1 TECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRANSFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 21
2 TECHNICAL SPECIFICATION FOR 11 & 22 KV DISTRIBUTION TRASNFORMERS OF RATINGS 63 KVA & 100 KVA CAPACITY (SPECIFICATION NO.WORKS T&D : 01-N/2001) 1. SCOPE : This specification covers oil immersed naturally cooled, three phase, 50 HZ, double wound outdoor type C.R.G.O. Core distribution transformers of capacities 63 and 100 KVA for use on system with nominal voltages of 11 kv and 22kV. 2. APPLICABLE STANDARDS : Unless otherwise modified in this specification, the distribution transformers shall comply with the latest versions of IS 1180 (Part-I), (Part-II) and IS SYSTEM DETAILS : The transformers shall be suitable for outdoor installation with 3 phase 50 Hz, 11 kv and 22 kv system in which the neutral is effectively earthed and they should be suitable for service under fluctuations in supply voltage upto 12% permissible under Indian Electricity Act and Rules there under. 4. WEATHER CONDITIONS : The material used in the construction of the distribution transformers shall be suitable for use under the following weather conditions: Temperature : 30 degree C to 50 degree C. Relative humidity : 100% Altitude : 0 to 1000 mtrs. 5. RATINGS : Primary voltage : 11 kv / 22kV. Secondary voltage : KV. The windings of the transformers shall be connected Delta on the primary side and Y (Star) on the Secondary Side. The neutral of the LT winding shall be brought out to a separate insulated terminal. The vector group shall be Dyn TEMPERATURE RISE : Temperature rise for top oil over an ambient temp. Of 40 dec. should be 45deg.C. Maximum (measured by thermometer as per IS-2026). Temperature rises for winding over an ambient temp. of 40 deg.c. should be 50 deg.c. maximum (measured by resistance in accordance with IS 2026). 7. NO LOAD VOLTAGE RATING : The no load voltage ratios shall be as follows : a) 11000/433 V for all capacities. b) 22000/433 V for all capacities. 8. TAPS : No tapping shall be provided on the higher voltage winding for variation of HV voltages. 9. DESIGN & CONSTRUCTION : Core - MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 2 OF 21
3 a) Material - C.R.G.O sheet. b) The core shall be of high grade cold rolled grain oriented annealed steel lamination having low loss and good grain properties, coated with hot oil proof insulation, bolted together to the frames firmly to prevent vibration or noise. All core clamping bolts shall be effectively insulated. The complete design of core must ensure permanency of the core losses with continuous working of the transformers. The lamination used shall be clearly stated in the offer along with graph. c) The transformer core shall not be saturated for any value of v/f ratio to the extent of 112.5% of the rated value of v/f ratio (i.e /50 or 22000/50 ) due to combined effect of voltage and frequency ) up to 12.5% without injurious heating at full load conditions and will not get saturated. The bidder shall furnish necessary design data in support of this situation. d) Flux density: Flux density at rated voltage and frequency shall not exceed teals. No load current at rated voltage and at 112.5% of rated voltage shall not exceed the values given in Table given below : Sr. KVA Rating Percentage of rated full load current No At 100 % Rated voltage At % Rated voltage The test for magnetic balance by connecting the LV phase by phase to rated phase voltage and measurement of an-bn-on voltage will be carried out. e) Number of steps of core shall be minimum 5. f) Diameter of core should not be less than 22kV class 11kv class i) For 63 KVA 115mm 100mm. ii) For 100 KVA 130mm 115mm. g) Effective core area of core should not be less than - 22kV class 11kv class i) For 63 KVA 94cm2 70cm2. ii) For 100 KVA 121cm2 92cm2. h) Core clamping : MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 3 OF 21
4 1. The core clamping shall be done by MS flat having sufficient thickness for effective clamping. 2. The top yoke channels if cut or holes are made for taking LV connections, suitable reinforcement to channel shall be made by adequate size of M.S flat with thickness not less than 6mm. 3. MS channel shall be painted with oil and corrosion resistant paint before use. 4. 4nos of 12 mm dia. MS rod shall be used as tie rods and will be efficiently insulated 5. Core base and bottom yoke shall be supported with 75mm X 40 mm. MS channel with proper bolting together. In no case flat or cut channels shall be accepted. 10. WINDINGS : a) Materials: Double paper covered aluminum conductor shall be used for 11kV class transformer. For 22 kv 63KVA & 100KVA DPC copper conductor shall be used. b) Current density for HV and LV should not be more than 2.8 A/sq.mm. (However, + 5 % tolerance for LV winding is permissible ) for copper and 1.6 A/sqmm for aluminum conductor. c) H.V. cross section shall not be less than Brno. Ratings LV Cross Section. 22kV class 11kv class i) For 63 KVA 0.39mm2 1.39mm2. ii) For 100 KVA 0.54mm2 2.27mm2. d) L.V. Cross Section should not be less than Sr.No. Ratings for 11 kv and 22 kv (5% tolerance is permissible) KVA 52.5 mm mm2 (5% tolerance is permissible) KVA 86.00mm mm2 (5% tolerance is permissible) Note : LV winding shall be in even layers so that the neutral formation will be at top. 11. LOSS & IMPEDANCES : A) For transformer without taps, losses and impedances at rated voltage for various ratings of transformers of 11 kv/22 kv class shall not exceed the value given below: TABLE Voltage KVA No load Full load losses % impedance Ratio Rating losses in in watts. (subject to tolerance watts.(max.) (Max.) as per IS-2026) / % MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 4 OF 21
