Lightning Protection Guidelines for Instrumentation Systems

Similar documents
Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Specifications for Lightning Protection. ASAE Engineering Practice

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Canopy Surge. User Manual

SECTION 22 LIGHTNING PROTECTION SYSTEM

TC Grounding and Bonding for Telecommunications Systems

Grounding & Bonding Why it is done And How to Install Properly

Chapter 9. Bonding and Grounding

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

Video Camera Installation Guide

800 Communications Circuits

ELECTRICAL SAFETY Information Bulletin

Lightning Arresters P KVA P KVA. Description & Installation

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Lightning Protection for Comrex Equipment

EMC Engineering Guidelines For Automation Systems PS 4 PS /97 AWB GB

Security Cameras, CATV, GPS & Satellite Protection. White Paper

STREETLIGHT SYSTEM GROUNDING AND BONDING

Introduction to Data Centre Design

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

EH-20 20m antenna. By VE3RGW

Scope: Communications and Electronic Systems addressed in this section include:

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

Installing Intrinsic Safety Termination Panels and Barriers

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES

TABLE OF CONTENT

Power surges can also be generated by equipment in your facility such as:

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

Cable management for rack-mounted systems

White Paper: Electrical Ground Rules

1. Franklin Rod Performance 2. LEC/DAS Performance

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Cable Discharge Event

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Earth Ground Resistance

David Brender Copper Development Association Inc. Miramar, March 8, 2013

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

Installation Guide Content for P250xV-240 microinverters

PXL-250: Network Wiring

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Current Probes. User Manual

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

INTERNATIONAL STANDARD

AC and DC Drive System Installation Information

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

CalMod Design-Build Electrification Services

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

IRRIGATION PUMPING Table of Contents - Section 900

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

Lightning Protection Introduction

About the BitStorm 6051 POTS Splitter

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

AC Module Installation Guide Content

LOXONE 12 Channel Amplifier

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Doc Ref: baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Substation Grounding Study Specification

Please check with your local inspection authority for any additional requirements before installation.

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

The Do s and Don ts of Pressure Transducers

E-Version SECTION CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

No Phone Line System. Quick Start Guide NPL II. 1.0 Installation

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

Operating Instructions

Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants

When power interruptions happen.

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

PART 1 - INTRODUCTION...

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Intersection Preassembled 19-inch Rack

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

HP UPS R1500 Generation 3

Electrical Grounding. Appendix C

Transient and Lightning Protection for the Water Industries

Section Grounding and Bonding for Communications

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

DYNAMIC MESSAGE SIGN WALK-IN

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Transcription:

Lightning Protection Guidelines for Instrumentation Systems D3P00701202 Installation Manual Revision B November 1995 This manual supercedes the issue dated une 1991.

See CE Statement in Section 1 PROVOX, is a mark of one or more of the Fisher-Rosemount group of companies. All other marks are the property of their respective owners. Fisher-Rosemount Systems, Inc. 1989, 1991, 1995. All rights reserved. PrintedinUSA The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

Your Evaluation Please... Name: Company: Control Title and Department: Years of Experience: Instrumentation Distributed Telephone: ( ) -- Education: High School Years College Degree ob Responsibility: Please indicate your evaluation of (Revision B November 1995). Attach extra sheets if needed. 1. How and when do you use this manual? V Read entire manual before attempting task V Read selected sections before attempting task V Read while attempting task V Attempt task first V Read as last resort 2. How well is the manual s content organized? Please explain. Understandable V Excellent parallels product s operation, very usable V Good representative of the product s operation, usable V Average usable but can be improved V Fair not very usable, should be improved V Poor not usable, must be improved V No Opinion Applicable 3. Is the manual s content understandable and applicable to the product s operation? Please explain. 4. How well do the manual s illustrations convey product information? Please explain. V V V V V V V Excellent very easy to understand, very applicable V Good easy to understand, applicable V Average applicable but some sections not easy to understand V Fair not very understandable/applicable, should be improved V Poor not understandable/applicable, must be improved V No Opinion V Excellent very easy to understand, extremely usable V Good easy to understand, very usable V Average fairly easy to understand, usable V Fair not easy to understand, should be improved, not very usable V Poor cannot understand, must be improved, totally unusable V No Opinion

