CT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK

Size: px
Start display at page:

Download "CT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK"

Transcription

1 Presentation 09.1 CT Analyzer: Coming to the Rescue Tony Porrelli, OMICRON, UK Introduction The Current Transformer (CT) may exist for many applications but for this paper we can think about them being for Protection and Measuring purposes. Generally speaking, protection CT s usually connect to protection relays and measuring CT s usually connect to meters. Specifications of CTs in the power network need to be considered carefully. Without going into too much depth, usually they are specified in terms of: Ratio Class Burden Knee Point Various Standards Institutes set methods for manufacturing and testing but more importantly how to classify CT s in terms of Accuracy and Burden. The accuracy class helps us to discriminate between a Protection CT and a Measuring CT. Construction Has anybody ever stopped to think What an interesting device the current transformer is. Essentially formed with four components: an Iron Core Insulation Copper Wire Terminations S1 / X1 S2 / X2 Fig. 1 Components of a Current Transformer (CT) This is of course the simplest form but the construction really depends on the voltage which has to be withstood between the Primary and Secondary. As voltage levels exceed approx. 5kV then porcelain will be included in the design and at even higher voltages, oil-immersion is necessary. How can such a simple assembly create such an aura and complexity? Firstly, we should look at the equivalent circuit. Equivalent Circuit When looking beyond its essential components, we reveal a complex electrical network of impedance s, voltages and currents. The current transformer equivalent circuit can be seen below. Fig. 2 CT Equivalent Circuit The resistance of the secondary winding is much higher than the leakage reactance which is usually ignored. The primary is normally considered to be a single conductor (1 Turn) where its resistance and reactance are so small that they too can be ignored. We see from Fig. 2 that the losses contain two components, that being the reactive (I xm ) and resistive (I rm ) losses making up the total error current, I e. The secondary current available for the load is now I s = (N p /N s x I p ) - I e. It shows that the primary current provides the exciting current for the magnetisation of the core and supplies the hysteresis and eddy losses. The quantity of exciting current is dependent upon the core material and the amount of flux to provide the burden requirements. The current that remains is transformed by the turns ratio to provide the secondary output. The model is crucial to modern testing devices and has been explained in many texts. The secondary load of a CT is termed the Burden and is expressed is volt-amperes (VA).The burden consists of connected instruments and associated leads and connections. Classification of a CT As the CT secondary current should represent the proportion of the primary load current, then

2 Presentation 09.2 accuracy of transformation to the turns ratio is required at rated burden depending on the classification of the CT. Therefore we see that due to the excitation current circulating in the magnetising branch of the circuit, it is not transferred to the secondary side output, the CT output will have deviations to what is expected. This ratio error is the percentage difference between the secondary current multiplied by the transformation ratio expressed as %. An error in phase also exists between the primary and secondary currents owing to the primary having to provide the exciting current. The phase angle being measured in minutes. The phase error is considered positive when the secondary current leads the primary. The simple CT can take on two guises: It can be the sleeping giant of the protection system, ready to roar when poked with a big stick. But also the pedigree workhorse, thanklessly operating day by day to provide the measurement system with accurate information. Measuring CTs must maintain accuracy over a limited range of primary current, typical between 5% and 120% of full load rating. These usually connect to instruments and meters with the advantage that they will saturate early to protect the instruments. Protection CTs however, must maintain accuracy over a wide range of primary current which can be up to 20 or 30 times rated full load value. Normally being connected to protection relays. In the past, CTs were designed to the British Standard BS3938 Specification which was superseded by IEC Manufacturers of CTs can supply to any country and will use the recommended standards that are relevant to that particular region. In many areas, such as Europe, the IEC standards are relevant but exist in many editions. IEC Instrument transformers: Current transformers IEC Combined transformers IEC Requirements for protective current transformers for transient performance IEC that supersedes the IEC60044 range but I will mention this later. Australia AS 1675 Current transformers - Measurement and protection One of the many differences between the IEC and the ANSI/IEEE standards is that the IEC allow secondary current definitions of 0.5, 1, 2, or 5A where the ANSI/IEEE standard defines 5A. CT Testing No matter which standard is used as the basis for design, there are many similarities in the tests that need to be conducted by a manufacturer. Some of basic tests include: Turns ratio by Primary injection Current Ratio by Primary injection, at rated burden when required Secondary winding resistance referenced to 75ºC Magnetisation curve measurement Knee point verification where applicable Accuracy Limit Factor verification for protection CT s such as class 5P & 10P Instrument Security Factor (FS) verification for measuring CT s if required ANSI/IEEE assessment to the Ratio Correction Factor and Phase Angle Parallelogram ANSI/IEEE testing at 0.5 or 0.9 Power Factors Polarity In the past, limited by advances in technology, the traditional measurement system for testing the ratio and burden of a CT has been commonly referred to as Primary Injection, where by various levels of Primary current are passed thought the CT and the secondary output is measured with full load and with additional load conditions according to the given Standard definitions i.e. according to IEC for 25% to 100% rated burden where applicable. The following photo shows how it was carried out in the past and it can be time consuming to set up when you consider a source, a measurement bridge, reference standard, and burden at the correct power factor. Not forgetting the pace of a human operator. For countries such as USA, Canada and Australia the following standards are relevant. ANSI/IEEE Std C : IEEE Standard requirements for Instrument transformers ANSI/IEEE Std C : IEEE Standard for High-Accuracy Instrument Transformers Canada CAN3-C13-M83: Instrument transformers