5 % 22000/ % % Note : for transformers with taps the permissible values for no load loss shall be 5% higher than those for transformers without taps. The values for load losses given here shall be applicable to such transformer at principle taps. B) The values guaranteed in G.T.P. for flux density, no load current at rated voltage, no load current at 112.5% of rated voltage and no load loss at rated voltage shall be individually met. Insulation material & clearances: a) Materials - Electrical grade insulating craft paper of Triveni/Ballarpur/Cauvery or equivalent make subject to approval of the employer. Press MSEDCL of Senapaty, Whitelay or Raman make or equivalent subject to the approval of the employer. Perma wood or Haldi wood blocks shall be used for top and bottom yoke insulation. b) Radial clearance of LV coil to core (bare conductor) shall not be less than - 1) For 63 KVA T/F mm. minimum. 2) For 100 KVA T/F mm. minimum. c) Radial clearance between HV & LV shall not be less than 11 mm. For 11 kv For 22 kv 1) 63 KVA } 11 mm 14 mm 2) 100 KVA} d) Phase to phase clearance between HV conductors shall not be less than For 11 kv For 22 kv 10 mm 15 mm With a minimum of 2 x 1 mm press MSEDCL to cover the rods. e) The minimum electrical clearance between the winding and body of the tank (between inside surface of the tank and outside edge of the windings) should be 30 mm. & 40 mm in case of 11 kv & 22 kv Class transformers respectively. f) Minimum end insulation to earth shall be 1) 11 kv - 25 mm 2) 22 kv - 40 mm g) No. of coils HV/ phase (minimum) 11 kv 22 kv 1) For 63 Kva 4 6nar 2) For 100 KVA 4 6 h) Thickness of locking spacers between HV coils - 10mm. minimum. i) No. of axial wedges between LV and MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 5 OF 21
6 HV winding equispaced around LV - 6 for 63 KVA 8 for 100 KVA. j) Minimum external clearances of bushing terminals HV - Ph to Ph mm. Ph to E mm. LV - Ph to Ph - 75 mm. Ph to E - 40 mm. 12. TANK : The transformer tank shall be robust construction and shall be built of electrically welded MS plates. All joints of tank and fittings should be oil tight and no bulging shall occur during service. The tank design shall be such that the core and windings can be lifted freely. The tank plates shall be of such strength that the complete transformer when filled with oil may be lifted bodily by means of the lifting lugs provided. Tank inside shall be painted by varnish. Top cover plate shall be slightly sloping approximately 5 to 10 dec. towards HV bushing and ends of cover plate should be bent to 45 to 90 deg. downwards so ass to avoid entry of water through the cover plate gasket. The width of bend plate shall be 25 mm min. The top cover shall have no cut a point of lifting lug. Shape of the tank shall be rectangular only. No other shape will be accepted. The tank shall be fabricated by welding at corners. No horizontal or vertical joints in tank side walls and its bottom or top cover will be allowed. In addition the cover of the main tank shall be provided with an air release plug. a) i. Side wall thickness : 3.15 mm. (min.) ii. Top and bottom plate thickness : 5.00 mm. (min.) b) Reinforced by welded angle on all the outside walls on the edge of tank to form two equal compartments. The permanent deflection is not more than 5mm. upto 750 mm. length and 6mm upto 1250 mm length when transformer tank without oil is subject to a vacuum of 760 mm of mercury. Pressure test shall be performed carefully at the time of 1 st stage inspection only to confirm the adequacy of reinforcement angle and gauge of the tank. c) Lifting lugs : 2 nos. welded heavy duty lifting lugs of MS plate of 8mm thick suitably reinforced by vertical supporting flat welded edgewise below the lug on the side wall, upto reinforcing angle. They shall be so extended that cutting of bend plate is not required. d) Pulling lugs: 4 nos. of welded heavy duty pulling lugs of MS plate of 8mm thick shall be provided to pull the transformer horizontally. e) Lifting lug for cover : 2 nos. of lugs of MS plate of adequate size shall be provided to lift the tank cover. f) Top cover gasket and bolt : g) The gasket provided in between top cover plate and tank shall be of 5mm thick neoprene rubberised oil resistant corksheets conforming to type B or C as per IS 4253, Part-II. ii) GI nut bolts shall be of size 3/8" x 1.5" with one plain washer suitably spaced to press the cover. MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 6 OF 21