5. Describe the amount of usable information in this manual including tables. Please explain. Sections V Too much information not all required to perform task V Proper amount provided not too much nor too little V Too little information needed additional information to perform task V No Opinion Index 6. How well is information cross-referenced in the manual s individual sections and index? Please explain. V V V V V V V V Excellent very easy to locate information, extremely usable V Good easy to locate information, very usable V Average fairly easy to locate information, usable V Fair not easy to locate information, should be improved, not very usable V Poor cannot locate information, must be improved, totally unusable V Did Not Use V No Opinion 7. How useful is the Glossary? V Useful V Useful but not complete/accurate V Not Useful V Did Not Use V No Opinion 8. What is your overall impression of this manual? Please explain. V Excellent met all needs, extremely usable V Good met most of my needs, very usable V Average usable V Fair should be revised, not very usable V Poor must be revised, totally unusable V No Opinion Please FAX or MAIL this form to: Fisher-Rosemount Systems, Inc. Technical Documentation Editor FAX Number: (512) 834-7200 8301 Cameron Road, MD#12 Attention: Technical Documentation Editor Austin, TX 78753 FISHER-ROSEMOUNT USE ONLY forwarded to: V Lead Writer V Engineering V Technical Support V Marketing V Project File

Documentation Map Documentation Map Lightning Protection Guidelines for Instrumentation Systems This map shows manuals used to plan the installation of a PROVOXr Process Management System. The number, title, and binder location are shown for each document, identifying where specific information is located. See the descriptions on the back of this map for more information. PROVOX Instrumentation Installation Manual YOU ARE HERE Lightning Protection Guidelines for Instrumentation Systems PN1:002 Planning the Installation PN1:003 AC and DC Power and Ground Wiring PN1:004 Signal Wiring and Highway System Guidelines PN1:005 Preventing Electrostatic Discharge PN1:006 Environmental Considerations for Instrumentation systems PN1:008 Site Evaluation Revision B November 1995 iii

Documentation Map PROVOX documentation supports each stage of system development. System Development Stages System Design Document Type & Contents Configuration Engineering Manuals Configuration data-entry help for a product, including theory of operation for improved product use. Installation and User Manuals for Configuration Products Installation procedures, and operating methods and procedures for using the configuration software. Technical Reference Manuals Advanced user information for expanding the capability of the PROVOX system. System Manager s Guide Expert users information for managing operating systems. System Planning and Installation System Startup and Operation Maintenance Installation Manuals Site preparation, including the environment, power, and grounding. Also, product signal wiring, cable connections, and hardware installation. User Manuals Operating methods and procedures for a product, and software installation. Tutorials Structured training for operators. Maintenance Manuals Preventative maintenance, calibration, troubleshooting, and repair procedures. Ordering Information To order additional manuals, contact your local sales representative, specifying the number, title, and quantity of each document required. iv Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems Contents Section/Title Page 1 Introduction... 1 1.1 Intended Audience... 1 1.2 CE Statement... 1 1.3 Manual Conventions... 2 1.4 Notes... 2 1.5 Related Documents... 2 1.6 Reference Documents... 3 1.7 Excellence in Documentation... 3 2 Lightning Risk Determination... 3 3 Lightning Protection Systems... 4 3.1 Lightning Rods... 4 3.2 Conductor System... 5 3.3 Grounding System... 6 3.4 Lightning Arrestors and Surge Protectors... 7 4 Implementing Lightning Protection... 8 5 Inspection and Maintenance of Lightning Protection Systems... 9 Figures 1 Minimum Conductor Bend Radius Requirements... 5 2 Typical Lightning Protection System... 6 3 Type DH7091 Transient Protection Assembly and User Supplied Mounting Plate... 10 4 Cabinet Grounding and PROVOX Highway Protection in a Multi-Cabinet Grouping... 11 5 Signal and Power Grounding, and PROVOX Highway Protection, in a Multi-Cabinet Grouping... 12 6 Single Cabinet (DC Cabinet Grounding System)... 12 7 Multiple Cabinet System Grounding and Transient Protection Assembly Placement... 13 Revision B November 1995 v

Contents This page intentionally left blank. vi Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 1 1 Introduction This installation planning manual provides guidelines for protecting PROVOXr Process Management Systems from lightning damage. A direct strike can disrupt critical processes, start fires, damage buildings and equipment, and injure personnel. Near strikes, too, can disrupt critical processes and damage electronic circuitry, by inducing voltage in unprotected wiring. Therefore, adequate lightning protection is essential in a modern processing plant. 1.1 Intended Audience Installation planning manuals are intended for use by plant engineering personnel, especially those charged with planning a control system installation. 1.2 CE Statement If you intend to have your PROVOX system certified for compliance to appropriate European Union directives, the following CE statement is extremely important to your ability to achieve that compliance. This manual describes installation and maintenance procedures for products which have been tested to be in compliance with appropriate CE directives. To maintain compliance, these products must be installed and maintained according to the procedures described in this manual. Failure to follow the procedures may compromise compliance. Revision B November 1995

2 Lightning Protection Guidelines for Instrumentation Systems 1.3 Manual Conventions This manual uses the following conventions: Acronyms and Abbreviations Terms are spelled out the first time they appear in text. Thereafter, only the acronym or abbreviation is used. Revision Control The title page lists the revision level and the printing date of this manual. When the manual is revised, the revision level and the printing date are changed. References References to other Fisher-Rosemount Systems manuals include the name and catalog number for manuals. 1.4 Notes Notes attract attention to essential information in this manual. The type of information included in a note is: Note Notes have this form and symbol. Notes contain installation, operation, or maintenance procedures, practices, conditions, statements, and so forth, that alert you to important information which may make your task easier or increase your understanding. 1.5 Related Documents The planning manuals listed below provide further information for system installation planning: PN1:002, Planning the Installation PN1:003, AC and DC Power and Ground Wiring PN1:004, Signal Wiring and Highway System Guidelines PN1:005, Preventing Electrostatic Damage PN1:006 Environmental Conditions for Instrumentation Systems PN1:008, Site Evaluation Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 3 1.6 Reference Documents The documents listed below provide further information for understanding lightning protection systems: Hart, William C. and Malone, Edgar W., Lightning and Lightning Protection, 1st ed., Don White Consultants, Inc., Gainesville, Virginia, 1979. NFPA, NFPA-78 Lightning Protection Code 1986, Quincy, Massachusetts: National Fire Protection Association, 1986. 1.7 Excellence in Documentation Our goal is to provide documents that meet your needs. Through surveys and interviews, we continually evaluate our documents as part of the broad Fisher-Rosemount Systems customer-support program. Various manuals are produced for different purposes and for readers with varying backgrounds and experience. Please assist us in the evaluation of this manual by completing the reader evaluation form located at the front of the document. In addition, if you have any suggestions for specific pages, return a marked-up copy along with your survey. 2 Lightning Risk Determination Two factors determine the level of protection required: Geographic location Process criticality Lightning strikes occur more often in some areas than in others. Elevation, humidity, latitude, and normal weather patterns influence the frequency of lightning strikes in a particular geographic area. Therefore, the typical lightning storm patterns at your site will influence the extent of protection needed. The other factor in determining appropriate lightning protection is process criticality. The more critical a process, the more important lightning protection is, even though the system may be in an area of low lightning occurrence. If any strike or near strike, no matter how unlikely, can cause loss of control of a critical process, severe financial loss, major equipment damage, or danger to personnel, a complete lightning protection system is appropriate. Revision B November 1995

4 Lightning Protection Guidelines for Instrumentation Systems 3 Lightning Protection Systems Lightning protection systems provide safe conduction paths to earth ground to minimize equipment damage and personal injury. A complete lightning protection system includes: Lightning rods Conductor system Grounding system Lightning arrestors and surge protectors Lightning rods (also referred to as air terminals) intercept lightning discharges above a building or facility. The conductor system is a safe discharge path from the lightning rods to the grounding system. The grounding system lets the lightning discharge or dissipate safely. Lightning arrestors and surge protectors protect power lines, data highway cables, instrumentation wiring, and other such equipment from induced voltages. Together, these elements minimize lightning discharge damage. Although a lightning protection system intercepts, conducts and dissipates the main electrical discharge, it does not prevent possible secondary effects, such as spark-over in nearby large metal structures. Note To minimize secondary effects of lightning strikes, make sure that all adjacent metal structures interconnect with and tie to the main conductor system. This construction maintains the same electrical potential throughout all structures in the vicinity. 3.1 Lightning Rods Lightning rods intercept a discharge above a structure, and direct the discharge to a safe path. In particular, lightning rods minimize the possibility of fire. Lightning rods should be on structures, and parts of structures, most likely to be struck. Therefore, chimneys, ventilators, towers, and other such higher parts of buildings should have lightning rods. The parts of flat-roofed building most likely to be struck are the roof edges. A large plant site area needs a complete system of properly located lightning rods. Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 5 3.2 Conductor System Once intercepted, a lightning discharge follows a low-impedance path to the earth (path of least resistance). Normally, the least resistant path is metal. A conductor system consists of one or more such metal paths. Each path must be continuous from the lightning rod to the ground. Paths must not have any sharp bends or loops. This ensures that the system provides the most direct path to earth for lightning discharge. As illustrated in Figure 1, no bend should form an angle of less than 90 degrees, and no bend should have a radius less than 10X the diameter of the RG-6U cable used for the path (approximately 3 inches (76.2 mm). A non-ferrous metal such as copper or aluminum is the preferred material for the path, as it is not susceptible to the rust or corrosion of a ferrous metal. R Radius must not be less than 10X cable diameter C L C L Figure 1 Bend angle must not be less than 90 Minimum Conductor Bend Radius Requirements The impedance of a conductor system is inversely proportional to the number of separate discharge paths. Therefore, increasing the number of paths decreases the impedance. In a multi-path conductor system, the paths (wires) should form a cage around the structure. The steel framework of a structure can substitute for separate conductors, but smooth connection straps must span any sharp bends or other hindrance. Figure 2 shows a typical protection system with a conductor, grounded steel framework, and connection straps. Revision B November 1995

