SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
|
|
|
- James Willis
- 9 years ago
- Views:
Transcription
1 SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the symmetrical components of the original phasors. The method of symmetrical components is a general one, applicable to any polyphase system. Usually, we apply symmetrical component method to symmetrical and unbalanced 3-ϕ circuits. The term 'symmetrical' in power systems is used for a poly phase N/W if and only if all the phases are having same impedance (i.e., in magnitude as well as phase angle). A N/W is said to be balanced if and only if all the phases containing voltages / currents in same magnitude but should be displaced by same phase angle. According to Fortescue's theorem, three unbalanced phasors of a three phase system can be resolved into three balanced systems of phasors. The balanced sets of components are : 1. Positive sequence components consisting of three phasors equal in magnitude, displaced from each other by 120 in phase, and having the same phase sequence as the original phasors. 2. Negative sequence components consisting of three phasors equal in magnitude, displaced from each other by 120 in phase, and having the phase sequence opposite to that of the original phasors 3. Zero sequence components consisting of three phasors equal in magnitude and with zero phase displacement from each other. * Three sets of balanced phasors which are the symmetrical components of three unbalanced phasors. Shown in below figures. Page : 1
2 Positive Sequence Components Negative Sequence Components Zero Sequence Components Fig Components Zero Sequence Components Considering the positive sequence components, the vector lags behind by 120 electrical and the vector leads the vector by 120 electrical since these three are also equal in magnitude * For the positive sequence components, Stator and rotor field directions are same. Considering the negative sequence components, the vector leads by 120 electrical, and the vector lags behind by 120 electrical. * Since these three are also equal in magnitude Page : 2
3 * For the negative sequence components, Stator and rotor field directions are reverse. For zero sequence components, we have Since the three un balanced vectors and can be resolved into three sets of balanced vectors, the vector is equal to the sum of the positive sequence component of phase a, the negative sequence component of phase a, and zero sequence component of phase a.and zero sequence component of phase a. * Since all power systems considered to be linear, so superposition principle holds good. Similarly 3 unbalanced vectors resolved into a total of 9 vectors, i.e, and and. Out of these, only 3 are unknown. So, only three components are linearly independent. (i.e. from the knowledge of the three vectors we can find out all the remaining vectors) OPERATORS: An operator 'a' is introduced, which when operates upon a phasor rotates it by +120 without changing the magnitude of the phasor upon which it operates. It is represented as * Assuming phases a as the reference, the relationship between the symmetrical components of phases 'b' and 'c' in terms of symmetrical component of phase 'a' can be written. (phase sequence is abc) Page : 3
4 or in matrix form = = [T] Where, T = symmetrical transformation matrix V a0 = (1/3) [V a + V b + V c ] V a1 = (1/3) [V a +a V b +a 2 V c ] V a2 = (1/3) [V a +a 2 V b +a V c ] or in matrix form = (1/3) = [T -1 ] where, T -1 = inverse symmetrical transformation matrix Current instead of Voltage: I a = I a1 + I a2 + I a0 I b = a 2 +a I a2 + I a0 I c = a I a1 + a 2 I a2 + I a0 or in matrix form = (1/3) = [T] Where, T symmetrical transformation matrix I a0 = (1/3) [ I a + I b + I c ] I a1 = (1/3) [ I a +a I b +a 2 I c ] Ia2 = (1/3) [ I a +a 2 I b +a I c ] Page : 4
5 or in matrix form = (1/3) = [T -1 ] where, T -1 = inverse symmetrical transformation matrix Average 3 phase power in Terms of Symmetrical Components: P = 3 [ V a0 I a0 + V a1 I a1 + V a2 I a2 ] Impedance: = [Z abc ] [T] = [Z abc ] [T] = [T -1 ] [Z abc ] [T] = [T -1 ] [Z abc ] [T] (since Z 012 = / ) [Z abc ] = & are self & mutual impedances [Z 012 ] = Sequence Impedance and Networks: The impedance of a circuit when positive sequence currents alone are flowing is called the impedance to positive sequence current. Similarly, when only negative sequence currents are present, the impedance is called the impedance to negative sequence current. When only zero sequence currents are present, the impedance is called the impedance to zero sequence current. Let Z a, Z b, Z c, & Z n are three phase impedances and neutral impedance Z a0 = 1/3 (Z a + Z b + Z c ) zero sequence Z a1 = 1/3 (Z a +az b +a 2 Z c ) positive sequence Z a2 = 1/3 (Z a +a 2 Z b +az c ) negative sequence Page : 5
6 3.2 Sequence N/Ws of a synchronous Generator: Positive sequence Network: The positive sequence network of a synchronous generator is a balanced and symmetrical three phase network with positive sequence generated voltages (E a1, E b1, E c1 ) in the three phase, symmetrical three phase star impedance Z, in each phase and positive sequence currents (I a1, I b1, ) flowing in the three phase of shown in the below figure. I c1 I a1 Z E C1 E a1 ~ ~ ~ E b1 + I b1 Z1 Z 1 I C1 Fig. 3.2 The three phase system can be replaced by a single phase network as shown in the below: I a1 + Z 1 E for the Generated voltage. E a1 - ~ V a1 V for the Terminal voltage. Fig. 3.3 The equation of the positive sequence network is V a1 = E a1 I a1. Z 1 Page : 6
7 3.2.2 Negative sequence network: In any general synchronous generator which is designed to generate, balanced voltages the negative sequence generated voltages are always zero. The negative network containing negative sequence impedance Z 2 in each phase and negative sequence currents flowing through these carrying negative sequence voltage drops as shown below figure. I a2 Z 2 N Z 2 Z 2 I c2 I b2 Fig. 3.4 The three phase network can be replaced by a single phase network as shown in the below figure. Z 2 I a2 V a2 Fig. 3.5 The equation for the negative sequence network is V a2 = - I a2.z Zero sequence Network: The equation for the zero sequence network is V a0 = - I a0 Z 0 2 Page : 7
8 Z 0 I a0 V a0 Fig. 3.6 The equivalent circuit for the zero sequence network is different from the positive and negative sequence networks the impedance offered to zero sequence currents depends on grounding of the star point. If the star point is not grounded, then the zero sequence impedance is infinity. If the star point is grounded through some impedance Zn, then the equivalent zero sequence impedance is equal to the sum of the zero sequence phase impedance and is equal to 3Z n. Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. The presence of negative or zero sequence currents in a three phase system introduces asymmetry and is indication of an abnormal condition of the circuit in which these components are found. The vector sum of the positive and negative sequence currents of an unbalanced three phase system is zero. The resultant solely consists of three zero sequence currents i.e., Vector sum of all sequence currents in three phase unbalanced system = + + In a three phase, 4 wire unbalanced system, the magnitude of zero sequence component is one third of the current in the neutral wire. In a three phase unbalanced system, the magnitude of negative sequence component cannot exceed that of the positive sequence component. If the negative sequence component are greater, the phase sequence of the resultant system would be reversed. The current of a single phase load drawn from a three phase system comprises equal positive, negative and zero sequence component Example: The line to ground voltage on the high voltage side of a step up Transformer are 100 kv, 33 kv, 38 kv on phases a, b, & c respectively. The voltage of phase leads That of phase by 100 & lags That of phase by Determine analytically The symmetrical component of voltage,, Page : 8
9 Solution: 3.3 FAULT CALCULATIONS: Faults can be classified as two types: 1. Series faults 2. Shunt faults Shunt faults are characterized by increase in current and decrease in voltage, frequency and power factor. Series faults are characterized by decrease in current and increase in voltage, frequency and power factor. The series faults are classified as 1. One open conductor fault 2. Two open conductors fault The shunt type of fault are classified as: 1. Single line to ground fault 2. Line to Line fault 3. Double line to Ground fault 4. Three phase fault The first three faults are the unsymmetrical faults. The three phase fault is symmetrical faults. Severity & occurrence of Faults: Page : 9