7 iii) The height of the tank shall be such that the minimum clear height upto the top cover plate of 120mm is achieved from top yoke. 13. HEAT DISSIPATION : a) Heat dissipation by tank walls excluding top and bottom should be 500 W/sq.m. b) Heat dissipation by fin type radiator 1.25mm thick will be worked out on the basis of manufacturers data sheet. The ten direr should submit the calculation sheet. c) For 63 and 100 KVA T/F, 2 nos. radiators shall be provided only on LV side and shall be of fin type. They should be fixed at right angle to the sides and not diagonally. The size of the radiator shall be such that it covers atleast 50% of bottom yoke, full core and complete top yoke. 14. TOTAL MINIMUM OIL VOLUME : Sr.No. KVA rating Oil in ltrs.(inclusive of oil absorbed Permissible oil In core coil assembly) absorption (ltrs.) KVA KVA Note : If the absorption of oil in core and winding assembly is more than permissible value, first filling oil of valium should be increased accordingly. Detailed calculation of absorption should be submitted. 15. CONSERVATOR : a) The total volume of conservator shall be such as to contain 10% of total quantity of oil. Normally 3% quantity of the total oil will be contained in the conservator. Dimention of the conservator shall be indicated on the General Arrangement Drawing. b) Oil level indicator shall be provided on the side which will be with fully covered detachable flange with single gasket and tightened with MS nut-bolt. c) The inside diameter of the pipe connecting the conservator to the main tank shall be within 20 to 50 mm and it should be project into the conservator in such way that its end is approximately 20mm above the totem of the conservator so as to create a sump for collection of impurities. The min. oil level (corresponding to (-) 5 deg.) should be above the sump level. The pipe from conservator tank connecting to main tank shall be of 30 mm(min.) dia and shall have a slopping flap so that the oil falling from the pipe shall not fall directly on the active job and shall fall on the side walls only. The conservator shall be provided with the drain plug and a filling hole (30mm dia) with cover. 16. BREATHER : Breather joints will be screwed type. It shall have die-cast aluminum body or of Poly propylene materials and inside container for silicagel shall be of tin sheet, in case of MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 7 OF 21
8 aluminum die cast breather. Makes of the breakers shall be subject to employer's approval. Volume of breathers shall be suitable for 250 gm. of silicagel. The make and design of breather shall be subject to approval of employer. 17. TERMINALS: Brass rods 12 mm dia for HT and LT with necessary nuts, check-nuts and plain thick tinned washers. 18. BUSHINGS: i. For 11 kv class, 12 kv bushing will be used and for 433 volts 1.0 kv terminal bushing will be used. Bushings of the same voltage class shall be interchangeable bushings with plainshed as per IS 3347 shall be mounted on the side of the tank and not on the top cover. Only one sheet metal pocket shall be provided for mounting of HV bushings and the same shall not be fixed on pipes. Sheet metal pocket shall be designed in such a way that all H.T. Bushings shall remain parallel and at equi-distance throughout. Bushings have type tested as per IS 3347 shall only be acceptable. ii. Internal connections: a) H.V. winding : 1. In case of H.V. winding all jumpers from winding to bushing shall have cross section larger than winding conductor. 2. In case of Al. Winding Delta joints shall be with Brazing only. 3. Lead from delta joint shall be connected to bushing rod by brazing only. b) L.V. winding : L.T. Star point shall be formed of Al./Cu. Flat of sufficient length. Lead from winding shall be connected to the flat by brazing. Any other arrangement shall be subject to the approval of Chief Engineer(Dist.). Firm connections of L.T. winding to bushing shall be made of adequate size of `L' shaped flat. Connection of L.T. Coil lead to `L' shape flat shall be by brazing. Alternatively `L' shape lug of adequate capacity effectively crimped shall be acceptable. `L' shape flat/lug shall be clamped to L.V. Bushing metal part by using nut, locknut and washers. For Aluminum windings, L&T Alkapee aluminum brazing rods with suitable flux will be used. 19. TANK BASE CHANNEL : It should be of two numbers of 75 x 40 mm channel for 63 KVA and 100 KVA T/Fs. 20. TERMINAL MARKING PLATES AND RATING PLATES : 1.1 Terminals shall be provided with terminal marking plates showing the relative physical position of the terminal and their marking as per drawing marked on plates. The transformer shall be provided with non-detachable rating plate of aluminum anodised MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 8 OF 21
