SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
|
|
|
- Osborne Barber
- 9 years ago
- Views:
Transcription
1 SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. In order to further understand the application of motor circuit testing and analysis on synchronous electric motors (synchronous machines), it is important to have a brief overview of the operation of a synchronous motor, most common faults, common test methods, how Motor Circuit Analysis (MCA) works with large synchronous motors, basic steps for analysis of synchronous stators and rotors, and, expected test results. In this paper, we will discuss these various aspects, referencing other materials for additional details. About Synchronous Machines Large synchronous motors have two basic functions: The first is to improve the electrical power factor in a plant. In any plant with large inductive loads, such as motors and transformers, current begins to lag behind voltage (poor power factor). When this becomes severe enough, the plant requires significantly larger amounts of current to perform the same amount of work. This can cause voltage sag and overheating of electrical components. A synchronous motor can be used in such a way as to cause little to no impact on power factor, or can be used to cause current to lead voltage to correct power factor problems. The second method of operation is to absorb pulsating loads, such as reciprocating compressors. Once a synchronous motor has achieved synchronous speed, it has coils which lock in step with the electric motor s rotating magnetic fields from the stator. If a torque pulse occurs (such as at the top of a reciprocating compressor stroke), the motor may come out of synch with the rotating fields. When this occurs, a special winding on the rotor called an amortisseur winding (see synchronous construction below) absorbs the energy from the torque pulse, keeping the rotor in synch. The basic construction of a synchronous motor is straight forward. There are three sets of windings, a stator, a rotor, bearings, and either a generator (brushless) or a static exciter (brush-type). The windings consist of: A standard three phase winding, very similar to a standard induction electric motor; A set of field coils, which are DC coils made of round wire for small machines and rectangular or ribbon wire on larger machines; And an amortisseur winding, which is similar to an induction motor rotor squirrel cage. The starting methods for both the brush-type and brushless synchronous motors are similar. The starting circuit will be different for both. Following is a description of the basic mode of operation, followed by a brief description of the differences: During the starting phase of a synchronous motor, it acts much the same as a standard induction motor. The stator receives an electrical current and a rotating magnetic field is developed (the speed = (120 * applied frequency) / # of poles). This field generates a current in the amortisseur winding, which is used to develop starting torque by generating its own magnetic field which interacts with the stator magnetic field in the air gap and causes the rotor to follow the stator magnetic fields. As the rotor starts to catch up to the stator fields, DC current is injected into the rotor field coils, creating north and south magnetic pairs (rotor coils are always found in pairs). These lock in step with the stator magnetic fields and follow at the same speed as the stator fields, whereas a standard induction motor always lags behind. In a brush machine, the DC source for the rotor fields usually comes from a static (electronic) starter, which converts a supplied AC power to DC. In most cases, the output DC is varied through the starting cycle. The drive may also be set up to short out the field coils of the machine to avoid rotor saturation and 2010, Dreisilker P. 1 of 6 Synchronous Motors
2 the resulting extremely high currents on the stator. Once the rotor begins to turn, DC is supplied to assist the motor in developing torque. The DC voltage is supplied through a pair of slip rings and brushes. In a brushless machine, a DC generator is installed directly on the shaft of the synchronous motor. As the synchronous motor starts, the generator provides very little DC through its commutator. As the speed increases, the DC voltage also increases, helping the motor generate torque then lock in step at synchronous speed. In this type of machine, the generator is wired directly to the rotor fields. There are also machines that have a generator mounted on the shaft of the rotor that feeds a separate control. This is used to first short the windings and then control the amount of DC fed to the rotor, just as the brush machine. Most Common Synchronous Motor Faults Large synchronous motors tend to be well built and sturdy. They are often overbuilt with material to withstand the severe loads that are applied. The most common failures for industrial synchronous machines, in order, are: Bearings due to general wear and contamination Rotor fields due to high temperatures, these will often burn up from the inside out Amortisseur windings mostly in reciprocating