROPOSED KISUMU HOUSING 3 BEDROOM-TYPE 1 ELECTRICAL INSTALLATION -SITE 01 DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: - 1.0 Final sub-circuit from Consumer Unit to lighting
More informationLOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationCustomer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances
Page 50 of 100 Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances (Replaces A-190556) THIS CUSTOMER REFERENCE SPECIFICATION (CRS) IS PART OF THE RULES FOR
More informationMobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
More informationSCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
More informationCAS 36 Ring Main Unit
Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationMagnetic proximity switches
Magnetic proximity switches Magnetic proximity switches Overview Page 38 Functional principle and installation Page 39 Cylindrical designs Page 41 Rectangular designs Page 42 37 Kurzübersicht Magnetoresistive
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More informationReduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U
Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U Applications The High Density Cabinets are suitable for Central Offices and can be used as fiber nodes and termination points
More informationSPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB
SPECIFICATIONS FOR BOON EDAM TOMSED MODEL TUT-65TMB PRODUCT DESCRIPTION: BOON EDAM TOMSED MODEL TUT-65TMB STAINLESS STEEL BARCODE SCANNING ELECTRONIC REGISTERING TURNSTILE SCOPE OF OPERATION: A. The TUT-65TMB
More informationAMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More informationWhitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada
Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are
More informationNow Available through:
Now Available through: Adhesive- Mount s s Perma Dome Packages Perma Plate Packages Mini Plate Packages Convenience. Support. Security. The PC Guardian ADVANTAGE Flexible and expandable adhesive-mount
More informationINDENT NO. : C/T/4100/20089405 DATED : 09.03.2009
LOW NOISE CABLES GRI NO.: GRI/27/10/08-09 PAGE : 1 of 1 INDENT NO. : C/T/4100/20089405 DATED : 09.03.2009 LOW NOISE CABLES : Reinforced, Double Screened, internal graphite coated, low noise co-axial cable,
More informationSeries 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
More informationPlease check with your local inspection authority for any additional requirements before installation.
Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be
More informationMechanical arms, belts and sheets
Car parks Mechanical arms, belts and sheets DETAIL ARM CAR PARK (mm) 5000 Platen 100x5mm Iron sheets 4mm 5000 485 2100 Belts type C 120x50x2 mm 4915 5400 Hot dipped galvanized UNE-EN ISO 1461 or black
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationTRITON CONTAINER INTERNATIONAL. Reefer Technical Bulletins. Version 4.0
TRITON CONTAINER INTERNATIONAL Version 4.0 February 2013 Table Of Contents (Hold Ctrl button and click on any item below to go directly to that section of the manual.) 1 INTRODUCTION... 3 2 REFRIGERATED
More informationORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS
GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS ~GSM SHELTER CONTAINERS ARE PROCUDED ACCORDING TO THE DEMANDED SIZE.~ (W x L x H) Page1 GENERAL FEAUTURES Environmental Conditions : Maximum outdoor temperature
More informationMETHOD STATEMENT FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER
Page 1 of 6 FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER 0 Issued for Review & Comments Rev. Date Description Eng. A.H Prepared by Checked by Approved by Page 2 of 6 REVISION CONTROL SHEET REV. NO. DATE
More informationAcceptability of Printed Circuit Board Assemblies
Section No.: 12I.2.3, Sheet 1 of 9 Rev Level: 16 Additional Distribution: PCB Assembly Subcontractors 1.0 Purpose 2.0 Scope Acceptability of Printed Circuit Board Assemblies 1.1 The purpose of this standard
More informationELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
More informationK17.11 DOOR BOLTS K17 DOORS 01.09.2013
K17 DOORS K17.11 01.09.2013 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com CONTENTS 1. Locking set series 86000...K17.11.03 2.
More informationTechnical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
More informationRE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
More informationTABLE OF CONTENTS FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE REFERENCES... 4 3 DEFINITIONS... 4
TITLE SPECIFICATION FOR MASTER PADLOCKS, CYLINDER LOCKS AND KEYS REFERENCE REV DATE: JAN 2009 PAGE: 1 OF 26 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE REFERENCES...
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationDRUM ROLLER. FAR-1, Article No. B69-6300-A DRUM CART FOR 200 LITER STEEL DRUMS. Model FK 1029-1 FK 1029-3 FK 1029-2 FK 1029-4
DRUM ROLLER Suitable for drums up to 200 liter capacity Made from fire-galvanized sheet steel ø 610 mm, with 4 polyamide swiveling castors ø 75 mm Model FAR-1: closed version with welded leak-proof base,
More informationInstallation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
More informationCable Installation Accessories. Cable Hoisting and Attachment. Snap-In Hangers. SnapStak Hangers
SnapStak Hangers New design increases stack height SnapStak hangers have become the industry standard for maximizing space utilization on crowded towers and now that utility is further expanded with the
More informationDistribution Boards & Consumer Units
Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories
More informationINSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
More informationOperating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
More informationTYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE
TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationMini USB and USB 2.0-IP67 Connector System
Mini USB and USB 2.0-IP67 Connector System Section 12 Mini USB and USB 2.0-IP67 Connector System CONEC has added the Mini-USB connector. This Mini-USB IP67 receptacle and plug family, feature a bayonet
More informationLINEAR MOTION CONTROL
LINEAR MOTION CONTROL Technical Data Sheet Static Locks RLSS Series Nexen s new generation of linear holding/locking devices take rod locking technology to the next level. With superior performance, these
More informationEH-20 20m antenna. By VE3RGW
EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationLinkeo 19" freestanding cabinets
87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3
More informationSERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp
SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS
More informationCircuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
More informationEC DECLARATION OF CONFORMITY FOR MACHINES
EC DECLARATION OF CONFORMITY FOR MACHINES (DIRECTIVE 98/37/EC) Manufacturer: Address: Declares that: FAAC S.p.A. Via Benini, 1-40069 Zola Predosa BOLOGNA - ITALY 770 mod. operator is built to be integrated
More information800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
More informationMEASURING WHEEL ALIGNMENT
MEASURING WHEEL ALIGNMENT 2003-04 WHEEL ALIGNMENT Specifications & Procedures - Hummer - H2 Steering and vibration complaints are not always the result of improper alignment. One possible cause is wheel
More informationStatic Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
More informationType-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
More informationOEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
More informationFRONT BUMPER INSTALLATION INSTRUCTIONS 2007-2011 DODGE / MERCEDES SPRINTER
Aluminess Products Inc 9402 Wheatlands Ct. #A Santee, CA 92071 619-449-9930 FRONT BUMPER INSTALLATION INSTRUCTIONS 2007-2011 DODGE / MERCEDES SPRINTER Please read before beginning Stainless steel hardware
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationPowerFlex 700S and 700H Frame 12 DC Bus Connector Kit
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives
More informationSwitchboard system. NorLine 800
Switchboard system NorLine 800 NorLine 800 SWITCHBOARD SYSTEM 2 NorLine 800 Switchboard system Table of contents Subject Page Table of contents 2 Overview 2-3 NorLine 800 technical specifications 4 Structural
More informationTECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC)
TECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC) Prepared by Committee for Technology Assessment and Analyzing the installation of Solar Water Heater Systems in Government
More informationMini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications
Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down
More informationHow To Wire Wireline Cable To A Cell Phone (New Zealand)
Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More information3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form
3M Mobile SkyWalk Series Horizontal Lifeline Product Return Form THIS FULLY COMPLETED DOCUMENT MUST BE INCLUDED WITH EACH RETURN SHIPMENT IN ORDER FOR CREDIT TO BE ISSUED. ALL CREDITS WILL BE ISSUED TO
More informationCHAPTER 5 PARTS. This chapter describes assemblies / subassemblies / parts considered replaceable at on-site field installation.
CHAPTER 5 PARTS PARTS BY PICTORIAL This chapter describes assemblies / subassemblies / parts considered replaceable at on-site field installation. NOTE: The following is a breakdown description of the
More information6. BILLS OF QUANTITIES
6. BILLS OF QUANTITIES HOUSING BUILDINGS Item Unit Measu Number of General note: This BoQ shall include the delivery of materials stated under the individual items and all miscellaneous unspecified material
More informationCABLE INSTALLATION SYSTEMS
The universal cable support systems are used for construction of cable link in closed production premises for direct mounting on even vertical surfaces. They are perforated metal grates and accessories
More informationJIC CONTINUOUS HINGE BOXES
JIC CONTINUOUS HINGE BOXES Austin JIC Continuous Hinge (JH) boxes are Underwriters Laboratories Listed and are designed for use as electrical junction boxes, terminal wiring boxes, and instruments housing.
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationAmphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH
Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief
More information3.) Remove Page Nos. 15, 16, 17, 18, 19, 20, 21, 22 of 30 and replace with Page Nos. 15, 16, 17, 18, 19 & 20 of 28 marked, REVISED 10/18/2013.
CITY OF HOUSTON Annise D. Parker Mayor P.O. Box 1562 Houston, Texas 77251-1562 Telephone Dial 311 www.houstontx.gov http://purchasing.houstontx.gov October 22, 2013 Subject: To: Letter of Clarification
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationButt Fusion Welding of HDPE Pipes Work Procedure
Butt Fusion Welding of HDPE Pipes Work Procedure A pipeline is as good as its weakest point. Accordingly it is not only important that quality pipes and components are used in a piping system, but also
More informationVCE VET ENGINEERING STUDIES
Victorian Certificate of Education 2013 SUPERVISOR TO ATTACH PROCESSING LABEL HERE STUDENT NUMBER Letter Figures Words VCE VET ENGINEERING STUDIES Written examination Section Wednesday 20 November 2013
More informationMAST ARMS & POLES. Ornamental Pole Top & Bases
Ornamental Pole Top & Bases Pelco s decorative pole top and bases help make the traffic signal aesthetically pleasing to the eye. Available for various pole diameters and multiple finish options. Ornamental
More information