10 power transfer slg II IIg 3- power Faults Time Fig. 3.7 Fault Severity Occurrence 1) 3- (LLL,LLLG) Severe 5% 2) Phase to phase ground (LLG) Severe 10% 3) Phase to phase fault (LL) Less Severe 15% 4) Single line to ground Faults (LG) Very less 70% * 1 cause of short circuit insulation failure. Overvoltage caused by lightning or switching surge. Insulation contamination salt spray, pollution. Mechanical causes overheating, abrasion Faults on T.L. Most common lines are exposed to elements of nature 60 70% lightning stroke over voltage causes insulation to flash over Line to ground short circuit or line to line s.c. High winds topple tower, tree falls on line. Winds an ice loading mechanical failure of insulation. For, salt spray, dirty insulation conduction path insulation failure. S. C. other elements. Cabels (10 15%), C.B. (10 12%) generator, motor, X-mer (10 15%) much less common over loading for extended periods deterioration of insulation Page : 10
11 3.3.2 Voltage of the Neutral: The potential of the neutral when it is grounded through some impedance or is isolated, will be at ground potential unbalanced conditions such as unsymmetrical faults. The potential of the neutral is given as V n =I n Z n where Z n is the neutral grounding impedance and I n is neutral current. Here negative sign is used as the current flow from the ground to the neutral of the system and potential of the neutral is lower than the ground. For a 3- phase system, I n = I a +I b +I c = (I a1 + Ia 2 + Ia 0 ) + ( Ia 1 +aia 2 Ia 0 ) + (a I a1 + a 2 Ia 2 + Ia 0 ) = I a1 (1+a+a 2 ) + Ia 2 (1+a+a 2 ) +3Ia 0 = 3Ia 0 V n = -3I a0 Zn Since the positive sequence and negative sequence components of currents through the neutral are absent, the drops due to these currents are also zero Single Line to Ground Fault: 1. Most frequently occurring fault. 2. Usually assumed the fault on phase a for analysis purpose, phase b and phase are healthy. The boundary conditions are a) V a = 0.(1) b) Ib = 0.(2) c) Ic = 0.(3) Page : 11
12 I a Z ~ - + E a + ~ - E c - - ~ E b + Z I b Z Fig. 3.8 I c The sequence network equations are V a0 = - I a0 Z 0..(4) V a1 =E a -I a1 Z 1 (5) V a2 = I a2 Z 2....(6) The solution of these six equations will give six unknowns V a0, V a1, V a2 and I a0, I a1, and I a2 Since I a1 = (1/3) [I a + a I b + a 2 I c ] I a2 = (1/3) [I a + a 2 I b + a I c ] I a0 = (1/3) [I a + I b + I c ] Substituting the values of I b and I c from equations (2), (3)in above three equations I a1 = I a2 = I a0 = I a /3.(7) Equation (1) can be written in terms of symmetrical components V a = 0 = V a1 + V a2 + V a0 Now substituting the values of V a0, V a1 and V a2 from the sequence network equation, E a - I a1 Z 1 I a2 Z 2 I a0 Z 0 = 0 (8) Since I a1 = I a2 = I a0 Equation (8) becomes Page : 12
13 E a I a1 Z 1 I a1 Z 2 - I a1 Z 0 =0 I a1 = I f = I a = I a1 + I a2 + I a0 ; connected in series. I f = and +ve, ve and zero sequence networks are single Line of Ground fault with Z f : I a1 = ~ Z 1 I a1 V a1 Z 2 I a2 V a2 Z 0 I a0 V a0 Conclusion: Fig The three sequence networks are connected in series. 2. If the neutral of the generator is not grounded, the Zero network is open circuited. Line to Line Fault The line to line fault takes place on phases b and c The boundary conditions are I a = 0. (1) I b + I c = 0. (2) V b = V c...(3) Page : 13
14 a I a E a Z E C C Z Z E b b I b I c Fig The sequence network equations are V a0 = -I a0 Z 0.. (4) V a1 = E a = I a1 Z 1 (5) V a2 = - I a2 Z 2 (6) The solution of these six equations will give six unknowns V a0, V a1, V a2, and I ao, I a1 and I a2 Since I a1 = (1/3) [I a + a I b + a 2 I c ] I a = (1/3) [I a + a 2 I b + a I c ] I a1 = (1/3) [I a + I b + I c ] Substituting the values of I a, I b and I c from equations in above three equations I a1 = (1/3) [0 +a I b - a 2 I b ] = (1/3) [a- a 2 ] I b I a2 = (1/3) [0 +a 2 I b - a I b ] = (1/3) [ a 2 - a] I b I a0 = (1/3) [0 + I b - I b ] I a0 = 0 Which means for a line to line fault the zero sequence component of current is absent and positive sequence component of current is equal in magnitude but opposite in phase to negative sequence component of current, i.e., Page : 14
15 Z 1 I a1 Z 2 I a2 E a V a1 V a2 Fig I a1 = -I a2 (7) Since V b = a 2 V a1 + av a2 + V a0.. (8) V C = av a1 + a 2 V a2 + V a0..(9) Substituting the equations (8) and (9) equations (3) a 2 V a1 + av a2 + V a0 = av a1 + a 2 V a2 V a0 V a1 = V a2 (10) i.e., positive sequence component of voltage equals the negative sequence component of voltage. This also means that the two sequence networks are connected in opposition. Now making use of the sequence network equation and the equation (10) V a1 = V a2. E a - I a1 Z 1 = -I a2 Z 2 = I a1 Z 2 I a1 = I f = I b = - I c = a 2 I a1 + ai a2 + I a0 (I a2 = - I a1, I a0 =0) = = I a1 Conclusion: 1. The connection of sequence currents are connected in parallel. 2. The phase difference between I a1 and I a2 for line to line fault should be 180 (I a1 = I a2 ). Line to Line fault with Z f I a1 = Double Line to Ground Fault: Here sequence networks are connected in parallel. Page : 15
16 Double line to ground fault takes place on phases b and c The boundary conditions are I a = 0.(1) V b = 0.(2) V c = 0.(3) The sequence network equations are V a0 = -I a0 Z 0.(4) V a1 = E a I a1 Z 1.(5) V a2 = -I a2 Z 2...(6) I a Z + E a Z E c E b Z I b C b I c Fig The solution of these six equations will give six unknowns Va0, V a1, V a2 and I a0, I a1 and I a2. Since V a0 = (1/3) [V a + V b + V c ] V a1 = (1/3) [V a + av b + a 2 V c ] V a2 = (1/3) [V a + a 2 V b + a V c ] Using above three equations and substituting for V a, V b and V c from the equation (2) and (3) V a0 = (1/3) [V a ] = V a /3 V a1 = (1/3) [V a +a. 0 +a 2. 0 ] = V a /3 Page : 16
17 V a2 = (1/3) [V a +a a.0 ] = V a /3 V a0 = V a1 = V a2.(7) Using this relation of voltages and substituting in the sequence network equations V a0 = V a1 I a0 Z 0 = E a I a1 Z 1 I a0 =..(8) Similarly V a2 = V a1 I a2 Z 2 = E a I a1 Z 1 I a2 =.(9) Now from equation (1) I a = I a1 + I a2 +I a0 = E a + Z1 V a1 Z 2 V a2 Z 0 + I a2 + I a0 I a1 Fig Substituting values of Ia2 and I a0 from the equation(9) and (8) I a1 = = 0 Therefore I a1 = I f =I b + I c = 3 I a0 I a0 = -I a1 I f = -3 I a1 Page : 17
18 Conclusion: Zero sequence and negative sequence networks are parallel and this is in series to the positive sequence. Double line to ground fault with Z f I a1 = 3.4 Three Phase Fault The boundary conditions are I a + I b + I c = 0 V a = V b =V c I a is taken as reference I b = a 2 I a and I c = ai a a I a E a Z E C Z Z E b C b I b I c Fig Ia1 =1/3 (I a + a I b + a 2. I c ) and substituting the values of I b and I c I a1 = 1/3 (I a + a. a 2 I a + a 2 a I a ) Ia 1 = Ia I a2 = 1/3 (I a + a 2 I b + a I c ) = 1/3 (I a + a 4 I b + a 2 I c ) = 1/3 (I a + a I a + a 2 I c ) Page : 18
19 = (1 + a + a 2 ) = 0 I a0 = 1/3 (I a + I b +I c ) = 0 V a1 = 1/3 (V a + a V b + a 2 V c ) = 1/3 (V a + a V a + a 2 V a ) = V a (1 + a + a 2 ) = 0 V a1 = 1/3 (V a + a 2 V b + a.v c ) = 0 Since V a1 = 0 = E a I a1 Z 1, I a1 = E a / Z1 The frequent fault in transformer line is single line to ground fault. The most severe fault is 3-phase fault. The most severe fault nearer to generator is single line to ground fault. From the analysis of the various faults, the following observations are made: 1. Positive sequence currents are present in all types of faults. 2. Negative sequence currents are present in all unsymmetrical faults. 3. Zero sequence currents are present when the neutral of the system is grounded and the fault also involves the ground, and magnitude of the neutral current is equal to 3 I a0. When currents are entering a delta connected winding, positive sequence components of line currents lead the corresponding positive sequence components of phase currents (winding current) in delta winding by 90. Positive sequence components of line currents on the star side of a star delta transformer, lead the corresponding positive sequence line currents on the delta side by 90. Positive sequence components of line and phase voltages on the star side of a star delta transformer lead the corresponding positive sequence line and equivalent phase voltages respectively on the delta side by 90. Proof: Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. Balanced system, Voltages must be in the form of V b = a 2 V a V c = av a From Inverse symmetrical transformation, Page : 19
20 V 012 = [T -1 ] V abc = (1/3) = (1/3) = (1/3) V a = 1/3 V a 1 + a + a 2 = 0 a 3 = 1, a 4 = a 3. a = a = So for balanced 3 ϕ system, V a0 = V a2 = 0; V a1 =V a Load Flow * Load cannot be same for all time in the system. The power flow idea is to find out the voltage at different bus bar, sub - station, node point & the flow of power on these lines, with given constraints and specifications. Types of Buses: 1. Load bus: In this type of bus, and are known. The unknowns are and. 2. Slack Bus Reference Bus Swing Bus:- This bus is a special type of bus. Here real and reactive powers are not specified only are known. and 3. Generator Voltage control PV Bus:- In this type of bus and are known. and are not known. Power System Network Page : 20
21 generator ~ ~ bus burs ~ 4 5 Fig L Load G Generator [Those bus who has self generator are called generated bus bar.] [Who s don t have generator called load bus bar.] to bus m to bus s to bus gen Load Fig Page : 21
22 Where injected power (real) in to bus. & injected (reactive) power into bus. For load bus So we can write (i) (ii) On the behalf of equation (i) and (ii) load bus are drawing the power. Example: to bus J to bus m to bus i Bus K Fig Static analysis of Power Network. Mathematical model of the Network T.L. nominal π model. Bus power injection.. But Admittance matrix Taking small example Page : 22
23 1 3 2 Fig equivalent π model. Shunt admittance Fig Page : 23
24 Now power equation converting in current equation. So we can write equation. self admittance. (Driving point admittance) transfer admittance or mutual adce. 1. formatting is so easy & & Z matrix comp. 2. is symmetric matrix matrix is sparse matrix. (Sparse means most of the elements of Because there are 90% elements are zero. 3. Dimension of is (N N) N = No. of bus matrix are zero) Power Flow Equation., k, n = 1, 2, N. Page : 24
25 Characteristics of power flow equation Power flow equation are algebraic static system nonlinear Iterative solution Relate P, Q in terms of V, δ & elements There are two methods to solve these non linear equations: 1. Newton Raphson method 2. Gauss Seidal method Newton Raphson (N.R.) method has got quadratic convergence and is fast as compared to Gauss Seidal and always converge. But N.R. method requires more time per iteration. Gauss Seidal has got linear convergence, convergence is affected by choice of slack bus and the presence of sense capacitor. Example: Assume a three phase system with a sustained supply voltage of 2,300 volts from line to neutral and with line impedance and. Compute the magnitude of fault current for a single line to ground fault at the end of the line. Solution: Supply voltage = 2300 V line/neutral For a single line to ground fault at a in Figure below. a b c Page : 25
26 then where is prefault voltage Also Page : 26
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been
Chapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
Steady-State Power System Security Analysis with PowerWorld Simulator
Steady-State Power System Security Analysis with PowerWorld Simulator S: Power System Modeling Methods and Equations 00 South First Street Champaign, Illinois 680 + (7) 384.6330 [email protected]
Scholars Research Library
Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
BALANCED THREE-PHASE CIRCUITS
BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
INDUCTION REGULATOR. Objective:
INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load
Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads
Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads Authors & Affiliation: V.Ravi Kiran, V.Manoj and P.Praveen Kumar Asst. Professor, EEE Dept GMRIT,
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
Fault Analysis I13-1. 2008 PowerWorld Corporation
Fault Analysis Analysis of power system parameters resulting from a ground or line to line fault somewhere in the system Simulator contains a tool for analyzing faults in an automatic fashion Can perform
A Direct Numerical Method for Observability Analysis
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL 15, NO 2, MAY 2000 625 A Direct Numerical Method for Observability Analysis Bei Gou and Ali Abur, Senior Member, IEEE Abstract This paper presents an algebraic method
Chapter 9 Balanced Faults
Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
Power Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
(3 )Three Phase Alternating Voltage and Current
EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system
Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models
EE Modul 1: Electric Circuits Theory Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models EE Modul 1: Electric Circuits Theory Current, Voltage, Impedance Ohm
Open Phase Conditions in Transformers Analysis and Protection Algorithm
Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON [email protected] Abstract This paper first provides an in-depth analysis of open phase
How To Understand And Understand The Theory Of Electricity
DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating
Chapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.
The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
Load Flow Analysis on IEEE 30 bus System
International Journal of Scientific and Research Publications, Volume 2, Issue 11, November 2012 1 Load Flow Analysis on IEEE 30 bus System Dharamjit *, D.K.Tanti ** * Department of Electrical Engineering,
Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems
Neutral to Earth oltage Reduction Methods in ThreePhase Four Wire Distribution Systems G. Ahmadi and S.M. Shahrtash ran University of Science and Technology (UST) [email protected] Center of Excellence
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
13 ELECTRIC MOTORS. 13.1 Basic Relations
13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This
UCI274C - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
UCI274H - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati
Measurement of Power in single and 3-Phase Circuits by : N.K.Bhati A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1 Areas Covered Under this Module 1. Power in
Three-phase analysis of unbalanced systems
Exercises of course ELEC0029 - Electric power systems analysis and operation Three-phase analysis of unbalanced systems Thierry Van Cutsem [email protected] www.montefiore.ulg.ac.be/~vct March 205
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS
PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section
PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards
1 Introduction. 2 Power Flow. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.061 Introduction to Power Systems Class Notes Chapter 5 Introduction To Load Flow J.L. Kirtley Jr. 1 Introduction
Lecture 7 Circuit analysis via Laplace transform
S. Boyd EE12 Lecture 7 Circuit analysis via Laplace transform analysis of general LRC circuits impedance and admittance descriptions natural and forced response circuit analysis with impedances natural
Lecture Notes ELE A6
ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth
HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
Network Theory Question Bank
Network Theory Question Bank Unit-I JNTU SYLLABUS: Three Phase Circuits Three phase circuits: Phase sequence Star and delta connection Relation between line and phase voltages and currents in balanced
2.1 Introduction. 2.2 Terms and definitions
.1 Introduction An important step in the procedure for solving any circuit problem consists first in selecting a number of independent branch currents as (known as loop currents or mesh currents) variables,
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65
COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the
Chapter 12 Three-Phase Circuit
Chapter 12 Three-Phase Circuit 馮 武 雄 教 授 長 庚 大 學 電 子 系 1 Chapter 12 Three-Phase Circuits 12.1 What is a Three-Phase Circuit? 12.2 Balance Three-Phase oltages 12.3 Balance Three-Phase Connection 12.4 Power
THREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
Introduction to PowerWorld Simulator: Interface and Common Tools
Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 [email protected] http://www.powerworld.com Fault Analysis Analysis
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
AC Generators. Basic Generator
AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
PM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
Electrical Fault Level Calculations Using the MVA Method
J.M. PNG & SH PT LTD Chapter lectrical ault Level Calculations Using the Method 5 With modern day personal computers, hand calculations for electrical fault level are becoming a thing of the past. The
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Motors and Generators
Motors and Generators Electro-mechanical devices: convert electrical energy to mechanical motion/work and vice versa Operate on the coupling between currentcarrying conductors and magnetic fields Governed
Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system
SYNCHRONOUS MACHINES Tze-Fun Chan Hong Kong Polytechnic University, Hong Kong, China Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting,
USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY.
USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY. INTRODUCTION Frequently customers wish to save money by monitoring a three-phase,
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
Motor Fundamentals. DC Motor
Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
Lecture L3 - Vectors, Matrices and Coordinate Transformations
S. Widnall 16.07 Dynamics Fall 2009 Lecture notes based on J. Peraire Version 2.0 Lecture L3 - Vectors, Matrices and Coordinate Transformations By using vectors and defining appropriate operations between
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC
Modeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
Design and Analysis of Switched Reluctance Motors
Design and Analysis of Switched Reluctance Motors İbrahim ŞENGÖR, Abdullah POLAT, and Lale T. ERGENE Electrical and Electronic Faculty, İstanbul Technical University, 34469, Istanbul, TURKEY [email protected],
Induction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD
. MEASEMENT OF OE CONSMTION OF THE NONBALANCED THEE-HASE LOAD Task of the measurement. Measure the active power and the reactive power of the nonsymmetrical -phase load in Y-connection. Do not connect
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
AP1 Electricity. 1. A student wearing shoes stands on a tile floor. The students shoes do not fall into the tile floor due to
1. A student wearing shoes stands on a tile floor. The students shoes do not fall into the tile floor due to (A) a force of repulsion between the shoes and the floor due to macroscopic gravitational forces.
Unified Lecture # 4 Vectors
Fall 2005 Unified Lecture # 4 Vectors These notes were written by J. Peraire as a review of vectors for Dynamics 16.07. They have been adapted for Unified Engineering by R. Radovitzky. References [1] Feynmann,
Definition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Circuit Analysis using the Node and Mesh Methods
Circuit Analysis using the Node and Mesh Methods We have seen that using Kirchhoff s laws and Ohm s law we can analyze any circuit to determine the operating conditions (the currents and voltages). The
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
TRANSFORMER: THREE PHASE
CONTENTS Transformer : Three Phase 1211 C H A P T E R 33 Learning Objectives Three-phase Transformers Three-phase Transformer Connections Star/Star or Y/Y Connection Delta-Delta or Connection Wye/Delta
Vectors Math 122 Calculus III D Joyce, Fall 2012
Vectors Math 122 Calculus III D Joyce, Fall 2012 Vectors in the plane R 2. A vector v can be interpreted as an arro in the plane R 2 ith a certain length and a certain direction. The same vector can be
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
A New Method for Estimating Maximum Power Transfer and Voltage Stability Margins to Mitigate the Risk of Voltage Collapse
A New Method for Estimating Maximum Power Transfer and Voltage Stability Margins to Mitigate the Risk of Voltage Collapse Bernie Lesieutre Dan Molzahn University of Wisconsin-Madison PSERC Webinar, October
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Module 2. DC Circuit. Version 2 EE IIT, Kharagpur
Module DC Circuit Lesson 4 Loop Analysis of resistive circuit in the context of dc voltages and currents Objectives Meaning of circuit analysis; distinguish between the terms mesh and loop. To provide
How To Balance Three Phase Power In A Balanced System
Three-Phase Circuits Three-Phase Circuit Three-Phase Circuits What is a Three-Phase Circuit? Balance Three-Phase oltages Balance Three-Phase Connection Power in a Balanced System Unbalanced Three-Phase
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Fast analytical techniques for electrical and electronic circuits. Jet Propulsion Laboratory California Institute of Technology
Fast analytical techniques for electrical and electronic circuits Vatché Vorpérian Jet Propulsion Laboratory California Institute of Technology PUBLISHED BY THE PRESS SYNDICATE OF THE UNIVERSITY OF CAMBRIDGE
W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören
W03 Analysis of DC Circuits Yrd. Doç. Dr. Aytaç Gören ELK 2018 - Contents W01 Basic Concepts in Electronics W02 AC to DC Conversion W03 Analysis of DC Circuits (self and condenser) W04 Transistors and
Math, Trigonometry and Vectors. Geometry. Trig Definitions. sin(θ) = opp hyp. cos(θ) = adj hyp. tan(θ) = opp adj. Here's a familiar image.
Math, Trigonometr and Vectors Geometr Trig Definitions Here's a familiar image. To make predictive models of the phsical world, we'll need to make visualizations, which we can then turn into analtical
ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES
ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES The purpose of this lab session is to experimentally investigate the relation between electric field lines of force and equipotential surfaces in two dimensions.
How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.
1 How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. The territory of high-performance motor control has
Symmetrical Components in the Time Domain and Their Application to Power Network Calculations
522 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 15, NO. 2, MAY 2000 Symmetrical Components in the Time Domain and Their Application to Power Network Calculations Gerardus C. Paap, Senior Member, IEEE Abstract
ACCURACY OF POTENTIALTRANSFORMERS
8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"
BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011
AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT