1 Lightning Arresters P KVA P KVA Description & Installation Printed in USA 09/11 TO330 Rev. B

2 Table of Contents Page 1.0 SCOPE PRODUCT OVERVIEW Intended Uses Lightning Arresters 18KVA, 10KVA kv Spark Gap PRODUCT FEATURES INSTALLATION Mounting Lightning Arrester Station Ground Connection Remote Ground Connection 3 General Information PHYSICAL CHARACTERISTICS Mechanical Configuration Environmental Requirements 5 Page 1

3 1.0 Scope This document describes the technical specifications, technical requirements and installation instructions for the P30027 and P30038 SNC Lyte Lynx Lightning Arrester packages. It provides an understanding of the basic functions and features available with these units. 2.0 Product Overview 2.1 Intended Uses The purpose of the lightning arrester is to protect the metallic shield of the CO/Remote cable and the isolation devices during lightning or fault conditions. When the voltage reaches the level of the arrester s discharge rating, the voltage will find a path to station ground rather than damaging the cable or isolation devices kV and 10kV Lightning Arresters SNC offers two models of Lyte Lynx Lightning Arresters. Since Lyte Lynx carries a continuous rating of 20kV, 60HZ, RMS as well as a 65kV impulse peak voltage, the 18kV model (P30027) is normally recommended. However, for installation where the dielectric condition of the incoming CO/Remote cable is questionable, the 10kV model (P30038) may be desired since GPR voltages rarely exceed 10kV, 60Hz, RMS maximum kV Spark Gap This feature allows termination of cable pairs for isolation transformer center tap drainage to provide protection for Class A service pairs whenever the lightning/surge arrester discharges. 3.0 Product Features The P30027 and P30038 use a non-shattering, polymer lightning arrester installed in an insulated housing. Each has a continuous kv arrester rating with a discharge voltage rating substantially lower than the tested 65 kv BIL of the Lyte Lynx system. During a lightning strike, the voltage potential difference between the CO/Remote cable shield and station ground is limited to the breakdown or discharge voltage of the arrester so that both the entrance cable and isolation equipment are protected. Mounted inside a fiberglass enclosure with a clear plastic protective cover, the arrester is normally installed near the CO/Remote cable entrance into the Lyte Lynx card shelf typically either directly below or alongside the shelf. 4.0 Installation CAUTION: To provide personnel isolation from local ground, stand on a thick rubber mat and use other adequate insulation devices (rubber gloves) when working on the Lyte Lynx system. Page 2

4 CAUTION: The incoming telephone pair(s) should be contained in insulated conduit (PVC, etc.), or the pair(s) should be jacketed with sufficient insulation to withstand a voltage rise from ground fault potential and from fault induction voltage. CAUTION: Any metallic shielding on the incoming CO/Remote pair(s) must be isolated from substation grounds all the way from the network low voltage interface (300 volt peak GPR point per IEEE Standard 487) to the entry into the Lyte Lynx. The conductors must also be isolated. 4.1 Mounting Lightning Arrester Drill holes in the back of the Lightning Arrester enclosure and securely mount to a non-metallic wall or backboard (use the backboard that the Lyte Lynx card cage is mounted to if backboard is large enough). Depending upon the space available, this can be to the left (looking at the front of the card cage) or just below the card cage. The Lightning Arrester may be mounted upside down to fit the situation. See Figure 1 for an example of how the lightning arrester is installed. 4.2 Station Ground Connection Connect a #6 AWG wire from the bus bar connector lug at the bottom of the arrester enclosure to station ground. Keep this wire as short as possible. See Figures 1 and Remote Ground Connection At the point where the cable would be centered in the Lightning Arrester enclosure, carefully strip off 4 to 6 inches of the cable jacket to reveal the cable shield. Open the cable shield by removing the center 2 or 3 inches of the exposed metallic cable shield. Try to do this without disturbing the cable pairs. Slip the cable through the PVC fittings on each side of the upper part of the enclosure. Holes in the PVC fittings allow the use of tie wraps (included) to secure the cable to the enclosure. Connect the wire attached to one end of the arrester to the CO side of the cable shield with a cable shield Bullit Bond (provided). Keep this wire from the cable shield to the arrester as short as possible avoid a large loop. Connect the wire attached to the 5kV spark gap to the station side of the cable shield - or with a separate wire - connect it directly from the spark gap to the ground terminal of the card shelf. See Figure 1. Page 3