loads. Because of the amount of energy absorbed, the winding bars will often crack. In particular if the rotor fields are beginning to fail and short, making it easier for the rotor to fall out of synch. Stator windings general wear and contamination. Stator windings in synchronous machines tend to be form wound and heavily insulated. Almost all of the winding faults that occur in a synchronous motor start between conductors in the rotor or stator coils. Common Test Methods, Strengths and Weaknesses Following are the traditional test methods for evaluating the condition of a synchronous motor: Insulation resistance testing: Using applied DC voltages as specified by IEEE , a potential is placed between the stator windings and ground. This measures only direct faults between the stator windings and the stator frame. Is also performed through the slip rings on a brush type machine. Polarization Index: Is a 10 minute to 1 minute ratio of insulation resistance. This has been traditionally used as a method to gage the condition of the insulation between the stator windings and frame. As with insulation resistance testing, this can also be performed through the slip rings on a brush type machine. As stated in IEEE , this test method is only truly valid on pre insulation systems and systems less than 5000 MegOhms. High Potential testing: Most common on large machines is DC high potential testing which is performed at a value of twice the motor nameplate voltage plus 1000 volts, times the square root of 3. On an existing insulation system, this value is often reduced to 75% of the potential voltage. This test highly stresses the insulation system and is potentially damaging (per IEEE Std ). This type of test should NEVER be applied to the rotor windings of a synchronous motor. Surge Comparison testing: Evaluates the turn to turn condition of the stator only by comparing the waveforms of two windings when a fast rise time pulse of twice the voltage plus 1000 volts. If there are correctable issues, such as contaminated windings, this test may damage the motor windings. Partial Discharge testing: Is a non-destructive test method that measures radio frequencies from discharges in voids within the insulation system of the motor windings. This is effective for trending on machines that are over 6.6 kv and only provide a brief warning from 4 kv. It does not detect any rotor faults. 2010, Dreisilker P. 2 of 6 Synchronous Motors
3 Electrical Signature Analysis: Was designed for rotor testing of rotating machines. Has excellent application with synchronous motors but cannot detect faults in de-energized equipment. Voltage Drop Test: Requires that the motor is disassembled. A 115 AC voltage is applied to the rotor windings and the voltage drop is measured with a volt meter across each coil. If there is a short, the voltage drop will vary more than 3%. The above list does not include equipment for mechanical testing of synchronous motors. About Motor Circuit Analysis The ALL-TEST IV PRO 2000 is a simple electronic instrument that performs in much the same manner as a multimeter, except that it provides a series of readings that cover the AC parameters of the motor circuit. It is a data collector and tester that sends a low voltage DC signal for simple resistance testing, in the same manner as a milli-ohm meter, and a low voltage, high frequency AC signal for AC readings. The instrument then uses a series of balanced electrical bridges to provide test results in engineering units of resistance, impedance, inductance, phase angle, current/frequency response and an insulation resistance test to ground. The primary differences between electronic testing of power equipment versus traditional power methods are: A more complete view of the motor circuit, including influences from changes in the condition of rotor field coil insulation. One instrument for a large range of equipment size. The test is limited only to the simple resistance range of the instrument (0.001 Ohm to 999 Ohms). Non-destructive no harmful voltage is applied. Easier data interpretation A few simple rules for data interpretation (See data interpretation below). Hand held vs equipment that may weigh from 40 to well over 100 lbs. Internal power source for the instrument. MCA technology is literally looking for changes to the electro-chemical makeup of the materials of the insulation system as well as direct break-downs of the insulation, such as cracks and damage. As an insulation system ages, or if the insulation system is contaminated and it is effecting the integrity of the insulation, the electrical circuit of the motor changes. Because the rotor is an integral part of the circuit, changes to the electrical integrity of the rotor circuit and insulation system are directly reflected through the stator windings, as well. This allows both immediate troubleshooting and long-term trending of the motor. Unique test information allows MCA to view enough parameters of the insulation system to detect and isolate: Shorted stator windings Shorted rotor fields Broken amortisseur winding bars Air gap eccentricity Winding contamination (rotor and stator) Ground insulation faults Basic Steps for the Analysis of Synchronous Machines with MCA The steps for testing synchronous machines are similar to those for evaluating the condition of standard induction motors. However, because there are field coils on the motor rotor, a few additional steps are involved when troubleshooting a fault. When testing a synchronous machine from the motor control center or starter: 2010, Dreisilker P. 3 of 6 Synchronous Motors
4 De-energize the equipment. Ensure that secondary sources of power are also de-energized. Perform the standard ALL-TEST IV PRO 2000 tests on the stator following the menu prompts on the instrument. Evaluate the test results If a fault is indicated, begin troubleshooting: o Adjust the position of the rotor, as much as possible, up to 45 degrees (any movement will do if the rotor is difficult to turn, but no less than 5 degrees) o Re-perform the tests and review the readings. If the fault has shifted, or changed by more than a digit, then the fault most likely is located in the rotor. o If the fault remains stationary (does not change with rotor position), then disconnect the leads at the motor terminal box and retest. If a fault is still indicated, it is most likely in the stator, if not, it is most likely in the cable. The average test time, other than troubleshooting, is approximately 3-5 minutes. When testing a disassembled synchronous machine, it is important to remember that the readings will be very different without the rotor in place: Perform the ALL-TEST IV PRO Auto test on the stator and evaluate the test results. This will provide an immediate indication of any faults. For the rotor test: o Perform the Auto test and compare to a past reading; or, o Perform the Auto test and compare to an identical rotor; or, o Perform the Auto test across each field coil instead of a voltage drop test. o All parameters for all three should meet the evaluation limits. Because of the style of testing, these results can be trended and compared between like machines. Other applications for motor circuit testing include evaluation and acceptance, and predictive maintenance. Expected Test Results As mentioned in the last section of this paper, the test results are similar to those found in three phase induction machines. Fault patterns are very straight-forward and apply regardless of equipment size, within the test range of the MCA instrument. Following is a brief overview of the test measurements and their results for basic troubleshooting: Simple resistance measurements: Are an indicator of high resistance connections, loose connections or broken conductors in the circuit. This test is important, especially if the resistance problem is in one spot as, based upon I 2 R, a resistive spot will put out a great deal of heat energy (in Watts). For instance, a 0.5 Ohm resistance across a point in a circuit that is seeing 100 Amps would give off: (100Amps 2 )(0.5 Ohms) = 5,000 Watts (5kW) worth of energy. This is about the same energy used to turn 6 horsepower worth of electric motor. Inductance measurement: Is an indicator of magnetic strength of a coil and the influence of other coils on one coil. It is impacted by the number of turns in a circuit, the dimensions of the coils and the inductance of other coils. This measurement, by itself, is only a good indicator of the condition of the amortisseur winding and rotor eccentricity. Inductance will only show a shorted winding if it is severe. Impedance measurement: Is the measurement of the complex resistance in the circuit. It can be used, much like inductance, for checking the amortisseur winding and rotor condition. However, when used along with inductance, it can be used to detect overheated windings and winding contamination quickly. By viewing the relationship of inductance and impedance between each phase: If the inductance and impedance are relatively parallel, then any inductive and impedance unbalance is in the relationship between the rotor and stator (rotor position); If they are not parallel, then there is an insulation problem such as insulation breakdown or winding contamination. 2010, Dreisilker P. 4 of 6 Synchronous Motors
5 Phase angle and I/F (Current/Frequency): Are both indicators of insulation faults between turns in the stator or rotor. Insulation Resistance: Evaluates the insulation to ground and will only indicated when the insulation has failed. The test limit recommendations, as outlined in IEEE Std are as follow: Table 1: Test Limits (peak to peak values) Measurement Limits Resistance 5% Impedance ~ 5%* Inductance ~15%* Phase Angle +/- 1 I/F +/- 2 Insulation Resistance > 100 M-Ohms *Can exceed this value if measurements are parallel. Following is an overview of the troubleshooting rules: Shorted Windings: o Shorted windings can be evaluated by viewing the phase angle and I/F readings from the instrument on similar coils or between phases: o Phase Angle (Fi) The phase angle should be within 1 digit of the average reading. For instance, a reading of 77/75/76 would be good because the average reading is 76. A reading of 74/77/77 would be bad. o Current Frequency Response (I/F) The current frequency response