1 Issued E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1 INDEX SECTION WTR01: ELECTRICAL CONNECTIONS PRIMARY.. Page 1 SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS.. Page 9 SECTION WTR02: GENERAL. Page 1 OVERHEAD... Page 1 PADMOUNTED. Page 5

2 Issued E.C.S. Section WTR01 INFORMATION SECTION Page 1 of 9 ELECTRICAL CONNECTIONS 1. PRIMARY a. Standard Connections Primary: 4.16 kv, kv, 13.2 kv, 13.8 kv, 24.9 kv or 24 kv 3-Phase Wye-Wye for 120/208 or 277/480 Volt Services 0~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X2 Leads for Subtractive Polarity Transformers

3 Section WTR01 E.C.S. Issued Page 2 of 9 INFORMATION SECTION ELECTRICAL CONNECTIONS Primary: 2.4 kv, 7.2 kv, 13.8 kv, 14.4 kv or 24 kv 3-Phase Delta-Wye for 120/208 or 2 77/480 Volt Services 30~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X2 Leads for Subtractive Polarity Transformer

4 Issued E.C.S. Section WTR01 INFORMATION SECTION Page 3 of 9 ELECTRICAL CONNECTIONS b. Maintenance Connections Primary: 4.16 kv, kv, 13.2 kv, 13.8 kv, 24.9 kv or 24 kv 3-Phase Floating Wye-Delta for 120/240 Volt Services 210~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X3 Leads for Subtractive Polarity Transformers

5 Section WTR01 E.C.S. Issued Page 4 of 9 INFORMATION SECTION ELECTRICAL CONNECTIONS A Primary: 4.16 kv, kv, 13.2 kv, 13.8 kv, 24.9 kv or 24 kv 3-Phase Open Wye-Delta for 120/240 Volt Services 210~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X3 Leads for Subtractive Polarity Transformers B C N a b c N

6 Issued E.C.S. Section WTR01 INFORMATION SECTION Page 5 of 9 ELECTRICAL CONNECTIONS Primary: 2.4 kv, 7.2 kv, 13.8 kv, 14.4 kv or 24 kv 3-Phase Open Delta-Delta for 120/240 Volt Services 180~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X3 Leads for Subtractiave Polarity Transformers

7 Section WTR01 E.C.S. Issued Page 6 of 9 INFORMATION SECTION ELECTRICAL CONNECTIONS A Primary: 2.4 kv, 7.2 kv, 13.8 kv, 14.4 kv or 24 kv 3-Phase Delta-Delta for 120/240 Volt Services 180~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X3 Leads for Subtractive Polarity Transformers B C N B H1 H2 H1 A C X3 X1 X3 X2 X2 a b c N

8 Issued E.C.S. Section WTR01 INFORMATION SECTION Page 7 of 9 ELECTRICAL CONNECTIONS A Primary: 2.4 kv, 7.2 kv, 13.8 kv, 14.4 kv or 24 kv 3-Phase Delta-Delta for 120/240 Volt Services 0~ Angular Displacement Additive Polarity Transformers Shown Reverse X1 and X3 Leads for Subtractive Transformers B C N H1 A C X3 a b c N

9 Section WTR01 E.C.S. Issued Page 8 of 9 INFORMATION SECTION ELECTRICAL CONNECTIONS Primary: 4.16 kv, kv, 13.2 kv, 13.8 kv, 24.9 kv or 24 kv 3-Phase Wye-Wye for 120/208 or 277/480 Volt Services 0~ Angular Displacement Addative Polarity Transformers Shown Reverse X1 and X2 Leads for Subtractive Polarity Transformers b' A PRIMARY C SERVICE c

10 Issued E.C.S. Section WTR01 INFORMATION SECTION Page 9 of 9 ELECTRICAL CONNECTIONS 2. SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS Low Voltage 120/ /480 High Voltage 8660 and Below 8661 and Above 8660 and Below 8661 and Above (Phase-Ground) KVA Low-voltage Connections & Bushing Arrangement (Letters refer to illustrations below) 100 and less A B D E 167 and larger C F