6 Lightning Protection Guidelines for Instrumentation Systems Optional Down Conductor If Steel Framework is not used Lightning Rods Steel Framework Connection Straps If Down Conductor Is Used, Strap to Steel Framework at Top and Bottom Plant Grounding System Figure 2 Grounding Rods Typical Lightning Protection System In metal structures, the conductor system can use the framing instead of separate conductor cables. In such cases, lightning rods should be electrically bonded to the top part of the framework, and ground terminals should be bonded to the bottom. Structures with electrically continuous metal exteriors may not require separate lightning rod and conductor systems, if the metal is at least 0.188 inch (4.76 mm) thick. The metal exterior itself can intercept lightning and conduct it to the ground. 3.3 Grounding System Proper grounds are essential for effective lightning protection. Installation manual, AC and DC Power and Ground Wiring, PN1:003, includes a complete description of recommended plant grounding systems. Each ground connection, and each branch of each ground connection, should extend below, and at least 2 feet (0.61 m) away from, a building s foundation walls. This construction minimizes wall damage. Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 7 3.4 Lightning Arrestors and Surge Protectors Note Lightning arrestors assist in the isolation of coaxial type highways, but strikes can still jump those systems. For the fullest protection, fiber optic links are recommended. Lightning arrestors and surge protectors minimize current induced in the wiring of an instrumentation system. Induction can occur in two ways: A lightning discharge passing through the conductor system generates a transient magnetic field, which induces current in nearby wiring. As the grounding system dissipates a discharge in the earth, a step difference in potential develops in the earth itself. This difference induces current in underground instrumentation wiring. Protection devices use three main types of circuits: Varistors Semiconductors (avalanche diodes) Gas discharge tubes Varistors and semiconductors provide protection from lower current levels. Gas discharge tubes protect the system from high current and voltages levels. Most protection devices have a combination of these circuits. Revision B November 1995

8 Lightning Protection Guidelines for Instrumentation Systems 4 Implementing Lightning Protection When planning a protection system, carefully consider environmental conditions and plant requirements. To implement the system, follow these suggestions: Ground the building and plant site to a single ground system. If there is a remote or separated building at the plant site, isolate the signals, power, and communications systems of the remote building. Installation manual, AC and DC Power and Ground Wiring, PN1:003, contains additional plant grounding guidelines. Use overhead cables when possible. The air around overhead cables acts as an insulator, so such cables are less susceptible to lightning induced voltage than are underground cables. Also, since overhead cables are not buried, they are less susceptible to step-potential induction in the earth than are underground cables. Ground both types of cables, including their conduits, pipe racking and cable trays. Install surge protectors on all cables running outside of buildings by: Installing a protection device for power wiring at either the substation entrance (preferred), or at each piece of powered equipment. Installing a protection device on each phone line coming into the building. Installing a protection device on instrumentation wiring, if the structures are not all grounded to a plant-wide system. Or, the equipment is not designed to handle an induced voltage surge. For instrumentation system communication cables, install a surge protector in each building at the cable entry site. System communication cables are coaxial cables for data highways and control I/O busses. Note Install protected cables in grounded conduit or cable trays. When building a lightning protection system, use mechanically strong materials with physical properties which resist rust and corrosion. Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 9 For protecting data highways and control I/O busses, Type DH7091 Transient Protection Assemblies are available. Figure 3 through Figure 7 show the different methods and types of application for PROVOX cabinet grounding combinations. Refer to installation manual, AC and DC Power and Ground Wiring, PN1:003, for additional information on cabinet grounding. The transient protection assemblies are grounded to the source of the signals that are being protected. For data highways, the ground is located within the cabinet area where the communications interface assemblies (CIA s and CIA II s) are located. For control I/O busses, the assemblies are grounded in the same area as the system cabinet ground. The ground can be at the cabinet level or remote I/O location, and connected to the cabinet ground system at any point from the cabinet back to the PROVOX Instrumentation Ground (PIG). 5 Inspection and Maintenance of Lightning Protection Systems Building additions or structural repairs done without consideration for a lightning protection system can reduce the system s effectiveness. Deterioration of or mechanical damage to the system itself may reduce its effectiveness in similar ways. To prevent a loss of protection, evaluate all proposed structural changes for effects on the protection system, and ensure that no structural repairs inhibit system protection. Inspect the structure periodically, at least annually, for deterioration and mechanical damage. Thoroughly inspect and test the lightning protection system every five years. Revision B November 1995

10 Lightning Protection Guidelines for Instrumentation Systems 1.4 (35.6) LINE EQUIP Mounting Plate Protector Top View (Mounted) 2.25 (57.2) 1.2 (30.5) 3.25 (82.6) INCH (mm) Protector Side View (Mounted) 2.94 (74.7) 0.154 (3.9) Typical 4 places 1.1 (27.9) 2.25 (57.2) 0.450 (11.4) DIA Hole 3.25 (82.6) Mounting Plate Top View 1.15 (20.2) Mounting Plate End View Figure 3 Type DH7091 Transient Protection Assembly and User Supplied Mounting Plate Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 11 PROVOX Highway Line Cabinet 1 Cabinet 2 Cabinet 3 Neutral Ground 1 Grounded Steel Column PROVOXr Instrumentation Ground (PIG) DC Ground Cabinet Ground Transient Protector. SeeFigure8 2 3 MGB Notes: 1 2 3 Plant Earth Ground Conductor used to connect the grounding electrode to the NEUTRAL Ground bond at the source of a separately derived instrumentation power system.(per NEC 250.6)(CSA22.1 Section 10) Supplemental conductor used to connect the grounding electrode for the source of a separately derived instrumentation Power System, directly to the Plant Ground Grid System. This conductor is used to provide low impedance ground reference for EMI/RFI high frequency noise. (Per NEC 250.81/250.83) (CSA 22.1 Section 10) Conductor used to provide a low impedance ground reference for the DC Power System (Logic, Transmitter, Output) and/or a Cabinet Ground for EMI/RFI high frequency noise protection of the instrumentation cabinets, file and wiring sheilds. Figure 4 Cabinet Grounding and PROVOX Highway Protection in a Multi-Cabinet Grouping Revision B November 1995

12 Lightning Protection Guidelines for Instrumentation Systems Power Bus Bar PROVOX Highway Power Bus Bar Cabinet 1 Cabinet 2 Cabinet 3 LGB To PROVOXr Instrumentation Ground (PIG) Cabinet Ground Straps Transient Protector. SeeFigure8 Legend SC PSC Figure 5 Signal and Power Grounding, and PROVOX Highway Protection, in a Multi-Cabinet Grouping Power Bus Bar PROVOX Highway Cabinet SC PSC To PROVOXr Instrumentation Ground (PIG) Transient Protector. SeeFigure8 Figure 6 Single Cabinet (DC Cabinet Grounding System) Revision B November 1995

Lightning Protection Guidelines for Instrumentation Systems 13 System Cabinet System Cabinet System Cabinet System Cabinet LGB LGB LGB LGB To PROVOXr Instrumentation Ground (PIG) DC MGB MGB CAB. MGB Transient Protection Assemblies Cabinet Ground BarorCable Notes: A local ground bus (LGB) is required for each cabinet grouping of 8 or less. A cabinet ground is required for each grouping of 8 or more. Solid Copper Bar GROUND WIRE SIZING CHART Up to 25 feet Up to 50 feet Up to 200 feet 1/0 AWG 2/0 AWG 4/0 AWG PRESTOFLEX Welding Cable is recommended. Figure 7 Multiple Cabinet System Grounding and Transient Protection Assembly Placement Revision B November 1995

14 Lightning Protection Guidelines for Instrumentation Systems This page intentionally left blank. Revision B November 1995

Notes Notes Revision B November 1995

Notes Notes Revision B November 1995

This page intentionally left blank.