should be within 2 digits of the average reading. For instance, a reading of 44/-45/-46 would be good. A reading of -40/-44/-44 would be bad. However, a reading such as -42/-44/-44 should be considered suspect. Winding Contamination and Rotor Position o Conclusion o o The position of the rotor within the electric motor may cause a natural phase unbalance. Winding contamination will also cause phase unbalances. The difference between the two can be evaluated quickly by looking at the pattern of impedance and inductance. Rotor Position Rotor position unbalances can be evaluated by looking to see if the inductance and impedance values are fairly balanced. For instance, if there are inductances of 17/18/19 and impedances of values 24/26/29, then the unbalance is due to rotor position. This may also be the case if the inductances are 5/5/5 and the impedances are 8/9/8. Winding Contamination Can also be found as overheated (burned) windings. These conditions are the result of changes to the insulation due to breakdown of the insulation system. The faults show as a change of impedance and the relationship between impedance and inductance result in un-parallel readings. For instance, if there are inductances of 10/11/12 and the impedance has values of 16/14/13, then they are not parallel and the most likely fault is in the windings as contamination or overheated insulation. Through a set of simple rules and instructions, the ALL-TEST IV PRO 2000 provides an excellent tool for troubleshooting and trending the condition of synchronous machines. The test is performed using simple, non-destructive test measurements that allow for a more complete view of the motor stator and rotor circuit than any other test. Test evaluation is simple and direct, regardless of equipment size or type. 2010, Dreisilker P. 5 of 6 Synchronous Motors
6 Bibliography IEEE Std , IEEE Guide for Induction Machinery Maintenance Testing and Failure Analysis, IEEE, Penrose, Howard W. Electrical Motor Diagnostics: 2 nd Edition, SUCCESS by DESIGN, About the Author Howard W Penrose, Ph.D., CMRP is the Vice President of Engineering and Reliability Services for Dreisilker, the Web Editor-in-Chief of the IEEE Dielectrics and Electrical Insulation Society, and the Director of Membership for the Society for Maintenance and Reliability Professionals (SMRP). He has won four consecutive UAW and General Motors People Make Quality Happen Awards ( ) for energy, conservation, production, and motor management programs developed for GM facilities globally and is an SMRP Certified Maintenance and Reliability Professional (CMRP). Dr. Penrose is the author of the Axiom Business Book Award (2008 Bronze and 2009 Bronze) winning Physical Asset Management for the Executive (Caution: Do Not Read This If You Are On An Airplane), and the 2008 Foreword Book of the Year Finalist textbook, Electrical Motor Diagnostics: 2 nd Edition. Dr. Penrose may be contacted by at [email protected]. To have Dreisilker personnel perform field service, testing, field repair, shop repair (to over 10,000hp), or more, visit us at or contact us at We also provide motor circuit analysis, motor current signature analysis and electrical signature analysis (Electrical Motor Diagnostics) for virtually any industry. We are available for service throughout the USA and abroad. Dreisilker Electric Motors, Inc. is located just outside of Chicago, Illinois, at 352 Roosevelt Road, Glen Ellyn, Illinois. 2010, Dreisilker P. 6 of 6 Synchronous Motors
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS An ALL-TEST Pro White Paper By Howard W Penrose, Ph.D. General Manager ALL-TEST Pro A Division of BJM Corp 123 Spencer Plain Rd Old Saybrook, CT 06475
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis
Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP SUCCESS by DESIGN Reliability Services Hello and welcome to our presentation on Evaluating Induction
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
Unit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
Motor Fundamentals. DC Motor
Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical
Induction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
DC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
Understanding Insulation Resistance Testing
Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Motors and Generators
Motors and Generators Electro-mechanical devices: convert electrical energy to mechanical motion/work and vice versa Operate on the coupling between currentcarrying conductors and magnetic fields Governed
Welcome to Linear Controls Quarterly Training
Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of
AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE
Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
Application Information
Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application
Current and Temperature Ratings
Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and
The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:
The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery
AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):
AC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.
Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of
Basics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Understanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
Electric Motor Repair: Research Project on Soft Foot
Electric Motor Repair: Research Project on Soft Foot Howard W Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. (c)1997 Penrose Hello and welcome
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Synchronous motor. Type. Non-excited motors
Synchronous motor A synchronous electric motor is an AC motor in which the rotation rate of the shaft is synchronized with the frequency of the AC supply current; the rotation period is exactly equal to
(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.
ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer [email protected] Rotating Machinery Diagnostics & Instrumentation
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Introduction. Upon completion of Basics of AC Motors you should be able to:
Table of Contents Introduction...2 AC Motors...4 Force and Motion...6 AC Motor Construction... 12 Magnetism... 17 Electromagnetism... 19 Developing a Rotating Magnetic Field...24 Rotor Rotation...29 Motor
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
AC Induction Motor Slip What It Is And How To Minimize It
AC Induction Motor Slip What It Is And How To Minimize It Mauri Peltola, ABB Oy, Helsinki, Finland The alternating current (AC) induction motor is often referred to as the workhorse of the industry because
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING HI POTENTIAL TETS None of the windings, either rotating or stationary should
Outline. Turbine Generators. Generator History 3/25/2014
Turbine Generators Andrew Kusiak 2139 Seamans Center Iowa City, Iowa 52242-1527 [email protected] Tel: 319-335-5934 Fax: 319-335-5669 http://www.icaen.uiowa.edu/~ankusiak Outline Generators Synchronous
How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.
1 How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. The territory of high-performance motor control has
Modeling and Simulation of a Large Chipper Drive
The Open Electrical & Electronic Engineering Journal, 009, 3, 1-8 1 Modeling and Simulation of a Large Chipper Drive Open Access Christian Kral, Anton Haumer, Hansjörg Kapeller and Gert Pascoli Austrian
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
THREE-PHASE INDUCTION MOTOR March 2007
THREE-PHASE INDUCTION MOTOR March 2007 A. PREPARATION 1. Introduction 2. The Rotating Field 3. Rotor Currents 4. Induction Motor Equivalent Circuit 5. Torque and Power Characteristics 6. Operation Beyond
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
FAULT FINDING MANUAL For Self Excited and Separately Excited Generators
FAULT FINDING MANUAL For Self Excited and Separately Excited Generators SAFETY PRECAUTIONS Before testing the generating set, read the generating set Installation Manual, and this Fault Finding Manual,
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING
HI POTENTIAL TESTS 4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING None of the windings, either rotating or
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
Shaft grounding. Carbon brushes for shaft grounding are used in turbo-generators, in distinct AC- and DC motors and as a special application in Ships.
