PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS
|
|
|
- Carmel Lee
- 10 years ago
- Views:
Transcription
1 PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS Monograph by: John Grizzy Grzywacz, Professor OSHA National Training Institute Arlington Heights, Illinois Contributing: Michael Kovacic, President TMK and Associates Chardon, Ohio Rev: 3/05 Portable generators used on construction sites have been much misunderstood, at least with respect to the regulatory requirements. There are three regulatory references to portable generators used in 29 CFR 1926, OSHA's Construction Standards. The first deals with the Grounding Electrode (ground rod or earthing electrode). The second reference lists the criteria for GFCI (Ground Fault Circuit Interrupter) exemption and the third addresses the Neutral Conductor Bonding requirement. These requirements are three distinctly separate issues and should not be confused or combined. This monograph addresses and explains each. Where adopted by OSHA, the National Electrical Code (NEC ) reference is also listed. The NEC should be referenced directly for additional clarification. I. Generator Grounding Electrode Exemption (system grounding) 29 CFR (f)(3) Portable and vehicle-mounted generators (i) Portable Generators. Under the following conditions, the frame of a portable generator need not be grounded and may serve as the grounding electrode (NEC Article Edition). This reference uses the term grounding electrode, which is code language for a system ground or the intentional connection of an electrical system to the earth or our surroundings. In other words, a ground rod is not required and, in fact, may create a hazard. The conditions referenced in (f)(3)(i) are: A) The generator supplies only equipment mounted on the generator and/or cord and plug connected equipment (i.e. saws, drills, lights, etc.) through the receptacles mounted on the generator, AND B) The grounding pin(s) of the generator-mounted receptacles are connected to the generator frame and the equipment grounding conductors of the portable equipment plugged into the generator are continuous to the generator frame. (See Figure 1) 1
2 Generator Figure 1 Drill case electrically connected to generator frame via equipment grounding conductor The principle function of the system ground, or grounding electrode (ground rod), is lightning protection for equipment (see NEC Article 250.4(A)(1) Electrical System Grounding). The likelihood of lightning striking a portable generator supplying some hand tools on a construction site is unlikely, to say the least. So, aside from the unlikelihood of a lightning strike, why eliminate the ground rod? Because the ground rod potentially introduces an electrocution hazard! Depending upon the internal wiring of the generator winding to the frame (see Figure 2), this hazard is introduced by creating an improved path for current to return to its source in the event of short circuits or insulation failure in equipment. So, just treat the generator frame as the ground rod and leave it at that, which this regulation permits. Generator Electrical fault to case Earth/Ground Figure 2 From a historical perspective, the grounding electrode (which is also a system ground) is required for other reasons and was the earliest grounding requirement in the National Electrical Code, becoming mandatory in the 1913 edition. The main purpose of grounding (earthing) the system at the neutral of 2
3 the transformer secondary was to prevent high (primary) voltages from being applied to premises wiring (homes) due to a breakdown of insulation between the transformer primary winding and secondary winding. A primary-to-secondary short would apply thousands of volts to the premises, whereby causing an insulation failure in the wiring and a subsequent fire. The requirement was precipitated by the insurance companies and their concern about fire loss. This system ground is different than the equipment grounding requirements which did not appear in the NEC until 1947, and which are for people protection. More specifically, the purpose of the equipment grounding conductor (code language) is to prevent electrocution in the event of a fault (short circuit) in the equipment that energizes the frame or enclosure of that equipment. The grounding requirements in the OSHA regulations are found in (f) and (f). More specifically, (f)(1), (2), (3) and (7) as well as (f)(1), (2), (3), (4), (5), (10) and (11) all address system grounding. The remaining references, (f)(4), (5) and (6), as well as (f)(6), (7), (8) and (9) all speak to equipment grounding requirements for the prevention of electrocution. In summary, the installation of grounding electrodes (ground rods) on portable generators is discouraged because they introduce a potential electrocution hazard, it serves no other purpose and the codes do not require it. II. Generator GFCI Exemption The second OSHA regulatory reference on portable generators is the GFCI exemption. 29 CFR (b)(1)(ii) reads, "Receptacles on a two-wire, single-phase portable or vehicle mounted generator rated not more than 5kW, where the circuit conductors on the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters. This same exemption was formerly in NEC Article 305-6(a) Exception, but was removed in the 2002 NEC as well as the 2004 NFPA 70E. This means that under these conditions, you do not need the normally required GFCI's on a generator. There are three conditions or criteria listed in the regulation and the generator must meet all three conditions in order to qualify for GFCI exemption. The criteria are simply these: 1. The generator must be two-wire, single phase. Reference to two wires does not include grounding or equipment grounding conductors. Only the conductors or wires which are normally current-carrying circuit conductors are to be considered. This restriction eliminates three-wire generators which have a neutral conductor. The neutral conductor is the center tap of the output winding, which also allows a reference point for dual voltages such as 120v/240v. In a two-wire supply there can only be one voltage derived. Therefore, a 120v/240v generator must be a three-wire generator and cannot meet these criteria. Also, 3Ø (three phase) generators, which are typically fourwire, cannot meet this exemption. Incidentally, a three-wire, or dual voltage (120v/240v) generator must have the neutral wire connected to the frame. This will be covered in more detail in the next section. Additionally, a two-wire system/generator (see Figure 1) has no neutral wire; both wires are normally current carrying. A true neutral would be a center-taped wire on a transformer (such as a 120v/240v single-phase, three-wire system), which carries the unbalanced current in a dual-voltage system. 2. The generator must be not over 5kW (kilo-watts/thousand watts). The size of the generator can be obtained from the manufacturer s nameplate on the generator, which includes the electrical specifications. Reference should be made to 29 CFR (g) "Marking. Electrical equipment shall not be used unless the manufacturer's name, trademark, or other descriptive marking by which the 3
4 organization responsible for the product may be identified is placed on the equipment and unless other markings are provided giving voltage, current, wattage, or other ratings as necessary. The markings shall be of sufficient durability to withstand the environment involved." (NEC Article Edition). The purpose of this requirement is to minimize capacitive coupling or capacitive reactance effects where alternating current at 60 Hertz could pass between the case of a generator and the winding, even with no direct electrical connection between the winding and the case. This effect could result in a path for current to flow back to its source, causing an electrocution in the event of a fault or in the equipment or damaged equipment cord plugged into the generator. This electrical effect becomes possible with windings of larger physical magnitude, as is the case when the generator is over 5kW (see Figure 3). The bottom line is that if the generator is over 5kW, then it cannot meet the exemption requirements and must be GFCI protected. Generator Over 5kW Electrical fault to case Generator sitting on ground No ground rod or electrical connection from winding to frame/case of generator Earth/Ground Figure 3 3. The circuit wires must not be connected to the generator frame, case, or other grounded surfaces. The two wires must be insulated or isolated and not electrically connected to the frame or other grounded surfaces. This refers only to the two conductors which are normally current-carrying. This does not refer to the equipment grounding conductor (See Figure 4). Bonded to frame Not isolated Conductors insulated/isolated from generator frame meets criteria Figure 4 4
5 Since these wires or conductors are internal to the generator, the only way to effectively determine if they are, in fact, electrically isolated is to measure their continuity to the frame using an electrical continuity tester, or ohmmeter. These types of tests are always made with the generator off - never to a live or energized circuit. The continuity test can be made from either blade of the receptacle (not the ground pin) to the case/frame of the generator. Be sure the test lead of the tester is penetrating the paint, rust, and all other contaminants on the generator case when making the measurement. If the test indicates continuity, then the wires are connected to the case and do not meet this third criteria for isolation, therefore the generator must be GFCI protected. It does not matter which receptacle blade is selected to make this measurement. The only difference is that one blade will be connected to the case through the generator windings, while the other blade will be connected directly to the case. Since the resistance of generator windings is typically below 10 ohms, both blades will indicate continuity if they are not isolated, whereby requiring GFCI protection. This requirement eliminates a return current path, preventing an otherwise lethal condition in the event of an equipment short circuit or insulation failure. The end result is that if the generator meets all three conditions or criteria, then even if one of the normal current-carrying conductors in a portable tool faults and energizes the case of the tool, no current path back to the source (generator winding) will exist to present an electrocution hazard to a person holding the tool. Furthermore, if the generator meets these three conditions, the generator does not need a GFCI. Remember, the generator must meet all three conditions to permit this GFCI exemption. As previously mentioned, this GFCI exemption was removed for the 2002 Edition of the NEC. As a result, the local electrical inspectors, as the Authorities Having Jurisdiction or AHJ s as they are referred to, will no longer accept this exemption and will require the use of GFCI s on portable generators used for temporary wiring such as on construction sites per Article 590 of the 2005 NEC. Although the exemption still appears in the OSHA construction regulations, this author suspects that it will eventually be totally eliminated and the required use of GFCI s will prevail in all cases. III. Neutral Conductor Bonding Requirements for Generators. The third and final issue for discussion can be found in 29 CFR (f)(3)(iii) "Neutral conductor bonding. A neutral conductor shall be bonded to the generator frame if the generator is a component of a separately derived system." This reference can be found in 1996 NEC Article 250-6(c) and in the 1999 Edition. Although slightly modified for the 2002 Edition the reference is still located in NEC Article (C). Consider this question. Is a generator on a construction site supplying only cord-and-plug-connected equipment (saws, drills, lights, etc.) through the receptacles mounted on the generator considered a separately derived system? The answer is a resounding Yes! It is always a separately derived system under those conditions and consequently the neutral must be bonded (electrically connected) to the frame of the generator. For a more detailed explanation of why it s a separately derived system, we must examine the NEC in more detail. NEC Article 100 definitions of Premises Wiring (System) and Separately Derived Systems clarify this. Premises Wiring Systems include temporary lighting and power circuits extending from the source to the outlet. This would encompass our generator supplying cord-and-plug lights and tools on a construction site. A Separately Derived System is a generator which does not have any electrical connection to any other system. An emergency backup generator with its neutral permanently connected at the panelboard to the neutral supplied from a local utility company, with only the hot or ungrounded conductors being switched in for emergency backup in case of power failure, would not be considered a separately derived system. Further clarification on when a generator is not a separately derived system can be found in the 1996 NEC, Article 250-5(d), FPN No. 1, or in the 2005 NEC, Article (D), FPN No.1. 5
6 Perhaps the most definitive information comes from the CMP (Code Making Panel) recommendations and amendments to the 1974 NEC. Prior to 1974, this generator issue was addressed in both NEC Article (a) and Article (Article 445 covers generators) Grounding. Code Making Panel #22 (as well as CMPs #5 and #11) proposed that the frames of generators be bonded to the neutral. The proposed amendments, including justification to the CMP, were not documented very thoroughly in those days. However, extensive research revealed this supporting comment which was the proposal to the 1974 CMP, "The required bonding (neutral conductor to frame) for portable or cord and cable connected wiring systems supplied from portable generators will provide an assured fault current path to actuate the circuit or system overcurrent device for user protection in the event of multiple faults and insulation failure. Without this bonding (electrical connection of the neutral to the frame of the generator) a multiple fault condition would expose persons to a 240- volt potential. (See Figure 5) This path will satisfy the intent of NEC Article & 250.4(A)(5), 2005 Edition (previous editions see Article ). 120/240v Generator X X Fault to case X X Fault to case 240-Volt outlet 120-Volt outlet Two faults create a 240v exposure and a current path, resulting in electrocution Earth/Ground Figure 5 In summary, remember, the Generator Grounding Electrode (system grounding) Exemption (I), the Generator GFCI Exemption (II) and the Neutral Conductor Bonding Requirements for Generators (III) are all mutually exclusive and have nothing whatsoever to do with each other. Each issue needs to be examined one at a time for its applicability with respect to the code requirements, or more simply stated, examine each generator for all three issues to ensure it meets the codes. 6
7 John Grizzy Grzywacz served as the OSHA Region II Training Director from 1988 to 1995 based in the New York City Regional OSHA Office. In January 1995 John accepted a faculty position at the OSHA National Training Institute and gave up Manhattan residency for the quiet suburbs of Des Plaines outside of Chicago. John trains OSHA compliance officers, State Plan Safety and Health Investigators, corporate safety and health directors, and other federal agencies in numerous areas including OSHA policy, safety and health regulations, safety and health management systems, legal aspects of investigations, and enforcement strategies. Currently John is called upon to investigate nearly a dozen electrical fatalities and accidents yearly and is consulted with on many more investigations nationwide. John received his teaching credentials from the State University of New York and is licensed by the New York State Department of education. John is also a certified electrical inspector. Prior to his arrival at OSHA John had been both an educator and administrator for various public and private schools for nearly a decade, and currently has over 25,000 hours of platform experience. John held the position of electronic department chairman and Deputy Director of Education at a New York City proprietary school for four years. In addition to being a nationally recognized seminar leader and educator, John has taught at Purdue University, University of Southern California at San Diego, Texas A & M University, and the New York State University System, just to name a few. John has found time to write and produce training videos and has works published in video, print and film. 7
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Title: Grounding and Bonding Rev-01
Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
Electrical Hazards. Power Tools. Extension Cords
Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance
WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new
Reverse-feed applications for circuit breakers
Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................
4.5 Transformer Connections
ELECTRIC POWER SYSTEMS IN COMMERCIAL BUILDINGS IEEE Std 241-1990 5) Flat Billing Ñ Certain applications involve service to the load of a Þxed characteristic. For such loads, the supplying utility may offer
How Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC
Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides
Services. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
November 2014. Stray Voltage Test Procedure for Electrical Contractors
Stray Voltage Test Procedure for Electrical Contractors 1 LIMITATION OF LIABILITY AND DISCLAIMER Any person who uses, relies on, or otherwise deals with this document and the information herein, does so
The Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure
This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. 10 The Entrance Objectives Information in this chapter will enable you to: List the components
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
16 Operation of portable generators Operation of portable generators By Mark Coles This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
Electric Service Guide for Commercial Construction
Electric Service Guide for Commercial Construction Contents Contacting KCP&L... 2 Voltages... 2 Temporary Service... 2 Customer-Provided Temporary Service... 2 KCP&L-Provided Temporary Service.... 2 Current
Are you aware. Outline
Electrical Safety of Medical Equipment Hasan Al-Nashash School of Engineering American University of Sharjah (AUS) 1 Are you aware Electrocutions are the 5th leading cause of accidental death in the U.S.
SAFETY AND HEALTH STANDARD KUC ELECTRICAL STANDARD Effective Date: 04/4/12 Standard: 15.1 Document Number: KUCSH0065 Rev: 06
15.1 INTRODUCTION 15.1.1 This standard is intended to provide guidelines regarding safe electrical work procedures, electrical competency requirements, access to electrical "controlled areas", grounding,
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Exploring the Necessity of the Hot Hipot Test
Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
Best Methods for Safe Hipot Testing
Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
CSA Z32 TESTING GUIDELINE AND PROCEDURES
PO Box 20020 Red Deer, AB T4N 6X5 Phone: 403.986.2939 Web: www.908eng.com July 9, 2012 CSA Z32 TESTING GUIDELINE AND PROCEDURES This document is intended to outline the various tests, procedures and preparations
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
Siemens STEP 2000 Course Basics of Electrical Products
Siemens STEP 2000 Course Basics of Electrical Products It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Commercial/Industrial Electricity
1 ELC 210 Commercial/Industrial Electricity Course Package Presented and Approved July 31, 2008 2 Contact person(s) DAVE WHITE Date of proposal to JULY 31, 2008 Curriculum Committee NEW COURSE PACKAGE
ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED
Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
NEC 2014 Code Changes
NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables
Dielectric Withstand Testing in a Production Environment
Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide
IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide *619751* P/N 619751 - Rev C IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
San Diego Area Chapter International Code Council
San Diego Area Chapter International Code Council Code Reference Subject Page 90.7 110.14 110.26 11 0.26(E) (2) Approval of Electrical Equipment Torque Requirements Electrical Equipment Rooms Outdoor dedicated
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
Photovoltaic System Grounding
Photovoltaic System Grounding Prepared by: John C. Wiles, Jr. Southwest Technology Development Institute College of Engineering New Mexico State University October 2012 Solar America Board for Codes and
Construction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
MODULE 1 INTRODUCTION TO ELECTRICAL SAFETY
INTRODUCTION TO ELECTRICAL SAFETY At the end of this module, you will be able to Recognize key statistics relating to electrical injuries. Recognize OSHA regulations and other standards relating to electrical
Electrocution Hazards
Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents
Charging what can be more simple? SAE J1772
Charging what can be more simple? SAE J1772 Charging What Can Be More Simple? We charge our electronic devices everyday Laptops Cell phones PDAs Bluetooth devices Power tools MP3 players Toys Other Why
STREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
City of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Exhibit C Design Review Guidelines
Exhibit C Design Review Guidelines January 2015 Included in this Exhibit for Design Guidelines includes: Electrical Design Guidelines Electrical and Mechanical /Plumbing Construction Requirements Temporary
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
National Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
MANCON Human Resources Workers Compensation 757-457-9312 or 888-892-0787 ext 312 or [email protected]
POLICIES AND PROCEDURES SAFETY MANUAL SAFETY TRAINING Employee Safety Training Maintenance SAFETY TRAINING FOR MANCON EMPLOYEES IN MAINTENANCE/MACHINERY POSITIONS MANCON employees perform a variety of
Arc Fault Circuit Interrupters Frequently Asked Questions
Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Buck - Boost Transformers
Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single
Department of Labor and Industry Electrical Licensing
Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants
Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering
Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.
CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn