PXL-250: Network Wiring
|
|
|
- Lynne Barker
- 9 years ago
- Views:
Transcription
1 This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification, the access network communication bus is guaranteed to communicate with a total network cable length of up to 4,000 feet and with the controllers connected in a single, continuous daisy chain. However, Keri Systems has identified specific extended network configurations that could be used to wire a controller network communication bus (subject to certain limitations defined on page 2). These configurations include a star pattern network communication bus, a spur cable length of up to 5,000 feet, and a total network cable length of up to 16,000 feet. Lab tested extended network configurations are presented beginning on page 2. Cable Requirements The RS-485 network should be wired using a cable with the following characteristics: twisted, shielded pair of stranded AWG 24 conductors (such as Belden 9501 or a larger gauge). Earth Ground Requirements A quality earth ground connection to the master controller is required to ensure the best possible operating conditions. Without a quality earth ground connection, an access control network may appear to operate correctly, but will be extremely susceptible to transients and electromagnetic interference. An earth ground brings all electrically neutral lines to the earth s surface potential (essentially a zero potential) providing three benefits. 1. An earth ground protects the network from electrical transients such as power surges and lightning strikes (also providing a degree of safety for an operator). 2. An earth ground provides a path to ground for electrical interference, minimizing data and communication problems for the reader data and network communication lines. 3. Through a feature on the PXL-250 controller, the shield for the entire RS-485 network is automatically grounded at the master controller minimizing communication problems. Possible earth ground sources: 1. copper shrouded ground rod 2. cold water pipe (must be a metal pipe not PVC) 3. steel building frame member (if the building s frame is embedded in the earth) 4. electrical system ground (at the breaker/fuse box) 5. telephone system ground NOTE: Communication buses such as RS-485 often appear to work when installed incorrectly, but can have intermittent communication problems. This intermittence can make diagnosing a problem difficult. Failure to properly install an RS-485 network can result in network communication errors and can cause the access control system to lock up. Application Note PXL-250 (800) (408) FAX (408) Page 1 of 6
2 Lab Tested Extended Network Configurations PXL-250: Network Wiring Application Note Specific extended network wiring configurations have been lab tested to be compatible with the PXL-250 controller. The extended network configurations described in this section have been verified in the lab to provide proper, reliable communication between all controllers in an access control network. Extended Network Guidelines There are several guidelines for installing an extended network. 1. The network uses a star pattern communication bus. Keri Systems defines a star pattern as a communication network with sets of daisy chained controllers all connected to the master controller at the center of the star. 2. Any daisy chain off the star can have a maximum cable length of 5,000 feet. 3. The total cable length of all daisy chains can be no more than 16,000 feet. 4. Any number of daisy chains can be installed as long as the cabling for these daisy chains meets the above guidelines. 5. Any number of controllers can be installed in any daisy chain (up to the 128-controller limit for the entire network). The Master For the best operating conditions the master controller for the access control network should be at center of the star. If an existing network is being upgraded to an extended network or when installing a new extended network, the master controller printed circuit board must be at level 002 Rev. A or greater to ensure proper network termination. The printed circuit board level information is at the lower right corner of the board (see Figure 1). Lithium Battery PXL REV A Figure 1 Location of Printed Circuit Board Level NOTE: Keri Systems has tested the functionality and data integrity of the extended network configurations presented in this document under lab conditions. Because of the nature of extended networks, the operation of extended networks in the field is strongly dependent upon the quality of the installation. (800) (408) FAX (408) Page 2 of 6
3 Generic Extended Network Wiring Diagram Figure 2 is a generic drawing for an extended network, meeting the guidelines listed above. *L1 *L2 Last Last * Total Cable Length for all Daisy Chains in the Network = 16,000 feet (L1 + L2 + L3 + L4 + Lx) Master Last Last Maximum Cable Length for 1 Daisy Chain = 5,000 feet Figure 2 Generic Extended Network Diagram Using Jumper Blocks to Attach Multiple Spurs to a Master The individual wiring locations on the terminal blocks on the PXL-250 controller can reliably hold a small number of wires. Certain star networks may have more spurs to be wired than can be held by the wiring locations. External jumper blocks can be used to make these connections. Perform the following steps to make an external jumper block. 1. Count how many spurs have been run to the master controller. 2. Provide jumper blocks with enough connector points to support three times the number of spurs (each spur has three wires:,, and ). This can be individual jumper blocks with three connectors for each spur or one large jumper block with enough connectors to handle all 3 sets of wires from all spurs (see Figure 3). 4 spurs x 3 wires per spur = 12 wire connection points Figure 3 Determining the Number of Jumper Block Connector Points OR *L3 *L4 Application Note PXL-250 NOTE: The remaining figures assume one large jumper block with enough connectors to handle all 3 sets of wires from all spurs has been provided for connecting wires. 3. On one side of the jumper block connect all three wires from each spur (see Figure 4). (800) (408) FAX (408) Page 3 of 6