"Modern AC-Motors don't need carbon brushes and are maintenance free " Until some years ago this thrilling statement could be heard from motor OEM's. Nowadays SCHUNK supplies carbon brushes and brush holders
FAULT FINDING MANUAL. For Stamford AC Generators
FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar
Rotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan
INDUCTION MOTOR AND SELFEXCITED INDUCTION GENERATOR TzeFun Chan The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China Keywords: threephase induction motor, singlephase induction motor,
MIT510/2, MIT520/2 and MIT1020/2
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog
Inductance. Motors. Generators
Inductance Motors Generators Self-inductance Self-inductance occurs when the changing flux through a circuit arises from the circuit itself. As the current increases, the magnetic flux through a loop due
The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics
The DC Motor/Generator Commutation Mystery One small, yet vital piece of the DC electric motor puzzle is the carbon brush. Using the correct carbon brush is a key component for outstanding motor life,
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
PowerFlex Dynamic Braking Resistor Calculator
Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing
Predictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
Service and Maintenance. SEW-EURODRIVE Driving the world
SEW Brakes Service and Maintenance 2 Objectives Upon completion of this session, you will be able to do the following: - Identify the components of an SEW brakemotor - Explain the operation of the SEW
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA
Speed Control Methods of Various Types of Speed Control Motors Kazuya SHIRAHATA Oriental Motor Co., Ltd. offers a wide variety of speed control motors. Our speed control motor packages include the motor,
User Guide. Model 380260 Insulation Tester / Megohmmeter
User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
We will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
PM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
Chen. Vibration Motor. Application note
Vibration Motor Application note Yangyi Chen April 4 th, 2013 1 Table of Contents Pages Executive Summary ---------------------------------------------------------------------------------------- 1 1. Table
AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles
AC Induction Motors Simplest and most rugged electric motor Consists of wound stator and rotor assembly AC in the primary member (stator) induces current in the secondary member (rotor) Combined electromagnetic
Fundamentals of Inverter Fed Motors
Fundamentals of Inverter Fed Motors Technical Manual 10/02 MN780 Contents Page The Growing Use Of Inverters.................................................................. 1 How Inverters Affect Motors....................................................................
NATIONAL CERTIFICATE (VOCATIONAL)
NATIONAL CERTIFICATE (VOCATIONAL) SUBJECT GUIDELINES ELECTRICAL PRINCIPLES AND PRACTICE NQF Level 4 September 2007 ELECTRICAL PRINCIPLES AND PRACTICE LEVEL 4 CONTENTS INTRODUCTION 1 DURATION AND TUITION
Principles and Working of DC and AC machines
BITS Pilani Dubai Campus Principles and Working of DC and AC machines Dr Jagadish Nayak Constructional features BITS Pilani Dubai Campus DC Generator A generator consists of a stationary portion called
SHIP SERVICE GENERATORS (AC)
CHAPTER 14 SHIP SERVICE GENERATORS (AC) INTRODUCTION All generators change mechanical energy into electrical energy. This is the easiest way to transfer power over distances. Fuel is used to operate the
Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance
ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an
GLOLAB Two Wire Stepper Motor Positioner
Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and
Lab 14: 3-phase alternator.
Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive
13 ELECTRIC MOTORS. 13.1 Basic Relations
13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This
Current Probes. User Manual
Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
Torque motors. direct drive technology
Torque motors direct drive technology Why Direct Drive Motors? Fast and effective Direct-drive technology in mechanical engineering is defined as the use of actuators which transfer their power directly
NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR
INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Odyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
THIS paper reports some results of a research, which aims to investigate the
FACTA UNIVERSITATIS (NIŠ) SER.: ELEC. ENERG. vol. 22, no. 2, August 2009, 227-234 Determination of Rotor Slot Number of an Induction Motor Using an External Search Coil Ozan Keysan and H. Bülent Ertan
Transformer circuit calculations
Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
. Failure. Analysis... Report...
. Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number
RADIANT PLASMA 4700 Plasma Spark Generator
RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................
The Starting System. Section 4. Starting System Overview. Starter. The starting system:
The Starting System Starter The starter motor drives the engine through a pinion gear that engages the ring gear on the flywheel. Fig. 4-01 TL623f401c Starting System Overview The starting system: Uses
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
Direct Current Motors
Direct Current Motors DC MOTORS The DC machine can operate as a generator and as a motor. Chap 5. Electrical Machines by Wildi, 6 e Lecturer: R. Alba-Flores Alfred State College Spring 2008 When a DC machine
IV. Three-Phase Induction Machines. Induction Machines
IV. Three-Phase Induction Machines Induction Machines 1 2 3 4 5 6 7 8 9 10 11 12 13 Example 1: A 480V, 60 Hz, 6-pole, three-phase, delta-connected induction motor has the following parameters: R 1 =0.461
DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.
DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into