11 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 1 of GENERAL a. Non-PCB Sticker for Distribution Transformer Identification A white on blue sticker has been made available to identify transformers that contain non-pcb oil. This sticker is applied by the manufacturer on new pole mounted transformers. It shall be applied to unlabeled units by the Transformer Repair Shop only after a transformer has been tested to contain, or filled with non-pcb transformer oil. The sticker shall be applied by the transformer repair shops on all transformers containing non- PCB oil in the following locations: 1) Pole-mounted transformers. -- Below the middle secondary bushing. 2) Padmounted transformers -- Upper right-hand corner of the low voltage compartment door. New padmounted transformers are labeled as non-pcb on the external nameplate. Older transformers may be labeled as non-pcb in one of three ways: IES - Blue Punch Card Label IPW - 6 x 6 Blue and White Label WP&L - Yellow Dot Label b. Secondary Breakers on CSP Transformers Voltages have been observed across the secondary terminals of distribution overhead and padmount transformers whose primaries were energized but whose secondary breakers were open. Caution should be used when the secondary circuit breaker is open. There may be sufficient coupling to the windings so that perceptible shock may be obtained from the secondary terminals. This voltage will generally be considerably less than 240 volts. In cases where it approaches or exceeds 300 volts, it will be a very low capacity voltage source and very little current will be available. In addition to the possibility of this coupling, the secondary breaker contacts are not visible and consequently the open circuit they are intended to provide cannot be visually confirmed. For those reasons, transformer secondary breakers cannot be positively relied upon to deenergize secondaries. 2. OVERHEAD a. Connections 1) Line-Equipment Transformer connections should be made with a stirrup and hot line clamp. The sequence of installation should be stirrup - hot line clamp - arrester - cutout, as shown in Figure 02-1 on Page WTR02.3. For transformers with tank mounted arresters, the sequence is stirrup, hot line clamp, cutout, arrester.

12 Section WTR02 E.C.S. Issued Page 2 of 17 INFORMATION SECTION 2) Grounding The correct method of grounding overhead distribution transformers is also shown in Figure 02-1 and 02-2: 1) The primary neutral bushing (if present) shall have a direct connection to the primary neutral conductor or pole ground. 2) The transformer case ground shall be grounded to the pole ground. The preferred method is to extend the primary neutral bushing jumper as shown on dual bushing transformers. 3) The primary neutral conductor shall be bonded to the pole ground. 4) The secondary neutral bushing shall be connected to the system neutral through the case ground jumper and the secondary cable neutral. 5) The grounding jumper shall be extended from the transformer case ground to the secondary neutral bushing if the secondary neutral case ground jumper is missing.

13 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 3 of 17 The following drawings illustrate the correct grounding connections.

14 Section WTR02 E.C.S. Issued Page 4 of 17 INFORMATION SECTION

15 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 5 of PADMOUNTED a. General 1) Clearances See " Clearance " Information Section. 2) Mounting Padmount transformers are designed for operation on a level surface. Excessive pad tilts can result in exposed conductors within the transformer causing disruptive failures or restrictive flow of oil through cooling fins resulting in overheating and decrease transformer life. 3) Fusing a) Oil in dry-well fuse canisters On occasion, oil may be found inside the dry-well fuse canisters of padmounted transformers. The above condition, if left uncorrected, can become a potential hazard. Current limiting fuses are intended to isolate the transformer from the line in the event of a faulted transformer, severe overload, or secondary fault. These fuses are designed to operate in a dry air environment which is provided by the dry-well canister. Any oil, water or other contaminant in the canister may cause misoperation of the fuse. A hazard may exist when working in close proximity to the fuse while the primary compartment door is open and the fuse(s) attempts to operate for a fault or overload. The oil-soaked fuse element can expel gases with enough pressure to eject the fuse holder assembly from the canister. Single or three-phase padmounted transformers with canisters known or found to be contaminated with oil must be removed from service and repaired. This requirement applies to both new and used transformers. If an in-service transformer is suspected of having a leaking canister(s), it is recommended that the unit be deenergized from a remote location before removing the fuse(s). Report any transformers with oil in canisters to Electric Distribution Standards utilizing " Report of Unsatisfactory Material ", Form A. b) Missing fuses in dry-well canisters Infrequently, a padmount transformer may be received without current limiting fuses in the dry-well canisters. Manufacturers will generally place a steel or wood rod in the drywell canisters in the unusual case they do not ship the transformers with fuses in place. The manufacturer should, but does not always, place a tag inside the transformer compartment warning that fuses are missing.

16 Section WTR02 E.C.S. Issued Page 6 of 17 INFORMATION SECTION In some locations, transformers installed without proper fuses may not be adequately protected from secondary faults. Therefore, the following precautions are recommended to prevent any unnecessary transformer damage: (1) Transformer repair shops should inspect all padmount transformers for the presence of correct size fuses prior to sending the units to the district or installation site. (2) All crews installing transformers should inspect for the presence of the correct size fuses before energizing any unit. (3) Be sure to take replacement fuses out of Stores stock, and not out of padmount transformers. (4) If an installed unit is suspected of not being properly fused, de-energize the transformer and make the appropriate corrections in accordance with applicable Safety Rules and Electrical Operating Practices. Report any such occurrences to Electric Distribution Standards utilizing " Report of Unsatisfactory Material ", Form A. 4) Protection When installing transformers near parking lots, driveways, alleyways, etc., place concrete filled or galvanized steel posts at the corners for protection from vehicular traffic. b. Single-Phase Single-phase padmount transformers are furnished with threaded stud secondary bushings. This design allows for space savings, minimizing of compression and bolted fittings, and reduced cable disturbance during changeouts. The secondary terminal blocks are aluminum alloy of inline, multi-position, set screw design, with " slip fit " mounting for quick disconnect capability. The blocks are disconnected from the stud via (1 or 2) Allen style set screws.

17 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 7 of 17 Figure 02-3 APPLICATION KVA STUD DIAMETER THREAD STUD LENGTH ITEM ID /8" 11-UNC-2A 1-1/4" " 14-UNS-2A 1-3/4" Each terminal block consists of five (5) main tap positions and one (1) streetlight tap position. The mains have a range of #4 to #350 MCM AWG, the streetlight tap ranges from #8 to #4 AWG. The streetlight position pressure screw may be a regular head machine screw or hex Allen style set screw. All hex Allen style pressure set screws have either 5/16 ", or 3/8 " sockets. Terminal blocks are packaged in a kit of three (3) blocks and two (2) insulating boots. 1) Block Installation The orientation of the terminal block on the transformer studs should be such that the set screws are directed upward to the left when facing the transformer. This aligns the cable holes at an angle for training the cables on a proper radius, rather than directly vertical. Once oriented, the set screws are tightened (as per manufacturer ' s instructions) after the block has been fully seated on the stud. On the neutral stud the jam nut provided is run against the terminal block. Any jam nuts on phase stud bushings should be removed, and only one should be used on the neutral bushing. This will allow the block to bottom out fully onto the stud and achieve optimum set-screw pressure and electrical contact over the stud length. The insulating boots can then be placed over the phase blocks for storage.

18 Section WTR02 E.C.S. Issued Page 8 of 17 INFORMATION SECTION 2) Grounding One jam nut only shall be used on the neutral stud for making the ground strap connection (if two jam nuts are provided, discard one). Install the block such that the ground strap is fastened between the jam nut and the back of the terminal block. 3) Cable Application Figure 02-4 The design allows for four (4) secondary cable runs. This leaves one (1) main position vacant on the two phase blocks; do not use. One (1) streetlight circuit is allowed per transformer, originating from one of the two phase blocks; the other is left vacant, do not use. See the chart below: Cable Application Chart Positions Block Streetlight Tap Phase Cable Cable Cable Cable Vacant 1 - Vacant 1 - Streetlight Cable Neutral Ground Cable Cable Cable Cable Streetlight Neutral The neutral block, however, is filled: With four (4) secondary cable neutrals, one (1) streetlight neutral, and the " fifth " main position with the ground conductor. Positions should be filled from the rear outward (Position #1, 2, etc.). Secondary cables and ground conductor should be " inside " of the primary cables for clear switching of the elbow terminators. The ground conductor should be placed in Position 1 of the neutral block.