9 material fitted in a visible position. The entries of the rating plate shall be in indelibly marked (i.e. by etching, engraving or stamping). 1.2 Marking as `M.S.E.D.C.L' and `Sr.No.' of transformer will be engraved in addition to above on transformer main tank below L.T. bushings. 1.3 The name of the company, order No., capacity, month and year of manufacturing shall be engraved on the tank of transformer just below the name plate clearly visible. The engraving can be done on separate plate which shall be firmly welded to main tank and shall form integral part of the tank. 21. FITTINGS : The fittings on the transformers shall be as under : 1. Rating and diagram plate - 1 no. 2. Earthing terminals with lugs. - 2 nos. 3. Lifting lugs. - 2 nos. 4. Oil filling hole with cap(on conservator) 1 no. 5. Drain valve - 20mm for all T/Fs - 1 no. - it shall be covered With metallic cover by spot welding). 6. Conservator with drain plug. - 1 no. 7. Thermometer pocket - 1 no. 8. Explosion vent - 1 no. (only for 22 kv T/F) 9. Silicagel breather - 1 no. 10. Platform mounting channel - 2 nos. 11. Oil level guage indicating positions of oil marked as below : Minimum - (-) 5 deg.c. 30 deg.c. Maximum - 98 deg.c. 12. HT & LT bushing - 3 nos. of HT bushing and 4 nos. of LT bushing shall be provided. 13. Radiator - As per Cl Arcing horns for HT bushings. 15. Pulling lugs - 5 nos. 16. Metallic cover spot welded to tank for drain valve shall be provided. 22. TRANSFORMER OIL : The transformer shall be supplied complete with first filling of oil and the same shall comply with IS 335/1983 with latest version thereof and aging characteristics specified. Type test certificates of oil being used shall be produced at the time of stage inspection. MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 9 OF 21
10 New oil - Ageing characteristics after accelerated ageing (open breaker method with copper catylist) a) Specific resistance (resistivity) i) at 27 dec.c x 10 ohm - cm (min) ii) at 90 dec.c x 10 ohm - cm(min) b) Dielectric dissipation factor (max.) (tan delta) at 90 deg.c. c) Total acidity, mg.(koh)/gms (max) d) Total sludge value (%) by weight (max) (The method of testing these ageing characteristics is given in Appendix-C of IS 335/1983). Characteristics of oil in the transformer : The important characteristics of the transformer oil after it is filled in the transformer (within 3 months of filling) shall be as follows : Sr.No. Characteristics Specification Electric strength (Breakdown voltage) 30 kv (Min.) 2. Dielectric dissipation factor 0.01 (Max.) (tan delta) at 90 deg.c. 3. Specific resistance (resistivity) 10 x 10 at 27 deg.c. (Ohm-cm) 4. Flash point, P.M. (closed) 140 dec.c (Min.) 5. Interfacial tension at 27 deg.c N/M (Min.) 6. Neutralization value (total acidity) 0.05 m/koh/gm (Max.) 7. Water content PPM. 33 (Max.) 23. A) ROUTINE TESTS : All transformers manufactured and to be supplied shall be subjected to the following routine tests (at the cost of the supplier). 1. Measurement of winding resistance. 2. Ratio, polarity and phase relationship. 3. Impedance voltage. 4. Load losses. 5. No load losses and no load current. 6. Insulation resistance. 7. Induced over voltage withstand test. MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 10 OF 21
11 8. Separate source voltage withstand test. B) Type tests : In addition to routine tests as above, all type tests as under shall be carried out at laboratories accredited by National Accreditation MSEDCL for Testing and Calibration Laboratories (NABL) in accordance with IS 2026/1977 as amended from time to time. i. Impulse voltage withstand test as per Clause No.13 of IS 2026 (Part-III)/81. Impulse voltage withstand test shall be for 75 KVp & 125 KVp for 11 kv and 22 kv Class transformers respectively. ii. Temperature rise test. iii. Air pressure test. iv. Dynamic Short circuit test. v. Unbalanced current test - unbalanced current should not be more than 2% of full load current. C. Test certificates : Type Test Reports (alongwith certified drawings/ oscillograms etc. of the offered equipment) from laboratories which are accredited by the National Accreditation MSEDCL for Testing and Calibration Laboratories (NABL) shall be furnished to prove that the equipments offered meet the requirements of the specification. The tenderer should also furnish a copy of Accreditation Certificate from NABL, valid ass on date of type test, and duly attested by testing laboratory where the type tests are carried out. If the type tests are carried out prior to 5 years from the date of opening of tender, the tenderer will have to carry out the test free of cost before despatch of first lot. The employer reserves the right to demand repetition of some or all the type tests in presence of employer s representative. For this purpose, the tenderer shall quote unit rates for carrying out each type test. However, such unit rates will not be considered for evaluation of the offer. 24. DRAWINGS : One copy of the dimensional drawing and internal construction drawing of each Transformer shall be submitted. These drawings shall be of A3 (420 x 297mm) size only. 24A The offers without following documents shall be stand rejected. 1) Type test report and accreditation certificate required as per Clause No.24C. 2) All the relevant information in Schedule `A' i.e. Guaranteed Technical Particular (GTP). 3) Drawings required as per Clause TOLERANCES : Unless otherwise specified herein, the test value of the transformers supplied should be within the tolerance permitted in the IS:2026 (Part-I) table on the guaranteed values Finishing : MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 11 OF 21