3 Presentation 09.3 designer would try to use a high flux density as this may lead to less core material and reduced costs. Continuing from this the CT may also require secondary winding resistance measured, and if it is a wound primary CT, possibly even the primary winding resistance. Typically, an old measurement bridge could have been used with great accuracy such as that shown in Fig 5. Fig. 3 Testing bay from the old past Another important measurement is that of the excitation curve, or magnetising curve as it is also known. Among other things, this is used to check the knee point which is defined by the IEC as a 10% increase in voltage giving rise to a 50% increase in current. ANSI/IEEE defines the knee point as the intersection of the excitation current curve with a 45º tangent line respectively or alternatively with a 30 tangent line for gapped core CTs. More test equipment is required that consists of a variac source, step up transformer, an ammeter and a voltmeter. A graph is produced based on the test voltage values and measured currents. This is also very time consuming. The typical circuit is shown below. V(V) Vkp Knee Point A Protection CT S1 S1/X1 Fig. 5 Typical resistance bridge Like all CT s, polarity is an important parameter to verify when connected to polarity-sensitive meters, control and protection relays. A traditional polarity checker can be seen below. It looks to me like something my grandfather would make on a Saturday morning from an old wardrobe. 10% 50% V Saturated Region S2/X2 Linear Region Measurement CT Ankle Point Region I (A) Fig. 4 Conventional mag curve testing circuit & typical measurement curve according to IEC In general, a protection CT would operate in the working range from the Ankle Point to the Knee Point region or above. The measurement CT may work around the Ankle Point region but in some cases can also work just under the knee point. The Fig. 6 Typical polarity checker For a CT manufacturer, these industrial devices may be accessible and permanently installed to assist with testing. But for the commissioning and maintenance engineer, this can become a huge problem. Especially when it comes to primary injection at rated burdens.

4 Presentation 09.4 It also becomes extremely difficult for the on-site engineer to test and verify to any International Standards such as the ANSI/IEEE or IEC. What is a PASS and what is a FAIL? Shouts the exhausted engineer. CT Analyzer to the rescue Firstly, the CT Analyzer (CTA) can conduct the majority of tests required by international standards and perform verification as to whether the CT will pass or fail. CT Analyzer: Rescue 1 All the industrial equipment examples we have previously seen are not really considered to be portable. The transportation requirements would be huge. The ideal solution would be for manufacturers and on-site engineers to be more streamlined and efficient taking only one device to cover most of the important electrical tests required. In addition to testing efficiency, test reports are generated automatically saving even more time. Weighing in at 8kg, the OMICRON CT Analyzer is the revolutionary lightweight test unit capable of testing Ratio, Burden, Resistance, Magnetisation Curve and much more taking only about 60 seconds to complete all tests, even referencing the resistance to 75ºC and providing the Remanence. It is extremely simple to use and in the event that there is no information about the CT under test, the unit can use the measured electrical data to provide an educational guess as to what classification the CT can meet. Ratio s up to 10000/1 and more can be tested. Knee point voltages up to 30kV can be checked. CT Analyzer: Rescue 2 Recently, however, the IEC made a decision to consolidate the many editions of the IEC60044 documents and now the new editions exist as follows: IEC Instrument transformers: General requirements IEC Additional requirements for current transformers This can impact manufactures and on-site engineers as they may now come up against a choice of many different standards. The CTA comes to the rescue in this instance as OMICRON has already implemented the automatic assessment to the IEC into its software. This gives the user easy access to verify against a multitude of international standards. The ANSI/IEEE Standard C is also under rework being launched sometime in the future. Again, the CT Analyzer will be ready to validate CTs to the new specifications. CT Analyzer: Rescue 3 Planning the requirements of a substation is very complex. It is no surprise that specifications constantly change, often very quickly after the initial design of an asset has been accepted and manufactured. For High Voltage Current Transformers (HV CT s) where there are expensive bushings and copper work, this can become challenging in terms of design and more importantly, cost. OMICRON s CT Analyzer helps determine the CT classification and can simulate various loads after a design change, in timely manner. Manufacturing companies put great effort into perfecting the manufacturing process in order to create instruments of high accuracy and quality. This is particularly true for the production of HV CTs where manufacturers have a real challenge to ensure the accuracy and quality of such high value equipment. Where critical specification changes are necessary, manufactures need to provide quick solutions, preferably limiting the need to re-design the product. Changed Specifications This scenario was encountered by a HV CT manufacturer, whereby their end customer had specified a number of multi-tapped high accuracy Class 0.2s units to be supplied. However, after the design had been accepted, manufactured and tested, the customer then requested a change to the specification. The challenge for the manufacturer was how to address the customers' needs with minimal impact

5 Presentation 09.5 on the design and cost. A further complication was the requirement for HV CT s to undergo approval testing at an overseas independent test laboratory. The HV CTs that already been dispatched overseas for testing were successfully approved to the original nameplate specification defined. options. Importantly, this device allows the user to play around with various test specifications. With this equipment, it is easy to make connections and to apply different test loads to the HV CT under test to evaluate its performance. The CT Analyzer helped to determine the load that can be applied to the HV CT to retain the classification of 0.2s. The manufacturer was thus able to return the HV CT to the independent overseas laboratory for approval, knowing that the equipment would successfully pass. The investigation and tests completed with the CT Analyzer took as little as 30 minutes. This would be impossible using traditional testing equipment, particularly given the location of the HV CTs and the time constraints. Literature [1] Connelly F.C.: Transformers: Their principles and design for light electrical engineers, Printed in UK, First Published 1950 [2] Brian D. Jenkins: Introduction to Instrument Transformers, Printed in UK, First Published 1967 [3] Jaun M. Gers and Edward J. Holmes: IET, Protection of Electricity Distributoin Networks, 2 nd Edition [4] IEC :2003 Standard Fig. 7 Example of the HVCT under test Due to size and weight, expensive shipping costs were incurred. The approved CT s were returned to the manufacturer and at this point, the end customer requested to re-define the CT tap, the VA rating and retain the Class 0.2s classification. This change meant that the units, following the respecification, would need to be returned to the overseas test laboratory for re-approval to the new specification. To avoid unnecessary shipment costs, and to avoid delay, the manufacturer wanted to be confident that the new specification would be met be the CT before returning it to the laboratory. Conducting traditional primary injection testing of this type of HV CT requires a powerful source and considerable time and effort to complete the required testing efficiently. However, the site where the HV CTs were stored was not the same site as the factory test site. About the Author Tony Porrelli attained his BEng (Hons) back in 1993 and many many years later left is home of Scotland and moved to England on January 1 st 2008 to begin his employment with OMICRON. Before joining OMICRON he was a current transformer design engineer based in Scotland. Now he has the responsibility of being the Regional Application Specialist for Instrument Transformers covering Europe and Africa. This is in addition to his role of providing technical and application support to all OMIRCON products covering the United Kingdom and Ireland Verification in 30 minutes OMICRON was contacted by the manufacturer who wanted assistance with this testing. It was recommended to use the CT Analyzer, a fast, portable, and easy to use test device which provides the user with a broad range of testing

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

CT Application Guide for the 489 Generator Management Relay

CT Application Guide for the 489 Generator Management Relay g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates

More information

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1 Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

Calculation of the Current Transformer Accuracy Limit Factor Application Note

Calculation of the Current Transformer Accuracy Limit Factor Application Note Calculation of the Current Transformer Application Note kansikuva_bw 1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4

More information

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331) Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24 1 X CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD

More information

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

0.84 x 2.00 Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP. SPLIT CORE CURRENT MODEL 1SP 0.84" x 2.00" PAGE No 3-2 REV 18DEC00 UL 1015 LEAD WIRE, STANDARD LENGTH IS 36 E DIMENSIONS A = 0.84 MIN B = 2.00 MIN C = 3.31 MAX D = 3.09 MAX E = 0.61 MAX F = 0 MAX F C B

More information

Lab 14: 3-phase alternator.