19 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 9 of 17 Cables should be dressed back to approximately 1/4 " more than the block thickness. Conductor strands should protrude out the top side slightly (1/4 " Max.) to ensure adequate strand contact. 4) Tooling Tool requirements include a crescent wrench for the jam nuts, screwdriver and an Allen style socket ratchet wrench. c. Three-Phase 1) Dimensions a) Cabinet Size

20 Section WTR02 E.C.S. Issued Page 10 of 17 INFORMATION SECTION Figure Three-Phase GY-GY Transformer Faceplate Layout Three-Phase GY-GY Transformer Faceplate Layout TC Pressure Relief Valve Primary Bushing Parking Stand Bayonet Tap changer operating handle Oil Fill Plug LFSA Loopfeed switch A-side LFSB Loopfeed switch B-side Loopfeed switch handles Secondary Bushings/Spades HV Compartment Dimensions (in.) HV Voltage D E F G 12.4 KV Ground Nut Locations as 12.4X switch per para. 9b KV

21 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 11 of 17 b) Footprint The following table shows the approximate dimensions of kvv padmounted transformers. Dual voltage transformers (24.9 kv or kv) have similar dimensions except for a few heights and weights. The heights off 150 kva to 500 kva duals are 67 inches. The weights of duals are usually 500 pounds to 1,200 pounds heavier, depending on the size of the transformer. Figure Three-Phase Padmounted Transformer Cabinet Dimensions

22 Section WTR02 E.C.S. Issued Page 12 of 17 INFORMATION SECTION Dimensions in Inches Type Kva Voltage A B C D E Height Weight Cooper /480v ,320 # Cooper /208v ,884 # Cooper /480v ,845 # Cooper /208v ,697 # Cooper /480v ,668 # Cooper /208v ,547 # Cooper /480v ,688 # Cooper /208v ,841 # Cooper /480v ,233 # Cooper /208v ,262 # Cooper /480v ,634 # Howard /208v Cooper /480v ,084 # Cooper 2500 Dual 277/480v 96* ,817 # Cooper kv 277/ ,000 # *=About 2' of cooling fins /12.47 Step ,000 # /12.47 Step ,541 # 2) Foundation a) Use of Table and Drawings Figure 02-7 on Page WTR (1) Pad Selection For initial installation of a 75 kva to 500 kva transformer use the dimensions given for PAD I. PAD I will also accommodate a 750 kva sized transformer for future growth. For initial installation of a 750 kva to 2,500 kva sized transformers use the dimensions given for PAD II. (2) Pad Dimensions Dimension "A" specifies the depth of the pad, dimension "B" specifies the width of the pad, dimension "C" specifies the distance from the right edge of the pad to the right edge of the pad opening, dimension "D" specifies the width of the pad opening, and dimension "E" specifies the depth of the pad opening.

23 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 13 of 17 In all cases the depth of the opening for Pads I and II will be 17 inches. The distance from the front of the pad to the front edge of the pad openings will be 13 inches. The outside pad dimension are selected to insure that the transformer cooling fins will not extend beyond the perimeter of the pad when following the transformer setting instructions. Typically, there will be about six (6) inches of the concrete pad extending beyond the fin perimeter of the transformer on the right side with respect to the width, and in front with respect to the depth.

24 Section WTR02 E.C.S. Issued Page 14 of 17 INFORMATION SECTION Figure 02-7 Maximum number of Secondary Conduits Allowed is eight. If more than eight are required, authorization from Distribution Engineer required. 1. Size and number of conduits must be obtained from Alliant Energy Engineering. 2. When oil sump is required, excavate 18 inches under and around pad, and fill with coarse, crushed rock. (Check with local municipal codes to determine if oil sump is required.) 3. Concrete shall have a minimum strength of 4000 lb./sq.in. after 28 days cure time. 4. Top of pad must be level.

25 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 15 of The pad shall be reinforced with #4 wire, 4 inch by 4 inch mesh with additional 3/8 inch reinforcing rod around the cable opening. The mesh shall not be less than one inch from the edges and opening, and installed three inches below the surface. If the #4 wire, 4 inch by 4 inch mesh is not available, two layers of #10 wire, 6 inch by 6 inch mesh staggered by 2 inches horizontally may be substituted for the #4 wire. 6. The pad shall have all edges and corners rounded off. b) Method of Positioning Transformer on the pad: The following steps are required in setting the transformer properly on the pads: Step 1: Line up the right side of the transformer secondary cable compartment with the right edge of the pad opening, making sure that the pad opening is not exposed outside of the cable compartment. This is shown by the dotted (MN) in Figure 02-8 on Page WTR This will insure that the secondary compartment is completely open at all times. Step 2: Line up the rear panelling of the cable compartment with the back edge of the pad opening as shown in Figure 02-8 on Page WTR02.16 by the dotted line (XY). This will insure that the tank will completely rest on solid concrete for weight support. Figure 02-8 on Page WTR02.16 shows the setting of a typical transformer on the pad using the positioning method mentioned above.

26 Section WTR02 E.C.S. Issued Page 16 of 17 INFORMATION SECTION Figure 02-8

27 Issued E.C.S. Section WTR02 INFORMATION SECTION Page 17 of 17 c) Pad Opening Dimensions and Location The width and depth of the pad opening are based upon the smallest cable compartment, width and depth, of the kva sizes for which that pad is designed. This will leave a minimum eight (8) inches of opening in the primary side of the cable compartment for the largest transformer compartment width for which the pad is designed. The thirteen (13) inch dimension from the front of the pad to the front of the pad opening will insure that larger cable compartments will not extend over the front edge of the pad, using the prescribed method of positioning the transformer. Other references: (1) Electrical Material Specifications No (2) Electric Service Information Manuals. (END)

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,

More information

STREETLIGHT SYSTEM GROUNDING AND BONDING

STREETLIGHT SYSTEM GROUNDING AND BONDING Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing of Residential Water Heaters Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

Step 1. Item 6. Item 1

Step 1. Item 6. Item 1 Voltage Regulators QD3/T350 Motor Replacement Kit Kit Number 57A63675100B Service Information S225-50-35 Contents General..................................... 1 Parts Supplied...............................

More information

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH The original design of the 03 Alpine Coaches (and perhaps other years as well) did not include any kind of engine fan engage mechanism

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877

More information

Instructions for Secondary Unit Substation Transformers 150-3000 KVA, Three Phase

Instructions for Secondary Unit Substation Transformers 150-3000 KVA, Three Phase ABB Inc. Instruction Booklet Distribution Transformers Jefferson City, MO ISO 9001 Certified I.B. 46-060-1, Section E ILUJ000004-BLE Effective: January, 2008 Instructions for Secondary Unit Substation

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

TABLE OF CONTENTS. I. TROUBLESHOOTING... 2 - Section 1.01: Common Problems/Solutions... 2

TABLE OF CONTENTS. I. TROUBLESHOOTING... 2 - Section 1.01: Common Problems/Solutions... 2 BAL Accu-Slide System I. Table of Contents TABLE OF CONTENTS I. TROUBLESHOOTING... 2 - Section 1.01: Common Problems/Solutions... 2 II. GETTING STARTED... 5 - Section 2.01: Tools You Will Need... 5 - Section

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Section 10 Electric Switchboards: 0 Through 600 Volts

Section 10 Electric Switchboards: 0 Through 600 Volts Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,

More information

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions Printing 3 March 2008 CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions This instruction is intended for CP2 cable pedestal installations and replacements. The following tools will be

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

42U/45U 28" Wide Rack Installation & Service Guide

42U/45U 28 Wide Rack Installation & Service Guide 42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

0095.05 June 30. 2011 July 18, 2014 1 of 7

0095.05 June 30. 2011 July 18, 2014 1 of 7 Standard Number: Superseding: Effective Date: Page: 0095.05 June 30. 2011 July 18, 2014 1 of 7 Pole Attachments, Automated Meter Reading and Cellular Phone Antennas 1. Scope 2. Application This standard

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

AMPSEAL* Automotive Plug Connector and Header Assembly

AMPSEAL* Automotive Plug Connector and Header Assembly AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

MGB Chrome Bumper Conversion

MGB Chrome Bumper Conversion MGB Chrome Bumper Conversion Installation Instructions For 1974 1/2-1980 MGB This kit requires cutting, welding, and painting. Professional installation recommended. Note: Every MGB body is slightly different

More information

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED

More information

Guidelines for Earthquake Bracing Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the

More information

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3

More information

MOBILE HOME SERVICE REQUIREMENTS GAS

MOBILE HOME SERVICE REQUIREMENTS GAS ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS

More information

PS6500 Storage Arrays Rack Mount Instructions

PS6500 Storage Arrays Rack Mount Instructions PS6500 Storage Arrays Rack Mount Instructions Part Number: R724M Rev. A01 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP

More information

Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4

Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4 This specification covers the requirements for application of ELCON Drawer Series Connectors: True Hot Plug, Blind Mating Mixed Signal and Power Connectors. These connectors are designed for use in pluggable

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances Page 50 of 100 Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances (Replaces A-190556) THIS CUSTOMER REFERENCE SPECIFICATION (CRS) IS PART OF THE RULES FOR

More information

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8

More information

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors Installation Manual Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors SW602206 Rev B Table of Contents Chapter 1: Safety Warning... 3 Chapter 2: Kit Contents... 4 Included in Kit...

More information

430 Power/Electronics Replacement

430 Power/Electronics Replacement Replacing the main board WARNING Before proceeding, turn off the main power switch and unplug the power cord. Caution Make sure you are properly grounded with an ESD strap before continuing. The main printed

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001

Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001 Express5800/120Ed Rack Mount Kit Installation Procedures PN: 455-01607-001 Proprietary Notice and Liability Disclaimer The information disclosed in this document, including all designs and related materials,

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

Trillium 40 Axis Spring Tensioner Wire Replacement Instructions

Trillium 40 Axis Spring Tensioner Wire Replacement Instructions Trillium 40 Axis Spring Tensioner Wire Replacement Instructions 1 Overview The objective is to replace the broken axis spring tensioner wire. This requires the following tasks: 1. Remove the seismometer

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual 0 P a g e H.264 Color or Day/Night SurroundVideo Installation Manual Inside the box: A. Arecont Vision SurroundVideo camera B. Mounting template C. RJ45 female to female coupler D. Hex key E. Security

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

About the HotWire 7900 10-Slot Standalone Shelf

About the HotWire 7900 10-Slot Standalone Shelf TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed

More information

Co-location Interconnect Power Panel (CIPP) Installation Guide

Co-location Interconnect Power Panel (CIPP) Installation Guide Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...

More information

Assembly Instructions for the InteliTrack 3000 Rail Tracking System

Assembly Instructions for the InteliTrack 3000 Rail Tracking System Assembly Instructions for the InteliTrack 3000 Rail Tracking System InteliTrack is a trademark of Sedona Solar Technology. Sedona Solar Technology 16 April 2013 1 1. Before you begin WARNING Safety equipment

More information

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10) Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

BRAKE DRUM AND ROTOR SERVICE INFORMATION

BRAKE DRUM AND ROTOR SERVICE INFORMATION SERVICE INFORMATION To achieve maximum drum life and optimum performance, proper brake maintenance and brake balance are essential. Consult your truck or trailer manufacturer s maintenance manual for proper

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual GreenWay Solar LED Path and Trail Lighting System Installation and Owner s Manual Important Notes and Warnings This installation and instruction manual provides installation, operation, and maintenance

More information

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range.

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range. ENGLISH ESPAÑOL INSTALLATION MANUAL ELECTRIC RANGE Please read these instructions thoroughly before installing and operating the range. LRE3025ST LRE3085ST LRE3083ST LRE3083SB LRE3083SW LRE3021ST LDE3037ST

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

Gas Meter Clearances and Service Installation Requirements

Gas Meter Clearances and Service Installation Requirements March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction

More information

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water

More information

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering Requirements Clearance Requirements August 2015 A current version

More information

Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V

Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................

More information

AMERBRITE UNDERWATER WHITE LED POOL LAMP

AMERBRITE UNDERWATER WHITE LED POOL LAMP AMERBRITE UNDERWATER WHITE LED POOL LAMP FOR USE ONLY WITH PENTAIR AMERLITE LUMINAIRE INSTALLATION AND USER S GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

Lathe Milling Attachment

Lathe Milling Attachment Lathe Milling Attachment By L C. MASON BY CLEVERLY stacking cold-rolled flat stock together, T-slots and slide for this lathe milling attachment are made without costly machinery. In fact, only two tools,

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

GAERTNER SCIENTIFIC CORPORATION 3650 Jarvis Ave. Skokie, Illinois 60076 U.S.A. tel: 1 847 673-5006 fax: 1 847 673-5009 email@gaertnerscientific.

GAERTNER SCIENTIFIC CORPORATION 3650 Jarvis Ave. Skokie, Illinois 60076 U.S.A. tel: 1 847 673-5006 fax: 1 847 673-5009 email@gaertnerscientific. 7109-C-244E-R1 Field Installation of HeNe Laser in B, C, and D-Type Auto Gain Ellipsometers GAERTNER SCIENTIFIC CORPORATION 3650 Jarvis Ave. Skokie, Illinois 60076 U.S.A. tel: 1 847 673-5006 fax: 1 847

More information

Uninterruptible Power Supply. 500 kva - 750 kva

Uninterruptible Power Supply. 500 kva - 750 kva 9 315 Uninterruptible Power Supply 500 kva - 750 kva T1 and T3 Installation Addendum 164201244-001 Rev. A ------------------------------------------------------------------------ ------------------------------------------------------------------------

More information

2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure

2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure 2100 AD 015 0009 Mirror Elevator Ball Nut Replacement Procedure Derek Guenther 1/28/2015 Rev. Purpose The purpose of this document is to describe the procedure necessary to replace one of the ball nuts

More information

Front axle components, overview

Front axle components, overview just a test. Front axle components, overview 40-1 General Information Load bearing components and parts of the suspension must not be welded or straightened. Vehicles without drive axle must not be moved,

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

INSTALLATION MANUAL. Installation Instructions

INSTALLATION MANUAL. Installation Instructions INSTALLATION MANUAL Power-Pole Signature Series Shallow Water Anchor Installation Instructions CAUTION: Read this instruction manual carefully. Become familiar with the controls and know how to operate

More information

No Phone Line II-48 System

No Phone Line II-48 System Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase

More information

Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual

Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification

More information

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property. INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,

More information

KEYLESS ENTRY UPGRADE SECURITY SYSTEM for 2004 TOYOTA HIGHLANDER

KEYLESS ENTRY UPGRADE SECURITY SYSTEM for 2004 TOYOTA HIGHLANDER KEYLESS ENTRY UPGRADE SECURITY SYSTEM for 2004 TOYOTA HIGHLANDER DEALER SERVICE AND INSTALLATION MANUAL KIT NO. 00016-30915 Contents PARTS LIST... 2 PARTS ILLUSTRATIONS... 2 VEHICLE PREPARATION... 3 INSTALLING

More information

It's large enough to handle most welding job shop projects, yet small enough to make it a worth while home-workshop tool

It's large enough to handle most welding job shop projects, yet small enough to make it a worth while home-workshop tool It's large enough to handle most welding job shop projects, yet small enough to make it a worth while home-workshop tool H Craft Print Project No. 272 ERE'S a metal bender that will enable you to bend

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Models No. 2012NB Description 304mm (12") Automatic Thickness Planer CONCEPTION AND MAIN APPLICATIONS * Compact and light weight (27 Kg./59 lbs) automatic thickness planer for easier

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S January 2009 Issue 6 Valu Guide Brackets The Ultimate in Adjustability and Cost Savings Valu Guide brackets are part of a family

More information

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed

More information

Rebuild Instructions for 70001 and 70010 Transmission

Rebuild Instructions for 70001 and 70010 Transmission Rebuild Instructions for 70001 and 70010 Transmission Brinn, Incorporated 1615 Tech Drive Bay City, MI 48706 Telephone 989.686.8920 Fax 989.686.6520 www.brinninc.com Notice Read all instructions before

More information

HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool. Tool P/N HT-0095

HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool. Tool P/N HT-0095 HT-0095 Mini PV Receptacles 22-32 AWG Crimping Hand Tool Tool P/N HT-0095 FCI MANUAL P/N 415988-001 Issued: Date (03/12/99) Page 1 of 18 HT-0095 Issued: Date (03/12/99) Page 2 of 18 Introduction Table

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information