12 The exterior of the transformer and other..fillings shall be thoroughly scrapped and given a primary coal and the two finished coats of.oil and weather resisting enamel paint. The colour of the finishing coats shall be dark green conforming to IS5 of 1961 (colours for ready mixed paints). 25A The month and year of supply shall be painted in red bold marathi lettering at two places, one on conservator and other at sum conspicuous place on the transformer which shall be clearly visible from the ground. The height of letter shall be as per applicable drawing. 26. GUARANTEED AND OTHER PARTICULARS FOR TRANSFORMERS : To be filled in and submitted by the tenderer. 27. DOCUMENTARY EVIDENCE : The tenderer will have to produce documentary evidence for the purchase of Amorphous Metal Sheet, oil and aluminum wire. 28. TESTING FACILITY : The manufacturer should have adequate testing facility for all routine and acceptance tests and also arrangement for measurement of losses, resistance, etc. 29. ROUTINE TEST CERTIFICATE : The successful tenderer shall submit the routine test certificate alongwith documentary evidence for having paid the Excise Duty for the following raw materials at the time of routine testing of the fully assembled transformer : Oil, aluminium for conductors, insulating materials, core materials, bushings. 30. INSPECTION : In respect of raw materials such as core stamping, winding conductor, insulating paper and oil, you shall use these materials manufactured/supplied by the standard manufacturers and furnish the manufacturers' test certificates as well as the proof of purchase from these manufacturers (documentary evidence for having paid the Excise Duty) for information of the employer. The successful tenderer will give 15 days advance intimation to the employer to organize for stage inspection of the transformer in which the assembly of core and the winding could be inspected. The employer may at its option open a transformer supplied, in presence of supplier at site. If any of the technical particulars are seen to be in variance than the guaranteed technical particulars, the whole lot of transformer will be rejected. In addition to the above, the employer may pick up any transformer and decide to get it type tested from CPRI at any other suitable laboratory or by independent agency at employer's cost. The tenderer will have to organize packing of the transformer at MSEDCL's Stores for which they will be paid necessary charges. If the transformer fails to meet the requirement of type tests, the quantity of transformers ordered on them will be forthwith rejected and the employer may purchase these transformers at the risk and cost of the supplier. 31. INSPECTION & TESTING OF TRANSFORMER OIL : To ascertain the quality of the transformer oil, the original manufacturer's test report should be submitted at the time of inspection. Also arrangements should be made for testing of transformer oil, after taking out the sample from the manufactured MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 12 OF 21
13 trasnsformers and tested in the presence of employer's representative or in an independent laboratory. 32. LOADING OF TRANSFORMER : The transformer should comply with IS: SCHEDULES : 33.1 The tenderer shall fill in the following schedules, which form part of the tender specification and offer. In schedule `A' the specific values shall be furnished and only quoting of IS reference is not sufficient. If the schedules are not submitted duly filled in with the offer, the offer shall be liable fore rejection. Schedule `A' - Guaranteed Technical Particulars. Schedule `B' - Schedule of Deviations from Specification. Schedule `C' - Schedule of Tenderer's Experience. Schedule `D' - Schedule of Deviations from specified standards. Schedule `E' - Schedule of Deviations from specified Test Requirements All deviations from the specification shall be brought out in the schedules of deviation (Schedules `B', `D', & `E'). The discrepancies between the specification and the catalogs, Literatures and indicative drawings, which are subject to change, submitted as part of the offer, shall not be considered and representation in this regard will not be entertained The deviation brought out in the schedule shall be supported by authentic documents and clarifications; otherwise the offer may be liable for rejection The tenderer shall submit the list of orders for similar type of equipments, executed of under execution during the last three years, with full details in the schedule of Tenderer's experience (Schedule `C') to enable the employer to evaluate the tender. MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 13 OF 21