5 General Information The above installation scheme meets the recommended protection practice of IEEE Standard remote ground outside the GPR zone of influence (300 volt GPR location) is accessible via a 5 kv spark gap located in the lightning surge arrester housing external to the card shelf. This installation scheme also provides for coordinated 65 kv BIL protection of both the isolation equipment (shelf and cards) and the dedicated entrance cable. The 5 kv gap coordinates drainage of surge voltage difference between the dedicated cable pairs and the shield should the power type surge arrester operate and equalize ground potential difference between station ground and remote ground via the cable shield. The isolation system is designed around the protection practice of IEEE Standard It is recommended that this configuration be used in any application environment where surges are possible. The BIL of the isolation system is assured and the dedicated cable receives similar BIL protection and insulation protection coordination between shield and cable conductors. Note: In some applications remote ground is directly needed for a circuit function such as for PBX ground start trunks (a less desirable trunk seizure configuration that is more prone to possible transient voltage and circuit noise problems than a loop start trunk). When a direct remote ground connection is required, a protection system application utilizing the 5kV spark gap must have the gap bypassed by one of the pairs to get central office ground directly accessible to the PBX card. This effectively disables the 5kV spark gap. Figure 2: 10KVA Lightning Arrester P30038 Page 4

6 Connect to Card Shelf Remote Ground Connect to CO Cable Shield Connect Station Ground to This Ground Lug Figure 3: Lightning Arrester Connections 5.0 Physical Characteristics 5.1 Mechanical Configuration Table 1: Physical Dimensions PART NUMBER HEIGHT WIDTH DEPTH P (36 cm) (54 cm) 7.10 (18 cm) P (28 cm) (38 cm) 5.30 (13.5 cm) 5.2 Environmental Requirements The Lyte Lynx Lightning Arrester system may be installed in an indoor or moderate outdoor environment and is guaranteed operable in temperatures ranging from 40ºC to 100ºC ( 40ºF to 212ºF) and under humidity conditions from 0 99% relative humidity non-condensing. Page 5

7 For further information or for technical support call or visit SNC Manufacturing Co., Inc. 101 West Waukau Ave., Oshkosh, WI or FAX Website: Page 6 TO330 Rev. B - 09/11

Data Isolation Cards. 2-Wire HDSL2/HDSL/56KBS Isolation Card P Wire HDSL2/HDSL/56KBS Isolation Card P30117

Data Isolation Cards. 2-Wire HDSL2/HDSL/56KBS Isolation Card P Wire HDSL2/HDSL/56KBS Isolation Card P30117 Data Isolation Cards 2-Wire HDSL2/HDSL/56KBS Isolation Card P30115 4-Wire HDSL2/HDSL/56KBS Isolation Card P30117 Printed in USA 12/11 T0401 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW

More information

Total Reach ISDN/DDS Isolation Card P P30058 Isolation Card

Total Reach ISDN/DDS Isolation Card P P30058 Isolation Card Total Reach ISDN/DDS Isolation Card P30101 120VAC/130VDC to 24VDC External Power Supply With Backup Battery P30058 Isolation Card Description & Installation Printed in USA 09/11 T0344 Rev. C Table of Contents

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

UNDERGROUND ARRESTERS

UNDERGROUND ARRESTERS C6 UNDERGROUND ARRESTERS 200 AMP 15/25/28/35 kv Experience & Reliability Cable Accessories UNDERGROUND ARRESTERS RATINGS & SPECIFICATIONS Voltage Per Unit High Current, Short Duration Low Current, Long

More information

Ground Fault. Current Detection Systems BGFL X X X - XXXX. Model BGFL (Relay) Trip Currents 5-60, , or A HOW TO ORDER RELAYS

Ground Fault. Current Detection Systems BGFL X X X - XXXX. Model BGFL (Relay) Trip Currents 5-60, , or A HOW TO ORDER RELAYS Ground Fault U L 110395 LR80793 Current Detection Systems Model BGFL (Relay) Trip Currents 5-60, 30-360, or 100-1200A OPERATING RANGE: Trip currents of 5-60, 30-360, or 100-1200A. Time delay from 0.10

More information

Type XPI-III Surge Arresters Maximum System Voltage 2 to 48 kv

Type XPI-III Surge Arresters Maximum System Voltage 2 to 48 kv Type XPI-III Surge Arresters Maximum System Voltage 2 to 48 kv XPI-III Metal Oxide Surge Arrester XPI-III Metal Oxide Surge Arresters are for protection of switchgear, transformers, and other equipment

More information

What is Grounding and Bonding for Telecommunication Systems?