Lab 14: 3-phase alternator. Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive

More information

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating. THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies

More information

Enhanced Quality with a Touch of Style

Enhanced Quality with a Touch of Style Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits PHYSCS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits This experiment is designed to investigate the relationship between current and potential in simple series

More information

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current

More information

Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved. Chapter 16 Current Transformer Design Table of Contents 1. Introduction 2. Analysis of the Input Current Component 3. Unique to a Current Transformer 4. Current Transformer Circuit Applications 5. Current

More information

CT ANALYZER. The Revolution in Current Transformer Testing

CT ANALYZER. The Revolution in Current Transformer Testing CT ANALYZER The Revolution in Current Transformer Testing The Unique Solution OMICRON s CT Analyzer delivers a unique capability for the fast comprehensive testing and calibration of current transformers,

More information

Current Transformers Ratio / Polarity / Types

Current Transformers Ratio / Polarity / Types CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s

More information

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS Sethuraman Ganesan ABB Inc. Allentown, PA ABSTRACT More and more sub-stations are retrofitted with numerical relays, meters and monitoring

More information

7CURRENT TRANSFORMERS

7CURRENT TRANSFORMERS 7CURRENT TRANSFORMERS Protective relays of the a-c type are actuated by current and voltage supplied by current and voltage transformers. These transformers provide insulation against the high voltage

More information

Full representation of the real transformer

Full representation of the real transformer TRASFORMERS EQVALET CRCT OF TWO-WDG TRASFORMER TR- Dots show the points of higher potential. There are applied following conventions of arrow directions: -for primary circuit -the passive sign convention

More information

Primary Test Manager (PTM) Testing and management software for primary assets

Primary Test Manager (PTM) Testing and management software for primary assets Primary Test Manager (PTM) Testing and management software for primary assets The ideal tool for diagnostic testing and condition assessment The Primary Test Manager TM (PTM) is the ideal software tool

More information

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com

Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com CURRENT TRANSFORMER MODEL J " x 7" PAGE No 2-2 REV 8DEC00 TERMINAL OPTION LEAD WIRE OPTION 8-2 BRASS SCREW TERMINALS (2 PLACES) SEE NOTE 9 6 9 8 6 Ø 2 9 (4 PLACES) UL 05 #6 AWG LEAD WIRE, STANDARD LENGTH

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

MEASURING INSTRUMENTS. By: Nafees Ahmed, Asstt, Prof, EE Deptt, DIT, Dehradun

MEASURING INSTRUMENTS. By: Nafees Ahmed, Asstt, Prof, EE Deptt, DIT, Dehradun MEASURING INSTRUMENTS By: Nafees Ahmed, Asstt, Prof, EE Deptt, DIT, Dehradun MEASURING INSTRUMENTS The device used for comparing the unknown quantity with the unit of measurement or standard quantity is

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Table of contents Tape Wound Measuring and Protection Current Transformers 2 MR Series Measuring Range 3 PR Series Protection Range 4 Class PX Current

More information

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear. OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in

More information

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable

More information

Instrument Transformers. Technical Information and Application Guide

Instrument Transformers. Technical Information and Application Guide Instrument Transformers Technical Information and Application Guide Table of Contents Technology Review An introduction to instrument transformer fundamentals, a discussion on power quality, and a detailed

More information

Current & Instrument Transformers

Current & Instrument Transformers Reliable & Accurate Inputs for Measuring & Protection Equipment Current & Instrument Transformers Type MKE11 Inside the Catalogue Range Specifications Ordering Code Delivering Value to You M-Kris Electric