14 SCHEDULE A GUARANTEED AND OTHER PARTICULARS FOR TRANSFORMERS Sr.No. Description Particulars 1. Make & Manufactured by : 2. Place of manufacture : 3. Voltage ratio : 4. Ratings in KVA : 5. Core material used & grade : 6. Maximum temp. rise of : a) Windings by Resistance : Method. b) Core by thermometer : c) Oil by thermometer : 7. Magnetising (No load) current a) Rated Voltage : Amps i.e. % of full load. b) Max. Voltage : Amps i.e. % of full load. (112.5% of rated voltage) 8. Core/no load loss in watts : at Rated voltage. 8. Resistance of windings at 20 deg.c. a) H.V. winding : b) L.V. winding : 10. Full load loss : 11. Current density used for : a) H.V. winding : b) L.V. winding : 12. Clearances a) Core & L.V. : b) LV & HV : c) HV Ph. To Ph. : MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 14 OF 21
15 d) End clearance to earth : e) Any point of winding : to tank 13. Efficiency at 75 dec. c at a) Unity P.F. & (b) 0.8 P.F. : a) b) i. 125% load : ii) 100% load : iii) 75% load : iv) 50% load : v) 25% load : 14. Regulation at - a) Unity P.F. & (b) 0.8 P.F. : a) b) at 75 dec.c. 15. % Impedance at 75 deg.c. : 16. Flash test - HV 28 KV for 1 minute : LV 3 KV for 1 minute : 17. Over potential test Double voltage & Double frequency For 1 Minute. 18. Impulse test value in KVp. : 19. Weight of a) Core lamination : Kg. b) Windings-Alu. : Kg. c) Tank and fittings : Kg. d) Oil : Kg. e) Oil : Ltr. f) Total weight : Kg. 20. Oil data 1) Quantity for first filling : Ltr. 2) Grade of oil used. : 3) Maker's name. : 4) BDV at the time of filling. : 21. Make of Breather & type : MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 15 OF 21
16 with capacity of silicagel filled In gm. 22. Transformers 1) Overall length x breadth x : height. 2) Tank length x breadth x : avg. height. 3) Thickness of plates for a) Side Plate : b) Too and Bottom plate : 23. Inter layer insulation provided in design for - 1) Top & bottom layer : 2) In between all layer : 3) Details of end insulation : 4) Whether wedges are : Provided at 50% tuns of the Coil. 24. Insulation materials provided : a) for conductors 1) HV 2) LV : b) for core. 25. Size of the wire used 1) HV a) SWG : b) Dia. : c) Area : 2) LV a) Strip size : b) No. of conductors In parallel. c) Total area of cross: Section. 26. Does the name plate give all : MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 16 OF 21
17 Particulars as required in tender. 27. Particulars of bushings. 1) Maker's name : 2) Type IS-3347/IS-1180 : 3) Rating as per IS. : 4) Dry flashover voltage at : 50 cycles KV. 5) Watt flashover voltage : at 50 cycles KV. MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 17 OF 21
18 SCHEDULE - B DEVIATIONS FROM SPECIFICATION SR.NO. CLAUSE No. DETAILS OF DEVIATION NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 18 OF 21
19 SCHEDULE - C SCHEDULE OF TENDERER'S EXPERIENCE Tenderer shall furnish here a list of similar orders executed/under execution by him to whom a reference may be made by employer in case he considers such a reference necessary Sr. Name of client Value Period of supply Name & Address to No. & Description. Of Order & commissioning whom reference may Be made NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 19 OF 21
20 SCHEDULE - D SCHEDULE OF DEVIATIONS FROM SPECIFIED STANDARDS Sr. Particulars Stipulation of Stipulation of Remarks No. specified standard adopted Standards. By tenderer Standard Stipula- Standard Stipulations Ref. tions. Ref NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 20 OF 21
21 SCHEDULE - E DEVIATIONS FROM SPECIFIED TEST REQUIREMENTS SPECIFIED IN RELEVANT AND PRESENT SPECIFICATIONS Sr. Name of Test Standard Requirement Proposed Reasons No. No. & Cl.No. of standards deviation for deviation TYPE TEST 2. ADDL. TEST 3. ACCPTANCE TEST. 4. ROUTINE TEST. NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 21 OF 21
TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)
TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR) (SPECIFICATION NO. DIST/MM-II/03/2005) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationSCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
More informationTECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before
More informationSCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY
More informationUGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
More informationCLAMPS CONNECTORS & EQUIPOTENTIAL RING
CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata
More informationLOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationTechnical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationTECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
More informationSPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:
REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range
More information1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More information1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationElectrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationPresentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
More informationAMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
More informationTasarım ve Baskı: AJANSBRAND A 15.09.2014
www.kosgeb.gov.tr Tasarım ve Baskı: AJANSBRAND A 15.09.2014 THE ENERGY TRANSFERRED TO NATURE www.atstrafo.com ABOUT Having been founded in Adıyaman Organized Industrial District in 2003, ATS Trafo carries
More informationHigh-ohmic/high-voltage resistors
FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.
More informationTECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC)
TECHNICAL SPECIFICATIONS & TERMS AND CONDITIONS FOR SOLAR WATER HEATER (FPC/ETC) Prepared by Committee for Technology Assessment and Analyzing the installation of Solar Water Heater Systems in Government
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationCOATING & WRAPPING OF UNDERGROUND PIPING
CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification
More informationAfter reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
More informationSPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM)
SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM) PROJECT EQUIPMENT Quantity : 2.5 MVAR STATCOM. The transformer will be used for connecting a 2.5 MVA Inverter with grid at 6.6 kv. : Transformer
More informationLEVEL GAUGES WITH MAGNETIC JOINT L 14 - L 22 - L 34
LEVEL GAUGES WITH MAGNETIC JOINT L 14 - L 22 - L 34 2 LEVEL GAUGES WITH MAGNETIC JOINT SIZE Ø 140/220/340 58 58 TYPE LA TYPE LA 14 30 S 22 33 TYPE LA 22-34 NO. HOLES Ø D2 76 O-RING CENTRE OF THE CONSERVATOR
More informationABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationOLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
More informationModular Locomotive System Instruction Manual for HBK8 George Body Kit
Modular Locomotive System Instruction Manual for HBK8 George Body Kit Roundhouse Engineering Co. Ltd. Units 6-10 Churchill Business Park. Churchill Road, Wheatley. Doncaster. DN1 2TF. England. Tel. 01302
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationScrew Plug Immersion Heaters
Immersion Heaters Overview Immersion Heaters consist of hairpin bent tubular elements brazed or welded into a screw plug and provided with terminal enclosures for electrical connections. Immersion Heaters
More informationT A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A
T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test
More informationTransformer oil cooler ALFA A02
A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using
More informationSELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationHigh-ohmic/high-voltage resistors
FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS
More informationUHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
More informationCross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
More informationTechnical catalogue About KOLEKTOR ETRA has been acting as transformer manufacturer over more than 75 years. Specializing in the manufacturing of power transformers rating up to 500 MVA and 420 kv the
More informationPPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
More informationInstallation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
More informationOne Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
More informationunderstanding medium frequency induction melting furnace and its components
understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA sales@electroheatinduction.com INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose
More informationHINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001
NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES
More informationCEG/GP/1534/257/RFQ27016/ [01] Technical specification for NB 350 CB pipe :
[01] Technical specification for NB 350 CB pipe : Size :- NB 350 Plain End, ID 336 MM, OD 406 mm, Length - 5.3 meters +/- 25 mm Outer shell : Rolled and welded from 5 mm thick carbon steel coil / plates
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationConnection Solutions
Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction
More informationTYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer
168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage
More informationInstallation Instructions
Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More informationPermanent Magnetic Generator Construction Manual
Permanent Magnetic Generator Construction Manual http://hojomotor.com Our Team Doing an On-site Assembly in Peru http://hojomotor.com Section 1) Introduction This manual describes how to build a 'permanent
More informationSunMor SM-V30 Solar Water Heater Installation Manual
SunMor SM-V30 Solar Water Heater Installation Manual Rev. 1.02 Congratulations on the purchase of your new SunMor SM-V30 from Nature s Comfort LLC! You must read this entire instruction manual before beginning
More informationALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
More informationData Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list
VITOSOL 100 Flat collectors for the utilisation of solar energy Data Sheet Part nos. and prices: see price list File in: Vitotec 1 Manual, Index 16 Vitosol 100 Type s 1.7 Vitosol 100 Type s 2.5 Vitosol
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More informationOUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
More informationTECHNICAL INFORMATION
TECHNICAL INFORMATION Models No. 2012NB Description 304mm (12") Automatic Thickness Planer CONCEPTION AND MAIN APPLICATIONS * Compact and light weight (27 Kg./59 lbs) automatic thickness planer for easier
More informationPART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
More informationTECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General
More informationProject : CONSTRUCTION OF BUILDING(including electrical and plumbing works) FOR NATIONAL CENTRE FOR SUSTAINABLE COASTAL MANAGEMENT,CHENNAI
Project : CONSTRUCTION OF BUILDING(including electrical and plumbing works) FOR NATIONAL CENTRE FOR SUSTAINABLE COASTAL MANAGEMENT,CHENNAI TENDER CLARIFICATIONS- no 3 dated 3rd Oct 13 issued in response
More informationSFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 *
SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards
More informationproduces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
More informationLead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc. Abstract The technology for connecting lead and magnet wires for electric motors and electro mechanical devices
More informationLV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationTwo most common lock nut groups: 1-Prevailing Torque Type Lock Nuts:
Two most common lock nut groups: 1. PREVAILING TORQUE a design feature of the lock nut produces friction between threads of mated components thereby increasing the force needed to tighten as well as loosen
More informationCooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
More information3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
More informationCHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION
CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION 1 This item shall consist of furnishing and erecting Chain-Link fence in accordance with these specifications and the details shown on the plans and in
More informationPower Cube Open Source Ecology Page 1. Power Cube. Version 4
Power Cube Open Source Ecology Page 1 Power Cube Version 4 Power Cube Open Source Ecology Page 2 Contents Table of Contents Power Cube... 1 Contents...2 Introduction... 3 Bill Of Materials...4 Discrete
More informationGivare NC-SRS 280 och 880
Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness
More informationECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationINSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS
INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationMiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
More informationEH-20 20m antenna. By VE3RGW
EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed
More informationTARIFF CODE and updates standard
TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of
More informationPower Transformers 10 to 100 MVA
Power Transformers 10 to 100 MVA Transformer technology at a glance An extensive transmission system with efficient transformers is indispensable to ensure a reliable supply of power. Consequently Siemens
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationLaserlyte-Flex Alignment System
Laserlyte-Flex Alignment System LaserLyte-Flex The LaserLyte-Flex Alignment System is a unique, interchangeable, low cost plug and play laser system. Designed specifically for aligning and positioning
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationCONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
More informationGUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT
GUIDELINES TO INSTALL, OPERATE AND MAINTAIN HT CAPACITORS & IT S ASSOCIATED EQUIPMENT GENERAL: 1. The selection of switchgear for switching the capacitors should be done carefully. The circuit breaker
More informationMounting Instructions for SP4 Power Modules
Mounting Instructions for SP4 Power Modules Pierre-Laurent Doumergue R&D Engineer Microsemi Power Module Products 26 rue de Campilleau 33 520 Bruges, France Introduction: This application note gives the
More informationTECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara 390 007 TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GETCO/E/TS PCBL025/RO DT.07-03-2008
More informationTRANSFORMER FITTINGS & ACCESSORIES
TRANSFORMER FITTINGS & ACCESSORIES CONTENTS 1. Low Voltage transformer bushing clamps... 3 1.1. TOGA type clamps... 5 1.1.1. TOGA 1 type clamps... 5 1.1.2. TOGA 2 type clamps... 6 1.1.3. TOGA 3 type clamps...
More informationOwner's Manual & Assembly Instructions
Owner's Manual & Assembly Instructions PM01 BASE KIT Model No. FDN1014 717090311 CAUTION: SOME PARTS HAVE SHARP EDGES. CARE MUST BE TAKEN WHEN HANDLING THE VARIOUS PIECES TO AVOID A MISHAP. FOR SAFETY
More informationAC and Pulse Film Foil Capacitors KP Radial Potted Type
AC and Pulse Film Foil Capacitors KP Radial Potted Type 0.5 L max. W max. Marking H max. FEATURES 5 mm lead pitch, supplied loose in box taped in ammopack or reel Material categorization: for definitions
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
More informationROOF DRAINS TABLE OF CONTENTS
Pictorial Index Product Recommendations Roof Drain Selection Factors Sizing Placement Material & Characteristics Pipe Connection Commonly Specified Options Typical Installations TABLE OF CONTENTS ROOF
More informationPeltier Application Note
Peltier Application Note Early 19th century scientists, Thomas Seebeck and Jean Peltier, first discovered the phenomena that are the basis for today s thermoelectric industry. Seebeck found that if you
More informationTECHNICAL SPECIFICATION FOR ELECTRICAL WIRING / PANELS / SWITCH GEAR
TECHNICAL SPECIFICATION FOR ELECTRICAL WIRING / PANELS / SWITCH GEAR 1.0 GENERAL REQUIREMENTS The installation shall generally be carried out in conforming with the requirements of the Indian Electricity
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More information