How Much Voltage Drop Is Acceptable?



Similar documents
STREETLIGHT SYSTEM GROUNDING AND BONDING

Protect your home and family with Advanced Technology from Cutler-Hammer

November Stray Voltage Test Procedure for Electrical Contractors

Electrical Grounding. Appendix C

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

Chapter 9. Bonding and Grounding

Grounding & Bonding Why it is done And How to Install Properly

Voltage Drop (Single-Phase)

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Electrical Design TABLE OF CONTENTS FOREWORD BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law

Arc Fault Circuit Interrupters Frequently Asked Questions

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Short Circuit Current Calculations

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

Construction Electrical Terminology. Electricians

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Title: Grounding and Bonding Rev-01

Douglas J. Reinemann, Ph.D. University of Wisconsin-Madison, Department of Agricultural Engineering Madison, Wisconsin. and

Services. Three Phase Service

ELECTRICAL CIRCUITS. Electrical Circuits

3053 Electrical Safety Training Program Course Outline

Electrical Code Regulation

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

Electrical Infrastructure in Remote Areas. A Review of Potential Threats to Safety and Sustainability

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

Commercial/Industrial Electricity

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Fault Characteristics in Electrical Equipment

SERVICE - GENERAL Residential, Commercial, Industrial

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

Electric Service Guide for Residential Construction

PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS

Voltage Drop. Voltage Drop 1

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Electric Service Guide for Commercial Construction

Determining the Cause of AFCI Tripping Branch/Feeder and Combination Arc Fault Circuit Interrupters Class 760

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

ELECTRICAL INSPECTION BULLETIN (Effective )

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

City of Riverside Building & Safety Division Phone: (951)

Section B: Electricity

County of Riverside Building and Safety Department

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

GROUNDING AND BONDING ELECTRICAL SYSTEMS

The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Electricity for the Entertainment Electrician Ef Technician

Who sets the rules for electrical testing and safety?

2 electrical. electrical PulteGroup, Inc. All Rights Reserved.

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

Line Loss WSDOT Winter 2008 BZA

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

Fundamentals of Power

CHAPTER 2 EXAMPLES AND TABLES

BASIC NEC CODE RULES AND DESIGN PRACTICE

Electrical Resistance Resistance (R)

Please check with your local inspection authority for any additional requirements before installation.

An Electrical Lab Exercise on Voltage Drop

Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Rule Fast Track Analysis for National Life Insurance Co.

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

Engineering Series Ratings: Is It Practical?

Hyperlinks are Inactive

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

CSA Z32 TESTING GUIDELINE AND PROCEDURES

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

GENERAL ELECTRICAL REQUIREMENTS

PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION

Application of Four-Pole Circuit Breakers within Data Centers

ELECTRICAL SAFETY RISK ASSESSMENT

Department of Labor and Industry Electrical Licensing

Electrical Drawings - Table of Contents

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

TABLE OF CONTENT

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO

Motor Protection Voltage Unbalance and Single-Phasing

Electrical Safety Training for the Manufacturing Industry

Top Commercial / Residential Electrical Requirements *

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Introduction to Arc Flash

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

Low Voltage Switchgear

How To Get A Power Line Extension

AFCIs Come of Age. by Douglas Hansen

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Transcription:

How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed 5% for optimum efficiency. This recommendation not only can improve safety but can insure proper equipment operation and power efficiency. Important: Note that this is a recommendation. Local inspectors, or other governing bodies, may use their own judgment on an acceptable level of voltage drop for the electrical system. For example, the Philadelphia Housing Development Corporation (PHDC) requires contractors to calculate the voltage drop prior to installing blown insulation in existing homes. If the voltage drop is 10 % or higher, the contractor must replace/repair the circuit prior to proceeding with the insulation. Why It s Here Prior to instituting this requirement, half a dozen smoldering fires resulted from the blown insulation installations. In the 2,500 homes insulated during a twoyear period after this electrical integrity test was instituted, there were no fires reported. At least 15 other municipalities have followed the PHDC s lead in requiring the load test as part of their winterization programs. Measuring Voltage Drop When using a digital multimeter to calculate voltage drop, all loads for the circuit must be removed for the no-load measurement. Next, find a load that will draw 60% to 80% of the maximum rating of the circuit. In this example we have a 15-amp circuit, so a 1400W load should do the trick. Now take your first reading with no-loads on the circuit at the last device or receptacle. Apply your 1400-watt to the circuit and measure the loaded RMS voltage reading. Voltage drop = (no-load voltage - loaded voltage) % Voltage drop = (Voltage drop/no-loaded voltage) x 100 Total impedance of the circuit can be calculated if you know the current Total resistance = Voltage Drop / Current. (R=E / I) Example: If the voltage drop on a circuit was 3Volts and the load drew 12 amperes then the impedance of both conductors would be 0.25 ohms. (3 volts/12 amp) Remember that voltage drop and impedance of the circuit are based on the load. So if you use an 800-watt hair dryer you are only drawing a little over 6 amperes. The voltage drop on a 120V circuit at 6 amperes would be about half compared with a 12 amperes load. Using a Circuit Analyzer like the IDEAL Industries SureTest Circuit Analyzer can make the job much easier. The SureTest Circuit Analyzer can calculate Voltage Drop and Percent of Voltage drop measurements for 12, 15, and 20 amp loads in a matter of seconds. With its patented technology, it can perform this even if there are loads on the circuit, without tripping a breaker or interrupting the load. VOLTAGE continued on page 64 62 C A P I T A L N O W capitallighting.com

Kraloy has been a pioneer and an industry leader in PVC conduit fittings for over 40 years, steadfast in the commitment to quality and the development of new products. Today, Kraloy manufactures and provides a comprehensive offering of nonmetallic products to the electrical industry. Whether it is PVC Conduit Fittings and Spacers, Nonmetallic Lighting, Nonmetallic Liquidtight Conduit and Fittings, or our Kwikon ENT systems only when you specify Kraloy by name are you guaranteed The Fitting Choice. For more information circle #63 on the reader service card Toll Free: 800-265-1815 www.kraloyfittings.com

VOLTAGE continued from page 62 The only thing to remember is no-load measurements are always more accurate with no-loads attached. Any other measurement would be relative to the present load on the line. Calculated Method of Voltage Drop This calculation is for a singlephase branch circuit only. In this example, the branch circuit is 100 feet of 12-gauge wire at a temperature of 72 degrees Fahrenheit. The Load current is 16 amperes. What is the total Voltage Drop and % Voltage Drop? First, let s look at the wire and wire size. The resistance of 12-gauge wire is 2 ohms per 1,000 feet. Answer: R (Resistance of the wire) is equal to 0.4 ohms. [We find the resistance of wire per 1000 feet in Chapter 9, Table 9 of the NEC codebook. (2ohms/1000) x 200 feet = 0.4ohms] I know, where did the 200 feet come from? Remember you have 2 conductors at 100 feet each, Line and Neutral Voltage Drop = Load Current X Circuit Resistance or Voltage Drop = 16 amperes x 0.4 ohms Voltage Drop = 6.4 volts, Troubleshooting A Standard Circuit Troubleshooting to identify the cause of the high impedance within the electrical system is actually quite simple. First, measure the voltage drop at the furthest receptacle from the panel on the branch circuit under test. If the voltage drop is high, then further investigation is necessary. Test the remaining receptacles in sequence, from next furthest from the panel to the closest to the panel. This will help you identify were and what is causing the problem. If the voltage drop reading changes significantly from one receptacle to the next, then the problem is likely between the two. It is usually located at a termination point, such as a bad splice or loose wire connection, but it might also be a bad receptacle. If the reading steadily decreases as you get closer to the panel with no significant decreases between receptacles then the wire may be undersized for the length of run, or rated load for the circuit. Check at the panel to see if the wire is sized per code, for the circuit. Some homes are wired with 14-gauge wire running in excess of 60 feet or more. Although this may not meet the NEC recommendation of 5% or less voltage drop, it my meet local code requirement and are acceptable runs. % of Voltage Drop = (Voltage Drop/ No-load Voltage) x100 % of Voltage Drop =(6.4 volts/120 volts) x100 % of Voltage Dro p= 5.3% Operating Voltage = 120 volts 6.4 volts Operating Voltage =113.6 VOLTAGE continued on page 66 64 C A P I T A L N O W capitallighting.com

Protect your people from arc flash. Safety is your responsibility, so learn all you can about arc flash. Arc flash can burn, blind, or even kill in an instant. And there is no one, failsafe protection. But there is an excellent defense: knowledge. The more you know about how arc flash occurs, the more you can do to prevent it. Ferraz Shawmut has been heavily involved in arc flash research and testing for many years, amassing a large and valuable base of knowledge that s available to you free at the website below. You ll learn how arc flash safety is the sum of many factors: routine electrical safety analysis, staff training, appropriate circuit protection devices, and the right personal protective equipment (PPE). In fact, the site even includes a PPE calculator to help you determine the appropriate levels of protection for your operation. Don t let your safety go up in a flash. Find out more about arc flash, and the products that can mitigate it, at us.ferrazshawmut.com/arcflash1. us.ferrazshawmut.com/arcflash1 For more information circle #65 on the reader service card Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

VOLTAGE continued from page 64 Ground Issues Maintaining a Low Impedance Ground A good electrical ground is more than following NEC requirements; it must also be a low impedance system. The ground path is the fault path for stray current. If electricity follows the path of least resistance, than the ground circuit must have a lower resistance than an individual to protect them. The rule of thumb for protecting people is to maintain a ground impedance of less than one Ohm. The IEEE recommends that any conductor impedance be less than 0.25 ohms. It is this writer s belief that the impedance of the ground wire or grounding circuit path be equal or less than that. Conditions that can result in higher-than-normal ground impedance include undersized wire and corroded or loose connections. False Grounds The neutral conductor can only be bonded to the ground conductor at the main neutral buss, where a large copper conductor carries all the return and faulted current back to the earth. Sometimes (through error or ignorance), the neutral and ground are connected or unintentionally touch upstream from the service entrance. This is called a false, or bootleg ground. When using common receptacle testers, this condition shows up as normally wired. This is a hazardous wiring condition but until the onset of new technology in branch circuit protection and testing it has gone undetected. AFCI circuit breakers will not function properly if a false ground is detected. Earth Ground The pathway to ground extends beyond the main panel to the earth ground system. The earth ground could be a single ground rod, multiple ground rods, a mat or a grid system. Section 250-56 addresses the system by stating that if the ground electrode is not less than 25 ohms a second electrode should be added at least 6 feet from the first.6 The grounding system can be tested with a three-pole earth resistance tester, or a ground resistance clamp meter. While testing the resistance of the ground electrode with a three pole or four poles tester it is necessary to supplement the ground with a secondary ground to perform the test. The resistance of the ground electrode is heavily dependant on the soil resistivity. Soil resistivity is not just dependent on the earth or soil. Moisture and environment changes like temperature have an effect on the resistance of the ground system. To ensure a low impedance grounding system, include the ground electrode, or earth ground as part of your standard testing procedures in your facility. F 66 C A P I T A L N O W capitallighting.com

For more information circle #67 on the reader service card