What is Grounding and Bonding for Telecommunication Systems? What is Grounding and Bonding for Telecommunication Systems? June 15, 2012 5 >> Why Do We Need Grounding and Bonding for Telecommunication Systems? With the increasing demand for computer network installations,

More information

About the BitStorm 6051 POTS Splitter

About the BitStorm 6051 POTS Splitter BitStorm 6051 Installation Instructions Document Number 6051-A2-GZ40-10 July 2002 About the BitStorm 6051 The BitStorm system enables simultaneous high-speed digital data access and analog voice service

More information

Elastimold. Cable Accessories. Ranger2 Terminations. Overview

Elastimold. Cable Accessories. Ranger2 Terminations. Overview Ranger2 Overview Elastimold are specifically designed for use on 15 thru 35 kv, XLP or EPR insulated, underground power distribution cable systems. Units allow proper transition and connection of the underground

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS. A. This Section includes methods and materials for grounding systems and equipment.

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS. A. This Section includes methods and materials for grounding systems and equipment. SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical equipment operations and to provide a low impedance path for possible

More information

About the Hotwire POTS Splitter

About the Hotwire POTS Splitter TM Hotwire POTS Splitter Central Office Installation Instructions Document Number 5020-A2-GN10-30 About the Hotwire POTS Splitter The Hotwire System enables simultaneous high-speed digital data access

More information

High Voltage Interfaces for Telecommunications Entering Electrical Substations and Generating Plants

High Voltage Interfaces for Telecommunications Entering Electrical Substations and Generating Plants High Voltage Interfaces for Telecommunications Entering Electrical Substations and Generating Plants c Kevin Jacobson, P.Eng. 2007.09.03 Jacobson Engineering Services www.jacobsonengineering.ca 1 Summary

More information

A. This Section includes methods and materials for grounding systems and equipment, plus the following special applications:

A. This Section includes methods and materials for grounding systems and equipment, plus the following special applications: PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

TDC 100/200 Stand-Alone Model Installation Instructions

TDC 100/200 Stand-Alone Model Installation Instructions TDC 100/200 Stand-Alone Model Installation Instructions Specifications: Controls up to 200 stations for the Stand-Alone model Input power supply 100 VAC, 50/60Hz 120 VAC, 50/60Hz 240 VAC, 50/60Hz TDC output

More information

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

A. Section includes grounding and bonding systems and equipment.

A. Section includes grounding and bonding systems and equipment. SECTION 26 as 26 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes grounding and bonding systems and equipment. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2 - PRODUCTS

More information

Presented by Joe Ellwood. 17th edition first amendment Surge protection

Presented by Joe Ellwood. 17th edition first amendment Surge protection Presented by Joe Ellwood 17th edition first amendment Surge protection Introduction Amended section 443 is surge protection required? Secondary lightning effects surges/transient overvoltages How do they

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION CABLE ENTRANCE FACILITY

SECTION CABLE ENTRANCE FACILITY CONTENTS SECTION 15 -- CABLE ENTRANCE FACILITY PAGE 1. GENERAL... 15-1 1.1. Introduction... 15-1 1.2. Requirements All CEFs... 15-2 1.3. Requirements Non-Insulating Joint CEFs... 15-2 1.4. Requirements

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

JOSLYN. Arresters. SURGE TEC Secondary Arresters FEATURES SURGE ARRESTER APPLICATION. Manufacturing Co.

JOSLYN. Arresters. SURGE TEC Secondary Arresters FEATURES SURGE ARRESTER APPLICATION. Manufacturing Co. JOSLYN Arresters SURGE TEC Secondary Arresters installed properly, they will divert lightning surges to ground very quickly. Surge Tec arresters offer the first line of defense for the entire electrical

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kits, 7620-T and 7690-T Series

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kits, 7620-T and 7690-T Series 3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kits, 5, 8, 15, 25/28 and 35 kv Data Sheet September 2016 Description 3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kits,

More information

Are you using the right CT's and PT's for your application?