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

CURRENT TRANSFORMERS INSTALLATION GUIDE

CURRENT TRANSFORMERS INSTALLATION GUIDE CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

2. Permanent Magnet (De-) Magnetization 2.1 Methodology

2. Permanent Magnet (De-) Magnetization 2.1 Methodology Permanent Magnet (De-) Magnetization and Soft Iron Hysteresis Effects: A comparison of FE analysis techniques A.M. Michaelides, J. Simkin, P. Kirby and C.P. Riley Cobham Technical Services Vector Fields

More information

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions

More information

UCI274C - Technical Data Sheet

UCI274C - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

UCI274H - Technical Data Sheet

UCI274H - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

Using Current Transformers with the 78M661x

Using Current Transformers with the 78M661x A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 (1) Instrument is a device for determining (a) the magnitude of a quantity (b) the physics of a variable (c) either of the above

More information

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321) Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:

More information

BCI184E - Technical Data Sheet

BCI184E - Technical Data Sheet BCI184E - Technical Data Sheet BCI184E SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models Dave Staton, Douglas Hawkins and Mircea Popescu Motor Design Ltd., Ellesmere, Shropshire,

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know? Unit 6 Transformers Lead-in What applications of transformers do you know? Basic principles Task 1 Match the words and phrases with the translations. 1. magnetic field 2. induced voltage 3. conductors

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

NEC Class 2 Power Circuits and Power Supplies

NEC Class 2 Power Circuits and Power Supplies NEC Class 2 Power Circuits and Power Supplies Abstract: The NEC (National Electrical Code) is a North American standard, which can be regarded as a law in most of the North American states. Among others,

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

ACCURACY OF POTENTIALTRANSFORMERS

ACCURACY OF POTENTIALTRANSFORMERS 8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

Percentage Restrained Differential, Percentage of What?

Percentage Restrained Differential, Percentage of What? Percentage Restrained Differential, Percentage of What? Michael J. Thompson Schweitzer Engineering Laboratories, Inc. 2011 IEEE. Personal use of this material is permitted. Permission from IEEE must be

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734B - Technical Data Sheet

PI734B - Technical Data Sheet PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil

More information

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section

More information

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Transformer Calculations

Transformer Calculations Transformer Calculations Transformers Transformers are one of the most basic yet practical devices used today. No matter where you are there is always a transformer nearby. They are used throughout alternating-current

More information

Everything you need for protection scheme testing

Everything you need for protection scheme testing Power System Simulator for Testing Protection Relays and Schemes Everything you need for protection scheme testing The is the only instrument with the high power, flexibility and software to perform full

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Approval Sheet for. Li-ion Battery (Lithium Iron Phosphate) Model: LiR14505F-600mAh

Approval Sheet for. Li-ion Battery (Lithium Iron Phosphate) Model: LiR14505F-600mAh Approval Sheet for Li-ion Battery (Lithium Iron Phosphate) Model: LiR14505F-600mAh AA Portable Power Corp (http://www.batteryspace.com) Address: 860 S, 19th St, Unit A, Richmond, CA, 94804 Tel: 510-525-2328

More information

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt. Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS VACUUMSCHMELZE GmbH & Co. KG (VAC) is one of the worldwide

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No.

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. Tutorial One: Calculation of leakage inductance of transformer using FEM Consider a transformer with the following rating: 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. of HV turns = 980 Although

More information

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH

More information

Testing of Power Transformers. Routine tests, Type tests and Special tests

Testing of Power Transformers. Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION Subject: Beware of Simplistic Voltage Drop Calculations By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION Iterative voltage drop calculations are some of the most tedious and time

More information

CORE LOSS TESTING THEORY CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT

CORE LOSS TESTING THEORY CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT LEXSECO developed the first commercial Core Loss Tester over thirty five years ago. Since inception, LEXSCO has performed core loss

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Development Of High Efficiency Brushless DC Motor With New Manufacturing Method Of Stator For Compressors

Development Of High Efficiency Brushless DC Motor With New Manufacturing Method Of Stator For Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2002 Development Of High Efficiency Brushless DC Motor With New Manufacturing Method Of

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards

More information

THE VALUE OF POWER FACTOR TESTING

THE VALUE OF POWER FACTOR TESTING THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer

More information

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter ELECTRICAL INSTRUMENT AND MEASUREMENT Electrical measuring instruments are devices used to measure electrical quantities such as electric current, voltage, resistance, electrical power and energy. MULTIMETERS

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information