4 Application Note Figure 4 Connecting the Spur Wires to One Side of the Jumper Block 4. On the other side of the jumper block connect jumper wires between each of the Txconnectors (see Figure 5). 5. Connect jumper wires between each of the connectors. 6. Connect jumper wires between each of the connectors. All s All Lines All Lines PXL-250 Figure 5 Jumpering Like Wires Together 7. Connect a single line from one of the connectors to TB-1/Pin-1 on the master controller (see Figure 6). 8. Connect a single line from one of the connectors to TB-1/Pin-2 on the master controller. 9. Connect a single line from one of the connectors to TB-1/Pin-3 on the master controller. (800) (408) FAX (408) Page 4 of 6
5 All Lines All Lines All s Figure 6 Connecting Jumpered Wires to the The completed star network wiring should look similar to Figure 7. All Lines All Lines All s Figure 7 Multiple Star Spurs Attached to a Master Once the network has been wired, all controllers have been addressed, and the network has been auto-configured by the Doors32 software, the network communication error rate can be viewed from the diagnostics routine in the master controller. Instructions are provided in the Troubleshooting and Diagnostics reference document (p/n , Rev. E or greater). Application Note PXL-250 (800) (408) FAX (408) Page 5 of 6
6 This page is intentionally left blank. PXL-250 Application Note (800) (408) FAX (408) Page 6 of 6
No Phone Line System. Quick Start Guide NPL II. 1.0 Installation
Used in conjunction with EntraGuard Gold Telephone Entry Systems, the provides No Phone Line communication and door or gate control through existing building telephone lines without the need purchase phone
No Phone Line II-48 System
Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase
NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.
This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
EMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
HSG Engineering Tech Bulletin
Specifications subject to change OCT 2013; Rev. 1.3 HSG Engineering Tech Bulletin Recommended RS-485 Wiring for NetAXS-4/NetAXS-123 Loops Overview This document provides the recommended RS-485 wiring for
Telebyte 209 Short Haul Modem
Telebyte 209 This document provides installation instructions for the Telebyte 209 (Keri Systems P/N SHM-232). This short haul modem can be used to assist in long-distance, direct, connections between
LocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
PXL-500 / PXL-510 Tiger Controller Quick Start Guide
This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing controllers. These instructions
Installation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
DALI Power Module (LQSE-2DAL-D) DALI Bus 1. DALI Bus 2. HomeWorks. Wallstation. Power. Eye QS Control Power Up to 100. Module.
DAI Module E-2DA-D DAI Fixture Controller DAI Module 369-650a 1 08.16.12 The DAI Module is a DI-rail mounted controller for DAI -compliant Digital Addressable loads. It provides DAI bus power and control
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
Wiring RS-485 Networks
KeyMaster Systems Revision A 2002-12-16 [RS-485 HIG Rev A ENG-US] www.controlsoft.com Building security solutions Controlsoft Contents Contents 2 Diagrams 3 Tables 3 Introduction 4 The Underwriters Laboratories
KERI SYSTEMS Keri System Components. Keri System Components
Keri System Components Keri System Components Keri s makes setting up an access control system easy! The Tiger controller is at the heart of the system, and with just the additional components required,
Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)
February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,
MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera
MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase
ELCOMPONENT LTD. User Manual
ELCOMPONENT LTD R-DCU - Remote Data a Collection Unit User Manual al CONTENTS Page 1. GENERAL... 1 2. SPECIFICATION... 4 3. INSTALLATION AND INSTRUCTIONS... 6 4. INSTRUMENT SET-UP AND RESET... 11 All rights
Access control designed simply for you
TruPortal Access control designed simply for you QUICK START GUIDE Introduction TruPortal access control solutions have been engineered and designed to install quickly and easily right out of the box.
Fire Fighter Phone System Installation Instructions
Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
MechoNet TM Network Interface (MNI) Specification Submittal
MechoNet TM Network Interface (MNI) Specification Submittal Models MechoNet Network Interface: MNI RJ (RJ45 Motor Ports): Stock No.: IMNI 0001 TP AS (US version) Stock No.: IMNI 0004 TP AS (UK version)
Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.
Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and
How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)
MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)
MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
BACnet Automation Interface Module (Network Version)
Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
STREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
TAC1 Telephone Entry System Installation and Programming Manual
TAC Telephone Entry System 4 7 3 6 8 9 Installation and Programming Manual The Chamberlain Group 84 Larch Ave. Elmhurst, IL 66-96 www.liftmaster.com TABLE OF CONTENTS SPECIFICATIONS 3 Cable Requirements
Crown Jewel Telephone entry system
The Chamberlain Group 845 Larch Ave. Elmhurst, IL 60125-1196 www.chamberlain.com Crown Jewel Telephone entry system 1 4 7 G UP 2 5 8 0 3 6 9 # CALL 1 4 7 G UP 2 5 8 0 3 6 9 # CALL Installation Manual TABLE
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note
Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
David Brender Copper Development Association Inc. [email protected]. Miramar, March 8, 2013
Grounding and Bonding in Communications Systems David Brender Copper Development Association Inc. [email protected] Ennes Workshop Miramar, March 8, 2013 MMXIII This talk concentrates on:
How To Fix A Cbus Network From A Power Supply To A Power Source
Online Introductory C-Bus Network Tutorial Square D Clipsal C-Bus Products Training Course Basic Series Online Introductory C-Bus Network Tutorial 1250SM0702A1 Square D Clipsal C-Bus Products Training
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
EQUIPMENT SPECIFICATIONS
EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access
ISHIDA BC-3000. Scale to Scale Communications
ISHIDA BC-3000 Scale to Scale Communications Setup Procedure & Operating Instructions March 2006 PN 94561 Revision History Date Page Description March 2006 Initial publication August 2006 2 Added RS-232
Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
Canopy Surge. User Manual
Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read
BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION
MANUAL INSTALLATION BACnet Wiring Guidelines For Price Controls Revision #: 01 Issue Date: 01/22/14 2014 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Overview...1 Power
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
ATS Communication Overview
ATS Communication Overview Viewpoint ATS 485 Communication link IBM Compatible Slide 1 of 23 Contents 1. Introduction 2. LonWork 3. Modbus Cards 4. Modbus Factory Configuration 5. Modbus Test Software
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK Field busses are industrial control systems using Programmable Logic lers (PLC) to control and manage field devices found in industrial environments. The communication
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.
7I29 MANUAL Rev 1.5 CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. THE 7I29 IS INTENDED FOR USE BY OEMS THAT WILL INTEGRATE IT INTO A SYSTEM WITH INTERLOCKS AND
WIRELESS READER INTERFACE - INDOOR
INSTALLATION INSTRUCTIONS WIRELESS READER INTERFACE - INDOOR (WRI-IN-12VDC or AUWRI-IN-12VDC) The most current version of this document is available for download at: http://www.ir-swa.com P/N: M053-014-C
CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Security Cameras, CATV, GPS & Satellite Protection. White Paper
Security Cameras, CATV, GPS & Satellite Protection White Paper Security Cameras, CATV, GPS & Satellite Protection Surge Protection Solutions for PTC 1 Security Cameras, CATV, GPS & Satellite Protection
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
DS 10.210A 07/99 MN MI I/A SERIES MICRONET INTERFACE APPLICATION SPECIFICATION
DS 10.210A 07/99 MN MI WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET INTERFACE APPLICATION Order Type: MNN-Ml-100 MicroNet NCP Interface The I/A Series MicroNet Interface (MI) provides network-level
Parallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
Audio, power, and control data
Shure DIS Cabling Best Practices Introduction The Shure DIS conferencing system operates on an isolated network of microphone units, interpretation stations, and additional conference accessories. Referred
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
Communication Setup Application Note
Communication Setup Application Note This Application Note describes how to install and set up communication between the inverter and the SolarEdge Monitoring Server. This document contains the following
How To Wire Wire Wire For A Decoder System
The Paige Irrigation Wiring Guide for Systems Background: The decoder system was first introduced to the irrigation industry in the late 1960s. It was invented by the world renowned golf course architect,
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
The Basics of Loop Vehicle Detection
The Basics of Loop Vehicle Detection There are a number of ways to detect vehicles, ranging from hose style detection to ultra-sonic, to inductive loop. For traffic control or drive-thru, inductive loop
EoVDSL: A Cost-Effective Solution for Transmitting Ethernet Data Over Existing Copper Wiring for ITS and Traffi c Applications
WHITE PAPER: Eo: A Cost-Effective Solution for Transmitting Ethernet Data Over Existing Copper Wiring for ITS and Traffi c Applications By Bruce M. Berman ComNet Vice President of New Business Development
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
White Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
Installation manual. Version 1.1. www.videx-security.com
Installation manual Version 1.1 www.videx-security.com 2 Table of Contents MANUAL INTRODUCTION... 4 SYSTEM INTRODUCTION... 4 SYSTEM COMPONENTS... 5 CONTROLS... 6 3.5A 13.8Vdc PSU... 6 CONTROL PCB... 6
Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure
Summary Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure This is a general procedure on how to replace Pathfinder 48-10kW shelf with a Cordex 3.6kW shelf. Part Numbers 010-567-20
East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
Integra32. Integrated Alarm Monitoring and Access Control HARDWARE MANUAL
Integra32 Integrated Alarm Monitoring and Access Control HARDWARE MANUAL C o p y r i g h t N o t i c e Copyright 1995-2010 by All rights reserved Worldwide. Printed in Canada. This publication has been
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
What is BACnet MS/TP?
and Wiring Installation Guide CARRIER CORPORATION 2014 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-461-01 8/5/2014 Verify that you have the most current version
ALL-USB-RS422/485. User Manual. USB to Serial Converter RS422/485. ALLNET GmbH Computersysteme 2015 - Alle Rechte vorbehalten
ALL-USB-RS422/485 USB to Serial Converter RS422/485 User Manual ALL-USB-RS422/485 USB to RS-422/485 Plugin Adapter This mini ALL-USB-RS422/485 is a surge and static protected USB to RS-422/485 Plugin Adapter.
Ethernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
Lightning Protection Guide. PTP 400 and 600 SERIES
Technical Note Lightning Protection Guide MOTOROLA POINT-TO-POINT BROADBAND WIRELESS SOLUTIONS MOTOROLA PTP 400 and 600 SERIES WIRELESS ETHERNET BRIDGES Table of Contents Introduction.... 3 Recommended
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
SECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
Installation Instructions
Installation Instructions Model TSTATG2111 Use with most systems: 2-Heat, 1-ool 1- Day Prog ram m ab l e Digital Thermostat u p t o 2 - H e a t & 1 - o o l ontrol up to 2 Heat & 1 ool Stages Backlit Display
Network Operation and Troubleshooting
and Troubleshooting 7 2 and Troubleshooting Starting the Network PLC as Master Networks If you re using a PLC as the master station, you must put the CPU in Run mode before the communications program can
Operating Instructions
CS101 CarSense Vehicle Motion Detector Operating Instructions CAUTIONS AND WARNINGS Never use the CS101 as a safety reversing or presence detection system. The CS101 requires that a vehicle be moving for
Introduction to Data Centre Design
Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within
Quick Design & Install Guide. Computerised Emergency Evacuation System LONWORKS TM Powerline Technology
Quick Design & Install Guide Computerised Emergency Evacuation System LONWORKS TM Powerline Technology The Quick Design and Install Guide This Zoneworks guide is designed as a quick reference or basic
GEU-0822 8-Port Gigabit Switch
GEU-0822 8-Port Gigabit Switch 1 V1. 1_20150622 1. INTRODUCTION... 3 1.1 Product Briefs... 3 1.2 Product Features... 3 1.3 Hardware Introduction... 4 2. CONNECTING THE SWITCH... 5 2.1 Package Contents...
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
Network Cabling Guide
Network Cabling Guide Poor or incorrectly installed network cabling can cause numerous problems with your computer network. Whilst we recommend that you employ a network / cabling specialist to wire and
Applied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
ASC and N2 Bus Networking and Troubleshooting Guide
Application Specific Controllers Technical Manual 636.3 Introduction Section Technical Bulletin Issue Date 0995 ASC and N2 Bus Networking and Troubleshooting Guide Introduction Page 3 Overview *3 Who Should
Nexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
Cable Guide. Click on the subject to view the information. Digi Cables Building Cables General Cable Information
Cable Guide Click on the subject to view the information. Digi Cables Building Cables General Cable Information Digi Cables Click on the subject to view the information. Digi Connector Options Digi Connector
INTERIM MARKET DOCUMENT CHANGE
INTERIM MARKET DOCUMENT CHANGE Title: MPLS and Alternative Communications for Medium Performance Facilities File #: IESO_IMDC_0169 Version #: 0.2 Part 1 General Information Document Affected: Market Manual
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