Are you using the right CT's and PT's for your application? Are you using the right CT's and PT's for your application? John Levine, P.E. Levine Lectronics and Lectric E-mail: John@L-3.com / 1 Alternate Title of Presentation Now I know what I do not know about

More information

UPS with Bypass Electrical Installation

UPS with Bypass Electrical Installation Chapter 3 UPS with Bypass Electrical Installation NOTE If you have a plug-receptacle unit, continue to Battery Cabinet Installation on page 57 for installing optional battery cabinets or to UPS Startup

More information

Surge Protection A General Overview. Mitchell Guthrie Independent Engineering Consultant Blanch, NC

Surge Protection A General Overview. Mitchell Guthrie Independent Engineering Consultant Blanch, NC Surge Protection A General Overview Mitchell Guthrie Independent Engineering Consultant Blanch, NC Overview Presentation of the philosophy behind surge protection for potential equalization Discuss standards

More information

Trinetics UltraVac Solid Dielectric

Trinetics UltraVac Solid Dielectric Trinetics UltraVac Solid Dielectric Motor Operated Vacuum Switches Installation and Operation Instructions Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to

More information

Installation Manual. Integrated Prepaid Keypad Meters. For HXE12-KP. Hexing Electrical Co., Ltd. [2013.3]

Installation Manual. Integrated Prepaid Keypad Meters. For HXE12-KP. Hexing Electrical Co., Ltd.  [2013.3] Installation Manual Integrated Prepaid Keypad Meters For HXE12-KP Hexing Electrical Co., Ltd. www.hxgroup.cn [2013.3] Meter Installation Manual-HXE12-KP 2 / 14 Introduction Range of validity The present

More information

M T E C o r p o r a t i o n MTE - SERIES RL LINE/LOAD REACTORS USER MANUAL PART NO. INSTR 011 REL MTE Corporation

M T E C o r p o r a t i o n MTE - SERIES RL LINE/LOAD REACTORS USER MANUAL PART NO. INSTR 011 REL MTE Corporation M T E C o r p o r a t i o n MTE - SERIES RL LINE/LOAD REACTORS USER MANUAL PART NO. INSTR 011 REL. 021126 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components

More information

SECTION A. UL rd Edition (2009 Revision effective 9/29/2009).

SECTION A. UL rd Edition (2009 Revision effective 9/29/2009). SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the materials and installation requirements for Surge Protective Devices (SPDs) and includes

More information

EPOXY MICA COUPLING CAPACITOR. Installation Manual. Epoxy Mica Coupling Capacitor - Installation Manual P/N: I1A-100

EPOXY MICA COUPLING CAPACITOR. Installation Manual. Epoxy Mica Coupling Capacitor - Installation Manual P/N: I1A-100 EPOXY MICA COUPLING CAPACITOR Installation Manual Copyright VibroSystM Inc., 2013 Epoxy Mica Coupling Capacitor - Installation Manual P/N: 9477-09I1A-100 Epoxy Mica Coupling Capacitor - Installation Manual

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 16400 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY 1. This Section includes methods and materials for grounding systems and equipment. 1.2 SUBMITTALS A. Product Data:

More information

DRY TYPE INSTRUCTION AND MAINTENANCE MANUAL

DRY TYPE INSTRUCTION AND MAINTENANCE MANUAL DRY TYPE INSTRUCTION AND MAINTENANCE MANUAL DELCOR POWER PRODUCTS 1129 THORNWOOD PLACE FAYETTEVILLE, NORTH CAROLINA 28304 DRY TYPE TRANSFROMER INSTALLATION AND MAINTENANCE INSTRUCTIONS UNLOADING AND HANDLING

More information

Instructions. Installation, Operation, and Maintenance of SVR-1 Step Voltage Regulators. Howard Industries, Inc. ISO-9001 Certified

Instructions. Installation, Operation, and Maintenance of SVR-1 Step Voltage Regulators. Howard Industries, Inc. ISO-9001 Certified Switch-Pad Instructions Installation, Operation, and Maintenance of s Howard Industries, Inc. ISO-9001 Certified Document No. 2.4.114 1 Document 2.4.114 READ THIS IMPORTANT SAFETY INFORMATION Read these

More information

General Description & Features Thermal Switches...47 Selection Charts Windings, Terminations & Construction...47

General Description & Features Thermal Switches...47 Selection Charts Windings, Terminations & Construction...47 Drive Isolation Transformers & AC Line Reactors Specifically designed to accommodate the special voltage and kva sizes unique to AC and DC drive applications. Shielded for extra protection from supply

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

GigaSPEED X10D F/UTP and S/FTP Cabling System

GigaSPEED X10D F/UTP and S/FTP Cabling System SYSTIMAX Solutions GigaSPEED X10D F/UTP and S/FTP Cabling System Earthing (Grounding) and Bonding Guidelines April 28, 2011 www.commscope.com 1 Introduction The earthing (grounding) and bonding of SYSTIMAX

More information

XPS. Surge Arrester - System Voltage 2 kv to 245 kv

XPS. Surge Arrester - System Voltage 2 kv to 245 kv XPS Surge Arrester - System Voltage 2 kv to kv XPS Station Class Silicone-oused Arresters Metal Oxide Surge Arrester XPS Protection of switchgear, transformers and other equipment in high voltage systems

More information

white paper Medium Voltage On-Site Generation Overview by Mike Kirchner, Technical Support Manager at Generac Power Systems INTRODUCTION

white paper Medium Voltage On-Site Generation Overview by Mike Kirchner, Technical Support Manager at Generac Power Systems INTRODUCTION white paper Medium Voltage On-Site Generation Overview by Mike Kirchner, Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As

More information

Section 9 Electric Metering: Components

Section 9 Electric Metering: Components Section 9 Electric Metering: Components 9.1. Scope This section provides information to help applicants select electric metering equipment that Pacific Gas and Electric Company (PG&E/ the Company) finds

More information

StarSine TM Power Quality Products

StarSine TM Power Quality Products StarSine TM Power Quality Products Medium Voltage Static Transfer Switch ( MV STS ) MV STS SIGNIFICANTLY IMPROVES THE UPTIME OF FACILITIES WITH DUAL FEEDER SERVICE BY SUB-CYCLE SWITCHING FROM ONE POWER

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

Automation System TROVIS 5400 Repeater TROVIS 5482

Automation System TROVIS 5400 Repeater TROVIS 5482 Automation System TROVIS 5400 Repeater TROVIS 5482 Mounting and operating instructions EB 5409-1 EN Edition December 2000 Application Contents Application.................................... 2 Principle

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single or multi-mode fiberglass Data sheet 3205_en_D 1 Description PHOENIX CONTACT 2014-10-23 2 Features

More information

COMPACT AND LIGHTWEIGHT MAXIMUM DEPENDABILITY FACTORY ASSEMBLED STURDY, RIGID CONSTRUCTION CLEAN, ATTRACTIVE APPEARANCE

COMPACT AND LIGHTWEIGHT MAXIMUM DEPENDABILITY FACTORY ASSEMBLED STURDY, RIGID CONSTRUCTION CLEAN, ATTRACTIVE APPEARANCE Park bus runs are complete lines of non-segregated phase bus designed for inter-connecting groups of metal-enclosed or metal-clad switchgear, power transformers or other related equipment. Bar type, with

More information

Why Choose A Line Reactor?

Why Choose A Line Reactor? Why Choose A Line Reactor? Utilizing variable speed drives to control motor speed has impacted industry both in energy savings and increased efficiencies. The challenge for today s designers is dealing

More information

Canopy Surge. User Manual

Canopy Surge. User Manual Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read

More information

TECHNICAL SERVICE BULLETIN

TECHNICAL SERVICE BULLETIN TECHNICAL SERVICE BULLETIN TITLE: Cabling Guidelines for Improving Voice over Internet Protocol (VoIP) Quality NUMBER: 56006180 ISSUE: GA RELEASED: November, 2003 PRODUCTS AFFECTED: (3300 ICP, 3100 ICP

More information

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Substation Manual 00.00) General These requirements are applicable to all customer owned substation facilities at which We Energies supply lines are terminated. 00.00.0) The requirements contained herein

More information

TRANSTECTOR OUTDOOR PPC DUAL AUTOMATIC TRANSFER SWITCH CONTOLLER WITH TVSS 100 AMP SERVICE 20 POSITION LOAD CENTER 64 H X 30 W X 12 D

TRANSTECTOR OUTDOOR PPC DUAL AUTOMATIC TRANSFER SWITCH CONTOLLER WITH TVSS 100 AMP SERVICE 20 POSITION LOAD CENTER 64 H X 30 W X 12 D REVISIONS LTR DESCRIPTION ECN DATE APPROVED A PRODUCTION RELEASE HP011 9/19/07 DLR TRANSTECTOR 1101-892 OUTDOOR PPC DUAL AUTOMATIC TRANSFER SWITCH CONTOLLER WITH TVSS 100 AMP SERVICE 20 POSITION LOAD CENTER

More information

IS Single Phase SCR Power Pak. Description. Wave Form Cycle Rate MXPC IP PDS. Features:

IS Single Phase SCR Power Pak. Description. Wave Form Cycle Rate MXPC IP PDS. Features: IP MXPC IP PDS Single Phase SCR Power Pak Features: 120-575 Vac @ 0-1200 Amp Phase Angle Firing Isolated Control Circuit Inputs: 0-5 ma, 0-20mA 0-50 ma, 1-5 ma 4-20 ma, -50 ma 0-5 Vdc, 0- Vdc Flexible

More information

Addendum WeatherTRAK Pro3 Dual (72 and 96 Station) Wall Mount Installation Instructions

Addendum WeatherTRAK Pro3 Dual (72 and 96 Station) Wall Mount Installation Instructions Addendum WeatherTRAK Pro3 Dual (72 and 96 Station) Wall Mount Installation Instructions WeatherTRAK s conventionally wired 72 and 96 station wall mount controller enables management of up to 96 stations

More information

Product shall be of the design, construction and physical dimensions specified on the applicable product drawing.

Product shall be of the design, construction and physical dimensions specified on the applicable product drawing. Product Specification 108-1403 07Nov08 Rev A All Paragraphs Revised AMPOWER* Wave Crimp System Self-Aligning Header and Receptacle Assemblies 1. SCOPE 1.1. Content This specification covers performance,

More information

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series Installation Manual APEX Series Silicon and MOV Panel Protection APEX Series 800.882.9110 208.772.8515 www.transtector.com APEX Series Installation Guide 2 Table of Contents Mechanical Installation 3 Table

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

COOPER POWER SERIES. Edison single-phase vacuum capacitor switch installation and operation instructions. Vacuum Switches MN230007EN

COOPER POWER SERIES. Edison single-phase vacuum capacitor switch installation and operation instructions. Vacuum Switches MN230007EN Vacuum Switches MN230007EN Effective November 2016 Supersedes March 2014 (S230-50-1) COOPER POWER Edison single-phase vacuum capacitor switch installation and operation instructions SERIES DISCLAIMER OF

More information

SPR-5200 and SPR-4600 Installation and Operation Manual

SPR-5200 and SPR-4600 Installation and Operation Manual SPR-5200 and SPR-4600 Installation and Operation Manual SunPower Corporation Document # 001 69178 Rev** 1 SunPower Inverter SPR-5200 and SPR-4600 Table of Contents SunPower Corporation Document # 001 69178

More information

Schneider Automation Modbus Plus Network Installing Clustered Node Devices 31000939 00 Version 2.0

Schneider Automation Modbus Plus Network Installing Clustered Node Devices 31000939 00 Version 2.0 Schneider Automation Modbus Plus Network Installing Clustered Node Devices 3000939 00 Version.0 Modbus Plus devices must be installed as specified in a network layout plan, showing each device s mounting

More information

LONG ISLAND POWER AUTHORITY REQUIREMENTS FOR INTERCONNECTION OF NEW DISTRIBUTED GENERATION UNITS WITH CAPACITY OF

LONG ISLAND POWER AUTHORITY REQUIREMENTS FOR INTERCONNECTION OF NEW DISTRIBUTED GENERATION UNITS WITH CAPACITY OF A. Design Requirements 1. Common LONG ISLAND POWER AUTHORITY REQUIREMENTS FOR INTERCONNECTION OF NEW DISTRIBUTED GENERATION UNITS WITH CAPACITY OF 300 kva OR LESS TO BE OPERATED IN PARALLEL WITH RADIAL

More information

3M Cold Shrink Hi-K Silicone Rubber Termination Kits QT-II, 5670 Series

3M Cold Shrink Hi-K Silicone Rubber Termination Kits QT-II, 5670 Series 3M Cold Shrink Hi-K Silicone Rubber Termination Kits QT-II, 5670 Series Data Sheet July 2010 Description Kit Contents 3M Cold Shrink Hi-K Silicone Rubber Termination Kits QT-II, 5670 Series are onepiece,

More information

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SATETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625

STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SATETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 September 2011 STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SATETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 MATERIAL SPECIFICATIONS FOR TRAFFIC VOLUME SYSTEM The

More information

Howard Industries, Inc. Open-Wound, Ventilated, Medium-Voltage Dry-Type Transformers. Catolog Section

Howard Industries, Inc. Open-Wound, Ventilated, Medium-Voltage Dry-Type Transformers. Catolog Section ISO-9001 Certified Introduction Howard open-wound, ventilated, medium-voltage, dry-type, transformers are designed to meet the demanding requirements of many industrial, commercial, and utility applications.

More information

ELECTRIC SERVICE RULES UNDERGROUND SECONDARY SERVICE Issued Jan 2016 ELECTRIC SERVICE RULES UNDERGROUND SECONDARY SERVICE

ELECTRIC SERVICE RULES UNDERGROUND SECONDARY SERVICE Issued Jan 2016 ELECTRIC SERVICE RULES UNDERGROUND SECONDARY SERVICE CHAPTER 4 UNDERGROUND SECONDARY SERVICE 400. SCOPE This chapter covers the requirements and rules for underground residential and commercial secondary services for Alliant Energy customers. Underground

More information

RADIANT PLASMA 4700 Plasma Spark Generator

RADIANT PLASMA 4700 Plasma Spark Generator RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

WHITE PAPER. Selecting and Applying Medium Voltage Fuses 2,400-38,000 VAC

WHITE PAPER. Selecting and Applying Medium Voltage Fuses 2,400-38,000 VAC WHITE PAPER Selecting and Applying Medium Voltage Fuses 2,400-38,000 VAC TECHNICAL APPLICATION GUIDE Applying Medium Voltage Fuses (2,400 38,000 Volts AC) Introduction Medium voltage fuses are applied

More information

CVM 8/13/01 ENGR. APPD: DWR 8/15/01 REVISIONS NOTED. C Update MOV data /16/02 MLH. D Add CE Listed /14/02 JDW

CVM 8/13/01 ENGR. APPD: DWR 8/15/01 REVISIONS NOTED. C Update MOV data /16/02 MLH. D Add CE Listed /14/02 JDW THIS DRAWING HAS BEEN GENERATED AND IS MAINTAINED BY A CAD SYSTEM. CHANGES SHALL ONLY BE INCORPORATED AS DIRECTED BY THE DESIGN ACTIVITY. REVISIONS LTR DESCRIPTION ECO NUM. DATE APPROVED C Update MOV data

More information

Technical Note. Equipment Rack Grounding RevA

Technical Note. Equipment Rack Grounding RevA Technical Note Equipment Rack Grounding 1485-009RevA Technical Note Equipment Rack Grounding Equipment Rack Grounding Equipment racks and cabinets can provide an unwanted path for lightning surge energy.

More information

A. This Section includes methods and materials for grounding systems and equipment.

A. This Section includes methods and materials for grounding systems and equipment. SECTION 260526 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes methods and materials for grounding systems and equipment. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B.

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

Combined Overcurrent and Earth-fault Relay SPAJ 135 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 135 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Two-stage phase overcurrent protection and single-stage

More information

TAMCO 11kV METALCLAD WITHDRAWABLE SWITCHGEAR: SCHEDULE OF TECHNICAL DATA. Description Ratings & Electrical Requirements Unit Performance Data*

TAMCO 11kV METALCLAD WITHDRAWABLE SWITCHGEAR: SCHEDULE OF TECHNICAL DATA. Description Ratings & Electrical Requirements Unit Performance Data* Item no. Description Ratings & Electrical Requirements Unit Performance Data* 1 General Details Manufacturer s Name Typical Layout and sectional Drg of Switchgear supplied to Australian environment Switchgear

More information

Iron-Core Versus Air-Core Harmonic Filter Reactors

Iron-Core Versus Air-Core Harmonic Filter Reactors Iron-Core Versus Air-Core Harmonic Filter Reactors Introduction At the medium voltage level, 2.4kV through 13.8kV, harmonic filters are often designed, specified, and manufactured with either Iron-core

More information

Analog I/O Interface with CL6800-Series Cards, Termination Panels, and Modules

Analog I/O Interface with CL6800-Series Cards, Termination Panels, and Modules PROVOX Process Management Systems BU4.2:CL6821 Analog I/O Interface with CL6800-Series Cards, s, and Modules CL6800-Series Analog I/O instruments are members of the PROVOX Control I/O family. They interface

More information

SECTION MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS:

SECTION MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Overvoltage and Undervoltage Relay SPAU 121 C. Product Guide

Overvoltage and Undervoltage Relay SPAU 121 C. Product Guide Overvoltage and Undervoltage Relay Issued: April 1999 Status: Updated Version: C/25.04.2006 Data subject to change without notice Features Combined overvoltage and undervoltage protection relay Single-phase

More information

Residual Overvoltage Relay SPAU 110 C. Product Guide

Residual Overvoltage Relay SPAU 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/25.04.2006 Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation

More information

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273

More information

GAS INSULATED INSTRUMENT TRANSFORMERS

GAS INSULATED INSTRUMENT TRANSFORMERS GAS INSULATED INSTRUMENT TRANSFORMERS FOR AIR INSULATED SWITCHGEARS SF 6 INSULATED CURRENT TRANSFORMERS The current transformer consists of one or several cores with their corresponding secondary windings

More information

WIRING SCHEMES AND GROUNDING

WIRING SCHEMES AND GROUNDING Electrical Distribution Systems Nuclear facilities rely on standardized wiring schemes to provide both singlephase and three-phase power distribution systems and protective grounds to insure safe operation.

More information

SuperLine 5030 POTS Splitter Installation Instructions. What Does the POTS Splitter Do? Document Number 5030-A2-GN11-00 September 1999

SuperLine 5030 POTS Splitter Installation Instructions. What Does the POTS Splitter Do? Document Number 5030-A2-GN11-00 September 1999 SuperLine 5030 POTS Splitter Installation Instructions Document Number 5030-A2-GN11-00 September 1999 What Does the POTS Splitter Do? The POTS (Plain Old Telephone Service) splitter and SuperLine IAD are

More information

About the 5920 POTS/ISDN Splitters

About the 5920 POTS/ISDN Splitters 5920 POTS/ISDN Splitter Installation Instructions Document Number 5920-A2-GZ40-00 May 2005 About the 5920 POTS/ISDN Splitters The 5920 POTS/ISDN splitters separate the DSL (Digital Subscriber Line) and

More information

Article 250: Grounding And Bonding

Article 250: Grounding And Bonding Part D: Code Book Questions Article 250: Grounding And Bonding 1.! A ground-fault is an unintentional, electrically conducting connection between an ungrounded! conductor of an electrical circuit and the

More information

Specifications, Installation, and Operating Instructions

Specifications, Installation, and Operating Instructions Specifications, Installation, and Operating Instructions Model: SP Plus Family CAUTION: THE INSTALLATION OF A SURGE PROTECTION DEVICE () MUST BE DONE BY QUALIFIED ELECTRICAL PERSONNEL. A MUST BE GROUNDED

More information

ELECTRIC SWITCHBOARDS VOLTS

ELECTRIC SWITCHBOARDS VOLTS ELECTRIC SWITCHBOARDS 0-600 VOLTS 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL METERING REQUIREMENTS 4.0 SWITCHBOARD - GENERAL 5.0 SWITCHBOARD SERVICE SECTION 6.0 SERVICE ENTRANCE LOCATION 7.0 UNDERGROUND

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1 SECTION PAD MOUNTED TRANSFORMERS

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1 SECTION PAD MOUNTED TRANSFORMERS KNOXVILLE, TENNESSEE SECTION 16460 PAGE 1 SECTION 16460 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK: A. Extent of transformer work is indicated by drawings and schedules. B. Types of transformers specified

More information

Grounding and Bonding According to the 2011 NEC

Grounding and Bonding According to the 2011 NEC Grounding and Bonding According to the 2011 NEC Utah Electrical License This course will cover system grounding and bonding according to the 2011 NEC. The following topics will be covered: grounding and

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

XP SoftswitchTM Panels

XP SoftswitchTM Panels GAFIK Systems XP SoftswitchTM Panels xp-1 05.11.06 -Through XP Without Branch Circuit Breakers XP With Branch Circuit Breakers Mini XP All voltages 4 to 16 switch legs Standard-Size XP All voltages 20

More information

Hotwire 5030 POTS Splitter Customer Premises Installation Instructions. What Does the Hotwire 5030 POTS Splitter Do?

Hotwire 5030 POTS Splitter Customer Premises Installation Instructions. What Does the Hotwire 5030 POTS Splitter Do? Hotwire 5030 POTS Splitter Customer Premises Installation Instructions Document Number 5030-A2-GN10-20 December 1999 What Does the Hotwire 5030 POTS Splitter Do? The Hotwire 5030 POTS Splitter and Hotwire

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

1ZSE en, Rev. 3. Transformer bushings, type GOH Technical guide

1ZSE en, Rev. 3. Transformer bushings, type GOH Technical guide 1ZSE 2750-107 en, Rev. 3 Transformer bushings, type GOH Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Installation Guidelines

Installation Guidelines 3/9/07, 9/11/15 Note: Always refer to winding diagram and user manuals set shipped with the Insulgard Installation Guidelines Installation of the InsulGard system is based on the physical layout of each

More information

SECTION SWITCHBOARD. A. Submit manufacturer's literature and technical data before starting work.

SECTION SWITCHBOARD. A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information