Line Insulation. Section APPLICATION OF RULE

Similar documents
Pole Guying More Complicated Than Meets the Eye. NRECA TechAdvantage 2014 Presented by Jason Settle, P.E.

Hendrix Spacer Cable

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Transmission Silicone Insulators Line Post 69 kv to 161 kv

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

WIRE AND CABLE ENGINEERING GUIDE

Please check with your local inspection authority for any additional requirements before installation.

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above

TECHNICAL MEMORANDUM

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

INTERNATIONAL STANDARD

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

Insulation Resistance Testing of Low Voltage Cables in the Field

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

Earth Fault Detection Basics in Theory

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit Ann Arbor Mt. Clemens Port Huron

HV glass suspension insulator U70BS and U70BL type Ball and socket type Standard profile

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

Analysis of Pollution Impact on Potential Distribution of Suspension Type Discs Insulators in Overhead Lines

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Unified requirements for systems with voltages above 1 kv up to 15 kv

AMP CO Plus Insert for Cat. 6 A Applications

Power transformers. Special transformers Railway

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

MANUFACTURER S CERTIFICATE OF COMPLIANCE

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

January 23, Minimum Design Standards Task Force

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: , , ,

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Hyperlinks are Inactive

Medium voltage insulator

Harmonics in your electrical system

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

The following table shows approximate percentage wise the

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Low Voltage Products. Switches Automatic Transfer Switches

HIGH VOLTAGE SHORE CONNECTION

The electrical energy produced at the gen

WIRE AND CABLE ENGINEERING GUIDE

PRESTRESSED CONCRETE POLES The Solid Alternative to Wood

Current Transformers

Trimming Trees Near Electric Lines. Understanding Niagara Mohawk s Role and Responsibilities

Litigation Services & Information

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

Code of Practice Electricity transmission and distribution asset management. February 2009

Services. Three Phase Service

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

Overhead lines in Ireland

NESC Update. James R. Tomaseski International Brotherhood of Electrical Workers

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

BASIC NEC CODE RULES AND DESIGN PRACTICE

Tape Wound, Split Core and Ebony Current Transformers

IRRIGATION PUMPING Table of Contents - Section 900

TABLE OF CONTENT

Radial Distribution Test Feeders

INTERNATIONAL STANDARD

Evaluating Water-Damaged Electrical Equipment

Measurement devices Accessories for analogue and digital instruments

When power interruptions happen.

CSA Z32 TESTING GUIDELINE AND PROCEDURES

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Exploring the Necessity of the Hot Hipot Test

Transformers. Special transformers Reactors products

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

FAQs-Main switchboard design criteria

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Industrial Control Power Transformers

Guide for Electric Service and Meter Installations

Low Voltage Transformers Sealed, General Purpose, Dry Type

Box and Conduit Fill Calculations

Grounding & Bonding Why it is done And How to Install Properly

This section applies to the design and installation of transformers.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Adaption of Cable Accessories for Onshore and Offshore Substation

CT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK

Gates, Circuits, and Boolean Algebra

INTRODUCTION TO BEAMS

UGVCL/SP/591/11KV HT AB CABLE

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

SECTION DRY-TYPE TRANSFORMERS

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

Transformer Bushings for GIS

Transcription:

Section 27 Line Insulation 270. APPLICATION OF RULE Line insulation in Sec. 27 applies to insulators for open conductor supply lines only, not communication lines or secondary duplex, triplex, or quadruplex (230C3) cables. Note 1 references Rule 243C6 (this should be Rule 243C5). Rule 243C5 states that the strength requirements in Sec. 27 apply to all grades of construction. There are not separate Grade B and Grade C strength factors for insulators. Note 2 references Rule 242E for insulation requirements of neutral conductors. Rule 242E states that supply neutrals, which are effectively grounded and not located above supply conductors of more than 750 V to ground, do not need to meet any insulation requirements. Even though effectively grounded neutrals do not need to meet any insulation requirements, it is common to see neutral conductors attached to insulators for support and termination purposes. Section 27 does not apply to secondary duplex, triplex, and quadruplex (230C3) cables, however, it is common to see the messengers of these cables attached to insulators for support and termination purposes. The Code rules related to the application of line insulation are outlined in Fig. 270-1. 271. MATERIAL AND MARKING Supply circuit insulators are required to be wet-process porcelain or other materials. Examples of insulators made of porcelain and other materials are shown in Fig. 271-1. 319

320 OVERHEAD LINES Rule 272 Fig. 270-1. Application of line insulation (Rule 270). The manufacturers must mark insulators for use at or above 2.3 kv with the manufacturer name or trademark and an identification (e.g., a catalog number) that will permit determination of the electrical and mechanical properties. The Code rules for marking insulators are outlined in Fig. 271-2. 272. RATIO OF FLASHOVER TO PUNCTURE VOLTAGE Rule 272 requires insulators to meet standards for a flashover to puncture voltage ratio. A list of applicable standards is provided. When a standard does not exist for the flashover to puncture voltage ratio, Rule 272 specifies a not-to-exceed value of 75 percent with an exception that permits not more than 80 percent in areas of high atmospheric contamination. The flashover to puncture voltage ratio is used by manufacturers but it is not always published in insulator catalog data. Insulator catalog data typically does include the low-frequency dry-flashover value.

Rule 273 LINE INSULATION 321 Fig. 271-1. Examples of insulators made of porcelain or other materials (Rule 271). 273. INSULATION LEVEL Rule 273 specifies insulator dry flashover voltages in NESC Table 273-1. The dry flashover tests must be done in accordance with ANSI Standard C29.1. Using dry flashover voltage ratings lower than the values in NESC Table 273-1 requires a qualified engineering study. Values higher than shown in NESC Table 273-1 must be used for areas with severe lightning, high atmospheric contamination (e.g., salt water fog, industrial plant pollution, etc.) or other unfavorable circumstances. The low-frequency dry flashover rating is the most common value referenced when comparing insulator specifications. Additional ratings are commonly published in insulator catalog sheets and in insulator specifications. Typical insulator ratings are listed in Fig. 273-1. In addition to electrical ratings, the NESC specifies mechanical ratings for insulators in Rule 277.

322 OVERHEAD LINES Rule 274 Fig. 271-2. Marking of insulators (Rule 271). Fig. 273-1. Insulation level requirements (Rule 273). 274. FACTORY TESTS Insulator factory tests per ANSI Standards are required for insulators at or above 2.3 kv. 275. SPECIAL INSULATOR APPLICATIONS Special consideration must be given to constant-current circuits (e.g., series street lighting). The voltage rating of the insulator must be based on the full load rated voltage of the supply transformer, not just the operating voltage of the circuit.

Rule 277 LINE INSULATION 323 Single-phase lines fed from three-phase lines are required to use insulators based on the three-phase line phase-to-phase voltages. See Fig. 275-1. 276. NUMBER 276 NOT USED IN THIS EDITION 277. MECHANICAL STRENGTH OF INSULATORS Rule 277 specifies the mechanical strength requirements for insulators. This is done in the form of strength factors that are applied to the insulators. Overload factors for wire tension, wire vertical (weight) loads, and wire transverse (wind) loads are not applicable. Rule 277 requires insulators to withstand the loads in Rules 250, 251, and 252. The overload factors in Rule 253 are not required and the extreme wind loads of Rule 250C are not required. Said another way, the overload factor for the loads on insulators is 1.0. The strength factor percentages provided in Rule 277 do not distinguish between Grade B and Grade C construction. After Rule 277 states that the extreme wind loads in Rule 250C are not applicable, the rule continues on requiring proper allowance for Rule 250C loads. Rule 250C only applies to structures and supported facilities more than 60 ft high. Fig. 275-1. Insulators of singe-phase circuits connected to three-phase circuits (Rule 275).

324 OVERHEAD LINES Rule 278 The strength factor percentages listed in Rule 277 are of the insulator s rated ultimate strength. The method in which rated ultimate strength is calculated for various types of insulators and various insulator materials is discussed in Note 1 and Note 2. Notes 1 and 2 reference ANSI and IEEE Standards for the test method used to determine rated ultimate strength. The rated ultimate strength of an insulator may not be very clear on an insulator catalog sheet. Catalog sheets may use terms like routine test load, maximum design load, average failing load, average breaking load, or maximum working load. The insulator manufacturer should be consulted or the ANSI and IEEE Standards should be reviewed to verify that the percentages provided in Rule 277 are being applied to the insulator s rated ultimate strength as specified in Notes 1 and 2 of Rule 277. Examples of cantilever, compression, and tension loads on insulators are shown in Fig. 277-1. 278. AERIAL CABLE SYSTEMS Aerial cable systems primarily consist of tree wire conductors described in Rule 230D. The insulators supporting aerial cables must meet Rule 273. The covered conductors of aerial cable systems are considered bare conductors for electrical insulation requirements. The insulators and spacers of an aerial cable system must meet Rule 277. Rule 278B2 requires that the insulating spaces used in aerial cable systems withstand the loads specified in Sec. 25. Section 25 includes Rule 253, which contains overload factors. Rule 277 does not require overload factors as Rule 277 specifies the loads in Rules 250, 251, and 252, not Rule 253. 279. GUY AND SPAN INSULATORS 279A. Insulators. The Code rules for the material properties of guy insulators and the electrical and mechanical strength of guy insulators are outlined in Fig. 279-1. The requirements for mechanical strength of a guy insulator hinge on the word required strength of the guy. Guy insulators do not require the application of strength factors like line insulators in Rule 277. Guy insulators indirectly have overload factors applied to them via the overload factors that are applied to wire tension and wind loading. See Fig. 279-2. Guys may be ungrounded and insulated per Rule 279A2a or grounded per Rule 215C2. The grounding methods for guys are provided in Rule 092C2. See Fig. 279-3. When guy insulators are installed, they must meet the physical location criteria provided in Rule 279A2b. Complex structures with multiple guyed circuits require careful application of Rule 279A2b. The Code rules related to installation of guy insulators are outlined in Fig. 279-4. If a guy insulator is used exclusively for the elimination of corrosion of an anchor attached to a grounded guy on an effectively grounded system, then it is

Rule 279A LINE INSULATION 325 Fig. 277-1. Examples of cantilever, compression, and tension loads on insulators (Rule 277).

326 OVERHEAD LINES Rule 279A Fig. 279-1. Properties of guy insulators (Rule 279A1). not classified as a guy insulator. Therefore, the electrical requirements (i.e., the dry flashover and wet flashover ratings) do not apply. The guy in this case is assumed to be grounded per Rule 215C2 using the grounding methods in Rule 092C2. The corrosion protection insulator must not reduce the mechanical strength of the guy. The Code is not specific in this case whether this is the required strength of the guy as stated in Rule 279A1c or the strength of the guy wire. An example of a guy insulator used exclusively for corrosion protection is shown in Fig. 279-5.

Rule 279B LINE INSULATION 327 Fig. 279-2. Example of the required strength of a guy insulator (Rule 279A1). Fig. 279-3. Use of guy insulators (Rule 279A2a). The clearance requirements between a guy insulator and energized conductors are provided in NESC Table 235-6. See Rule 235E for a discussion. 279B. Span-Wire Insulators. The requirements of span-wire insulators are similar to guy insulators. Rule 274 is referenced for insulator testing. The rated ultimate strength of a span wire insulator is based on the required strength of the span wire in which it is located.

Fig. 279-4. Installation of guy insulators (Rule 279A2b). Fig. 279-5. Example of a guy insulator for corrosion protection (Rule 279A3). SECTION NUMBER 28 NOT USED IN THIS EDITION SECTION NUMBER 29 NOT USED IN THIS EDITION